1. ESYLUX ELH CORIDOR AND OPEN AREA LED DALI SELF TEST EMERGENCY LIGHTING MANUAL ELH C LED SC SM EN10080005 ELH C LED SC FM EN10080012 ELH 0 LED SC FM EN10080029 ELH 0 LED SC SM EN10080036 ESYLUX GmbH An der Strusbek 40 22926 Ahrensburg Germany info esylux com www esylux com UW I WN ESYLUX EEN 1 DESCRIPTION EE 4 SAFETY INSTRUCTIONS cccccccuccccccuucucuuucuueauuuuuuuenneauuuuuuuenneuuuuuuutentteuuunnnes 5 INSTALLATION AND COMMISSIONING RR eee nennen nnns 5 OPERATING MODES cccccccccccccuuccuccuuuuuuuucueeauuuuuuuenneuuuuuuuetnnuuuuuunennneuuuunnes 4 1 SELF TEST MODE nnn eene enhn sss sss ss a 7 4 2 OID an 7 TESTING OPTIONS WHEN OPERATING WITH DALI GuUsS 8 5 1 LOCALLY CONTROLLED TESTING i estas ance a ace aate Sa rb Ka Aquen Ee aar e 8 5 2 CENTRALLY CONTROLLED TESTING ccccccccccccccccccccccececcccceceeeeunenunuguueceeentess 8 LOCAL STATUS INDICATORS ccccccccccuccccuccuucucuuuueeueuuuueeneuuuuuenuuuuvensuuuuennsags 9 icc 10 7 1 YPES OF TEST 10 ZllfvpteorrEer re re rera sss assesses aana 10 7 1 2 DURATION TEST 10 7 2 TEST INITIATION 11 7 2 1 TESTS INITIATED AUTOMATICALLY BY THE MODULE ceccececceccececcecceeeeeees 11 7 2 2
2. Connections Power Mains SM Version Power Mains FM Version e DALI LED illuminant e Color rendering index e luminous flux e Energy efficiency class EEG note This luminaire contains built in LED lamps changed in the luminaire Battery e Battery e Charging time e Battery Lifetime Operation and display Green Status LED Temperature range e Operation Environmental conditions Humidity ELH C O LED SC SM FM 16 von 18 ESYLUX 230 V AC 4 3 W 2 5 mm 1 5 mm Bus connection terminal 1 5 mm 5 Ra approx 155 Im A to A The lamps cannot be rechargeable NiCd battery 4 8 V 2000 mAh 20 hours min 4 year 5 C to 35 C max 95 Non condensing MA00683400 USER MANUAL ESYLUX Appearance design SM e Protection type IP 20 e Protection class Installation type Surface ceiling mounting e Dimensions H x W x D 190 mm x 190 mm x 44 mm e Weight kg 1 15 Kg e Material and colour powder coated metal White similar RAL 9016 Appearance design FM e Protection type IP 20 e Protection class e Installation type Recessed ceiling mounting Dimensions Diameter x D 0 55 mm x 25mm e Installation dimension Installation depth 45 mm installation hole size 43 mm e Weight kg 0 42 Kg e Material and colour UV stabilised polycarbonate White similar RAL 9016 CE MARK IN ACCORDANCE WITH e EMC 2004 108 EN 55015 2006 1 2007 2 2009 6
3. TESTS INITIATED BY DALI COMMAND ccceccecceccccceccccccececcecuecuecueaueanes 11 7 3 DELAYED TEST 11 7 4 TESTING DURING PERIODS OF MINIMUM Risk 11 PAUL CONDITIONS dod TUUM NUUS bm 12 8 1 LAMP FAULT cccccccccccccccccccccucscccucccunuuucceeeeenunueceeeennnnguceeeetnnngueeenennes 12 8 2 BATTERY FAULTS cccccceccccccccccucccccccccueucucceeeeeeuuucceeeennnnguceeeetnnunueeenennes 12 8 2 1 BwImrEpRvEAILURE eR Rene nehmen mehrere re esie isses 12 8 2 2 BATTERY CAPACITY INSUFFICIENT TO MEET RATED DURATION 12 8 2 3 BATTERY NOT CHARGING ne he sese serene ases assesses sese sara 12 8 3 DALI BUS FAULT ssssese IIR n RR Rhe rrn nnnm rrr nnns nennen 13 CLEARING FAULT CONDITIONS AND RE COMMISSIONING 13 9 1 CLEARING AN INDICATED EAULT hn nenne nennen nennen nnne 13 9 2 RE COMMISSIONING THE SYSTEM FOLLOWING A LAMP OR BATTERY REPLACEMENT 13 ELH C O LED SC SM FM 2 von 18 0683400 USER MANUAL ESYLUX 10 ADDITIONAL OPERATING MODES ENABLED DALI 14 LOI PROON KEE 14 IO ZINHIBITMODE mmm IRR Rennen nnne nnn rns 14 REST MODE eege e EE EE DEE EES 15 10 4 IDENTIFICATION MODE m IH Rennen rrr enhn rrr rrr 15 11 TECHNICAL DATA EE 16 12 ESYLUX MANUFACTURER S GUARANTEE eeennr RR 18 ELH C O LED SC SM FM 3 von 18 MA00683400 USER MANUAL ESYLUX 1 DESCRIPTION The single battery
4. emergency light illuminate the escape route in the event of failure of the general power supply This light contains built in LED lamps The lamps cannot be changed in the luminaire 30 0 30 0 CO C180 cd 1000 Im CO C180 cd 1000 Im Figure 1 Polar graph ELH C Figure 2 Polar graph ELH C The ELH DALI Digital Addressable Lighting Interface Self test Emergency Lighting modules are designed to be compatible with the DALI Standard IEC 62386 202 as well as the Control Gear Standards IEC 61347 2 72 IEC 61347 2 13 and IEC 62384 and Automatic Test System Standard IEC 62034 The modules are DALI device type 1 and are suitable for use on a dedicated DALI emergency lighting system or in conjunction with other DALI compatible devices as part of a DALI general lighting system The module will adopt a self test automatic test mode If it is not connected to a DALI bus or the DALI communication is missing 62386 202 2009 Digital addressable lighting interface Particular requirements for self contained emergency lighting EC 61347 2 7 2006 Particular requirements for d c supplied electronic ballasts for emergency lighting 3 EC 61347 2 13 2006 Particular requirements for d c or a c supplied electronic control gear for LED modules IEC 62384 2006 A1 2009 DC or AC supplied electronic control gear for LED modules Performance requirements EC 62034 2006 Automatic test systems for battery powered
5. module will adopt a self test automatic test mode If it is not connected to a DALI bus or the DALI communication is missing Whilst in self test mode the module will continue to monitor for a DALI signal and if one is detected the module will go into DALI mode On completion of the self commissioning check see section 3 the self test program starts with the first function and duration tests being carried out after randomly generated delay times which will occur as shown below Subsequent function and duration tests occur after the test interval settings as follows e Delay time to initial function test randomly generated value between O and days e Delay time to initial duration test randomly generated value between 4 and 52 weeks e Function test interval days e Duration test interval 52 weeks 4 2 DALI MODE The module is connected to the DALI bus via the da da terminals which are not polarity sensitive Once the module has received a valid DALI command the module will enter DALI mode and will have the factory set default settings as detailed below e Prolong time e est delay time e Function test delay time MODI ES e Duration test delay time ELH C O LED SC SM FM von 18 0683400 USER MANUAL ESYLUX e Function test interval days e Duration test interval 52 weeks est Execution timeout days Default values are defined in Table 1 of IEC 62386 202 2009 Digital addressable lighting interfa
6. not revert back to self testing mode CLEARING FAULT CONDITIONS AND RE COMMISSIONING A test must be carried out to clear an indicated fault or to re commission the system following a lamp or battery replacement 9 1 CLEARING AN INDICATED FAULT For a lamp or battery fault the cause of the fault must first be corrected and the appropriate test done in order to clear the indicated fault e g a duration test must be done to clear a duration fault NOTE In the case of a battery charging fault the indicated fault clears automatically once the cause of the fault has been corrected and normal charging has been restored A test to clear a fault may be initiated by the method described in section 7 2 9 2 RE COMMISSIONING THE SYSTEM FOLLOWING A LAMP OR BATTERY REPLACEMENT An appropriate test must be carried out to re commission the system following a lamp or battery replacement After a lamp replacement either a function or duration test 15 required After a battery replacement a duration test Is required For modules connected to a DALI bus a function or duration test may be initiated via the appropriate DALI command ELH C O LED SC SM FM 13 von 18 0683400 10 USER MANUAL ESYLUX For modules operating in stand alone mode i e a DALI bus is not connected a duration test may be initiated by disconnecting all power to the module mains and battery and then re connected to initiate self commissioning see section 3 ADD
7. the guarantor will within a reasonable period either repair the device or replace it The guarantee does not cover further claims in particular the guarantor will not be liable for damages resulting from the device s defectiveness If the claim is unfounded e g because the guarantee has expired or the fault is not covered by the guarantee then the guarantor may attempt to repair the device for you for a fee keeping costs to a minimum ELH C O LED SC SM FM 18 von 18 0683400
8. 1547 2009 EN 61000 3 2 2006 A1 2009 A2 2009 EN 61000 3 3 2008 e LVD 2006 95 EC EN 60598 1 2008 EN 60598 2 22 1998 A1 2003 A2 2008 EN 62493 2010 EN 62471 2008 e ROHS 2011 65 EU EN 50581 2012 ELH C O LED SC SM FM 17 von 18 0683400 USER MANUAL ESYLUX 12 ESYLUX MANUFACTURER S GUARANTEE ESYLUX products are tested in accordance with applicable regulations and manufactured with the utmost care The guarantor ESYLUX Deutschland GmbH Postfach 1840 D 22908 Ahrensburg Germany for Germany or the relevant ESYLUX distributor in your country visit www esylux com for a complete overview provides a guarantee against manufacturing material defects in ESYLUX devices for a period of three years from the date of manufacture This guarantee is independent of your legal rights with respect to the seller of the device The guarantee does not apply to natural wear and tear changes interference caused by environmental factors or damage in transit nor to damage caused as a result of failure to follow the user or maintenance instructions and or as a result of improper installation Any illuminants or batteries supplied with the device are not covered by the guarantee The guarantee can only be honoured if the device is sent back with the invoice receipt unchanged packed and with sufficient postage to the guarantor along with a brief description of the fault as soon as a defect has been identified If the guarantee claim proves justified
9. FAULTS For a battery fault the local LED indicator flashes red at either a slow or fast rate according to the type of battery fault 8 2 1 BATTERY FAILURE If the battery is unable to supply the emergency lamp during a function test then bit 2 battery failure and bit 6 function test failed of the FAILURE STATUS information byte are set Additionally the local LED indicator flashes red at a slow rate 8 2 2 BATTERY CAPACITY INSUFFICIENT TO MEET RATED DURATION If the battery has insufficient capacity to supply the emergency lamp during a duration test then bit 1 battery duration failure and bit 7 duration test failed of the FAILURE STATUS information byte are set Additionally the local LED indicator flashes red at a slow rate 8 2 3 BATTERY NOT CHARGING If the module detects that the battery is not being charged then bit 2 battery failure of the FAILURE STATUS information byte is set Additionally the local LED indicator flashes red at a fast rate NOTE The battery charging is ELH C O LED SC SM FM 12 von 18 MA00683400 USER MANUAL ESYLUX monitored continuously whilst the modules are in normal Mains operation Standby mode Therefore if normal charging is restored after a failure has been detected the fault condition clears automatically 8 3 DALI BUS FAULT It is the responsibility of the master controller to report if a bus fault exists and it should be noted that the module does
10. ITIONAL OPERATING MODES ENABLED VIA DALI COMMAND 10 1 PROLONG TIME Prolong time allows the emergency operation to be extended following the restoration of the mains supply Typical applications include HID lamps which when used for normal lighting may not re light immediately following the restoration of the mains supply The prolong time may be set via DALI command from O to 127 5 minutes in units of 0 5 minutes The default factory setting is O 10 2 INHIBIT MODE The activation of inhibit mode causes emergency lamps to be extinguished during active emergency mode automatically upon loss of the mains supply Inhibit mode 15 activated via the DALI command 225 INHIBIT when the module Is in normal operating standby mode NOTE To prevent inadvertent loss of emergency operation inhibit mode is automatically cancelled by the module after a 15 minute timeout period To maintain the inhibit mode longer requires the inhibit command to be repeated within the 15 minute timeout period whereupon the module resets the timeout period for a further 15 minutes Whilst in inhibit mode the local LED indicator is off and slow flashes a double green pulse Inhibit mode may be cancelled when the mains supply is present via the DALI command 226 RE LIGHT RESET INHIBIT ELH C O LED SC SM FM 14 von 18 0683400 USER MANUAL ESYLUX If the mains supply s lost the operation is as described for rest mode see section 10 3 Inhibit mode is
11. ce Particular requirements for self contained emergency lighting Settings may be modified via the DALI bus using the appropriate DALI configuration commands as listed in the DALI Standard IEC 62386 202 If the DALI bus is disconnected the module does not revert back to self test mode i e it will not randomly generate delay times but will use the DALI mode settings 5 TESTING OPTIONS WHEN OPERATING WITH A DALI BUS Modules may be configured for two types of testing regimes when operating with a DALI bus J 1 LOCALLY CONTROLLED TESTING Function and duration tests are initiated by the module i e modules perform automatic self testing according to the locally stored settings NOTE The local settings for test intervals and delay times can be set up by the system commissioning engineer If the settings are left as the factory default values then all the modules may enter test at the same time Polling 15 carried out by the master controller to monitor system operation and to log the test results 9 2 CENTRALLY CONTROLLED TESTING Function and duration tests are initiated by the master controller if the automatic self testing 15 disabled Automatic self testing 15 disabled by setting the test interval times to zero ELH C O LED SC SM FM 8 von 18 0683400 USER MANUAL ESYLUX 6 LOCAL STATUS INDICATORS A single bi colour LED indicates the module status The LED shows permanent green or flashing green when conditions are
12. emergency escape lighting ELH C O LED SC SM FM 4 von 18 0683400 See NOTE All ELH DALI emergency modules are non dimmable i e no arc power commands are supported 2 SAFETY INSTRUCTIONS WARNING Work on electrical systems must be carried out by authorised personnel only with due regard to the applicable installation regulations Switch off the power supply before installing ers the system NOTE this device must not be disposed of as unsorted household waste Used devices must be disposed of correctly Contact your local town council for more Information NOTE used batteries must not be disposed of as unsorted household waste Used batteries must be recycled and may be returned free of charge to the place of sale Batteries contain substances which are harmful to the environment and to human health and must therefore be disposed of correctly d 3 INSTALLATION AND COMMISSIONING The light should only be installed on a stable flat surface Follow the design guide Before installation connect the battery to the emergency light Connect the emergency light according to the circuit diagram ELH C O LED SC SM FM 5 von 18 0683400 TER d a m 230 V supply gt 2 O ur t EN 1 Figure 3 ELH SM Figure 4 ELH FM An automatic self commissioning check will be done once a permanent mains supply and t
13. he battery have been connected to the module This will ensure that the system the emergency lamp and battery are performing correctly Whilst this check is in progress the local LED indicator will slowly flash green and it 15 still possible for the module to be put into a function test to check emergency operation either by a DALI command or by interrupting the mains supply As part of the self commissioning check a full duration test is performed once the battery has been charged for 20 hours If this initial charge period 15 interrupted the charge level is reset to zero and the 20 hour charge period recommences The self commissioning check ends after successful completion of the duration test The local LED indicator then changes to a steady green once the check is complete NOTE If a self commissioning check that is in progress is cancelled due to a module receiving a DALI 229 STOP TEST command It is then the responsibility of the system commissioning engineer to ensure that the modules self commissioning check is completed Automatic self commissioning 15 repeated whenever all power is removed from the module and then restored equally if the battery is fully discharged after an interruption to the mains supply ELH C O LED SC SM FM 6 von 18 MAOO0683400 USER MANUAL ESYLUX 4 OPERATING MODES The ELP DALI modules adapt their operating mode depending on whether a DALI bus signal is connected 4 1 SELF TEST MODE The
14. n 8 Fault conditions the local LED indicator either changes to a permanent or flashing red and the appropriate DALI status flag 15 set 7 1 2 DURATION TEST A duration test simulates a mains failure and checks the operation of the lamp from the battery supply for the rated duration of the module NOTE The battery is required to be fully charged before a duration test can be started If the battery is not fully charged the test is delayed see section 3 The local LED indicator slowly flashes green whilst the duration test is in progress If there is a failure during a duration test the local LED indicator either changes to a permanent or flashing red and the appropriate DALI status flag 15 set ELH C O LED SC SM FM 10 von 18 0683400 USER MANUAL ESYLUX 7 2 TEST INITIATION Tests may be initiated in two ways 7 2 1 TESTS INITIATED AUTOMATICALLY BY THE MODULE Modules perform automatic function and duration tests as per locally stored settings 7 2 2 TESTS INITIATED BY DALI COMMAND Function and duration tests can be requested by the DALI commands 227 START FUNCTION TEST and 228 START DURATION TEST respectively 7 3 DELAYED TESTS If local conditions prevent a test from starting immediately the start of the test is delayed and the module sets the respective test pending flag in the EMERENCY STATUS information byte A module may delay a test for the following reasons e insufficient battery charge e a
15. normal and permanent red or flashing red if a fault condition 15 present Two flashing rates are used e Slow flash 0 5 Hz a flash every 2 seconds e Fast flash 2 0 Hz a flash every 0 5 second A full description of the indicator codes is given in following table MODULE MODE INDICATOR LED STATUS EMERGENCY LAMP Mains operation Permanent green Normal Off mode Standby mode Function test in Fast flashing green Normal On progress Duration test in Slow flashing green Normal On progress Commissioning in Slow flashing green Normal Off except during progress testing Identification mode Slow flashing Normal Off alternating green red Prolong mode Off Normal On Inhibit mode Slow flashing Normal Off double pulse green Rest mode Green slow flashing Normal Off double pulse off Emergency operation Off Normal On mode ELH C O LED SC SM FM 9 von 18 MA00683400 Seer Lamp fault Permanent red Fault Off Battery Test failure Slow flashing red Fault Off Battery charging Fast flashing red Fault Off failure Loss of mains and Off Fault Off battery supply TESTING 7 1 TYPES OF TEST Modules perform two types of test as defined in IEC 62034 7 1 1 TYPES OF TEST A function test is a 30 second test that simulates a mains failure and checks the operation of the lamp from the battery supply The local LED indicator fast flashes green whilst the function test is in progress If there is a failure during a function test See sectio
16. nother test is in progress e the permanent mains supply has been interrupted e the module is waiting for a period of minimum risk see section 7 4 A delayed test is executed automatically by the module once conditions permit If a delayed test cannot be executed by the module within the TEST EXECUTION TIMEOUT period this is then set in the respective part of the FAILURE information byte 1 4 TESTING DURING PERIODS OF MINIMUM RISK This is applicable to switch maintained applications only i e a switched live feed must be connected to the module When automatic self testing is enabled the modules adjust the start time of tests automatically to coincide with periods when the switched live feed from the local switched lighting circuit is off a period of minimum risk If the switched live feed from the local switched lighting circuit is permanently on tests are started following a period equal to half the TEST EXECUTION TIMEOUT ELH C O LED SC SM FM 11 von 18 MAOO0683400 USER MANUAL ESYLUX NOTE The testing during periods of minimum risk feature does not apply to tests that are requested via DALI command FAULT CONDITIONS The local LED indicator is permanently red or flashes red if a fault is detected by the module 8 1 LAMP FAULT For a lamp fault the local LED indicator remains permanently red and the appropriate DALI status flag is set A lamp fault may be recorded during a function or duration test 8 2 BATTERY
17. then cancelled automatically when the mains supply is restored NOTE It is the responsibility of the person operating the DALI system to ensure that the activation of inhibit mode does not result in a hazardous condition in the event of actual mains failure 10 3 REST MODE The activation of rest mode allows emergency lamps to be extinguished during active emergency mode to prevent unwanted discharge of batteries e g if a building is unoccupied Rest mode is activated via the DALI command 224 REST when the module is in active emergency mode Whilst in rest mode the local LED indicator is green and slow flashes a double pulse oft Rest mode is cancelled automatically when the mains supply is restored NOTE It is the responsibility of the person operating the DALI system to ensure that the activation of rest mode does not result in a hazardous condition in the event of actual mains failure 10 4 IDENTIFICATION MODE Identification mode allows for the physical location to be identified during system commissioning or when locating a fault Module start or restart a 30 second identification procedure when the DALI command 240 START IDENTIFICATION is received When the identification mode is active the local LED indicator alternates red and green at a slow flash rate ELH C O LED SC SM FM 15 von 18 0683400 USER MANUAL 11 TECHNICAL DATA Power supply e Operating voltage e Approx power consumption
Download Pdf Manuals
Related Search
Related Contents
Teléfono con Altavoz de Dos Líneas con Identificador de Llamada Audioline POWER PMR 44 Mode d`emploi Asunto: Régimen opcional de solicitud de intervención del Imp X7-S_fr:1_Impressa X7-S_D Samsung NV7 OPS User Manual HP LaserJet 3050z Getting Started Guide しおがま水道ガイド帳(PDF:2545KB) 送り付(6A迄】 座 安全に関するご注意 Copyright © All rights reserved.