DAM-E3025 User`s Manual

image

Contents

1. Multiple Relay Setting Function Code OF Request Domain Name Byte Value Function Code 1 byte 0XOF Start Address Setting 2 bytes 0 X 0000 to 0 X FFFF Length Setting 2 bytes 0 X 0000 to 0X 07B0 Byte Count 1 byte n Content Setting n bytes Response Domain Name Byte Value Function Code 1 byte 0 X0OF Start Address Setting 2 bytes 0 X 0000 to 0 X FFFF Length Setting 2 bytes 020000 to 0X 07B0 Exception Domain Name Byte Value Function Code 1 byte 0X OF 0 X 80 Error Code 1 byte OX1or0X2 Example IRequest IResponse Domain Name Data hex Domain Name Data hex Function Code OF Function Code OF Set Address High byte 00 Set Address High byte 00 Set Address Low byte 13 Set Address Low byte 13 Set Amount High byte 00 Set Amount High byte 00 Set Amount Low byte OA Set Amount Low byte OA IByte count 02 Set Content High byte CD Set Content Low byte 01 DAM E3025 User s Manual V6 10 Set Multiple Holding Registers Function Code 10 Request Domain Name Byte Value Function Code 1 byte 0X10 Start Address Setting 2 bytes 0 X 0000 to 0 X FFFF Length Setting 2 bytes 0 X 0000 to 0X07B0 Byte Count 1 byte 2n Content Setting 2n bytes Response Domain Name Byte Value Function Code 1 byte 0
2. 13 38 h 36 status 05 Read Switch Input Function Code 02 Description Read input switch status Data Description Address Description Note 10001 10005 For Switch Input Status 6 Channels 0 for no power 1 for power on Reservation 10033 10038 For Rising Edge Latched Status 6 Channels 0 for No Latch 1 for Latch Reservation 10065 10070 For Falling Edge Latched Status 6 Channels 0 for No Latch 1 for Latch Reservation Request Domain Name Byte Value Function Code 1 byte 0X02 Start Address 2 bytes 0 X 0000 to 0 X FFFF DAM E3025 User s Manual V6 10 Read Amount 2 bytes 1 to 2000 0 X 7D0 Response Domain Name Byte Value Function Code 1 byte 0x02 Byte Count 1 byte n Read Amount 7 8 Input Status n bytes Exception Domain Name Byte Value Function Code 1 byte 0X02 0 X 80 Error Code 1 byte 0X1 or0X2 Example Request Response Domain Name Data hex Domain Name Data hex Function Code 02 Function Code 02 Start Address H byte 00 Byte Count 03 Start Address L byte C4 204 h 197 status AC Read Amount H byte 00 212 h 205 status DB Read Amount L byte 16 218 h 213 status 35 Read Holding Register Function Code 03 Note Read the holding register value Data Description Address Description Note 40001 For Ch01 Pulse Output L Level 16 bits
3. 40002 For Ch01 Pulse Output H level 16 bits 40003 For Ch02 Pulse Output L Level 16 bits 40004 For Ch02 Pulse Output H level 16 bits 40005 For Ch03 Pulse Output L Level 16 bits 40006 For Ch03 Pulse Output H level 16 bits 40007 For Ch04 Pulse Output L Level 16 bits 40008 For Ch04 Pulse Output H level 16 bits 40009 For Ch05 Pulse Output L Level 16 bits 40010 For Ch05 Pulse Output H level 16 bits 40011 For Ch06 Pulse Output L Level 16 bits 40012 For Ch06 Pulse Output H level 16 bits Reservation 40065 For Ch01 Switch Pulse Count L 16 bits 40066 For Ch01 Switch Pulse Count H 16 bits 40067 For Ch02 Switch Pulse Count L 16 bits 40068 For Ch02 Switch Pulse Count H 16 bits 40069 For Ch03 Switch Pulse Count L 16 bits 40070 For Ch03 Switch Pulse Count H 16 bits 40071 For Ch04 Switch Pulse Count L 16 bits DAM E3025 User s Manual 40072 For Ch04 Switch Pulse Count H 16 bits 40073 For Ch05 Switch Pulse Count L 16 bits 40074 For Ch05 Switch Pulse Count H 16 bits 40075 For Ch06 Switch Pulse Count L 16 bits 40076 For Ch06 Switch Pulse Count H 16 bits Reservation 40129 For Pulse Output Enable Register Set bit Enabled Space Disabled 40130 For Input Latch Enable Register Set bit Enabled Space Disabled 40131 For Input Count Enable Register Set bit Enabled Space Disabled 40132 For Input Count Mode Register Set
4. 0x2 Example Request Response Domain Name Data hex Domain Name Data hex Function Code 15 Function Code 15 Byte Count OB Byte Count OB Sub Function Code 06 Sub Function Code 06 File Number High byte 00 File Number High byte 00 File Number Low byte 04 File Number Low byte 04 Record Number High byte 00 Record Number High byte 00 Record Number Low byte 01 Record Number Low byte 01 Read Length High byte 00 Write Length High byte 00 Read Length Low byte 02 Write Length Low byte 02 Write Data 4 bytes Write Data 4 bytes EEPROM Assignment file 0 define MODULE NET ADDR 0x0000 define MODULE_VER_ADDR 0x0020 file 1 define NET_CONFIG_ADDR 0x0000 file 2 define DIG POWER ADDR 0x0000 define DIG SAFE ADDR 0x0004 define CNT_CFG_ADDR 0x0080 file3to file 7 Note EEPROM is 8kbyte capacity divide to 8 file blocks every block 1kbyte o 1 MODULE_NET_ADDR DAM E3025 User s Manual V6 10 Restore to factory defaults network configuration parameter Byte 4 4 4 6 Content IP Address Default Gateway Subnet Mask MAC Address 2 MODULE_VER_ADDR Module Version Information Byte 42byte Content DAM E3024 _ V6 20 2006 09 01 ID DAME123456 3 NET_CONFIG_ADDR Network configuration parameter call table 1 for structures 4 DIG POWER ADDR Digital output power on value 2 bytes 5 DIG SAFE ADDR Digital output safe value 2 bytes
5. Name Byte Value Function Code 1 byte 0X14 Byte Count 1 byte 0x07 to OxF5 Sub Function Byte Count 1 byte 0x07 to OxF5 Sub Function Code 1 byte 0x06 Data 2n bytes Exception Domain Name Byte Value Function Code 1 byte 0X 14 0X80 Error Code 1 byte 0X1lor0X2 Example Request Response Domain Name Data hex Domain Name Data hex Function Code 14 Function Code 14 Byte Count 07 Byte Count 06 Sub Function Code 06 Respond Count 05 File Number High byte 00 Sub Function Code 06 File Number Low byte 04 Record Data High byte 0D Record Number High byte 00 Record Date Low byte FE Record Number Low byte 01 Record Data High byte 00 Read Length High byte 00 Record Date Low byte 20 Read Length Low byte 02 Write File Record Function Code 15 06 Request Domain Name Byte Value Function Code 1 byte 0x15 Byte Count 1 byte 0x07 to OxF5 Sub Function Code 1 byte 0x06 File Number 2 bytes 0x0000 to OxFFFF Record Number 2 bytes 0x0000 to 0x270F Write Length 2 bytes n Data 2n bytes DAM E3025 User s Manual V6 10 Response Domain Name Byte Value Function Code 1 byte 0x15 Byte Count 1 byte 0x07 to OxF5 Sub Function Code 1 byte 0x06 File Number 2 bytes 0x0000 to Ox FFFF Record Number 2 bytes 0x0000 to 0x270F Write Length 2 bytes n Data 2n bytes Exception Domain Name Byte Value Function Code 1 byte 0x15 0x80 Error Code 1 byte 0x1 or
6. bit Rise Space Fall Reservation 40513 For Watchdog Control Register bit0 0 disabled 1 enabled bit1 O normal 1 overflow bit2 O normal lreset 40514 For Watchdog Overflow Register Watchdog Overtime Constant 40515 For Watchdog Reset Register OxSSAA Reservation Request Domain Name Byte Value Function Code 1 byte 0X03 Start Address 2 bytes 0 X 0000 to 0 X FFFF Read Amount 2 bytes 1 to 125 0X7D Response Domain Name Byte Value Function Code 1 byte 0X03 Byte Count 1 byte 2n Input State 2n bytes Exception Domain Name Byte Value Function Code 1 byte 0X 03 0 X 80 Error Code 1 byte 0X1 or0X2 Example Request Response Domain Name Data hex Domain Name Data hex Function Code 03 Function Code 03 Start Address H byte 00 Byte Count 02 Start Address L byte 08 Holding Registers High 00 Read Amount H byte 00 Holding Register Low OA Read Amount L byte 01 Note 1 The unit of the pulse output level width millisecond The unit of the watchdog timer length millisecond Note 2 When power on the highest bit of the watchdog control register is 1 can be done to do determine whether the DAM E3025 User s Manual module is rested or not Write Single Relay Function Code 05 Request Domain Name Byte Value Function Code 1 byte 0x05 Address Setting 2 bytes 0 X 0000 to 0 X FFFF Content Setting 2 byte
7. AD COIL STATUS 02 READ INPUT STATUS 03 READ HOLDING REGISTERS 04 READ INPUT REGISTERS 05 FORCE SINGLE COIL 06 PRESET SINGLE REGISTER 15 FORCE MULTIPLE COILS 16 FORCE MULTIPLE REGISTERS 20 READ FILE RECORD 21 WRITE FILE RECORD Address Mapping Table Read Relay Status Function Code 01 Description Read the state of the output relay Data Description Address Description Note 00001 00005 For Switch Output Current Status 5 Channels 1 for H Level 0 for L level DAM E3025 User s Manual V6 10 TE T Reservation 00033 00037 For Switch Output Power on Status 5 Channels 1 for H Level 0 for L level Reservation 00065 00069 For Switch Output Safe Status 5 Channels 1 for H Level 0 for L level Reservation Request Domain Name Byte Value Function Code 1 byte 0x01 Start Address 2 bytes 0 X 0000 to 0 X FFFF Read Amount 2 bytes 1 to 2000 0 X 7D0 Response Domain Name Byte Value Function Code 1 byte 0x01 Byte Count 1byte n Read Amount 7 8 Coil Status n bytes Exception Domain Name Byte Value Function Code 1 byte 0x02 0 X 80 Error Code 1 byte 0X1 or0X2 Example Request Response Domain Name Data hex Domain Name Data hex Function Code 01 Function Code 01 Start Address H byte 00 Byte Count 03 Start Address L byte 13 27 h 20 status CD Read Amount H byte 00 35 h 28 status 6B Read Amount L byte
8. DAM E3025 User s Manual Y Beijing ART Technology Development Co Ltd DAM E3025 User s Manual V6 10 DAM E3025 Module Introduction Features 6 ch Isolated Digital Input 5 ch Power Relay Output General Power Consumption 2 5W 24Vpc Power Supply unregulated 10 30Vpc gt gt gt Support double watchdogs gt Support 10 100Mbps Ethernet gt Provide default web page or custom built web page Digital Input gt Channels 6 gt Input Dry Contact Grounding or open circuit Wet Contact Logic Level 0 1V max Logic Level 1 4V 30V gt Isolated Voltage 3750V gt Input channel can be used as a 500Hz counter Relay Output A type gt Channels 5 gt Output Mod common anode gt Contact Rating 250Vac 1A 30Vpc 2A Relay on Time 7ms Relay off Time 3ms Breakdown Voltage 500Vac VV V WV Insulation Resistance 1000M Q Easy to operate DAM E3025 utility software can help you to select configuration set the operating parameter for your process control needed Industrial Design DAM E3025 was designed to use in industrial environment It can be installed in standard DIN rail inside the cabinet And it can be powered by unregulated 10 30Vpc to meet the various power supplied source in field It also withstands ambient temperature up to 60 C and resists the effects of vibration and mechanical shock DAM E3025 User s Manual V6 10 Wiring amp Installation Power supply requirement
9. X10 Start Address Setting 2 bytes 0 X 0000 to 0 X FFFF Length Setting 2 bytes 0 X 0000 to 0X 07B0 Exception Domain Name Byte Value Function Code 1 byte 0X 10 0X80 Error Code 1 byte 0Xlor0X2 Example Request Response Domain Name Data hex IDomain Name Data hex Function Code 10 Function Code 10 Set Address High byte 00 Set Address High byte 00 Set Address Low byte 01 Set Address Low byte 01 Set Amount High byte 00 Set Amount High byte 00 Set Amount Low byte 02 Set Amount Low byte 02 Byte Count 04 Set Content High byte 00 Set Content Low byte OA Set Content High byte 01 Set Content Low byte 02 Read File Record Function Code 14 06 Read file record in MODBUS file is considered to be 16 bit array addressing according to address Read file set the start address and read length and change the Start Address and Read Length can traverse the entire file The file does not have a name it has number only You can only read and write one file at one time Reguest Domain Name Byte Value Function Code 1 byte 0x14 Byte Count 1 byte 0x07 to OxF5 DAM E3025 User s Manual Sub Function Code 1 byte 0x06 File Number 2 bytes 0x0000 to OxFFFF Record Number 2 bytes 0x0000 to 0x270F Read Length 2 bytes n Sub Function Code 1 byte 0x06 Response Domain
10. s unregulated 10 Vpc 30 Vpc Vs is a positive and GND is ground The Ethernet interface is connected to a computer switch directly via network cable If the wiring and power is ok then the power indicator should be stop flash and keep on The module initialization is completed The indicator flashes according to the transmitted data when the module is working DAM E3025 CA Fig 1 DAM E3025 Drawing DAM E3024 can be installed in standard DIN rail inside the cabinet 1t also can be installed by stacking mode Fig 2 DAM E3025 standard DIN installation DAM E3025 User s Manual V6 10 Fig 3 DAM E3025 stack installation Application Wiring ZIEK IN S OF T1 6nD Fig 6 TTL CMOS signal input DAM E3025 User s Manual V6 10 Fig 7 Open collector signal input Default Setting If the module s network configuration is wrong or forget the last modified value the module can be reverted to default settings Steps short circuit the INIT and GND when there is no power power on for 3 seconds power off disconnect INIT and GND The module is reverted to the default settings 1 IP Address 192 168 2 80 Subnet Mask 255 255 255 0 Default Gateway 192 168 2 1 TCP Port 502 HTTP Port 80 SU ge ALO Communication Protocol At present Ethernet Distributed Acquisition Modules of our company use MODBUS TCP mode Supported function code includes the following categories 01 RE
11. s 0x0000 or OxFFOO 0x0000 release relay OxFFO0 engage relay Response Domain Name Byte Value Function Code 1 byte 0x05 Address Setting 2 bytes 0x0000 to OxFFFF Content Setting 2 bytes 0x0000 or OxFFOO Exception Domain Name Byte Value Function Code 1 byte 0x05 0x80 Error Code 1 byte 0x1 or 0x2 Example Request Response Domain Name Data hex Domain Name Data hex Function Code 05 Function Code 05 Set Address H byte 00 Set Address H byte 00 Set Address L byte 05 Set Address L byte 05 Set Content H byte FF Set Content H byte FF Set Content L byte 00 Set Content L byte 00 Set Single Holding Register Function Code 06 MODBUS Request Domain Name Byte Value Function Code 1 byte 0X06 Address Setting 2 bytes 0 X 0000 to 0 X FFFF Content Setting 2 bytes 0 X 0000 to 0 X FFFF MODBUS Response Domain Name Byte Value Function Code 1 byte 0X06 Address Setting 2 bytes 0 X 0000 to 0 X FFFF Content Setting 2 bytes 0 X 0000 to 0 X FFFF Exception Domain Name Byte Value DAM E3025 User s Manual V6 10 Function Code 1 byte 0X 06 0 X 80 Error Code 1 byte 0X1 or0X2 Example IRequest IResponse Domain Name Data hex Domain Name Data hex Function Code 06 Function Code 06 Set Address High byte 00 Set Address High byte 00 Set Address Low byte 08 Set Address Low byte 08 Set Content High byte 00 Set Content High byte 00 Set Content Low byte 19 Set Content Low byte 19