Home
1769-IN076A-EN-P, Compact 1769-OF4VI Isolated Analog Output
Contents
1. data output data echo file words 0 3 During normal operation these input words represent the analog values that the outputs are directed to by the control program B Bit Position 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 S3 S2 S1 SO 1 H3 U3 03 H2 U2 02 H1 U1 01 HO UO 00 2 Channel 0 Data Value 3 Channel 1 Data Value 4 Channel 2 Data Value 5 Channel 3 Data Value e H Output held bit S General status over range under range ot low high clamp exceeded e U Under range or low clamp exceeded alarm e O Over range or high clamp exceeded alarm IMPORTANT The output module s input data file reflects the analog output data echo of the module not necessarily the electrical state of the output terminals It does not reflect shorted or open outputs Publication 1769 IN076A EN P July 2005 Compact 1769 OF4VI Isolated Analog Output Module 13 Configuration Data File The manipulation of the bits from this file is normally done with programming software e g RSLogix 500 RSNetworx for DeviceNet etc during initial configuration of the system In that case graphical screens are provided by the programmer to simplify configuration However some systems like the 1769 ADN DeviceNet Adapter also allow the bits to be altered as part of the control program using communication rungs In that case it is necessary to understand the bit arrangeme
2. module door is closed Publication 1769 INO76A EN P July 2005 10 Compact 1769 OF4VI Isolated Analog Output Module Removing the Finger Safe Terminal Block To remove the terminal block loosen the upper and lower retaining screws The terminal block will back away from the module as you remove the screws When replacing the terminal block torque the retaining screws to 0 46 Nm 4 1 in lbs upper retaining screw Gi PP 9 wiring the finger safe terminal block lower retaining screw Wiring the Finger Safe Terminal Block When witing the terminal block keep the finger safe cover in place 1 Loosen the terminal screws to be wired 2 Route the wire under the terminal pressure plate You can use the bare wire or a spade lug The terminals will accept a 6 35 mm 0 25 in spade lug TIP The terminal screws are non captive Therefore it is possible to use a ting lug maximum 1 4 inch o d with a 0 139 inch minimum i d M3 5 with the module 3 Tighten the terminal screw making sure the pressure plate secures the wire Recommended torque when tightening terminal screws is 0 68 Nm 6 in lbs TIP If you need to remove the finger safe cover insert a screw driver into one of the square wiring holes and gently pry the cover off If you wire the terminal block with the finger safe cover removed you will not be able to put it back on the terminal block because the wires will be in the way Publ
3. 0b RTB lower retaining screw Publication 1769 INO76A EN P July 2005 Compact 1769 OF4VI Isolated Analog Output Module 3 Module Installation Compact I O is suitable for use in an industrial environment when installed in accordance with these instructions Specifically this equipment is intended for use in clean dry environments Pollution degree 2 and to circuits not exceeding Over Voltage Category 1 EC 60664 1 9 Prevent Electrostatic Discharge Electrostatic discharge can damage integrated circuits or semiconductors ATTENTION ectrostatie diseharge c ge integ if you touch bus connector pins or the terminal block Follow these guidelines when you handle the module e Touch a grounded object to discharge static potential e Wear an approved wrist strap grounding device e Do not touch the bus connector or connector pins e Do not touch circuit components inside the module e If available use a static safe work station e When not in use keep the module in its static shield box Remove Power ATTENTION Remove power before removing or inserting this module When you remove or insert a module with power applied an electrical arc may occur An electrical arc can cause personal injury or property damage by e sending an erroneous signal to your system s field devices causing unintended machine motion e causing an explosion in a hazardous environment Electrical arcing causes excessive wear to
4. AB Installation Instructions UF Compact 1769 OF4VI Isolated Analog Output Module Inside Module Description stews nett ate oem 2 Module Installation 3 System Assembly 4 Mounting Expansion 1 0 5 Replacing a Single Module within a System 7 Module Spare Replacement Bartz 8 Field Wiring Connections KU Memory Mapping anis Specifications oo eeceseteceeecseeeseesecsecseesseessseseesecstecsseatessesstsesessneesneess 16 Hazardous Location Considerations c ccccccecscecsecseeteeteeeeeneeeeen 19 Environnements dangereux cccceccccescssessestesessesteseeseseesesteseeseateseeseavese 20 For More Information 21 Publication 1769 INO76A EN P July 2005 2 Compact 1769 OF4VI Isolated Analog Output Module Module Description 1 2a Item Description bus lever with locking function Anal 2a upper panel mounting tab 2b SSN lower panel mounting tab 4 module status LED module door with terminal identification label 888888899 5a movable bus connector with female pins 5b stationary bus connector with male pins nameplate label Ta upper tongue and groove slots 7b lower tongue and groove slots 8a upper DIN rail latch 8b lower DIN rail latch write on label user ID tag 10 removable terminal block RTB with finger safe cover 10a RTB upper retaining screw 1
5. Over Full Temperature 0 8 Range 0 to 60 C 32 to 140 F Output Impedance lt 1Q Open and Short Circuit Protection Yes Short Circuit Current 35 mA typical 42 mA max Output Overvoltage Protection Yes Output Response at System Power Up Power up 1 2V dc spike for less than 0 4 ms and Power Down Power down 1 2V de spike for less than 21 ms Rated Working Voltage 30V ac 30V de Output Group to Bus Isolation 500V ac or 710V de for 1 minute qualification test 30V ac 30V de working voltage IEC Class 2 reinforced insulation Module OK LED On module has power has passed internal diagnostics and is communicating over the bus Off Any of the above is not true Channel Diagnostics 1 Output ripple is the amount a fixed output varies with Over or under range by bit reporting ime assuming a constant load and temperature 2 Repeatability is the ability of the output module to reproduce output readings when the same controller value is applied to it consecutively under the same conditions and in the same direction 3 Rated working voltage is the maximum continuous vol signal and the value that floats above ground potentia ground age that can be applied at the output terminal including the output for example 10V dc output signal and 20V dc potential above Publication 1769 INO76A EN P July 2005 Compact 1769 OF4VI Isolated Analog Output Module 19 Specifica
6. ail mounted Non Operating 40G panel mounted 30G DIN rail mounted Agency Certification e C UL certified under CSA C22 2 No 142 e UL 508 listed e CEcompliant for all applicable directives Hazardous Environment Class Class Division 2 Hazardous Location Groups A B C D UL 1604 C UL under CSA C22 2 No 213 Radiated and Conducted Emissions EN50081 2 Class A Electrical EMC The module has passed testing at the following levels ESD Immunity IEC1000 4 2 e kV contact 8 kV air 4 kV indirect Radiated Immunity IEC1000 4 3 0 V m 80 to 1000 MHz 80 amplitude modulation Fast Transient Burst IEC1000 4 4 2 kV 5 kHz Surge Immunity IEC1000 4 5 e 1 kV galvanic gun e Conducted Immunity IEC1000 4 6 OV de 0 15 to 80 MHz 1 1000 MHz Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiat Publication 1769 INO76A EN P July 2005 ed Immunity frequency range is 30 MHz to Compact 1769 OF4VI Isolated Analog Output Module 17 Output Specifications Specification Analog Norma Operating Ranges 1769 0F4VI 10V dc 0 to 10V dc 0 to 5V dc 1 to 5V de Full Scale Analog Ranges 10 5V dc 0 5 to 10 5V dc 0 5 to 5 25V dc 0 5 to 5 25V dc Number of Outputs 4 isolated differential Bus Current Draw max 145 mA at 5V de 75 mA at 24V de Heat Dissipation 2 0 Total Watts all points 10V de int
7. ation en environnement de Classe 1 Division 2 e Ne pas remplacer de composants ou d connecter l quipement sans s tre assur que l alimentation est coup e et que l environnement est class non dangereux e Ne pas connecter ou d connecter des composants sans s tre assur que l alimentation est coup e ou que l environnement est class non dangereux Ce produit doit tre install dans une armoire Publication 1769 INO76A EN P July 2005 Compact 1769 OF4VI Isolated Analog Output Module For More Information For Refer to this Document Pub No A more detailed description of how to install and MicroLogix 1500 Programmable 1764 UM001 use your Compact 1 0 with MicroLogix 1500 Controllers User Manual programmable controller Detailed information on installing programming Compact 1 0 Analog Modules User 1769 UM002 and troubleshooting your Compact Analog 1 0 anua modules A detailed description of how to install and use 1769 ADN DeviceNet Adapter User 1769 UM001 your Compact 1 0 with the 1769 ADN DeviceNet Manua Adapter An overview of the MicroLogix 1500 system icroLogix 1500 Programmable 1764 S0001 including Compact UU Controller with Compact 1 0 for Expansion More information on proper wiring and ndustrial Automation Wiring and 1770 4 grounding techniques Grounding Guidelines If you would like a manual you can e download a free electronic version from the internet ww
8. ble 0 Disabled 1 output Enabled process changes e Reserved Set to zero e SIU System interrupt low clamp under range alarms 0 Disabled 1 Enabled e SIO System interrupt high clamp over range alarms 0 Disabled 1 Enabled e LA Latch low high clamp under over range alarms 0 Disabled 1 Enabled e ER Enable ramping 0 Disabled 1 Enabled Ramp rate limited by fault states e FM Fault mode 0 Hold Last State 1 User Defined Value e PM Program mode 0 Hold Last State 1 User Defined Value e HI Hold for initialization 0 Disabled 1 Enabled e PFE Program idle to fault enable 0 Disabled 1 Enabled Publication 1769 INO76A EN P July 2005 Compact 1769 OF4VI Isolated Analog Output Module 15 The first two words of each eight word group in the configuration file allow you to change the parameters of each channel independently For example words 8 and 9 correspond to channel 1 while words 16 and 17 correspond to channel 3 Define Indicate this These bit settings 15114113112 1110918 7161514132111 0 Program Program Idle Mode 0 Ga Enable Data Applied 2 Fault Mode Data 1 Applied Hold for Disabled 0 Initialization Enabled 1 HE Hold Last State 0 User Defined 1 Value Fault Mode Hold Last State 0 User Defined Fault 1 Value Enable D
9. contacts on both the module and its mating connector Worn contacts may create electrical resistance Il Pollution Degree 2 is an environment where normally only non conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected Over Voltage Category Il is the load level section of the electrical distribution system At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product s insulation Pollution Degree 2 and Over Voltage Category Il are International Electrotechnical Commission IEC designations Publication 1769 INO76A EN P July 2005 4 Compact 1769 OF4VI Isolated Analog Output Module System Assembly The module can be attached to the controller or an adjacent I O module before or after mounting For mounting instructions see Panel Mounting on page 6 or DIN Rail Mounting on page 7 To work with a system that is already mounted see Replacing a Single Module within a System on page 7 The following procedure shows you how to assemble the Compact I O system 1 Disconnect power 2 Check that the bus lever of the module to be installed is in the unlocked fully right position 3 Use the upper and lower tongue and groove slots 1 to secure the modules together or to a controller 4 Move the module back along the tongue and groove slots until the bus connectors 2 line up with each oth
10. e 18 Whitfield Road Causeway Bay Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Headquarters for Dodge and Reliance Electric Products Americas Rockwell Automation 6040 Ponders Court Greenville SC 29615 4617 USA Tel 1 864 297 4800 Fax 1 864 281 2433 Europe Rockwell Automation Br hlstraRe 22 D 74834 Elztal Dallau Germany Tel 49 6261 9410 Fax 49 6261 17741 Asia Pacific Rockwell Automation 55 Newton Road 11 01 02 Revenue House Singapore 307987 Tel 65 351 6723 Fax 65 355 1733 Publication 1769 INO76A EN P July 2005 PN 40071 205 01 1 Copyright 2005 Rockwell Automation Inc All rights reserved Printed in the U S A
11. en the screws of adjacent modules Before installing the replacement module be sure that the bus lever on the module to be installed and on the right side adjacent module are in the unlocked fully right position Slide the replacement module into the open slot Connect the modules together by locking fully left the bus levers on the replacement module and the right side adjacent module Replace the mounting screws or snap the module onto the DIN rail Publication 1769 INO76A EN P July 2005 8 Compact 1769 OF4VI Isolated Analog Output Module Module Spare Replacement Parts e Terminal block catalog number 1769 RTBN18 e Door catalog number 1769 RD 2 per kit Field Wiring Connections Grounding the Module This product is intended to be mounted to a well grounded mounting surface such as a metal panel Additional grounding connections from the module s mounting tabs or DIN rail if used are not required unless the mounting surface cannot be grounded Refer to Industrial Automation Wiring and Grounding Guidelines Allen Bradley publication 1770 4 1 for additional information System Wiring Guidelines Consider the following when wiring your system e Channels are isolated from each other e Use Belden 8761 or equivalent shielded wire e Under normal conditions the drain wire and shield junction must be connected to earth ground via a panel or DIN rail mounting screw at the analog I O module end Keep t
12. er 5 Push the bus lever back slightly to clear the positioning tab 3 Use your fingers or a small screwdriver Publication 1769 INO76A EN P July 2005 Compact 1769 OF4VI Isolated Analog Output Module 5 6 To allow communication between the controller and module move the bus lever fully to the left 4 until it clicks Ensure it is locked firmly in place ATTENTION When attaching I O modules it is very important that the bus connectors are securely locked together to ensure proper electrical connection 7 Attach an end cap terminator 5 to the last module in the system by using the tongue and groove slots as before 8 Lock the end cap bus terminator 6 TENTE 1769 ECR ot 1769 ECL right or left end cap must be used to terminate the end of the serial communication bus Mounting Expansion 1 0 ATTENTION During panel or DIN rail mounting of all devices be sure that all debris metal chips wire strands etc is kept from falling into the module Debris that falls into the module could cause damage on power up Minimum Spacing Maintain spacing from enclosure walls wireways adjacent equipment etc Host Controller Allow 50 mm 2 in of space oO oO lt gt oO oO aya E S Oo fo Compact 1 0 Compact 0 Compact 1 0 on all sides for adequate ventilation as shown Bottom Publication 1769 INO76A EN P July 2005 6 Compact 1769 OF4VI Isolated Analog O
13. he shield connection to ground as short as possible e To ensure optimum accuracy limit overall cable impedance by keeping your cable as short as possible Locate the I O system as close to your sensors or actuators as your application will permit e Load resistance for each voltage output channel must be equal to or greater than 2K QO II In environments where high frequency noise may be present it may be necessary to ground the shield via a 0 1uF capacitor at the load end and also ground the module end without a capacitor Publication 1769 INO76A EN P July 2005 Compact 1769 OF4VI Isolated Analog Output Module 9 Wiring Output Devices Basic wiring of output devices is shown below e Miswiting of the module to an AC DC source will damage the module e Be careful when stripping wires Wire fragments that fall into a module could cause damage at power up Once wiring is complete ensure the module is free of all metal fragments E N C KS GC Vout 0 V out 0 K N C D V out 1 Voltage Load V out 1 R e earth ground N C E Q a V out 2 Ki Q EE N C a GI Vouts V out 3 Gi we ue e Labeling the Terminals A removable write on label is provided with the module Remove the label from the door mark the identification of each terminal with permanent ink and slide the label back into the door Your markings ID tag will be visible when the
14. ication 1769 INO76A EN P July 2005 Compact 1769 OF4VI Isolated Analog Output Module 11 Wire Size and Terminal Screw Torque Each terminal accepts up to two wires with the following restrictions Wire Type Wire Size Terminal Screw Retaining Screw Torque Torque Solid Cu 90 C 194 F 14 to 22 AWG 0 68 Nm 6 in lbs 0 46 Nm 4 1 in lbs Stranded Cu 90 C 194 F 16 to 22 AWG 0 68 Nm 6 in lbs 0 46 Nm 4 1 in lbs 1 0 Memory Mapping Output Data File For each module slot x words 0 3 in the output data file contain the channel 0 through channel 3 output data Word 4 is used to unlatch any alarm condition that has been latched Refer to your module s user manual for additional details B Bit Position 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 SGN Analog Output Data Channel 0 1 SGN Analog Output Data Channel 1 2 SGN Analog Output Data Channel 2 3 SGN Analog Output Data Channel 3 4 UU3 U03 UU2 UO2 UU1 UO1 UUO UO0 e SGN Sign bit in two s complement format e UU Unlatch under range or low clamp exceeded alarm e UO Unlatch over range or high clamp exceeded alarm Publication 1769 INO76A EN P July 2005 12 Compact 1769 OF4VI Isolated Analog Output Module Input Data File For each module slot x input data file words 2 5 contain the state of the module s output
15. isabled 0 Ramping Enabled 1 System Disabled 0 Hit Clamp Enabled i System Disabled 0 Interrupt Low Clamp Enab ed 1 Enable Disabled 0 Channel Enabled 1 Il These functions are not supported by all controllers e g MicroLogix 1500 using any configuration method Refer to your controller manual for details Define Indicate this These bit settings 15114113112111101918171615 4 NNN Output 10 to 10V de 0100 Range Otosvdc loi Select 0 to 10V de 01110 1 to 5V de INN Output Raw Proportional 0 100 Data Counts Select Engineering Units 01011 Scaled for PID 01110 Percent Range 01111 Publication 1769 INO76A EN P July 2005 16 Compact 1769 OF4VI Isolated Analog Output Module Specifications General Specifications Specification Dimensions Value 118 mm height x 87 mm depth x 35 mm width height including mounting tabs is 138 mm 4 65 in height x 3 43 in depth x 1 38 in width height including mounting tabs is 5 43 in Approximate Shipping Weight 270g 0 6 Ibs with carton Storage Temperature 40 C to 85 C 40 F to 185 F Operating Temperature 0 C to 60 C 32 F to 140 F Operating Humidity 5 to 95 non condensing Operating Altitude 2000 meters 6561 feet Vibration Operating 10 to 500 Hz 5G 0 030 in peak to peak Shock Operating 30G 11 ms panel mounted 20G 11 ms DIN r
16. lso contact a special Customer Support number for initial help in getting your module up and running PP ping 8 P 8 United States 1 440 646 3223 Monday Friday 8am 5pm EST Outside United Please contact your local Rockwell Automation representative for any States technical support issues New Product Satisfaction Return Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned United States Contact your distributor You must provide a Customer Support case number see phone number above to obtain one to your distributor in order to complete the return process Outside United Please contact your local Rockwell Automation representative for return States procedure www rockwellautomation com Corporate Headquarters Rockwell Automation 777 East Wisconsin Avenue Suite 1400 Milwaukee WI 53202 5302 USA Tel 1 414 212 5200 Fax 1 414 212 5201 Headquarters for Allen Bradley Products Rockwell Software Products and Global Manufacturing Solutions Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Rockwell Automation SA NV Vorstlaan Boulevard du Souverain 36 BP 3A B 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation 27 F Citicorp Centr
17. nt The channel configuration words the first two words of each eight word group are described on page 14 Refer to your module s user manual for additional details Word Description Word Description 0 Channel 0 Configuration Word 0 16 Channel 2 Configuration Word 0 1 Channel 0 Configuration Word 1 17 Channel 2 Configuration Word 1 2 Channel 0 Fault Value Word 18 Channel 2 Fault Value Word 3 Channel 0 Program Idle Mode Word 19 Channel 2 Program Idle Mode Word 4 Channel 0 Low Clamp 20 Channel 2 Low Clamp 5 Channel 0 High Clamp 21 Channel 2 High Clamp 6 Channel 0 Ramp Rate 22 Channel 2 Ramp Rate 7 Channel 0 Spare 23 Channel 2 Spare 8 Channel 1 Configuration Word 0 24 Channel 3 Configuration Word 0 H Channel 1 Configuration Word 1 25 Channel 3 Configuration Word 1 0 Channel 1 Fault Value Word 26 Channel 3 Fault Value Word 1 Channel 1 Program Idle Mode Word 27 Channel 3 Program Idle Mode Word 2 Channel 1 Low Clamp 28 Channel 3 Low Clamp 3 Channel 1 High Clamp 29 Channel 3 High Clamp 4 Channel 1 Ramp Rate 30 Channel 3 Ramp Rate 5 Channel 1 Spare 31 Channel 3 Spare Publication 1769 INO76A EN P July 2005 14 Compact 1769 OF4VI Isolated Analog Output Module Channel Configuration Words Word Bit E 0 Word 0 Reserved SIU SIO LA ER PM HI PFE Word 1 Reserved Output Data Reserved Output Format Select Type Range E Channel Ena
18. o 2 k worst case calculated Digital Resolution Across Full Range 15 bits plus sign bipolar 10V de 15 89 bits 330 pV bit 0 to 5V dc 13 89 bits 330 yV bit 0 to 10V de 14 89 bits 330 pV bit 1 to 5V de 13 57 bits 330 pV bit Conversion Rate all channels max 120 ms Step Response to 63 lt 2 9 ms Load Output Current 5 mA max Load Range Output gt 2KQ Max Capacitive Load 1 pF Field Calibration Overall Accuracy 3 None required 0 5 full scale at 25 C Il The over or under range flag will come on when the normal operating range over under is exceeded The module will continue to convert the analog output up to the maximum full scale range The flag automatically resets when within the normal operating range unless configured 0 latch 2 Step response is the period of time between when the D A converter was instructed to go from minimum to full range until the device is at 63 of full range 3 Includes offset gain drift non linearity and repeatability error terms Publication 1769 INO76A EN P July 2005 18 Compact 1769 OF4VI Isolated Analog Output Module Specification 1769 OFAVI Accuracy Drift with Temperature 0 0086 FS per C Output Ripple 0 05 range 0 to 50 kHz referred to output range Non linearity in percent full scale 0 05 Repeatability 0 05 in percent full scale Output Error
19. tion 1769 OF4VI System Power Supply Distance The module may not be more than 8 modules away from the system power Rating supply Recommended Cable Belden 8761 shielded Vendor I D Code 1 Product Type Code 10 Product Code 42 Input Words 6 Output Words 5 Configuration Words 32 Hazardous Location Considerations This equipment is suitable for use in Class I Division 2 Groups A B C D or non hazardous locations only The following ATTENTION statement applies to use in hazardous locations ATTENTION EXPLOSION HAZARD e Substitution of components may impair suitability for Class I Division 2 e Do not replace components or disconnect equipment unless power has been switched off or the area is known to be non hazardous e Do not connect or disconnect components unless power has been switched off or the area is known to be non hazardous e This product must be installed in an enclosure All wiring must comply with N E C article 501 4 b Publication 1769 INO76A EN P July 2005 20 Compact 1769 OF4VI Isolated Analog Output Module Environnements dangereux Cet quipement est con u pour tre utilis dans des environnements de Classe 1 Division 2 Groupes A B C D ou non dangereux La mise en garde suivante s applique une utilisation dans des environnements dangereux ATTENTION DANGER D EXPLOSION e La substitution de composants peut rendre cet quipement impropre une utilis
20. unting time during drilling and tapping of the next group TIP 7 Repeat steps 1 to 6 for any remaining modules Publication 1769 INO76A EN P July 2005 Compact 1769 OF4VI Isolated Analog Output Module 7 DIN Rail Mounting The module can be mounted using the following DIN rails 35 x 7 5 mm EN 50 022 35 x 7 5 or 35 x 15 mm EN 50 022 35 x 15 Before mounting the module on a DIN rail close the DIN rail latches Press the DIN rail mounting area of the module against the DIN rail The latches will momentarily open and lock into place Replacing a Single Module within a System The module can be replaced while the system is mounted to a panel or DIN rail Follow the steps below in order 1 Remove power See important note on page 3 On the module to be removed remove the upper and lower mounting screws from the module or open the DIN latches using a flat blade or phillips style screwdriver Move the bus lever to the right to disconnect unlock the bus On the right side adjacent module move its bus lever to the right unlock to disconnect it from the module to be removed Gently slide the disconnected module forward If you feel excessive resistance check that the module has been disconnected from the bus and that both mounting screws have been removed or DIN latches opened TIP It may be necessary to rock the module slightly from front to back to remove it or in a panel mounted system to loos
21. utput Module Panel Mounting Mount the module to a panel using two screws per module Use M4 or 8 panhead screws Mounting screws are required on every module Panel Mounting Using the Dimensional Template Spacing for single wide modules 35mm 1 378 in Spacing for one and a half wide modules 52 5mm 2 067 in Refer to host controller documentation for this dimension mer Note Overall hole spacing tolerance 0 4mm 0 016 in 5 Ss Oo RD S 30535 M Panel Mounting Procedure Using Modules as a Template The following procedure allows you to use the assembled modules as a template for drilling holes in the panel If you have sophisticated panel mounting equipment you can use the dimensional template provided on page 6 Due to module mounting hole tolerance it is important to follow these procedutes 1 Ona clean work surface assemble no more than three modules 2 Using the assembled modules as a template carefully mark the center of all module mounting holes on the panel 3 Return the assembled modules to the clean work surface including any previously mounted modules 4 Drill and tap the mounting holes for the recommended M4 or 8 screw Place the modules back on the panel and check for proper hole alignment 6 Attach the modules to the panel using the mounting screws If mounting more modules mount only the last one of this group and put the others aside This reduces remo
22. w ab com micrologix or www ab com literature e purchase a printed manual by contacting your local distributor or Rockwell Automation representative calling 1 800 963 9548 USA Canada or 001 330 725 1574 Outside USA Canada MicroLogix and Compact are trademarks of Rockwell Automation Belden is a trademark of Belden Inc Publication 1769 INO76A EN P July 2005 22 Compact 1769 OF4VI Isolated Analog Output Module Notes Publication 1769 INO76A EN P July 2005 Compact 1769 OF4VI Isolated Analog Output Module 23 Publication 1769 INO76A EN P July 2005 Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using our products At http support rockwellautomation com you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these ools For an additional level of technical phone support for installation configuration and roubleshooting we offer TechConnect Support programs For more information contact yout local distributor or Rockwell Automation representative or visit http support rockwellautomation com Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation please review the information that s contained in this manual You can a
Download Pdf Manuals
Related Search
Related Contents
MANUAL DE USUARIO 取扱説明書 - ALBIT Page 1 Page 2 Page 3 Page 4 Page 5 Page 6 Page 7 2 医療機君島 Todo al alcance de sus dedos 取扱説明編 - 岩通計測 PR Solo 1200 User Manual AI-15522-1 User Manual, AX50 INSTALLATION MANUAL MANUEL D`INSTALLATION Hampton Bay 27131 Instructions / Assembly DBT Protection Numérique de Supervision de Copyright © All rights reserved.
Failed to retrieve file