Home

LonWorks to Modbus Module

image

Contents

1. Keypad Modbus Port Label i L1 L2 ATV58 D16M2 D46M2 M in Control 2 ATV58 D28N4 D79N4 Board i JL1 jL2 is PA PB U V W ATV58HC10N4X Do Not Use Figure 2 DC Bus Voltage Measurement Point Locations ATV58HU09M2 shown 14 2001 2003 Schneider Electric Rights Reserved VVDED300055USR11 03 Section 2 Hardware Setup and Wiring 11 2003 Mechanical Installation 3 Read the model number of the drive controller from the nameplate and identify the corresponding and measurement points from Table 1 and Figure 2 4 Open the door or cover of the drive controller 5 Set the voltmeter to the 1000 Vdc scale Measure the voltage between the and measurement points identified in step 3 Verify that the DC bus voltage has discharged below 45 V before servicing the drive controller 6 If the DC bus capacitors will not discharge below 45 V contact your local Square D Schneider Electric representative Do not operate the drive controller 7 Replace all covers or doors after servicing the drive controller MECHANICAL INSTALLATION Perform the bus voltage measurement procedure which begins on page 13 before installing the module LonWorks Module The LonWorks module cannot be mounted internally to the ATV58 TRX drive controller 1 Cho
2. Refer to the ATV58 TRX Keypad Display Instruction Bulletin VVDED397047US for more details on how to select between the two modes of local control Remote Auto Control In remote auto control mode The drive controller is managed by the LonWorks serial network The speed reference and the start stop control cannot come from separate sources FORCED LOCAL Switching between local and remote control is achieved by a switch wired to a logic input on the controller terminal block as illustrated in Figures 3 and 4 on page 20 The logic input must be assigned to the function Forced Local When the logic input assigned to forced local is active high all control of the drive controller is assigned to the selected local hand control mode In this case command requests by the LonWorks network are refused Command parameters can be monitored All other adjustment and display parameters can be read write accessed WARNING LOSS OF CONTROL When in forced local mode all commands from the communication ports are ignored Failure to consider the implications of unanticipated operation can result in death serious injury or equipment damage When the logic input is not active low all management of the drive controller is transferred to the LonWorks network if wired as shown in Figures 3 or 4 The only local hand controls that are still monitored by the drive controller include the logic input assigned to Forc
3. This network variable provides the LonWorks master the status of the node comm failure If communication over the Modbus link goes down this is reported by setting this bit in nvoObjStatus out of limits Variables used by the object Possible values of the variables If a command value from the LonWorks master Control Device is out of range for this register it is reported by setting this bit in nvoObjStatus 2001 2003 Schneider Electric All Rights Reserved 31 Section 5 LonWorks Configuration VVDED300055USR11 03 The LonWorks Interface 11 2003 Drive Object Variable Speed Motor Drive 6010 nvoDrvSpeed SNVT_lev_percent nvoDrvCurnt SNVT_amp nviDrvSpeedStpt SNVT switch nviDrvSpeedScale SNVT lev percent Mandatory Network Variables Optional Network Variables nv27 nc23 nciMinSpeed mandatory nv40 nc49 nciSndHrtBt mandatory Configuration nv28 nc20 nciMaxSpeed mandatory nv41 52 nciMinOutTm optional gura nv29 nc158 nciNmlSpeed mandatory nv42 nc48 nciRcvHrtBt optional Properties nv30 nc159 nciNmlFreq mandatory nv43 nc17 nciLocation optional nv31 nc160 nciRampUpTm mandatory nv44 nc52 nciDrvSpeedScale optional nv32 nc161 nciRampDownTm mandatory nvoFreqOut SNVT freq hz nvoDrvPwr SNVT lev percent nvoTemplnvrtr Manufacturer SNVT lev percent Defined nvoMotorTorque Network
4. gt mio SNVT_lev_percent Variables Input SNVT_volt nvoAl2Input mE SNVT amp nvoAl3Input SNVT volt nvoKWH SNVT count nviResetFault nva SNVT switch nv9 Continued on the next page Figure 6 Variables and Configuration Properties in Drive Object 32 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 Section 5 LonWorks Configuration 11 2003 The LonWorks Interface Continued from the previous page nvoAlarmWrd1 SNVT count nvoAlarmWrd2 nvia SNVT count nvoAlarmWrd3 SNVT_count nvoAlarmWrd4 SNVT_count nvoAlarmWrd5 SNVT_count nvoAlarmWrd6 SNVT_count nvoAlarmWrd7 SNVT count nvoAlarmWrd8 SNVT count nvoStatusWord SNVT count Manufacturer Defined Network Variables nv21 nv24 Manufacturer nv33 001 nciEnergSave nv37 SQD5 nciPlIntGain Defined nv34 5002 nciCntrlStop nv38 SQD6 nciCurrLimit Configuration nv35 SQD3 nciPISetPoint nv39 SQD7 nciPlFeedBackScl Properties nv36 SQD4 nciPIProGain nv45 SQD8 nciAcceptAddress E nvoRunTimeHr SNVT count nvoAlarmWord SNVT count nvoDrvStatus SNVT count 2001 2003 Schneider Electric All Rights Reserved e Section 5 LonWorks Configuration VVDED300055USR11 03 The LonWorks Interface 11 2003 Input Network Variables for Drive Control nvi s Table 5 Drive Control Variables nvi s Parameter Variable Name Function This input network vari
5. the power supply connector 5 and the 35 mm DIN rail connector 6 1 4 in 3in 35 mm 77 mm 2 0 in 51 mm 3 7 in 93 mm p m of DIN Rail Mount LONWORKS Status Module Status Service pa Wink Front View Right Side View A 3 0 in 5 77 mm y Bottom View Figure 1 LonWorks Module Layout 12 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 11 2003 Section 2 Hardware Setup and Wiring Bus Voltage Measurement Procedure BUS VOLTAGE MEASUREMENT PROCEDURE Verify that all power has been removed from the ATV58 TRX drive controller as well as from any other connected equipment on the panel or in the enclosure before installing the LonWorks to Modbus module Before connecting the module to the ATV58 TRX drive controller measure the bus voltage as described in this section A DANGER HAZARDOUS VOLTAGE e Read and understand the bus voltage measurement procedure before performing the procedure Measurement of bus capacitor voltage must be performed by qualified personnel DO NOT short across DC bus capacitors or touch unshielded components or terminal strip screw connections with voltage present Many parts in this drive controller including printed wiring boards operate at line voltage DO NOT TOUCH Use only electrically insulated tools Electrical shock will result in death or serious injury The DC bus vo
6. Low network input config The value of the minimum speed must be validated against the value Speed SNVT lev percent of the maximum speed as follows Setpoint nciMinSpeed 0 minimum speed x maximum speed x 163 830 An incoming negative value in nciMinSpeed sets nciMinSpeed to 0 zero Scaling The value sent to the drive 0 005 x nciMinSpeed x nciNmlFreq Valid range 0 to HSP High Speed Setpoint This configuration property is used to define the maximum speed of a motor It s value is entered as a percent of nominal frequency as defined by the Nominal frequency nciNmlFreq configuration value If nciNmIFreq 60 Hz and nciMaxSpeed 120 the maximum speed High network input config is 72 Hz Speed SNVT lev percent The value of the maximum speed must be validated against the value Setpoint nciMaxSpeed of the minimum speed as follows 0 x minimum speed x maximum speed x 163 830 Scaling The value sent to the drive 0 005 x nciMaxSpeed x nciNmlFreq Valid range LSP Low Speed Setpoint to TFR Maximum Frequency Nominal network input config This configuration property is used to enter the nominal speed of the Motor SNVT rpm motor in RPM Enter the value provided on the motor nameplate Speed nciNmlSpeed Valid range 0 to 32767 This configuration property is used to provide the nominal frequency of the motor in Hertz This value is necessary to determine the minimum Nominal network input config j Motor SNVT_freq_hz and maximum
7. TRX Drive Controller Configuration on page 22 16 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 Section 2 Hardware Setup and Wiring 11 2003 Electrical Wiring If the ATV58 TRX drive controller is supplied with a Modbus option card connect the 9 pin Sub D connector on the Modbus cable to the option card Modbus port Refer to the user s manual supplied with the Modbus option card for the location of the port 3 LonWorks connection The LonWorks module accepts a two conductor shielded cable as recommended for LonWorks networks The connector accepts wire sizes from 16 AWG 1 3 mm to 24 AWG 0 5 mm Secure the two conductors of the LonWorks network cable to terminals NET A and NET B of the LonWorks pull apart connector on the front of the module see Figure 1 on page 12 The connections are polarity insensitive Secure the cable shield to the SHIELD terminal Torque these connections to 2 Ib in 0 22 0 25 Nem 4 Power supply connection Connect the two wires from the 24 Vdc power supply to the pull apart terminal block on the bottom side of the LonWorks module Be sure to observe connection polarity Use wire size between 12 AWG 2 5 mm to 24 AWG 0 5 mm Torque these connections to 4 5 Ib in 0 5 0 6 Nem Cable Routing Practices When wiring the ATV58 TRX drive controllers to a LonWorks network follow all wiring practices required by nat
8. key Bit 14 1 Stop from keypad STOP key Bit 15 0 Forward direction of rotation output frequency Bit 15 1 Reverse direction of rotation output frequency 42 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 11 2003 Table 10 Variable Name and Function network output SNVT_count nvoDrvStatus This output register indicates various internal drive states Section 5 LonWorks Configuration The LonWorks Interface Drive Status 2 Variables nvo s Possible Values and Condition Bit 0 0 Write parameters authorized Bit 0 1 Write parameters not authorized EEPROM saving in progress Bit 1 2 0 No parameter consistency check drive controller locked at stop Bit 1 1 Parameter consistency check Bit 2 0 Clear fault not authorized Bit 2 1 Clear fault authorized Bit 3 Reserved Bit 4 0 Motor stopped Bit 4 1 Motor running Bit 5 0 Bit 5 1 Bit 6 0 Bit 6 1 Bit 7 0 No thermal overload alarm Bit 7 1 Thermal overload alarm No DC injection DC injection Drive controller in steady state Drive controller in transient state Bit 8 0 No alarm if excessive braking Bit 8 1 Alarm if excessive braking Bit 9 0 Bit 9 1 Bit 10 0 Drive controller not decelerating Bit 10 1 Drive controller decelerating Drive controller not accelerating Drive controller accelerating Bit 11 2 0 No current limit alarm Bit 11 2 1 Current limit alarm B
9. maintain DC bus p Value 2 Command follow ramp Valid range 0 to 2 Valid range 0 to 10000 Note For an adjustment to PI Setpoint to be valid the ATV58 TRX network input config PI Regulator function must be enabled through Menu 5 of the keypad PI Setpoint SNVT count display or the I O menu in the test and commissioning software nciPISetPoint Connect the PI feedback signal to the analog input on the drive controller terminal strip selected when the PI regulator function is enabled Valid range 1 to 10000 PI network input config Note For an adjustment to PI Proportional Gain to be valid the Proportional SNVT count ATV58 TRX PI Regulator function must be enabled through Menu 5 of Gain nciPIProGain the keypad display or the I O menu in the test and commissioning software betworkinput sont Valid range 1 to 10000 PI Integral p 9 Note For an adjustment to PI Integral to be valid the ATV58 TRX 1 SNVT_count Gain PI Regulator function must be enabled through Menu 5 of the keypad nciPlintGain display or the menu in the test and commissioning software Scaling The value sent to the drive nciPlFeedBackScale 20 PI Feedback network input config Valid range 10 to 1000 Scale Factor SNVT lev percent nciFeedBackScl Note For an adjustment to PI Scale Factor to be valid the ATV58 TRX PI Regulator function must be enabled through Menu 5 of the keypad display or the menu in the test and commissioning software
10. network input config Valid range 10 to 136 of the drive constant torque output current Current SNVT amp rating shown on the drive nameplate Limit MO See Instruction Bulletin VVDED397047US ATV58 TRX Keypad nciCurrLimit Display for further details on the drive current limit function This input configuration network variable defines the maximum period Send network input config of time that expires before nvoDrvSpeed automatically updates Heartbeat SNVT time sec If nciSndHrtBt is set to 0 the Send Heartbeat mechanism is disabled Time nciSndHrtBt SNVT default value 0 seconds Valid range 1 10 seconds 36 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 Section 5 LonWorks Configuration 11 2003 The LonWorks Interface Table 6 Drive Configuration Properties nci s continued Parameter Properties Name Function This input configuration network variable controls the minimum period natwork inbut eenfi of time that expires before the network output variables nvo s can be Minimum a 9 resent This is good for limiting use of bandwidth the LonWorks SNVT_time_sec Send Time nciMinOutTm channel If nciMinOutTm is set to 0 transmission limiting is disabled SNVT default value 0 This configuration property is used to control the maximum time that elapses between updates to either nviDrvSpeedStpt or nviDrvSpeedScale If timeout occurs the Lon
11. speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed entered as percent of nominal Frequency nciNmlFreq frequency Valid range 10 0 to TFR Maximum Frequency Acceleration Time network input config SNVT_time_sec nciRampUpTm This configuration property is used to set the ramp up time Valid range 0 05 to 999 9 Deceleration Time network input config SNVT_time_sec nciRampDownTm This configuration property is used to set the ramp down time Valid range 0 05 to 999 9 2001 2003 Schneider Electric All Rights Reserved 35 Section 5 LonWorks Configuration The LonWorks Interface Parameter Table 6 Properties Name network input config VVDED300055USR1 1 03 11 2003 Drive Configuration Properties nci s continued Function This configuration property enables the automatic energy savings function in the drive controller The drive controller must be set for VT Energy j mode in the Macro Configuration menu k SNVT_switch Saving nciEneraSave State 0 Value 0 Command no automatic energy saving function 9 State 1 Value 100 Command energy saving function enabled Valid range 0 to 1 This configuration property determines how the drive responds and rietwork input eonti stops the motor in the event of a power loss Controlled 9 Value 0 Command no controlled stop SNVT count Stop nciCntrSto Value 1 Command
12. the selector switch Additional ATV58 TRX Drive Controller Configuration Table 2 on page 24 lists the subset of ATV58 drive controller configuration parameters that are accessible both through the drive controller s regular programming tools keypad display or test and commissioning software and over the LonWorks network If using the drive controller s regular programming tools this configuration should be completed before the LonWorks module is connected to the drive controller and configured for operation on the network This is necessary as the module will read drive controller configuration values from the ATV58 TRX drive controller during its power up sequence The LonWorks module does not read the drive controller s configuration parameters each time the LonWorks master requests a value Instead to improve response time for drive controller commands and status data it reads the drive controller s configuration parameters only during initialization after power up and subsequently provides the parameter values from its own internal memory After the module is initialized if a drive controller parameter is changed through a programming tool it is possible that the parameter value stored in the module will not match the value stored in the drive controller and the LonWorks master could read an incorrect value To avoid this situation restart the module after changing any drive controller parameter with a programming tool Als
13. thermal sensor 18 DC bus overvoltage fault 19 Input supply overvoltage fault 20 Motor phase failure fault 21 Input supply phase failure fault gt 1 s 22 Input supply undervoltage fault 200 ms 23 Motor short circuit fault phase to earth 24 Overspeed fault with speed feedback 11 2003 Table 8 Drive Fault Variables nvo s Fault Variable Name and Function network output SNVT count nvoAlarmWord Current This output register displays the currently active fault Fault This register may only momentarily show an integer value before the fault is recorded in the past fault register network output Past Fault 1 SNVT count nvoAlarmWrd1 This output register records the most recent fault network output Past SNVT count nvoAlarmWrd2 Fault 2 This output register records the second most recent fault network output Past Fault 3 SNVT count nvoAlarmWrd3 This output register records the third most recent fault network output Past SNVT count nvoAlarmWrd4 Fault 4 This output register records the fourth most recent fault network output Past Fault 5 SNVT count nvoAlarmWrd5 This output register records the fifth most recent fault network output Past Fault 6 SNVT count nvoAlarmWrd6 This output register records the sixth most recent fault network output Past SNVT count nvoAlarmWrd7 Fault 7 This output register records the seventh most recent fault network output SNVT c
14. DED300055NA 12 2002 11 2003
15. EC 60068 2 3 Ambient temperature Storage 13 to 158 F 25 to 70 C Operation 32 to 122 F 0 to 50 C Altitude 9900 ft 3000 maximum EMC immunity and emissions Complies with IEC 61000 6 Certifications USING THIS MANUAL cULus CE marked To prepare the ATV58 TRX drive controller for connection to a LonWorks network refer to the following sections Section 2 Hardware Setup and Wiring on page 12 e Section 3 Control Modes on page 19 Section 4 ATV58 TRX Drive Controller Configuration on page 22 Section 5 LonWorks Configuration on page 26 For startup refer to Section 6 Minimum Startup Procedure on page 44 Refer to Section 7 Diagnostics on page 46 for troubleshooting assistance For information about specific drive controller parameters see Instruction Bulletin VVDED397047US latest revision ATV58 TRX Keypad Display For information on the installation start up wiring and maintenance of the drive controller refer to the installation guide delivered with the drive controller 2001 2003 Schneider Electric All Rights Reserved 11 Section 2 Hardware Setup and Wiring VVDED300055USR11 03 LonWorks Module Layout 11 2003 SECTION 2 HARDWARE SETUP AND WIRING LONWORKS MODULE LAYOUT Figure 1 identifies the layout of the LonWorks module the LonWorks connector 1 the service pin 2 the diagnostic LEDs 3 the Modbus RJ45 female port 4
16. EK KE or pa RE be DS 21 2001 2003 Schneider Electric All Rights Reserved 5 LonWorks to Modbus Module VVDED300055USR11 03 Contents 11 2003 SECTION 4 ATV58 TRX DRIVE CONTROLLER CONFIGURATION 22 KEYPAD MODBUS co ex kak kk KK E MSS 22 MODBUS OPTION CARD c obe pet e de ea ats 22 FORCED LOCAL FUNCTION dte nion Reps rust 23 ADDITIONAL ATV58 TRX DRIVE CONTROLLER CONFIGURATION 23 SECTION 5 LONWORKS CONFIGURATION 26 OPTIMIZING NETWORK PERFORMANCE 26 INITIAL nant kk mote tese adie Uf KK KK edd 26 LONWORKS MODULE CONFIGURATION 27 NETWORK MASTER DEVICE n o onnaa nnana eee 28 SERVICE PIN e de ato UA a e wek 28 WINK COMMAND iod rbv des inal etu ced aet Evae Cot 28 THE LONWORKS INTERFACE sss else 28 NETWORK VARIABLE TYPES 29 NODE OBJECT etae vete zara ide emus ff dE 30 DRIVE OBJECT Lannan naonna cta DR Ru E MEDII 32 INPUT NETWORK VARIABLES FOR DRIVE CONTROL NVI S 34 INPUT NETWORK CONFIGURATION PROPERTIES FOR DRIVE CONFIGURATION NCI S se eere kK RD KE ket Es 35 OUTPUT NETWORK VARIABLES FOR DRIVE FEEDBACK 5 40 SECTION 6 MINIMUM STARTUP PROCEDURE 44 MINIMUM STARTUP 44 SECTION 7 DIAGN
17. Electric All Rights Reserved 19 Section 3 Control Modes VVDED300055USR11 03 Local and Remote Control Modes 11 2003 See Figures 3 and 4 for assistance in designing Local Off Remote control For the Run Reverse and Forced Local functions select any unused logic inputs on the main control board Assign a logic input to the Run Reverse function only if appropriate for the application 24 Remote Auto Local Hand Off The cross hatch X under the selector switch position indicates a closed contact LI1 Run Forward Run Reverse Lly Forced Local Figure 3 Example 2 Wire Control 24 Local Remote Hand Off Auto The cross hatch X under L 1 Stop the selector switch position LI2 Run Forward indicates a closed contact LIx Run Reverse Lly Forced Local Figure 4 Example 3 Wire Control NOTE While the selector switch is in the remote auto position removing the local run forward or run reverse commands will not stop the drive controller Local Hand Control There are two modes of local hand control The drive controller is managed by operators such as push buttons switches and a speed potentiometer that are wired to the drive controller terminal block or The drive controller is managed by the digital keypad display buttons 20 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 Section 3 Control Modes 11 2003 Forced Local
18. Hz 0 Critical avoidance Frequency frequencies 230 or 400 460 V Nominal 200 to 240 V depends on the Nominal motor voltage Motor 3 UnS or 380 to V main control board given on the motor Voltage 500V Switch for 400 nameplate label 460 V controllers Percent of drive controller s constant torque current rating Nominal Motor 3 nCr 25 to 136 0 1 A Depends on drive See drive controller controller rating nameplate Set this to Current the full load amperage level that appears on the motor nameplate 60 or 72 Hz i Maximum depends on the Dine tFr 40 to 500 Hz maximum operating Frequency main control board frequency switch 2001 2003 Schneider Electric All Rights Reserved 25 Section 5 LonWorks Configuration VVDED300055USR11 03 Optimizing Network Performance 11 2003 SECTION 5 LONWORKS CONFIGURATION OPTIMIZING NETWORK PERFORMANCE To enhance network performance INITIAL POWER UP When structuring the information exchange requirements for a network consider the speed of the communication required to implement the application properly Use the communication method that best matches the speed requirements of the information exchange Communicate information only when required by the application Minimize network traffic by design For example when controlling a simple process requiring only a few control functions send only those registers This minimizes network traffic and maintains
19. LonWorks to Modbus Module VW3A58312PU Instruction Bulletin Retain for future use Schneid Telemecanique A DANGER HAZARDOUS VOLTAGE e Read and understand this bulletin in its entirety before installing or operating Altivar 58 TRX drive controllers Installation adjustment repair and maintenance of the drive controllers must be performed by qualified personnel The user is responsible for conforming to all applicable code requirements with respect to grounding all equipment e Many parts in this drive controller including printed wiring boards operate at line voltage DO NOT TOUCH Use only electrically insulated tools DO NOT short across DC bus capacitors or touch unshielded components or terminal strip screw connections with voltage present Before servicing the drive controller e Disconnect all power including external control power that may be present before servicing the drive controller Place a DO NOT TURN ON label on the drive controller disconnect e Lock the disconnect in the open position WAIT TEN MINUTES for the DC bus capacitors to discharge Then follow the DC bus voltage measurement procedure on page 13 to verify that the DC voltage is less than 45 V The drive controller LEDs are not accurate indicators of the absence of DC bus voltage e Install and close all covers before applying power starting and stopping the drive controller Failure to follow these instru
20. OSTICS o 00 ccc ec cece eese 46 PED STATES Uu cree east sete 46 TROUBLESHOOTING oit autos Mp Made rU Er lee P Ss 47 6 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 Section 1 Introduction 11 2003 Product Overview SECTION 1 INTRODUCTION PRODUCT OVERVIEW The Altivar 58 TRX ATV58 TRX family of adjustable frequency AC drive controllers is used for controlling three phase asynchronous motors They range from e 11075 hp 0 75 to 55 kW constant torque 400 460 V three phase input e 1 to 500 hp 0 75 to 315 kW variable torque 400 460 V three phase input 0 5 to 7 5 hp 0 37 to 5 5 kW constant torque 208 230 V single phase input 0 5 to 30 hp 0 37 to 22 kW variable torque 208 230 V single phase input 21040 hp 1 5 to 30 kW constant torque 50 hp variable torque 208 230 V three phase input This bulletin explains how to integrate an ATV58 TRX drive controller into a LonWorks network with the LonWorks to Modbus module Use this bulletin to install wire and configure the LonWorks module The VW3A58312PU LonWorks to Modbus module is a protocol converter that allows the ATV58 TRX drive controller to be integrated into a new or pre existing LonWorks network with plug and play simplicity The LonWorks module can be incorporated into a new drive installation or can be incorporated with an installed ATV58 TRX drive controller The module uses the Echelon
21. Works module implements two objects one node object and one drive object The node object controls the drive object Objects within a node communicate with other network objects in the same or in other nodes by exchanging network variables Therefore to control and monitor the ATV58 TRX drive controller the LonWorks master must be programmed to read and write the network variables supported by the module Network Variable Types A network variable is an object on one node that can be connected to one or more network variables on one or more additional nodes A node s network variables define its inputs and outputs from a network point of view and allow the sharing of data in a distributed application When a program writes into one of its output network variables the new value of the network variable is propagated across the network to all nodes with input network variables connected to that output network variable For example to turn on a light over a LonWorks network a switch node has its output network variable nvoSwitch connected or bound to the input variable nviSwitch on the lamp node When the switch is activated the network variable is propagated across the network and received by the lamp node which turns on the light The LonWorks to MODBUS module uses two classes of network variable types Standard Network Variable Type SNVT and Standard Configuration PropertiesType SCPT SNVT Standard Network Variable Type T
22. Works module stops all communication with the drive and nviDrvSpeedStpt and network input config nviDrvSpeedScale adopts their default values SNVT time sec nciRevHrtBt If nciRcvHrtBt is set to 0 the Receive Heartbeat mechanism is disabled and the motor will continue to run at its present speed when communication with the LonWorks master is lost SNVT default value 7 seconds Minimum value allowed 1 second Receive Heartbeat Time A WARNING LOSS OF CONTROL If the Receive Heartbeat Time feature is disabled provide another means to control the drive as recommended on page 19 when communication is lost Failure to follow this instruction can result in death serious injury or equipment damage This configuration property can optionally be used to provide more 5 descriptive physical location information than can be provided by the network input config m _ Location neuron chip s 6 byte location string The location relates to the object SNVT str asc Label Heil ocatiori and not to the node Maximum number of ascii characters is 30 NULL terminator SNVT default value Filled up with NULL characters 0 j This parameter is used for setting default value to nviDrvSpeedScale network input config Default SNVT lev percent on every start up Value SNVT default value 0 nciDrvSpeedScale Valid range 163 84 to 163 83 2001 2003 Schneider Electric All Rights Reserved 37 Section 5 L
23. _percent j T Setpoint nviDrvSpeedScale Receive Heartbeat function is set up for use Scaling Valid Range 163 840 to gt 163 830 SNVT default value defined by nciDrvSpeedScale If nviDrvSpeedScale 0 Normal direction If nviDrvSpeedScale lt 0 Reverse direction This input network variable clears the fault in the drive if the fault condition is no longer present State 0 Value 0 Command no action State 1 Value 100 Command reset fault On a transition from 0 to 1 this input network variable clears the fault condition in the drive Following a reset this variable must be set to 0 and sent to the module to enable the next reset SNVT default value 0 NOTE Only resettable faults are cleared See the keypad manual VVDED397047US for a list of resettable faults network input SNVT_switch nviResetFault Fault Reset 34 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 11 2003 Section 5 LonWorks Configuration The LonWorks Interface Input Network Configuration Properties for Drive Configuration nci s Parameter Table 6 Properties Name Drive Configuration Properties nci s Function This configuration property is used to define the minimum speed of a motor Its value is entered as a percent of nominal frequency as defined by the nominal frequency nciNmlFreq configuration value If nciNmIFreq 60 Hz and nciMinSpeed 10 the minimum speed is 6 Hz
24. able provides start stop control and a low resolution speed setpoint When nviDrvSpeedStpt State is set to zero the drive is stopped SNVT default value Default value is AUTO state OxFF This value is adopted at power up and in case of not receiving an update to nviDrvSpeedStpt or nviDrvSpeedScale within receive heartbeat time if used This input network variable may use the Receive Heartbeat nciRcvHrtBt function depending on if Receive Heartbeat function is set up for use The actual value of drive speed does also depend on settings of nviDrvSpeedScale and nciNmlFreq Drive network input Scaling 0 5 x nviDrvSpeedStpt Value up to 200 to get percent value Speed SNVT switch If nviDrvSpeedStpt Value is larger than 200 the percent value is Setpoint nviDrvSpeedStpt set to 10095 nviDrvSpeedStpt State 0 Stop command nviDrvSpeedStpt State 1 Run command Valid Range of nviDrvSpeedStpt State Value Equivalent Requested Percent Speed 0 N A N A STOPPED 1 0 0 0 1 1 to 200 0 5 to 100 0 5 to 100 1 201 to 255 100 100 AUTO invalid This input network variable provides scaling for nviDrvSpeedStpt For example if nviDrvSpeedStpt value is 100 and nviDrvSpeedScale value is 150 then actual speed setpoint value is 150 meaning Drive network input reverse 1 5 times nominal frequency This input network variable may Speed use the Receive Heartbeat nciRcvHrtBt function depending on if A SNVT_lev
25. ation changes to the drive including communication parameters and the forced local function 8 Apply power to the LonWorks module 9 Install Commission the ATV58 TRX drive node using a LonWorks network management tool 10 Configure the ATV58 TRX drive node using the LonWorks network management tool This includes pressing the service pin on the module 11 Use the Drive Speed Setpoint and Drive Speed Setpoint Scaling SNVT s to start the drive and supply it with a speed reference 2001 2003 Schneider Electric All Rights Reserved 45 Section 7 Diagnostics LED States SECTION 7 DIAGNOSTICS VVDED300055USR11 03 11 2003 LED STATES The LonWorks module has four diagnostic LEDs that indicate the status of the module and the communication link with the drive and the LonWorks network see Figure 1 on page 12 Table 11 shows the LED states what they indicate and suggested corrective actions Table 11 LED Status Indicators LED LED Color Function Action Solid green Modbus communication okay No action Cycle 24 power on the module Replace the or off longer Hardware error module if the LED is still lit after next power up than 4 seconds Module Flashing red Seria error Check the connections to the drive controller Modbus link to drive not ji Status 8 times per The module will continue trying to communicate second i
26. cal Wiring on page 16 Wire the selector switch to the ATV58 TRX drive control terminal block Refer to Figures 3 and 4 on page 20 Determine if the keypad display will be normally mounted on the drive controller If the keypad display is not normally mounted to the drive see Keypad Modbus Port on page 22 Connect an ATV58 TRX programming tool to the keypad Modbus port Apply power to the drive Make the needed configuration changes to the drive including communication parameters and the forced local function Remove power from the drive Follow the Bus Voltage Measurement Procedure to ensure it is safe to remove the ATV58 TRX programming tool _ Install the interconnecting Modbus cable between the LonWorks module and the keypad port Reapply power to the drive 44 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 Section 6 Minimum Startup Procedure 11 2003 Minimum Startup Procedure If the keypad display is normally mounted on the drive see Modbus Option Card on page 22 Install the Modbus option card VW3A58303U into the drive On the Modbus card set the address switches for an address of 1 and set the configuration switches for Modbus operation Install the interconnecting Modbus cable between the LonWorks module and the port on the Modbus option card With the keypad display installed apply power to the drive controller Make the necessary configur
27. ciation to define Standard Network Variable Types SNVT Standard Configuration Property Types SCPT and Standard Functional Profile Types SFPT Network Master Device Service Pin Wink Command The LonWorks network must be configured with only one master The master controls the speed scaling and speed set point variables The network master is identified to the module by the nciAcceptAddress variable described on page 38 The LonWorks module has a service pin on the front panel It is used when installing the module as a LonWorks node Pressing the service pin causes the module node to send a message that includes the neuron ID This informs the network or installation tool about the node This command can be issued from the network management tool to visually identify a particular node on the network during installation This causes the LEDs to flash in a sequence Refer to Table 11 on page 46 for the flash sequence THE LONWORKS INTERFACE A LonMark profile defines a functional profile for a node communicating with other nodes on the network A LonMark profile specifies which variables are used and provides meaning to the information they communicate 28 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 Section 5 LonWorks Configuration 11 2003 The LonWorks Interface When a profile is implemented in a node it is called a LonMark object A single node may implement multiple objects The Lon
28. ctions will result in death or serious injury VVDED300055USR11 03 LonWorks to Modbus Module 11 2003 Contents SECTION 1 INTRODUCTION ssssssss eene 7 PRODUCT OVERVIEW otra tae pt etc educ ee SAT 7 DRIVE FIRMWARE 9 REVISION LEVEL heri bor b ri al orice KK KK ra 9 NEW FEATURES OF VERSION 1 1 LONWORKS TO MODBUS GATEWAY 9 RECEIVING PRELIMINARY INSPECTION AND 10 STATIC PRECAUTIONS Unions oes hese satin ages 10 ENVIRONMENTAL SPECIFICATIONS sss eee 11 USING THIS MANUAL veu RO est DESCR ans tst 11 SECTION 2 HARDWARE SETUP AND 12 LONWORKS MODULE LAYOUT ssssssss e esiti 12 BUS VOLTAGE MEASUREMENT PROCEDURE 13 MECHANICAL INSTALLATION tecto tint ob eer duros sais 15 LONWORKS MODULE m res stress 15 24 VDC POWER SUPPLY ssssssss eres sri 16 MODBUS OPTION CARD PART NUMBER VW3A58303U 16 ELECTRICAL WIRING uitae mero buen cec ben rec 16 CABLE ROUTING PRACTICES 17 SECTION 3 CONTROL MODES 19 LOCAL AND REMOTE CONTROL 19 LOCAL HAND CONTROL or oi side hae 20 REMOTE AUTO CONTROL Wu kak kk KK sees 21 FORCED LOCAL cete me curte m ie
29. d the network management tool can be removed from the network At installation each node gets a unique network identity For more information on installing LonWorks nodes see the manual provided with your network installation tool To simplify the installation a number of files are included on the diskette supplied with the LonWorks module They include a Readme file XIF files and Device Resource files NOTE Some network management tools let the user decide if the initial data configuration properties should be loaded from the node or set from the XIF file at the time of commissioning The XIF file helps a network management tool define a device before it is connected to the network as a node 2001 2003 Schneider Electric All Rights Reserved 27 Section 5 LonWorks Configuration VVDED300055USR11 03 The LonWorks Interface 11 2003 To reduce the time needed to install the node the XIF files provide network variables and configuration properties Network variable types Documentation Hardware information such as the transceiver type and initial communication parameters Device Resource Files are included to define the components of an external interface for a LonWorks device They allow installation tools and operator interface applications to properly interpret and format the data sent to them by the LonWorks master These files supplement standard resource files available from the LonMark Interoperability Asso
30. e up in the 1 position 2 Set both of the configuration switches to Modbus JBUS position This is the rightmost position Menu 8 through Keypad Display or Test and Commissioning Software 1 Verify that the address AdrC is set to 1 This is determined by the address switches on the Modbus card 2 Verify that the protocol Pro is set to Modbus RTU 3 Setthe transmission speed bdr to a baud rate of 9 600 bps It is possible to configure bdr to 19 200 bps The module will autodetect to 9600 or 19 200 bps 4 Set format For to 8N1 for 8 data bits no parity and 1 stop bit 5 After changing the baud rate setting of the optional Modbus card cycle power to the LonWorks gateway to re establish communications between the gateway and the drive controller at the new baud rate For more information see Instruction Bulletin VVDED397054US supplied with the VW3A58303U Modbus option card 22 2001 2003 Schneider Electric Rights Reserved VVDED300055USR11 03 Section 4 ATV58 TRX Drive Controller Configuration 11 2003 Modbus Option Card Forced Local Function As described in the section Forced Local on page 21 a logic input must be assigned to the function Forced Local Using the keypad display or test and commissioning software enter the I O Menu Menu 5 on the keypad display Select an unused Logic Input LI and assign it to the function Forced Local FLO Use this logic input for Forced Local when wiring in
31. ed Local and any input assigned to a drive controller stop function Examples include the stop button on the keypad display logic input one LI1 which is assigned to the function STOP if the ATV58 TRX drive controller is configured for 3 wire control and any logic input assigned to the functions freewheel stop DC injection braking and fast stop See the ATV58 TRX Keypad Display Instruction Bulletin VVDED397047US for more details 2001 2003 Schneider Electric All Rights Reserved 21 Section 4 ATV58 TRX Drive Controller Configuration VVDED300055USR11 03 Keypad Modbus Port 11 2003 SECTION 4 ATV58 TRX DRIVE CONTROLLER CONFIGURATION Configuration of the ATV58 TRX drive controller is dependant on which port is used for the Modbus connection to the module KEYPAD MODBUS PORT If the cable from the LonWorks module is attached to the drive controller keypad Modbus port the address of the ATV58 TRX drive controller must be set to 1 Using the keypad display or test and commissioning software set the Add parameter Menu 4 to a value of 1 Do not change the baud rate of the keypad port this renders the keypad inoperable MODBUS OPTION CARD If the Modbus option card part number VW3A58303U is installed in the drive controller and the cable from the LonWorks module is attached to the option card port the following settings must be made Switches on the Modbus Card 1 Setthe card to an address of 1 Only DIP switch 7 should b
32. eedback signal available on the VW3A58202 Digital I O Extension Card an option for the drive Drive network output Total kilowatt hours used since last reset through keypad parameter Kilowatt Hour SNVT count nvoKWH RPR This parameter is only available with drives equipped with firmware version 4 0 and later network output Total run time in hours used since last reset through keypad R n SNVT_count parameter RPR This parameter is only available with drives nvoRunTimeHr equipped with firmware version 4 0 and later 40 2001 2003 Schneider Electric Rights Reserved VVDED300055USR11 03 Section 5 LonWorks Configuration The LonWorks Interface Possible Values and Conditions 0 1 No fault saved Internal fault 2 EEPROM memory fault Configuration parameters incorrect initialization Configuration parameters invalid i As if writing a configuration 5 Standard communication link fault link break 6 Fast communication link fault link break 7 Fast communication NET fault 8 External fault 9 Overcurrent fault prolonged ICL 10 Precharge relay fault 11 Loss of speed feedback fault 12 Ramp not followed 13 Loss of follower fault 14 Thermal sensor fault 15 Motor overheating fault thermal sensor 16 Drive controller overheating fault on heatsink 17 Motor overload fault thermal simulation or
33. er on the module Replace the module if the LED continues to be solid red after cycling power 46 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 Section 7 Diagnostics 11 2003 Troubleshooting TROUBLESHOOTING What will module do if it loses contact with the LonWorks network This occurs when the module can no longer detect the heartbeat variable on LonWorks network When the SNVT specified for receive heartbeat nciRcvHrtBt is not updated within the maximum time allowed since the last update the module will assume a LonWorks network failure The module will stop all communication with the drive and the error will be indicated by the module status LED flashing red 2 times per second The module will remain in this state until an update to either nviDrvSpeedStpt or nviDrvSpeedScale is received from the Master Control Device When LonWorks communication has been reestablished the module will resume normal operation and the module status LED will be set to solid green What will the module do if it loses communication with the ATV58 TRX drive If there is no response to Modbus messages sent to the drive or if the responses indicate too many errors the module status LED will indicate the error by flashing red 8 times per second The module will report the loss of drive controller communication to the LonWorks Master Control Device by use of the SNVT nvoObjStatus All other nvo values will be set to zero Communica
34. four seconds If these self tests detect a failure the LonWorks status LED will remain unlit after four seconds or the module status LED will be lit red continuously After the self test the module assumes default values for all network input variables network output variables and for network configuration variables The module then attempts to establish communications with the ATV58 TRX drive controller If this is not possible the red module status LED flashes rapidly 8 flashes per second to indicate a serial communication problem with the drive The module will attempt to achieve a connection to the drive If communication with the drive is established the module status LED will be set to solid green Once communications have been established with the ATV58 TRX drive controller the module reads initial values from the drive for both drive configuration parameters and for LonWorks network output variables LONWORKS MODULE CONFIGURATION After the ATV58 TRX drive controller has been configured and the LonWorks module has established communications with the drive and downloaded the drive specific information it is ready to be configured and installed as a node on the LonWorks network Address assignment commissioning network variable bindings and configuration must be performed with a LonWorks network management tool The bindings connect network variables on different nodes Once the commissioning and binding is finishe
35. free topology transceiver FTT 10A The transceiver connects to the LonWorks network via a single twisted pair cable with a data transmission rate of 78 kbps The compact module is connected point to point through the supplied 29 5 in 750 mm cable to either the ATV58 TRX integrated keypad Modbus port or to the 9 pin connector on the Modbus option card part number VW3A58303U The user must supply 24 Vdc power separately The module is DIN rail mounted External Interface files XIF versions 4 4 4 1 3 1 and 2 0 and Device Resource files are supplied on diskette 2001 2003 Schneider Electric All Rights Reserved 7 Section 1 Introduction VVDEDS300055USR1 1 03 Product Overview 11 2003 When connected to the LonWorks module the ATV58 TRX drive controller joins other HVAC devices in a low cost building control network As a node on the network the ATV58 TRX drive controller provides the following functions Command and setpoint control e PI process control Adjustment and configuration Monitoring values such as motor speed current and drive status Display of kilowatt hours and total run time on drive controllers with ATV58 TRX drive controller firmware version 4 0 or later Remote fault reset Module and drive controller diagnostics The LonWorks module for the ATV58 TRX drive controller complies with LonMark Interoperability Guidelines Version 3 3 and with the LonMark Functional Profile for Variable Speed Moto
36. he LonMark organization has approved a number of network variables that represent different types of standard data representation for example drive speed current and voltage These network variables are called Standard Network Variable Types SNVTs and are listed in the SNVT Master List and Programmers Guide from Echelon Corporation SNVTs contain information about type resolution and range they may be either nvi network variable inputs or nvo network variable outputs The LonMark association defines objects that can be described as a group of SNVTs used for a specific application 2001 2003 Schneider Electric All Rights Reserved 29 Section 5 LonWorks Configuration VVDED300055USR11 03 The LonWorks Interface 11 2003 SCPT Standard Configuration PropertiesType Configuration properties are used to store parameters that need to be preserved in non volatile memory In the LonWorks to Modbus module Standard Configuration Properties Types SCPTs can be implemented only as network variables The network variables used for parameters are defined to store the information in flash memory onboard the LonWorks to Modbus module The specific objects and variables used by the LonWorks to Modbus module are defined on the following pages For more detail on ATV58 TRX drive controller configuration parameters refer to the ATV58 TRX Keypad Display Instruction Bulletin VVDED397047US Node Object Node Object Ma
37. ional and local electrical codes Avoid areas of high temperature moisture vibration or other mechanical stress Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or twisting the cable Use cable ducts raceways or other structures for protecting the cable These structures should be used for signal wiring paths and should not contain power wiring Avoid sources of electrical interference that can induce noise into the cable Use the maximum practical separation from such sources 2001 2003 Schneider Electric All Rights Reserved 17 Section 2 Hardware Setup and Wiring VVDED300055USR11 03 Electrical Wiring 11 2003 When planning cable routing within a building follow these guidelines Maintain a minimum separation of 3 3 ft 1 m from the following equipment air conditioners elevators escalators large blowers radios and televisions intercom and security systems and fluorescent incandescent and neon lighting fixtures Maintain a minimum separation of 10 ft 3m from the following equipment power wiring transformers generators and alternators When wiring in electrical equipment rooms or large elecirical equipment line ups observe the following guidelines for cable segregation and separation of circuits Use metallic conduit for drive controller wiring Do not run control network and power wiring in the same conduit Separate non metallic conduits or cable
38. is feature provides function related name strings for all network variables 2001 2003 Schneider Electric All Rights Reserved 9 Section 1 Introduction VVDED300055USR1 1 03 Receiving Preliminary Inspection and Storage 11 2003 Network Variable Aliases Version 1 1 supports up to 46 network variable aliases used to circumvent the binding constraints in some installation scenarios Network variables are used when connecting an output variable on one node to several input variables on another single node to ensure that each binding gets a unique selector value Normally the network management tool such as LonMaker for Windows handles the use of network variable aliases making it transparent to the user RECEIVING PRELIMINARY INSPECTION AND STORAGE Before installing the LonWorks module read this manual and follow all precautions Before removing the module from its packing material verify that there is no shipping damage to the packing carton Damage to the packing carton usually indicates improper handling and the potential for device damage After removing the module from its packaging inspect its exterior for shipping damage If any damage is found notify the carrier and your local Square D Schneider Electric representative Do not install a damaged device Ensure that the part number printed on the box label is the same as the number on the packing slip and corresponding purchase order Verify that the information
39. it 12 Reserved Bit 14 0 Bit 13 2 0 Drive controlled via terminals Bit 14 0 Bit 13 1 Drive controlled via keypad display Bit 14 1 Bit 18 0 Drive controlled via keypad Modbus port Bit 14 1 Bit 13 1 Drive controlled via Modbus option card Bit 15 0 Forward direction of rotation requested reference Bit 15 1 Reverse direction of rotation requested reference 2001 2003 Schneider Electric All Rights Reserved 43 Section 6 Minimum Startup Procedure VVDED300055USR11 03 Minimum Startup Procedure 11 2003 SECTION 6 MINIMUM STARTUP PROCEDURE MINIMUM STARTUP PROCEDURE The minimum requirements to command the drive controller from the LonWorks network 1 Ensure that a LonWorks network master is installed and operating and that the network cable has been run out to the ATV58 TRX drive controller location Install the supplied External Interface File XIF and Device Resource Files Mount the LonWorks module to a grounded DIN rail close enough to the ATV58 TRX drive to allow the 29 5 in 750 mm Modbus cable to extend between the Modbus ports on the module and the drive Modbus port without straining either the cable or port connections Refer to LonWorks Module on page 15 Wire an appropriately sized 24 Vdc power supply into the module power supply connector observe polarity Refer to 24 Vdc Power Supply on page 16 Connect the LonWorks network cable to the LonWorks module Refer to Electri
40. k variable provides the drive output current Current SNVT amp nvoDrvCurnt in amperes Output P 7 Frequency to network output Output frequency in Hz Always positive i e no information about Mer Y SNVT freq hz nvoFreqOut direction of revolution forward reverse Drive Output Power network output SNVT lev percent nvoDrvPwr Scaling the value in nvoDrvPwr ATV58 TRX output power measurement x 200 to fit SNVT lev percent resolution Drive NetWork Scaling the value in nvoTemplnvrtr drive thermal state Thermal SNVT_lev_percent measurement x 200 to fit SNVT lev percent resolution State nvoTemplnvrtr Motor output Scaling the value nvoMotorTorque drive calculated motor SNVT_lev_percent Torque torque x 200 to fit SNVT lev percent resolution nvoMotorTorque Signal network output Scaling the value in nvoAl1Input the signal measured at drive Analog Input SNVT volt nvoAl1Input analog input 1 100 to fit SNVT volt resolution Signal 12 network output Scaling the value in 21 the signal measured at drive Analog Input ampil analog input 2 50 to fit SNVT_amp_mil resolution g np nvoAl2Input 9 _ 8 Scaling the value in nvoAl3lnput the signal measured at drive Signal network output analog input 3 100 to fit SNVT volt resolution This function is not Analog Input SNVT volt nvoAl3Input compatible with the encoder f
41. ltage level is determined by monitoring the and measurement points Their location varies by drive controller model number as listed in Table 1 and shown in Figure 2 on page 14 The drive controller model number is listed on the nameplate Table 1 and Measurement Points Measurement Point Measurement Point Drive Controller T inal T inal rmina ermina Catalog Number Terminal Terminal Block or Block d ATV 58900000 Designation Designation Connector Connector U09M2 and U18M2 J2 J2 U29M2 to D12M2 J2 PA J18 7 U18N4 to D23N4 D16M2 to 46 2 J2 D28N4 to D79N4 C10N4X to C33N4X PA PC 2001 2003 Schneider Electric All Rights Reserved 13 Section 2 Hardware Setup and Wiring VVDED300055USR11 03 Bus Voltage Measurement Procedure 11 2003 To measure the DC bus capacitor voltage 1 Disconnect all power from the drive controller including external control power that may be present on the control board and the option board terminals 2 Wait 10 minutes for the DC bus capacitors to discharge The J18 connector is in the upper left hand corner of the main control board behind the flexible shield Use a thin probe to access the connector pin t OOOOOO J18 7 1 ATV58 U29M2 D12M2 J ATV58 U18N4 D23N4 Flexible Shield 1 L1 L2 L3 PA PB U V W ATV58 U09M2 U18M2 a
42. ndatory Network Variables nvoObjStatus nviObjRequest SNVT obj status SNVT obj request n nv0 Figure 5 Node Object 30 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 11 2003 Parameter Node Object Request Table 4 Node Object Network Variable and Status network input SNVT_obj_request nviObjRequest RQ_NORMAL RQ_UPDATE_STATUS Section 5 LonWorks Configuration The LonWorks Interface Function This input provides a way to request a particular mode for a particular object within a node If the object was in the disabled or overridden state this request cancels that state and returns the object to normal operation The status of the object is sent to the output network variable nvoObjStatus The state of the object is unchanged The LonWorks master should issue this request periodically to monitor the status of the module If any active status conditions are reported through nvoObjStatus this request should be followed by CLEAR STATUS so that a new status condition can be reported REPORT MASK The status bits that are supported by the object are sent to the output network variable nvoObjStatus RQ CLEAR STATUS This input clears all object status bits Network variables of type SNVT obj status are used Node Object Status network output SNVT obj status nvoObjStatus t to indicate the status of the various objects within a node
43. nitialized or time out on with the drive controller Modbus communication Check the connection to the LonWorks network Flashing red Heartbeat variable not Ensure that the LonWorks master is operating 2 times per detected no communication properly second with LonWorks master Ensure that the LonWorks master is sending Drive Speed Setpoint and Drive Speed Scaling in the required amount of time has an application The module is ready to be installed with an Flashing green but is not yet installed in a installation tool Service network unconfigured OO Turned off This node I5 Gonfigured and No action installed in network This node is unconfigured Try to reset the module v contigursd by Solid green SM unconfiguring with the installation tool If not and applicationless j i possible there is an internal error in the module Wink Flashing fed This command is sent from an installation tool alternates slow The node has received a 2 en O O when visual identification of the module is eo and fast for LonWorks Wink command desired 20 seconds j Solid green Power on No action LonWork Flashing red It is possible that module will recover from this Ss ome 4 times per Recoverable error error by itself Check LonWorks network wiring second Cycle 24 Vdc power on the module eo The module will not recover from this error by O O Solid red Untecovarable eiror itself Cycle 24 Vdc pow
44. o note that for some LonWorks network management tools it is necessary to synchronize the configuration properties between the management tool and the LonWorks module 2001 2003 Schneider Electric All Rights Reserved 23 Section 4 ATV58 TRX Drive Controller Configuration Modbus Option Card VVDED300055USR11 03 11 2003 Table 2 Drive Controller Configuration Parameters Accessible through the Network Parameter Keypad Keypad 2 Range nits Factory Settin omments Name Menu Code 9 y yS gc pow Speed LSP 0 to setting Hz 0 Setpoint 50 or 60 Hz tFr is the drive controller s High Speed HSP LSP setting to Hz depends on main maximum frequency limit Setpoint tFr setting control board which cannot be set over switch the network Rated RPM as listed on a motor nameplate This Nominal Depends on drive value is used in Motor 3 nSP 0 to 9999 RPM controller rating calculating the drive Speed controller output speed value Rated frequency as listed on the motor nameplate Nominal J This is set by the position depends on main Motor 3 FrS 40 to tFr setting Hz of the 50 60 Hz switch on control board f Frequency the main control board switch The network can overwrite this value Acceleration ACC 0 05 to 999 9 second 3 Time 1 Deceleration dEC 0 05 to 999 9 second 3 Time 1 Choice valid only if drive Energy 3 nLd No yes Yes controller 9610 Saving configuration is set fo
45. on the module nameplate matches the box label Contact your local Square D Schneider Electric representative if there are any errors The package should contain the following four items 1 LonWorks to Modbus module 2 Interconnecting cable from the module to the drive 3 Diskette with External Interface Files XIF and Device Resource Files for the LonWorks installation tool 4 Instruction bulletin Static Precautions Observe the following precautions for handling static sensitive components when removing the module from its packaging for installation Keep static producing material plastic upholstery carpeting etc out of the immediate work area Avoid touching conductors with skin or clothing 10 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 11 2003 Section 1 Introduction Environmental Specifications To store the module replace it in its original package including the antistatic bag and store it in a clean dry area where the ambient is between 13 to 158 F 25 to 70 ENVIRONMENTAL SPECIFICATIONS Enclosure type IP20 Standard EN50178 Resistance to vibration 1 5 mm zero to peak from 3 to 18 Hz 1 g from 13 to 150 Hz IEC 60068 2 6 Resistance to shock 15 g for 11 ms IEC 60068 2 27 Ambient pollution degree Pollution degree 2 IEC 664 1 and UL840 Relative humidity 95 maximum at 50 C non condensing and without dripping I
46. onWorks Configuration VVDED300055USR11 03 The LonWorks Interface 11 2003 Table 6 Drive Configuration Properties nci s continued Parameter Properties Name Function This parameter is used to identify which network master has control over the drive When this feature is enabled the module accepts write commands for nviDrvSpeedStpt and nviDrvSpeedScale only from the specified LonWorks node Instead of a standard variable type SNVT this variable uses a manufacturer defined variable type UNVT address which is defined as follows typedef struct Authorized J network input config Network UNVT address Master nciAcceptAddress short unsigned subnet short unsigned node UNVT address The high byte means SUBNET and the low byte means NODE The function is disabled by writing O to both SUBNET or NODE This enables the drive to be controlled by any node on the network The function is activated when writing values to the nciAcceptAddress variable as seen in this example If the master has address 10 12 SUBNET 10 and NODE 12 then 10 should be written to the first byte SUBNET and 12 should be written to the second byte NODE in nciAcceptAddress 38 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 Section 5 LonWorks Configuration 11 2003 The LonWorks Interface WARNING LOSS OF CONTROL Ensure that the module s Authorized Network Master is a valid host control device at all
47. ontroller recovers from a power up sequence including such unplanned events as an AC line power disturbance it immediately responds to local controls that may be active before the LonWorks module initializes and assumes control of the drive controller This will result in unintended equipment operation It is therefore required that all local run and start commands to the drive controller be removed when the system is in the remote auto mode It is possible to stop the drive controller in the remote auto mode by activating one of the local stop commands such as the keypad display stop button Refer to the discussion of forced local on page 21 4 WARNING UNINTENDED EQUIPMENT OPERATION Commands sent over the LonWorks network can restart the drive controller if the drive controller is not in a forced local condition e Itis necessary to put the drive controller into the forced local mode when the selector switch is in the local hand or off position Failure to follow these instructions can result in death or serious injury The user must provide a 3 position selector switch with the following functionality In local hand mode forced local must be enabled e In off mode all run terminal inputs must be disabled via open circuit and forced local must be enabled nremote auto mode the run terminal inputs must be disabled via open circuit and forced local must be disabled 2001 2003 Schneider
48. ose a location on the panel to mount the module Mount the module as far as possible from the line and load wiring The module should be near enough to the ATV58 TRX drive controller that the supplied 29 5 in 750 mm Modbus cable can extend from the Modbus port on the module to the Modbus port on the ATV58 TRX drive controller Ensure that there is sufficient slack in the cable to avoid stress on the Modbus port connectors Maintain a minimum of 1 in 25 mm spacing around the top and sides of the module Allow 3 in 75 mm minimum on the bottom of the module for making the Modbus and 24 Vdc power connection Maintain minimum spacing from the drive controller as published in the installation guide delivered with the drive controller Do not mount the module in the path of the heated air being discharged from the top of the ATV58 TRX drive controller Ifthe module is mounted below the ATV58 TRX drive controller do not block the airflow circulated through the drive heatsink 2001 2003 Schneider Electric All Rights Reserved 15 Section 2 Hardware Setup and Wiring Electrical Wiring VVDED300055USR11 03 11 2003 2 Securely fasten to the panel DIN rail of sufficient length to allow the module and any necessary end stops to be attached The distance from the top of the module to the center of the DIN rail is 2 in 50 mm 3 Ensure that the DIN rail is properly grounded 4 Attach the module to the DIN
49. ount nvoAlarmWrd8 Past Fault 8 This output register records the eighth most recent fault 1 11 x HSP without feedback 1 2 x TFR The integer value in the register indicates the fault condition 2001 2003 Schneider Electric All Rights Reserved 41 Section 5 LonWorks Configuration The LonWorks Interface Table 9 Variable Name and Function network output SNVT count nvoStatusWord This output register indicates various internal drive states VVDED300055USR1 1 03 11 2003 Drive Status 1 Variables nvo s Possible Values and Condition Bit 0 0 Power not ready Bit 0 1 Power ready for startup Bit 1 0 Drive controller not ready Bit 1 1 Drive controller ready Bit 2 2 0 DRIVECOM stop Bit 2 1 DRIVECOM run Bit 3 0 No fault Bit 3 1 Fault present Bit 4 0 Power present Bit 4 1 Power not present Bit 5 0 Fast stop in progress Bit 5 1 No fast stop Bit 6 0 Status OUTPUT SWITCHING DISABLED Bit 6 1 Status OUTPUT SWITCHING DISABLED freewheel stop Bit 7 0 Alarm absent Bit 7 1 Alarm present Bit 8 1 Reserved Bit 9 0 Local forcing in progress Bit 9 1 No local forcing Bit 10 0 Reference not reached transient state Bit 10 1 Reference reached steady state Bit 11 2 0 LFRD reference normal Bit 11 1 LFRD reference exceeded gt HSP or lt LSP Bits 12 and 13 Reserved Bit 14 0 No stop from keypad STOP
50. r variable torque Drive controller action upon loss of an input Controlled 6 NMS FRP No phase See keypad Stop manual VVDED397047US for further description Percent of drive D pends an drive controller s constant Current Limit 3 CLI 0 to 136 0 1 A p torque current rating See controller rating i drive controller nameplate 24 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 Section 4 ATV58 TRX Drive Controller Configuration 11 2003 Modbus Option Card Table 3 is a partial list of other drive controller configuration changes that may also need to be changed before operating the system These parameters are not accessible over the LonWorks network They must be changed with a programming tool Table 3 Important Drive Controller Configuration Parameters Not Accessible through the Network Parameter Keypad Keypad gt Units Setting Comments Name Menu Code g y g For PI Control and Variable Energy Savings to be Torque Macro CFG Hdg VT GEn Hdg available in the drive Configuration Configuration controller the setting must be VT Percent of drive controller s constant Motor torque current rating Thermal 25 to 136 01A Depends on drive See drive controller Protection controller rating nameplate Set this to Level the full load amperage level that appears on the motor nameplate Jump 2 JPF 0 to HSP
51. r Drives 6010 Version 1 1 Information on the LonWorks network is available from www lonmark org and www echelon com Information on the ATV58 TRX drive controller is available from www SquareD com A WARNING LOSS OF CONTROL The designer of any control scheme must consider the potential failure modes of control paths and for certain critical control functions provide a means to achieve a safe state during and after a path failure Examples of critical control functions are emergency stop and overtravel stop Separate or redundant control paths must be provided for critical control functions System control paths may include communication links Consideration must be given to the implications of unanticipated transmission delays or failures of the link Failure to follow these instructions can result in death serious injury or equipment damage NOTE For additional information refer to NEMA ICS 1 1 latest edition Safety Guidelines for the Application Installation and Maintenance of Solid State Control and to NEMA ICS7 1 latest edition Safety Standards for Construction and Guide for Selection Installation and Operation of Adjustable Speed Drive Systems 8 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 Section 1 Introduction 11 2003 Drive Firmware Compatibility To use the LonWorks module the installer must supply separate equipment Ifthe ATV58 TRX drive controller doe
52. rail The metal plate on the module should contact the DIN rail to provide a ground path 24 Vdc Power Supply 1 The LonWorks module must be supplied with 24 Vdc x 209 It draws a maximum current of 140 mA 2 Follow the manufacturer s instructions when mounting the power supply to the panel Modbus Option Card Part Number VW3A58303U 1 If a keypad display is regularly installed on the ATV58 TRX drive controller a Modbus option card must be installed into the drive controller to supply a Modbus port connection for the LonWorks module 2 Follow the instructions in user s manual VVDED397054US delivered with the Modbus option card to install the card into the ATV58 TRX drive controller ELECTRICAL WIRING 1 Route all wiring to the LonWorks module as far as possible from the drive controller line and load power wiring Avoid parallel cable runs Follow the recommendations in the section Cable Routing Practices on page 17 2 Modbus connection Attach the supplied Modbus cable s RJ 45 connector to the Modbus port on the module see Figure 1 on page 12 Ifthe ATV58 TRX drive controller is not supplied with a Modbus option card connect the 9 pin Sub D connector on the Modbus cable to the keypad Modbus port on the drive controller Refer to Figure 2 on page 14 for the location of the keypad Modbus port Make make this connection after the drive controller configuration has been completed See Section 4 ATV58
53. rk Master variable If appropriate for the application the original master can reclaim control by writing its own address to the module s Authorized Network Master variable To prevent an inappropriate device from being permanently designated as the Authorized Network Master the master can periodically write its own address to the module s Authorized Network Master variable 2001 2003 Schneider Electric All Rights Reserved 39 Section 5 LonWorks Configuration The LonWorks Interface VVDED300055USR1 1 03 11 2003 Output Network Variables for Drive Feedback nvo s Parameter Drive Output Speed Table 7 Variable Name network output SNVT level percent nvoDrvSpeed Drive Output Variables nvo s Function This output network variable provides the speed of the drive controller as a percentage of the nominal speed This output network variable is also periodically transmitted to the LonWorks master so that it serves as a heartbeat signal at the rate specified by nciSndHrtBt to indicate the health of the LonWorks communication interface Calculated as the rate in percent between the drive controller output motor frequency and nciNmlFreq For normal direction this value is positive for reverse direction the value is negative Value in nvoDrvSpeed drive controller output frequency applied to motor nciNmlFreq x 20000 to fit SNVT lev percent resolution Drive Output network output This output networ
54. s not have a keypad display installed a programming option must be supplied only one programming option is necessary to configure one or multiple drives Keypad display part number VW3A58101 PowerSuite Software on CD part number VW3A8104 and PC connection kit part number VW3A8106 For each drive controller that has a keypad display permanently installed supply a Modbus option card part number VW3A58303U A power supply 24 Vdc 2096 for the LonWorks module Each module requires a maximum of 140 mA A 35 mm DIN rail for mounting the module A Local Off Remote operator must be installed as shown on page 20 DRIVE FIRMWARE COMPATIBILITY The LonWorks to Modbus module is compatible with ATV58 TRX drive controllers loaded with firmware version V3 1 IE16 and later Kilowatt hours and total run time values are available with ATV58 TRX drive controller firmware version 4 0 and later The label indicating the firmware version is located on the main control board just above the keypad Modbus port see Figure 2 on page 14 Revision Level This release is for version 1 1 of the VW3A58312PU LonWorks card New Features of Version 1 1 LonWorks to Modbus Gateway Version 1 1 features the following enhancements Network Variable Documentation Strings Documentation strings for all network variables are stored directly in the gateway so you can install the gateway onto a LonWorks system without using the XIF files Th
55. the best overall network speed For better network security keep drive controllers and their associated control devices on the same local network If possible minimize or eliminate the need for drive controller controls to cross repeaters Use distributed control where possible The ATV58 TRX drive controller has a large number of application functions that can be used in conjunction with network communications Use these functions to allow local control by the drive controller while using the network to communicate supervisory information This minimizes the information exchange burden on the network and the controlling device Understand the failure possibilities of the designed network Provide control redundancies and contingencies appropriate for the intended application Follow the wiring practices described in Section 2 Hardware Setup and Wiring on page 12 Improperly installed network wiring can cause noisy or intermittent data transmission with resulting loss of network speed and deterioration of security When the LonWorks module is powered up the following occurs Internal hardware and software tests are performed Three LEDs not the service LED are lit briefly If the module passes the self tests the LonWorks status LED will be lit green after approximately 26 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 Section 5 LonWorks Configuration 11 2003 LonWorks Module Configuration
56. times Failure to follow this instruction can result in death or serious injury While a given LonWorks device is designated as the module s Authorized Network Master it is possible for another device to be designated as the master This allows devices such as a LonWorks configuration tool to assume temporary control of the module s operation When the temporary controller s operations are finished the user must load the original LonWorks master address back into the Authorized Network Master variable so that the original master can resume control of the module If the new master device neither controls the module nor returns control to the original master the module s response depends on its Receive Heartbeat setting f the Receive Heartbeat feature is enabled the module will eventually detect a Receive Heartbeat Fault and stop communications with the drive which will in turn undergo a communications time out and stop the motor fthe Receive Heartbeat feature is disabled the module will continue to communicate with the drive which will continue to operate at its current speed and parameters settings In either case when the original master attempts to write the Speed Setpoint and or Speed Scale parameter to the module the module will refuse the request thus informing the original master that it might not be the Authorized Network Master The original master can verify this by reading the module s Authorized Netwo
57. tion with the Master Control Device will continue The module will keep trying to reestablish Modbus communication with the drive If it succeeds the module status LED will be set to solid green and the program will resume normal operation What will happen if there is an internal problem with the module If there is an internal problem in the module it will suspend all LonWorks and Modbus communication Depending on the type of internal problem either the module status LED will be lit red continuously or the LonWorks status LED will be red either solid or flashing What will happen if the 24 Vdc supply goes out of specification The module has a specified operating range of 19 2 Vdc to 28 8 Vdc Above 30 Vdc a transient diode will start conduct and the module will not work until the power supply is brought within the specified range again The module s operation is unreliable with an input voltage below 19 2 Vdc 2001 2003 Schneider Electric All Rights Reserved 47 LonWorks to Modbus Module Instruction Bulletin Schneider Electric 8001 Highway 64 East Knightdale NC 27545 1 888 SquareD 1 888 778 2733 www SquareD com Electrical equipment should be installed operated serviced and maintained only by qualified personnel No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material VVDED300055USR11 03 2001 2003 Schneider Electric All Rights Reserved Replaces VV
58. trays used to carry power wiring from metallic conduit carrying low level control network wiring by at least 12 in 305 mm Separate metallic conduits carrying power wiring or low level control network wiring by at least 3 in 76 mm Cross the metallic conduits and non metallic conduits at right angles whenever power and control network wiring crosses Attenuate conducted emissions from the drive controller to the line in some installations to prevent interference with telecommunication radio and sensitive electronic equipment Such instances may require filters or line reactors Consult the Altivar 58 TRX AC Drive Catalog 8806CT9901 for selection and application of these filters For additional information on wiring guidelines for LonWorks networks and a list of cable vendors refer to the LonWorks Engineering Bulletin Junction Box and Wiring Guidelines for Twisted Pair LonWorks Networks Part No 005 0023 1 This bulletin is available on the Echelon website at www echelon com 18 2001 2003 Schneider Electric All Rights Reserved VVDED300055USR11 03 Section 3 Control Modes 11 2003 Local and Remote Control Modes SECTION 3 CONTROL MODES LOCAL AND REMOTE CONTROL MODES The ATV58 TRX drive controller can be commanded in local and remote control modes When the ATV58 TRX drive controller is powered up it defaults to local hand control Refer to the discussion of local and remote control on page 20 After the drive c

Download Pdf Manuals

image

Related Search

Related Contents

Hotpoint O3 User's Manual  Lire l`article complet  TOUCHSCREEN Universal Learning Remote Control  Grainmaster i–S ®  Ficha técnica  Manual de instalación  Wireless Presentation System User Manual  documento "Instrucciones resumidas de  Ramón y Cajal: a century after the publication of his  Lire l`article complet  

Copyright © All rights reserved.
Failed to retrieve file