Home
Bosch Auto Parts d8125mux Welder User Manual
Contents
1. Figure8 Wiring the D8125MUX to Detection Table 4 D8125MUX Line Length Systems Multiplex Points l MUX BUS A lt pu ES Maximum Wire Impedance 33 Q a D8125MUX AWG mm Length in Ft m EE A 22 0 8 mm 2000 610 18 1 2 mm 5000 1524 i MUX BUS B III Maximum Wire Impedance 33 Q i CO AWG mm Length in Ft m hab ve fe i 22 0 8 mm 2000 610 E eae os gt 18 1 2 mm 5000 1524 Current requirements for multiplex points vary The maximum allowable distance you can locate remote points might be reduced Do not exceed 75 mA maximum on each MUX bus output Control Panel to D8125MUX Distance Table 5 Maximum Impedance 4 05 Q at 68 F 20 C nominal Maximum Distance Size 250 ft 22 AWG 600 ft 18 AWG 76m 0 65 mm 193 m 1 02 mm Fire applications require 18 AWG Wiring Multiplex Devices to MUX Bus Figure 9 D8125MUX N SC D8125MUX 1 Multiplex device Bosch Security Systems Inc 9 08 FO1U034973 02 D8125MUX Operation and Installation Guide 3 0 Installation 3 7 Installing a Multiplex Device As shown in Table 6 several types of multiplex devices are available Each multiplex accessory device is packaged with instructions connecting to the multiplex bus output Table6 Multiplex Devices Product Point Type DS7432 Eight Input Remote
2. 22 Bosch Security Systems Inc 10 09 FO1U034973 02 D8125MUX Operation and Installation Guide 5 0 Troubleshooting EN 23 Table 17 Troubleshooting continued Symptom Diagnosis Remedy All off board points report as MISSING Points on the DS7432 all appear missing Short on Aux power Terminal 3 or Zonex power Terminal 24 If only one D8125MUX is connected to the control panel the D8125MUX might be incorrectly connected to the control panel or MUX bus wiring might be disconnected from the D8125MUX Multiplex power terminals or MUX bus terminals on DS7432 might be incorrectly wired Address switches on DS7432 set for Points 121 through 128 Terminals 3 and 24 share a common circuit breaker Check wiring and devices connected to these terminals for shorts or grounds Check connections to D8125MUX and control panel for errors Check the green Operation LED on the D8125MUX to see if it is flashing Verify the wiring on DS7432 is correct Ensure address switches on DS7432 are not set for Points 121 through 128 These points are reserved for control panel functions 6 0 Specifications Table 18 Specifications Operating Voltage Current Requirements Maximum Current Draw using both MUX bus outputs and both power outputs Operating Temperature Relative Humidity Dimensions H x W x D Nominal 12 VDC D8125MUX only 140 mA 678
3. 097 098 a 161 162 e 099 100 EIE Pets 163 164 e e e 101 102 SR S i 165 166 e e e 103 104 SA aaa 167 168 e e o e 105 106 SERIES A n 169 170 e o 107 108 ai A EEA 171 172 e o e 109 110 dol SERIES 173 174 e o e 111 112 ex mer ST 175 176 e o e le 113 114 pom R 177 178 e o o 115 116 sarai Calia 179 180 e je je e 117 118 aa z E 181 182 e e o o 119 120 ca SMS SF ESI 183 184 e o e e je 121 122 a lege det HE x 185 186 e 123 124 EE ESSEN pe uk 187 188 e e Installation Bosch Security Systems Inc 9 08 FO1U034973 02 17 D8125MUX Operation and Installation Guide 3 0 Installation Table 10 DS7460i Switch Settings When 3 9 Single Input Multiplex Devices Using D8125MUX continued The devices listed in Table 10 reserve a single point on the MUX bus Single Input Multiplex points can be programmed as Points 9 through 127 Zonex 1 and SORS Switch Number ON 129 through 247 Zonex 2 238 devices on the EE EE D9412GV2 D9412G D9412 and D9112 Points 9 through 75 67 devices on the D7412GV2 D7412G 189 190 D D D D7412 and D7212 Points 9 through 40 on the 191 192 B ex ses D7212GV2 and D7212G 32 devices When Em programming the point type for Single Input Multiplex d points using a D5
4. 3 6 Wiring Multiplex Devices to the Multiplex Bus Table 4 D8125MUX Line Length 9 T TT 9 Table5 Control Panel to D8125MUX Distance 9 3 7 Installing a Multiplex Device 10 Table 6 Multiplex DeviceS 10 3 7 1 Adding Multiplex Devices to the Control Panel Table 7 Point Conversion Table 11 cn 10 Table 8 DS7457i DS7461i and DS7465i Switch 3 7 2 Removing Multiplex Devices from the Control Settings When Using D8125MUX on Panel ue alari iano eA 10 LONO Loire 12 3 8 Point Matrix Tables eee 11 Table 9 DS7457i DS7461i and DS7465i Switch 3 9 Single Input Multiplex Devices 18 PRU When Using D8125MUX on 3 10 MX250 Photoelectric Smoke Detectors and onex Sa n pis 14 MXB2W Base or D7050 Photoelectric Smoke Table 10 DS7460i Switch Settings When Using Detector and D7050 B6 Base Be nm aA nn inne bes NA 19 D8125MUX R Sates EH EEN EE 10 3 11 DS7460 Dual Input Multiplex Module 19 Table 11 Single Input Multiplex Device Point 3 12 DS7482 Eight Input Remote Module 20 Response Configuration 18 3 13 DS7465 Input Output Module 20 Table 12 MX250 MX250TH D7050 and D7050TH p HDI aaa Point Type Configuration 19 4 0 Testing the System eese 21 Table 13 DS7460 Point Type Configuration 19 Ms petal Walk Test Command lalla
5. 9 through 127 and the sheet marked Bank 2 for Points 129 through 247 The D7412GV2 D7212GV2 D7412G D7212G D7412 and D7212 Control Panels use the sheet marked Bank 1 Bosch Security Systems Inc 9 08 FO1U034973 02 11 D8125MUX Operation and Installation Guide 3 0 Installation Table 8 DS7457i DS7461i and DS7465i Table 8 DS7457i DS7461i and DS7465i Switch Settings When Using Switch Settings When Using D8125MUX on Zonex 1 D8125MUX on Zonex 1 continued Point Point Relay Switch Number ON Relay Switch Number ON Address Address 1 2 3 4 I5 J6 7 8 TID IT B Ise 7 8 009 e 037 i x 010 z 5 038 5 e 5 011 e e e 039 e e e e 012 O O 040 L gt 013 l e e Maximum Number of Points D7212G 014 O 5 L 041 e e e 015 gt i S 042 e e e 016 z 043 e e e 017 gt 044 e e e 018 e 045 e e e 019 e E 046 e e e e 020 L e 047 e D D e e 021 e n z 048 e je 022 A 5 S 049 e e e 023 5 050 e e e 024 S O 051 e e e e 025 e A 052 e e e 026 H 5 5 053 e e o e 027 pa e e 054 e e e e 028 L O O 055 e e D e e 029 P e e 056 e e e 030 A 5 o L 057 e e e e 031 i i E 058 e e e e 032 6 059 e D e e e 033 x e 060 e e e e 034 5 5 61 e e e e 035 e e e 062 e e e e e 036 O 063 e e e a e e Note When using the DS7465i Input Out
6. R 039 040 p ex ESSE E sn SE 041 042 R 239 lt s p s 043 044 e 5 e e 240 E E E x 045 046 e e e e 241 REPRE PER 047 048 e e o e o 242 L 3 G 7 B 049 050 e e e 243 m 2 m n x 051 052 e e e e 244 S E L S E 053 054 e e e e 245 Ss Pa le le 055 056 e je e je 246 E x z 3 3 E 057 058 e e e e 247 e e e e e e e DERE e e 2 248 NOT USED 16 Bosch Security Systems Inc 10 09 F01U034973 02 D8125MUX Operation and Installation Guide 3 0 Table 10 DS7460i Switch Settings When Table 10 DS7460i Switch Settings When Using D8125MUX continued Using D8125MUX continued Ps ne Switch Number ON Ba e Switch Number ON TOTEM SU i la e a H EHe H 061 062 ect ei E 125 126 Le Hee REUS 063 064 SEA SEH erai 127 128 NOT USED 065 066 S 129 130 e 067 068 E SIE 131 132 e e 069 070 S z 133 134 e o 071 072 E I 135 136 e e je 073 074 R A S 137 138 i 075 076 E 7 En 139 140 e e 077 078 i EUM i 141 142 e e 079 080 E R Ra ET 143 144 e e 081 082 3 S S 145 146 e o 083 084 L F Dees 147 148 e o e 085 086 A A n E 149 150 e e o 087 088 E B EF ETE 151 152 e e o 089 090 x ilta R 153 154 e 091 092 E SIS STE 155 156 e e 093 094 i dg z 157 158 e e 095 096 E E ese nir eio 159 160 e ollo
7. multiplex devices Connecting or disconnecting a multiplex device while the D8125MUX is powered causes the multiplex device address setting to reprogram or scramble Bosch Security Systems Inc 9 08 F01U034973 02 D8125MUX Operation and Installation Guide 3 0 Installation Figure 6 D8125MUX Mounting Locations 1 Module mounting location Figure 7 D8125MUX Wiring Diagram o op o eg es es EEEEEEEE SEEPEREE 1 D9412GV2 D7412GV2 D7212GV2 D9412G 3 When connecting the D8125MUX to a D9412 or D9112 only D7412G D7212G D7412 or D7212 use 2 The Fire Walk Test terminal does not operate on Terminals 3 and 9 in place of Terminals 24 this model and 23 respectively 4 Supervised Power Limited 3 4 Wiring the D8125MUX to Multiplex Points Do not use shielded or twisted pair cable 1 Connect Power A and Power A on the D8125MUX to multiplex devices that require uninterrupted auxiliary power Refer to Figure 8 on page 10 Up to 200 mA is available at these terminals 2 Connect MUX BUS A and A on the D8125MUX to the positive and negative bus wires of the multiplex points The maximum allowable current on MUX BUS A is 75 mA 8 Bosch Security Systems Inc 10 09 F01U034973 02 D8125MUX Operation and Inst
8. 060 Programmer refer to Table 11 195 196 ja n Fall for information on how to configure the point type 197 198 Tamper conditions on multiplex points are treated as eb Missing conditions by the control panel 199 200 E cialis 201 202 m n n Table 11 Single Input Multiplex Device Point Response Configuration 203 204 e e e e 205 206 S Device Type Point Point 207 208 e e o b lo Type Response 209 210 e el DS7450 Flush Mount Single 1 NO Multiplex Contact Point aiya e e o e o DS7452 Surface Mount Single 1 NO 213 214 m z Multiplex Contact Point DS7457 Single Multiplex Input 2 Configurable 215 216 T Galia ERIS NOIN 217 218 e o e MX775 DS7470 Multiplex 2 NO 219 220 B 5 E 7 fey Minas Detector 50 ft 221 222 e le e e MX934 DS7471 Multiplex 2 NO 223 224 E S z E a Detector 35 ft 225 226 e o e e MX938 DS7472 Ceiling 2 NO 227 228 E z z E S GE DIR Intrusion 229 230 e le e le e MX540 DS7473 Multiplex 2 NO PIR Intrusion Detector 40 ft 231 232 ZS a f s e z 12 m Fresnel Lens 233 234 e le o e MX794 DS7474 Multiplex 2 NO 235 236 SIRENE Ad o ER PIR Intrusion 237 238 e o je e e MX950 DS7476 Multiplex E NO 239 240 PIR Microwave TriTech T is M lt 5 x Intrusion Detector 241 242 e o o e e MX835 DS7477 Multiplex 2 NO 243 244 PIR Microwave TriTech E E x Intrusion Detector with Pet 245 246 S e e e e Immunity 247 248 NOT USED 18 Bosch Security Systems Inc 10 09
9. 078 e e e e 098 L 079 e e e e e 099 e e 080 L L 100 E E S e e 101 e e e e me k E t 102 e e e e Se e 103 e e e e e 084 O 5 5 104 5 S S 085 e e e e 105 e e i 086 e e e e 106 5 L 5 5 087 e e e e e 107 e i vdd z e 2 108 e e e e i E E 109 e e e e e 2 Si L 110 e e e e e o1 d Note When using the DS7465i Input Output Module only 092 5 E e Addresses 009 through 064 support the relay option 009 through 024 on the D7212GV2 and D72126 Bosch Security Systems Inc 9 08 FO1U034973 02 13 D8125MUX Operation and Installation Guide 3 0 Installation Table 8 DS7457i DS7461i and DS7465i Table 9 DS7457i DS7461i and DS7465i Switch Settings When Using Switch Settings When Using D8125MUX on Zonex 1 continued D8125MUX on Zonex 2 Point Zone Relay Switch Number ON Point Switch Number ON Address Address 1 2 3 4 I5 J6 VEMM ES Va 03220 54220 ta EG 7 8 111 e e e e e e 129 e e 112 e ede 130 A 113 e e e e 131 e e e 114 5 le Ib 132 H le 115 e e e e e 133 e e e 116 e e e e 134 e e e 117 e e e e e 135 e e e e 118 5 he Ib o Ib 136 6 119 e e e e e e 137 e e 120 H Ie Ss a 138 o A 121 e e e e e 139 e e e 122 e e e e e 140 e e 1
10. 125MUX as shown in Figure 4 Figure3 Installing Multiplex Points without DIP Switches Wiring Diagram 1 External power 35 2 D8125MUX CQ 2 CD 3 D5060 Multiplex Point Programmer Figure 5 Programmer Cables included D V QQ 2 S 1 External power 35 2 D8125MUX i iu 3 Multiplex point without DIP switches non i models Cx xX d c 4 D5060 Multiplex Point Programmer 1 C310 Serial Cable C319 External Power Supply Cable 3 C320 Multiplex Programmer Cable N Bosch Security Systems Inc 9 08 F01U034973 02 5 D8125MUX Operation and Installation Guide 3 0 3 2 Programming 3 2 1 Powering the D5060 Turn on the D5060 by pressing and holding the 1 key until the unit beeps To turn the unit off press and hold the and keys simultaneously until the unit beeps After 5 minutes of inactivity the programmer powers down automatically to conserve power 3 2 Programming Points 1 The D5060 shows the prompt Adr after it is powered This indicates that it is ready to begin programming 2 If the multiplex device has no DIP switches connect the D5060 to the point to be programmed as shown in Figure 3 on page 5 If the mutiplex device has DIP switches program the device using its DIP switches If the mutiplex device has no DIP d switches co
11. 15 140 20 164 44 188 68 212 92 236 116 141 21 165 45 189 69 213 93 237 117 142 22 166 46 190 70 214 94 238 118 143 23 167 47 191 71 215 95 239 119 144 24 168 48 192 72 216 96 240 120 145 25 169 49 193 73 217 97 241 121 146 26 170 50 194 74 218 98 242 122 147 27 171 51 195 75 219 99 243 123 148 28 172 52 196 76 220 100 244 124 149 29 173 53 197 TT 221 101 245 125 150 30 174 54 198 78 222 102 246 126 151 31 175 55 199 79 223 103 247 127 152 32 176 56 200 80 224 104 3 8 Point Matrix Tables Only use one D8125MUX per zonex output Refer to Table 8 beginning on page 12 for Zonex 1 Refer to Table 9 beginning on page 14 for Zonex 2 If configuring the system with DS7457i DS7461i or DS7465i MUX devices Refer to Table 10 on page 16 if configuring the system with the DS7460iMUX device The type of multiplex device used determines the quantity of devices you can connect to the D8125MUX Do not program two multiplex points to the same point number After programming all the points perform a Service Walk Test Refer to the control panel s operation and installation guide for information on the Service Walk Test If a multiplex point is not functioning check for duplicate addresses Two sheets of peel off labels are supplied with the D8125MUX Each label has two parts Place the smaller part with the point number on the multiplex point Throw away the larger part Use the sheet marked Bank 1 for Points
12. 21 Table 14 DIP Switch Settings 20 4 2 Missing Maa Points EE 21 Table 15 DS7432 Point Type Configuration 90 4 3 Extra Multiplex Potts roue 21 Table 16 DS7465 Point Type Configuration 20 4 4 Ground Fault Notification on Multiplex Table 17 Troubleshooti Devices tenen 21 PRSA FOYO CSNOOUNG aeie piran Pa 5 0 Troubleshooting 22 Table 18 Specifications n 23 6 0 SPeCifi E 23 2 Bosch Security Systems Inc 10 09 FO1U034973 02 D8125MUX Operation and Installation Guide 1 0 Introduction 1 3 Listings 1 0 Introduction The D8125MUX is UL Listed as a subassembly in the 1 1 Description following categories Use the D8125MUX Multiplex Bus Interface Module A e Ge i SL to connect multiplex points to the zonex bus on the T NBSX M BIET STE SS qs following Bosch S ity Syst trol Is Doc DADO T a e UL1610 Central Station Alarm Units AMCX D7412G D7212G D9412 D7412 D7212 D9112 UL609 Local Alarm Units AOTX and D9124 with version 5 22 or greater firmware UL365 Police Station Connect Alarm Units Install the D8125MUX on Zonex 1 and Zonex 2 APAW l D9412GV2 D9412G D9412 and D9112 only The UL1076 Proprietary Alarm Units APOU multiplex bus interface supports two independent multiplex buses therefore a fault on one multiplex The D7212GV2 and D7212G are not UL bus does not prevent the other from operating Listed for UL 864 commercial fire normally applications The D81
13. 23 e e e e e e 141 e e e 124 L L L L e 142 e e e 125 e e e e e e 143 e e e e 126 e e e e e e 144 e e 127 e e e e e e e 145 e e e 128 NOT USED 146 e b 5 Note When using the DS7465i Input Output Module only 147 i n Addresses 009 through 064 support the relay option 009 through 024 on the D7212GV2 and D7212G 148 5 ie s 149 e e e e 150 e e e e 151 e e e e e 152 5 153 e 154 H 155 A e 156 A 157 A e s 158 L elo 14 Bosch Security Systems Inc 10 09 F01U034973 02 D8125MUX Operation and Installation Guide 3 0 Installation Table 9 DS7457i DS7461i and DS7465i Table 9 DS7457i DS7461i and DS7465i Switch Settings When Using Switch Settings When Using D8125MUX on Zonex 2 continued D8125MUX on Zonex 2 continued Zone Zone Point Switch Number ON Point Switch Number ON Address Address 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 159 e e e e 189 e e e 160 5 5 190 5 5 5 161 e e e 191 e e e e 162 L 192 O S 163 e e e e 197 e e e e 164 e e e 198 e e e e 165 e e e e 199 e e e e e 166 5 5 5 e 200 ej O 167 e e e e e 201 e e e 168 5 5 202 5 O 5 169 e e e 203 e e e e 170 5 5 L 204 O O 5 171 e e e e 205 e e e e 172 e e e 206 e e e e 173 e e e e 207
14. 25MUX scans the multiplex points connected to it and reports the points status to the control panel Point index programming then determines if the Do not mix fire and non fire products on control panel initiates an action for example alarm the same communication bus response trouble response and so on Also available on the D8125MUX are auxiliary power terminals labeled Power A Power B that support remote devices requiring an uninterrupted source of power D8125MUX is a Class B Style 4 signaling line circuit For additional D8125MUX installation information refer to the D9412GV2 D7412GV2 Approved Applications Compliance Guide P N F01U003639 1 2 Programming The D8125MUX is programmed using the D5060 Multiplex Point Programmer The D5060 connects to the D8125MUX PROG PORT located next to the POWER A terminal Individual point addresses and point types are then programmed into the D8125MUX EEPROM In addition the programmer must also program each multiplex point that is connected to the system unless the point is equipped with programming DIP switches Reset pins are provided located above Zonex Bus Out terminal to clear the D8125MUX of all programmed points Refer to Section 3 2 Programming on page 6 for programming information Bosch Security Systems Inc 9 08 F01U034973 02 3 D8125MUX Operation and Installation Guide 2 0 Operation 2 0 Operation The D8125MUX continuous
15. 60 Programmer and Adr Enter address placing the shorting bar over the A dr Enter address for Interrogation Mode Reser Bl The LED rapidly flashes bAd Battery voltage is below 15 V twice followed by a pause Err Point was not programmed correctly Lob Battery voltage is below 16 V noP No response from point PnL Communications with the D8125 failed rSP Point responds to address tYP Enter point type t YP Enter point type for Interrogation Mode 4 Bosch Security Systems Inc 10 09 FO1U034973 02 D8125MUX Operation and Installation Guide 3 0 Installation 3 1 Connecting the D5060 Programmer Figure4 Installing Multiplex Points with DIP 1 When using external power attach the flying Switches Wiring Diagram leads of the included power cable to the output terminals of a 16 5 VAC transformer Insert the plug end into the jack labeled EXT POWER on the programmer Refer to Figure 3 Figure 4 and Figure 5 2 Usethe serial cable provided to connect the D8125MUX to the jack labeled SERIAL PORT on the programmer 3 For multiplex devices without DIP switches use the multiplex programmer cable provided to connect the point to be programmed to the port labeled MUX POINTS as shown in Figure 3 Use the appropriate connector either the alligator clips or the probes to connect the programmer to a point For multiplex points with programmable DIP switches program the point using the DIP switches Connect the programmer to the D8
16. 8125MUX and multiplex points connected to Zonex 2 must be programmed in the D8125MUX with DIP switches as Points 9 through 127 Refer to Table 7 on page 11 A 3 7 2 Removing Multiplex Devices from the Control Panel To remove a multiplex device from the system 1 Connect the device to the D5060 2 Enter the address 3 Enter 0 for the point type Ensure that the D8125MUX is not powered before connecting or disconnecting multiplex devices Connecting or disconnecting a multiplex device while the D8125MUX is powered causes the multiplex device address setting to reprogram or scramble After any programming or hardware change do a functional test of the system as required by local codes E O 10 Bosch Security Systems Inc 10 09 F01U034973 02 D8125MUX Operation and Installation Guide 3 0 Installation Table 7 Point Conversion Table If Zonex Program If Zonex Program If Zonex Program If Zonex Program If Zonex Program 2Pt is as 2Pt tis as 2Pt is as 2Pt tis as 2 Pt is as 129 9 153 33 177 57 201 81 225 105 130 10 154 34 178 58 202 82 226 106 131 11 155 35 179 59 203 83 227 107 132 12 156 36 180 60 204 84 228 108 133 13 157 37 181 61 205 85 229 109 134 14 158 38 182 62 206 86 230 110 135 15 159 39 183 63 207 87 231 111 136 16 160 40 184 64 208 88 232 112 137 17 161 41 185 65 209 89 233 113 138 18 162 42 186 66 210 90 234 114 139 19 163 43 187 67 211 91 235 1
17. D8125MUX Operation and Installation Guide EN Multiplex Bus Interface 6 BOSCH EN 2 D8125MUX Operation and Installation Guide Contents Figures Contents Figure 1 D8125MUX Multiplex Bus Interface e 2 Module iint tetris 4 10 Introduction sssssseseossecssssssssosococceseessssssseococeese 3 Figure2 D5060 Multiplex Point Programmer 4 1 1 EE EE 3 Figure 3 Installing Multiplex Points without DIP 12 Programming 3 Switches Wiring Diagram 5 13 Listings 3 Figure 4 Installing Multiplex Points with DIP 2 s xu c uu Switches Wiring DEBIAN ua 5 SS pan G RR CRISE TE K T E asentan 5 3 uan Figure 6 D8125MUX Mounting Locations 8 95 E 8 Se M Figure 7 D8125MUX Wiring Diagram 8 S rogramming queo ame uet UOC Figure 8 Wiring the D8125MUX to Detection 3 2 1 Powering the 5060 aaa Ze 6 Systems Multiplex Points 9 3 2 2 Programming Ponts 6 Figure 9 Wiring Multiplex Devices to MUX Bus 9 3 2 8 Removing a Point from the D8125MUX 6 3 2 4 Interrogation Mode ssesesseseseeeseseserseserersesess 7 2 Tables 3 3 Installing and Wiring the D8125MUX to the l GEN Control Panel temer 7 Tablet X Operation LED Descriptions 4 3 4 Wiring the D8125MUX to Multiplex Points 8 Table 2 D5060 LED Definitions 4 3 5 Using Power B and MUX BUS B Optional 9 Table 3 Point Type Entry Code n os 6
18. F01U034973 02 D8125MUX Operation and Installation Guide 3 0 Installation 3 10 MX250 Photoelectric Smoke Detectors and MXB2W Base or D7050 Photoelectric Smoke Detector and D7050 B6 Base The MX250 and MX250TH Photoelectric Smoke Detectors with MXB2W Base or D7050 and D7050TH Photoelectric Smoke Detectors and D7050 B6 Base reserve a single point on the multiplex bus Single input Multiplex points can be programmed as points 9 through 127 Zonex 1 and 129 through 247 Zonex 2 238 smoke detectors on a D9412GV2 D9412G D9124 D9412 or D9112 points 9 through 75 67 smoke detectors on a D7412GV2 D7412G D7412 and D7212 and 32 smoke detectors points 9 through 40 on the D7212GV2 and D7212G Other wiring restrictions can reduce the maximum number of photoelectric smoke detectors on the multiplex bus Refer to the MX250 Installation Guide P N 45253 and the D7050 Installation Instructions P N 47458 for additional information When programming an MX250 Series or D7050 Series Photoelectric Smoke Detector and base with a D5060 Programmer refer to Table 12 for information on configuring the point type Table 12 MX250 MX250TH D7050 and D7050TH Point Type Configuration Point Point Type Response Device Type Photoelectric Smoke 4 NO Detector and Base The rotary address switches must be set to the B range address to work with the D8125MUX 3 11 DS7460 i Dual Input
19. MUX does not have nicks or cuts in the insulation that can short to nearby conduit Make sure wires are tight under terminals of multiplex points and on the D8125MUX Remove the sensor wiring from the multiplex point and meter it for continuity There should be no more than 100 of resistance plus the EOL resistance If you read less than the EOL resistance look for shorts in the wiring With the wires for the sensor removed use a meter to check them for continuity to ground A ground before the EOL resistor on a multiplex points sensor loop is interpreted as a short If the multiplex point is programmed for trouble on short a ground before the EOL causes the multiplex point to send a trouble report The control panel ignores events generated while the programming or reset switch is down Multiplex points programmed for the same address do not function correctly Check the programming of each multiplex point with the multiplex point programmer A short on either MUX BUS A or MUX BUS B terminals generates a PT BUS TROUBLE report A short on BUS A or BUS B does not prevent the other from normal operation Determine what series of points is wired to BUS A and BUS B Check wiring for shorts Confirm that a multiplex point is not programmed as Point 128 or 248 Multiplex points cannot be used as Points 128 or 248 these are reserved for control panel functions OctoPOPITs cannot be used for Points 121 to 128 or 241 to 248
20. Module 6 DS7450 Flush Mount Single Multiplex 1 Contact Point DS7452 Surface Mount Single Multiplex 1 Contact Point DS7457 Single Multiplex Input Module 2 DS7460 Dual Zone Input Module 6 DS7465 Input Output Module 3 MX775 DS7470 Multiplex PIR Intrusion 2 Detector 50 ft 15 m Mirror MX934 DS7471 Multiplex PIR Intrusion 2 Detector 35 ft 11 m Mirror MX938 DS7472 Ceiling Mount Multiplex 2 PIR Intrusion Detector MX540 DS7473 Multiplex PIR Intrusion 2 Detector 40 ft 12 m Fresnel Lens MX794 DS7474 Multiplex Long Range 2 PIR Intrusion Detector MX950 DS7476 Multiplex 2 PIR Microwave TriTech Intrusion Detector MX835 DS7477 Multiplex 2 PIR Microwave TriTech Intrusion Detector with Pet Immunity MX250 Photoelectric Smoke or Photo with 4 Heat Detector and MXB2W Base D7050 D7050TH Photoelectric or Photo 4 with Heat Detector and D7050 B6 Base Lot 4249 and greater 3 7 1 Adding Multiplex Devices to the Control Panel Off board points for the D9412GV2 D9412G D9124 D9412 and D9112 are numbered 9 through 127 and 129 through 247 D7412GV2 D7412G D7412 and D7212 use off board Points 9 through 75 only D7212GV2 and D7212G use off board Points 9 through 40 only The D9412GV2 D9412G D9412 and D9112 reserves Points 128 and 248 for internal use The D8125MUX connected to Zonex 1 monitors Points 9 through 127 whereas the D8125MUX connected to Zonex 2 monitors Points 129 through 247 The D
21. Multiplex Module The DS7460 i reserves two points on the MUX bus Dual input multiplex points can be programmed as Points 9 through 127 Zonex 1 and 129 through 247 Zonex 2 59 per zonex 118 modules on D9412GV2 D9412G D9412 and D9112 Points 9 through 75 33 modules on a D7412GV2 D7412G D7412 and D7212 Points 9 through 40 on the D7212GV2 and D7212G 16 modules When programming dual points they occupy first an odd point number then an even point number For example DS7460 i Modules must be programmed to occupy Points 9 and 10 not 10 and 11 When using the D5060 programmer only program the odd or first point on the module The even or second point is automatically added The DS7460i cannot be used for Point 75 on the D7412GV2 D7412G D7412 and D7212 or for Points 127 or 247 on the D9412GV2 D9412G D9412 and D9112 Failure to observe these programming requirements will result in intermittent missing conditions In addition both points on the DS7460i must have a Point Index assigned to it when programming the control panel If one of the two points is not required on the device simply place the 47 kO end of line EOL resistor on the point input terminals and program the unused point with the same Point Index When programming the point type for the DS7460 i using the D5060 Programmer refer to Table 13 for information on configuring the point type Tamper conditions on multiplex points are trea
22. allation Guide 3 0 Installation 1 To Loop B BUS 5 2 To Loop B BUS 6 3 To Loop B Power 7 4 To Loop B Power 8 To Loop A BUS To Loop A BUS To Loop A Power To Loop A Power 3 5 Using Power B and MUX BUS B Optional It might be necessary to use the Power B and MUX BUS B terminals for isolation purposes For example an Authority Having Jurisdiction AHJ might require that fire points and burglar points be on independent buses 1 Connect Power B and Power B on the D8125MUX to multiplex devices that require uninterrupted auxiliary power Up to 200 mA is available at these terminals 2 Connect MUX BUS B and B on the D8125MUX to the positive and negative bus wires of the multiplex points The maximum allowable current on MUX BUS B is 75 mA 3 6 Wiring Multiplex Devices to the Multiplex Bus Use one two wire data expansion loop using MUX BUS A or distribute the devices on both MUX BUS A and B Table 4 shows the maximum distance per MUX bus output each D8125MUX has two multiplex bus outputs Table 5 shows the maximum distance between the control panel and the D8125MUX Determine the required wire gauge for each multiplex bus expansion loop Table 4 Programming the individual multiplex points with the D5060 assigns them to point numbers Daisy chain and T tapping configurations are acceptable Refer to Figure 9
23. and is connected to either Zonex 1 or Zonex 2 on the control panel 1 Align the D8125MUX with any of the three mounting locations shown in Figure 6 on page 8 Then fasten the module with the three mounting screws provided 2 Remove AC and DC power from the control panel 3 Connect 12 V from the D8125MUX to Zonex Power Terminal 24 on the D9412GV2 D7412GV2 D7212GV2 D9412G D9412 and D9112 Terminal 3 on the 7412G D7212G D7412 and D7212 as shown in Figure 7 on page 8 4 Connect IN on the D8125MUX to Zones Out 1 Terminal 28 or Zonex Out 2 Terminal 26 on the control panel 5 Connect OUT on the D8125MUX to Zonex In 1 Terminal 27 or Zonex In 2 Terminal 25 on the control panel 6 Connect GND on the D8125MUX to Zonex Common Terminal 23 on the D9412GV2 D7412GV2 D7212GV2 D9412G D9412 and D9112 Terminal 9 on the D7412G D7212G D7412 and D7212 7 Connect Power A and Power A on the D8125MUX to multiplex devices that require auxiliary power Up to 200 mA are available at these terminals 8 Connect MUX BUS A and A on the D8125MUX to the positive and negative bus wires of the multiplex points 9 When using Loop B connect Power B if applicable and MUX BUS B on the D8125MUX to the power and bus wires of the multiplex points Power B and B also have up to a 200 mA capacity Observe correct polarity Ensure the D8125MUX is not powered before connecting or disconnecting
24. c 10 09 F01U034973 02 D8125MUX Operation and Installation Guide 4 0 Testing the System Control the relay output on each DS7465 using any of the following control panel options e Relay follows Point for Points 9 through 64 Points 9 through 34 for D7212GV2 D7212G refer to the Relay Response Type section in the control panel s program entry guide When the DS7465i is programmed to follow a point the relay can have a delayed response of 2 to 5 sec Area or Panel Wide Relay functions Schedules skeds Command 5 4 Remote Programming Software control Enter Key Relay Number refer to Command Center Assignments in the control panel s program entry guide e BFSK Relay D7412GV2 D7212GV2 D7412G D7212G D7412 and D7212 only 4 0 Testing the System 4 1 Local Walk Test Command 44 While disarmed check the security system s status by entering COMMAND 4 4 at the D1255 or D1260 Keypad This command initiates a System Walk Test Each point of protection is scanned by the control panel and points are displayed on the D1255 as they are activated An accompanying tone is heard from the keypad to alert the user of an activated point When all the burg points are tested 0 POINTS TO TEST appears and the system returns to normal operation Points failing to report during the Walk Test can be viewed by pressing NEXT until the display reads VIEW UNTESTED Press NEXT to view the faulty points Ref
25. d on the control panels is 56 as points 9 through 64 for the D9412GV2 D7412GV2 D9412G D7412G D9412 D7412 D7212 and D9112 and 16 as points 9 through 24 for the D7212GV2 and D7212G Place the DS7465 i on the D8125MUX connected to Zonex 1 If only the relay is required for the installation assign a Point Index for the programmed point location and place a 47 KQ EOL resistor on the point input terminals Refer to Table 16 for point type configuration Table 16 DS7465 i Point Type Configuration Points 127 128 and 247 248 cannot be programmed when using DS7432s D9412GV2 D9412G D9412 or D9112 Program starting point locations for the DS7432 on the D7412GV2 D7412G D7412 D7212 as follows 9 17 25 33 41 49 57 and 65 Program starting point locations for the DS7432 on the D7212GV2 and D7212G as follows 9 17 25 and 33 Failure to observe this programming requirement will result in intermittent missing conditions All eight points on the DS7432 must also have a Point Index assigned to them If any of the eight point inputs are not required Device Type Point Type Point Response DS7465 i Input Output 3 Configurable Module NO or NC Tamper conditions on multiplex points are treated as Missing conditions by the control panel Using DS7465i Input and Output Modules on the system does not interfere with the use of D8129 OctoRelay Modules 20 Bosch Security Systems In
26. dicating it is ready to program the next point If the point was not programmed correctly the unit sounds a three beep error tone and one of the following messages appears Err The point was not programmed correctly PnL Communications with the D8125MUX failed 7 Press to clear the entry or press to reprogram If programming the D8125MUX and multiplex device simultaneously and only one receives the program the D5060 shows Adr If having troubles with the point after installation try programming the D8125MUX and multiplex devices separately 3 2 8 Removing a Point from the D8125MUX 1 Apply power to the D5060 and connect the programmer to the D8125MUX only 2 Enter the address of the point you want to remove 3 When prompted for a point type press 0 Refer to Table 3 Then press 4 Press 1 to remove the point 5 If the point is programmed correctly the D5060 beeps once and Adr appears o Bosch Security Systems Inc 10 09 F01U034973 02 D8125MUX Operation and Installation Guide 3 0 Installation 3 2 4 You can also use the programmer to read information from the D8125MUX and multiplex points Refer to Section 3 1 Connecting the D5060 Programmer on page 5 to install the D5060 Reading Information from the D8125MUX 1 To enter Interrogation Mode press and hold 7 and 9 simultaneously until the unit beeps 2 The LED marked INTERROGATION MODE lights A dr appears promptin
27. e e e e e 174 e e e e 208 e e e 175 e e e e e 209 e e e e 176 e e e 210 e e e e 177 e e e e 211 e e e e e 178 e e e e 212 e e e e 179 e e e e e 213 e e e e e 180 e e e e 214 e e e e e 181 e e e e e 215 e e e e e e 182 e e e e e 216 e e 183 e e e e e e 217 e e e 184 H 218 5 b 5 185 s 219 x A i 186 5 5 220 O L 5 187 e e e 221 e e e e 188 5 O 222 ej e D Bosch Security Systems Inc 9 08 F01U034973 02 15 D8125MUX Operation and Installation Guide 3 0 Installation Table 9 DS7457i DS7461i and DS7465i Table 10 DS7460i Switch Settings When Switch Settings When Using Using D8125MUX D8125MUX on Zonex 2 continued Zone Pan ec Switch Number ON JM Switch Number ON 1 2 3 4 5 6 7 8 i e kee Ie S 223 B lt R a 011 012 r5 e e 224 B S 013 014 e e e 225 lt lt i n 015 016 e e e e ES sae S E 017 018 S 257 IF p Le 019 020 i ex TE Fs ines 021 022 n 259 agp PEE z 023 024 n S EET 25m mes SH A 025 026 le a 231 e e e e e e UMP a TE SCHEI 029 030 e ia 233 EE A 031 032 e o o o e e DEFENSE 033 034 x e on l l mir 035 036 S SO TR ma 037 038 R s vee ail
28. er to the Security System Owner s Manual P N 71 06633 000 for more details on the Local Walk Test features 4 2 Missing Multiplex Points Multiplex points appearing as missing on the display are usually not connected properly to the multiplex bus not programmed correctly nor have incorrect DIP switch settings Check the multiplex bus wiring to the missing point and its programming 4 3 Extra Multiplex Points Extra Points occur when the D8125MUX sends point transitions back to the control panel and the control panel does not have a Point Index programmed for it Extra multiplex points are reported to the control panel as a trouble event at the keypad or central station The keypad shows the default custom text for the point number as programmed in the RADXPNTS handler When an extra point is activated during the Service Walk Test it appears as an extra point in the control panel s event log and at the local printer if installed Use VIEW LOG to view the control panel s event log Once an extra point is identified check the programming to see if it has a Point Index programmed Determine if the point belongs in the system Refer to Section 5 0 Troubleshooting on page 22 for more information 4 4 Ground Fault Notification on Multiplex Devices When the Loop Input is in a normal condition a ground fault on the Loop Input terminal is initially signaled as a point trouble A ground fault condition is signaled b
29. g you to enter a starting address 3 Enter an address followed by The Interrogation LED flashes 4 Press f to read point information from the D8125MUX at that address 5 Press 4 to read the previous address information from the D8125MUX 6 Press 6 to read the next address information from the D8125MUX Interrogation Mode If communication between the unit and the D8125MUX fails the unit sounds a three beep error tone and shows PnL 7 Exit Interrogation Mode by pressing and holding until the unit beeps Reading Information from MUX Points Disconnect all multiplex points from the D8125MUX and the multiplex bus before reading multiplex point information 1 To enter Interrogation Mode press and hold 7 and 9 simultaneously until the unit beeps The LED marked INTERROGATION MODE lights 2 The display reads A dr prompting you to enter a starting address Enter an address and press tt 3 Press 1 4 When t YP appears at the keypad enter the point type of the multiplex point as shown in Table 3 on page 6 and press t 5 Ifa point responds to the address the programmer beeps once and rSP appears If the point does not respond the unit beeps three times and the display reads noP 6 Exit Interrogation Mode by pressing and holding until the unit beeps 3 3 Installing and Wiring the D8125MUX to the Control Panel The D8125MUX is installed in the control panel enclosure
30. ly monitors itself for proper operation and indicates its condition using the green Operation LED Figure 1 Refer to Table 1 for a description of the Operation LED D8125MUX Multiplex Bus Interface Module Figure 1 3 0 Installation Use the D5060 Programmer Figure 2 and Table 2 to program multiplex bus points for the D9412GV2 D7412GV2 D7212GV2 D9412G D7412G D7212G D9412 D7412 D7212 and D9112 Control Panels In addition to programming points the D5060 can also be used to program and read information from a D8125MUX Figure 2 D5060 Multiplex Point Programmer O ai Is Gun Wen oo RESET IUAY PROG test PORT E e POWER A MUX BUS A POWER B MUXBUSB _ 1 Operation LED EXT SERIAL PORT MUX POWER POINTS LU o INTERROGATION MODE J ON HOLD Table 1 Operation LED Descriptions LED Status Meaning Flashing 1 2 The D8125MUX scans its second on 1 2 programmed multiplex points and NE SL second off operates normally HOLD Off A module fault is indicated Refer MULTIPLEX POINT PROGRAMMER to Section 5 0 Troubleshooting on page 22 On The Multiplex Point Programmer Table 2 D5060 LED Definitions is connected to the D8125MUX Double flash Reset the D8125MUX EEPROM Display Definition with the reset pin by plugging in the D50
31. mA 0 to 93 32 F to 120 F 0 C to 49 C 1 0 in x 3 25 in x 5 5 in 25 mm x 8 3 cm x 14 0 cm Bosch Security Systems Inc 9 08 FO1U034973 02 23 Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 9199 800 289 0096 2008 Bosch Security Systems Inc F01U034973 02 s 6 BOSCH
32. nnect the D8125MUX and the mutiplex device to be programmed to the D5060 for simultaneous programming Figure 3 If the mutiplex device has DIP switches program the device using its DIP switches and program the D8125MUX using the D5060 Figure 4 on page 5 3 Enter the points three digit address The address must be between 1 and 255 Press t The programmer shows tyP 4 Enter the number corresponding to the point type you are programming as shown in Table 3 and press t The programmer alternately shows the address and the point type When you program for a mutiplex smoke device by entering decimal value 4 or 5 Table 3 an 18 second timer starts counting Do not disconnect the mutiplex smoke device until after the timer counts down to zero Installation Table3 Point Type Entry Code Decimal Point Type Value 0 Remove point from D8125MUX 1 Contact 2 Sensor or single point module 3 IYO module 4 Multiplex smoke without low temperature 5 Multiplex smoke with low temperature 0 C 6 Dual point 5 Press to program a point connected to the D5060 and the D8125MUX if connected or press 1 to program the D8125MUX only If the mutiplex device has DIP switches program the device using its DIP switches Press at any time to return to a previous step in the procedure 6 Ifthe point is programmed correctly the unit beeps once and shows Adr in
33. o MUX bus Check wiring Multiplex point not programmed MUX bus wires not connected to D8125MUX Noise problem on MUX bus loop Intermittent shorts or opens on the MUX bus wires The MUX bus is open shorted or grounded Opens shorts or grounds at various points in the MUX bus can cause alarms and troubles depending on multiplex point programming Control panel s reset hook Switch is down when event was generated Two multiplex points are programmed for the same address Short on D8125MUX MUX bus terminals or short on control panel Zonex data terminals 25 amp 26 27 amp 28 A multiplex point is programmed for address 128 or 248 or a D8128D OctoPOPIT on the same system has address switches set for Points 121 through 128 or Points 241 through 248 Verify that a multiplex point programmed for the missing multiplex point is connected to the MUX bus wiring Make sure its polarity is correct Check the Green Operation LED on the D8125MUX It should be flashing An LED OFF indicates no power a D8125MUX PCB failure or an EEPROM failure on the D8125MUX Verify the missing point s programming with the Multiplex Point Programmer Verify the MUX bus wires are connected to the correct terminals on the D8125MUX Verify correct polarity Make sure MUX bus wires do not run over fluorescent lighting or near large AC power transformers or conduits Verify the wiring to the multiplex points and the D8125
34. put Module only 064 e 009 through 024 onthe D72126V and D72126 Beier When using the DS7465i mpuyOutout Module only 009 through 024 on the D7212GV2 and D7212G 12 Bosch Security Systems Inc 10 09 F01U034973 02 D8125MUX Operation and Installation Guide 3 0 Installation Note When using the DS7465i Input Output Module only Addresses 009 through 064 support the relay option 009 through 024 on the D7212GV2 and D7212G Table 8 DS7457i DS7461i and DS7465i Table 8 DS7457i DS7461i and DS7465i Switch Settings When Using Switch Settings When Using D8125MUX on Zonex 1 continued D8125MUX on Zonex 1 continued Point Point Relay Switch Number ON Relay Switch Number ON Address Address di 2 fs e EA RG Z EG a a2 3 5 6 7 8 065 e e 084 Z s 066 e e 085 e i 067 e e 086 5 n fa 068 e e 087 i i P e 069 e e e 088 e 5 070 e e e 089 i 071 H e e e 090 e 5 e 072 e e 091 S Sei 073 e e e 092 S Ewa 074 e e e 093 e e e 075 e e e e 094 e 5 5 5 095 e e e e e 076 S Sab naa SR 077 e e e e 097 e e e
35. sed Open Closed 49 169 Open Open Closed Closed Open 57 177 Open Open Closed Closed Closed 65 185 Open Closed Open Open Open 73 193 Open Closed Open Open Closed 81 201 Open Closed Open Closed Open 89 209 Open Closed Open Closed Closed 97 217 Open Closed Closed Open Open 105 225 Open Closed Closed Open Closed 113 233 Open Closed Closed Closed Open 121 241 Open Closed Closed Closed Closed on the device place the 47 kO EOL resistor on the point input terminals Refer to Table 15 for information on configuring the point type Tamper conditions on multiplex points are treated as Missing conditions by the control panel Removing the cover and activating the tamper results in a missing condition for all eight points Table 15 DS7432 Point Type Configuration Device Type Point Type Point Response DS7432 Eight Input 6 Configurable Remote Module NO or NC 3 13 DS7465 i Input Output Module This device type reserves a single point on the MUX bus and provides a Form C NO C NC relay output The relay output number assigned to this module is the same as the point number assigned to it For example if this device was programmed as Point 27 the relay number is also 27 The relay output on this module is a fully programmable relay and follows the relay programming of the control panel The maximum number of DS7465i Modules that can be place
36. ted as Missing conditions by the control panel Table 13 DS7460 i Point Type Configuration Device Type Point Type Point Response DS7460i Dual 6 Configurable Input Multiplex N O or N C Module Bosch Security Systems Inc 9 08 FO1U034973 02 19 D8125MUX Operation and Installation Guide 3 0 Installation 3 12 DS7432 Eight Input Remote Module This device type reserves eight points on the multiplex bus Each D8125MUX supports fifteen DS7432s on the D9412GV2 D9412G D9412 and D9112 Control Panels up to eight on the D7412GV2 D7412G D7412 and D7212 Control Panels and up to four on the D7212GV2 and D7212G Control Panels The DS7432s occupy groups of eight points however when programming the DS7432 with the multiplex point programmer program them as four sets of dual points For example if using a DS7432 on the system for Points 9 through 16 program Points 9 11 13 and 15 as dual points with the even points being added automatically Program starting point locations for the DS7432 on the D9412GV2 D9412G D9412 and D9112 Control Panels as follows 9 17 25 33 41 49 57 65 73 81 89 97 105 113 121 Refer to Table 14 Table 14 DIP Switch Settings DIP Switch Zonex 1 1 2 3 4 5 Zonex 2 9 129 Open Open Open Open Closed 17 137 Open Open Open Closed Open 25 145 Open Open Open Closed Closed 33 153 Open Open Closed Open Open 41 161 Open Open Clo
37. y the system after the normal 30 second ground fault detect time To witness the ground fault indication on the keypad the point trouble must be cleared from the display by pressing Command 4 on a D1255 and D1260 or Trouble Silence on a D1256 The control panel History Log shown on a keypad or sent to the central station also indicates the ground fault detection An Alarm condition is still indicated even during the occurrence of a ground fault condition When the loop is in an open position a ground fault on the Loop Input terminal disrupts supervision An open on the loop does not indicate a new fault because the ground fault is interpreted as an open A short might indicate an Alarm condition depending on the control panel s programming Bosch Security Systems Inc 9 08 F01U034973 02 21 D8125MUX Operation and Installation Guide 5 0 Troubleshooting 5 0 Troubleshooting Table 17 Troubleshooting Symptom Diagnosis Remedy Multiplex point appears as missing at the keypads Points intermittently appear as missing One or more multiplex points remain in trouble or alarm when all devices appear normal Faulted multiplex points do not generate alarms or troubles as programmed Control panel transmits PT BUS TROUBLE reports Erroneous alarm or trouble reports might follow Erroneous alarm or trouble reports appear at keypads Multiplex point is not connected t
Download Pdf Manuals
Related Search
Related Contents
MdPM 56360 S&P Rev F Oct 2003 MANUAL DO UTILIZADOR - Icon Heath & Fitness User Manual - Novo Supply Seguridad de las Cortadoras de Césped Massive Table lamp 43227/43/10 Philips Cordless phone answer machine 取扱説明書 CFロガー 取扱説明書 Untitled Copyright © All rights reserved.
Failed to retrieve file