Home

User Manual

image

Contents

1. 5B 5C UNIT mm Outline and Drilling Diagram Figure 1 The EAO7 is equipped with adjustable under frequency protection and adjustable over excitation voltage protection for preventing generator from over loading or over excitation Both protections status are indicated by two individual LED when protection is activated Also the AVR has a built in EMI filter to prevent interference to the generator Over Excitation Protection 40 Max VDC 0 3 20sec Under Frequency Protection Adjustable range 42 60 Hz EMI Suppression Internal electromagnetic interference filtering Unit Power Dissipation Max 5 watt Operating temperature 40 65 C Storage temperature 40 80 C Dimensions 97mm L 92mm W 39mm H Weight 2759 2 ATTENTION AVR can be mounted directly on the engine genset switchgear control panel or any position that will not affects operation For dimension reference please see Figure 1 All voltage readings are to be taken with an average reading voltmeter Meggers and high potential test equipment must not be used Use of such equipment could damage the AVR Secure all wiring connection Do not install AVR at a place with high vibrations to prevent loose connections For safety do not touch the heat sink while in operation Fuse specification 20mm 6 3A 250V EA07 3 WIRING ADJUSTMENTS 3 1 Field Excitation Wiring 3 F 1 F e Connect AVR terminal 3 to
2. field connect AVR terminal 1 to the field NOTE The Exciter field resistance is between 10 100 Ohm e field resistance is less than 10 Ohm when generator is under full load and the field voltage is under the maximum output please series a suitable wattage W resistor to have the overall field resistance to equal to 10 100 Ohm 3 2 Sensing Input 4A 5 The rated sensing input range is 90 to 350VAC If the generator voltage is greater than the rated please connect through N Neutral to phase Reference from Figure 2 3 3 Frequency Selection 6 5A When the terminals 6 amp 5A on the AVR are bridged the system frequency is 60Hz In the contrary when bridge is removed the system frequency is 50Hz 3 4 External Voltage Adjustment VR 7 5B Connect a 100K Ohm 1 2W voltage rheostat at VR terminals to enable a 7 voltage adjustment from rated voltage The terminals must be bridged when the external voltage adjustment function is none required 3 5 Power Input 3A 5C The Power input range is 80 to 270VAC connecting from either main winding or auxiliary winding 3 6 VOLT Voltage Adjustment User can adjust the generator voltage by rotating the VOLT potentiometer on the AVR Rotate the potentiometer clockwise to increase voltage and decreasing when rotate counterclockwise The voltage adjust rate is less than 1 when the power factor equals to 1 to 0 8 PF 1 to 0 8 a
3. supplied spare protection fuse for fuse replacement x Please accept our sincere apology if any modification in performance specification or appearance is made without prior notice EA07 5
4. BAO Generator Automatic Voltage Regulator Operation Manual Suitable for Single or Three Phase Self Excited Brushless Generator Compatible replacement for Mecc Alte SR 7 Not a genuine Mecc Alte product HURRA LARAOS KUTAI ELECTRONICS INDUSTRY CO LTD Headquarters No 3 Lane 201 Chien Fu ST Chyan Jenn Dist Kaohsiung TAIWAN Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw 1 SUMMARY 5107 is a self excited Analogue type Automatic Voltage Regulator The sensing and power inputs are independent and accept power input from the auxiliary winding The wide voltage adjustment range fulfills any voltage adjustment requirements 2 SPECIFICATION Sensing Input 4A 5 Voltage Range 90 350VAC 1 phase 50 60Hz Power Input 3A 5C Voltage 80 270V 1 phase 50 60Hz Output F F Voltage Max 63 VDC 220VAC Current Continuous 6A Max Intermittent 7A for 10 sec Exciter Field DC Resistance 10 100 Ohm Voltage Regulation lt 1 with 4 engine governing Voltage Build up Residual voltage at AVR terminal gt 5 VAC 25Hz External Volts Adjustment 100K ohm 1 2 watt 7 Be ou 16 3 810 DOA aVlS ZH P dN 30 ore SINE WARNING High Temperature hd 1000 00 D DOO 1 2 3 3A 4 4A 5 6 SA 7
5. R or the exciter e Adjustment procedure 1 Start generator and let voltage build up 2 Adjust engine frequency to the appropriate low frequency value 3 Slowly adjust Hz Potentiometer until the U F LED illuminates 4 Finally adjust the engine frequency until the LED is turned off 4 OPERATION PROCEDURE 4 1 Please confirm the follow condition before starting the generator e Starting Setting 1 Confirm if the AVR specification conforms to the system requirements 2 Confirm the AVR wiring 3 Confirm correct frequency selected 4 Confirm the generator rated voltage with the AVR sensing input 5 Adjust VOLT potentiometer fully counterclockwise Adjust STAB potentiometer to the center position Adjust AMP potentiometer fully clockwise 4 2 Starting Generator 1 Reconfirm all setting and wiring ATTENTION The AVR reading AC voltage are all average value 2 Start generator and adjust to rated frequency The first measured voltage value should be under the rated voltage If not then reconfirm the start setting 3 Slowly adjust VOLT potentiometer to the rated voltage at this time the generator voltage may become unstable Adjust the STAB potentiometer anticlockwise until the oscillation stabilizes Over adjustment may cause short oscillation when load applied or load type varies SUGGESTION Adjust the STAB potentiometer to the point where the oscillatio
6. n occurs and then adjust the potentiometer counterclockwise by 1 6 of rotation 4 If voltage can not be adjusted or to the rated value please check to see if the generator frequency is too slow Under frequency protection activated If residual voltage is below 5VAC then please execute field flashing to help build up the residual voltage 5 Make sure the generator and AVR are both under normal operation conditions 6 The voltage adjustable range should be 1 under no load or full load If the adjustable range in not within such range please check the below e Generator under frequency Lower than low frequency protection knee point e Severely deformed generator output wave form e Capacitive load over ratio Power factor in lead e Change the AVR and restart e Under over excitation voltage protection Overload protection 4 3 Field Flashing When the regulator is operated with the generator for the first time the polarity residual magnetism may not correct or the magnitude not enough If the generator does not build up after startup shut down the prime mover and proceed with the following steps 1 Stop generator operation disconnect AVR and wirings then apply a DC source Not grounded of not more than 12VDC to generator F Positive and F Negative in series with a limiting resistor of 3 to 5 ohms 20 watt 2 Allow approximately 3 seconds before removing the dc source 3 Start generato
7. nd frequency variation within 696 EA07 3 7 STAB Stability Adjustment e Slowly and precise adjustment of STAB potentiometer can change the respond time between the AVR and generator Inadequate adjustment will cause voltage instability and over adjusting will cause sudden overly voltage variation under heavy load e Analogue type multi voltmeter is suggested when adjusting the voltage stability Adjust the STAB potentiometer until the pointer on the multi voltmeter is oscillating to its minimal 3 8 Circuit Protection e AMP Over Excitation Protection Adjustment Overload protection Set the AMP Overload protection value according to the generator maximum excitation voltage 40 Max VDC When over excitation occurs maintain the status for a short period of time then decrease the generator voltage down to residual voltage When the Over excitation protection is activated the O E LED will illuminate the higher the over excitation value is the shorter delay time becomes The generator will require stopping operation to reset NOTE When AMP potentiometer is adjusted fully clockwise the Over Excitation protection will be disabled e Hz Under Frequency Protection Adjustment Hz Is used to set the under frequency protection knee point When the generator frequency declines to setting point the generator voltage will also decrease in the same time to prevent high excitation current from damaging the AV
8. r and measure residual voltage at generator leads 3A 5C If measured voltage is greater then 5VAC please carefully reconnect all AVR wirings Please repeat field flashing procedure if less than 5VAC residual voltage is measured 4 f residual voltage is greater than 5VAC but AVR still unable to build up voltage please replace with another AVR WARNING Overly field flashing may damage the AVR or generator excitation winding 4 4 Maintenance Regular maintenance to make sure the AVR surface is clean and free from oil or moisture All connection terminals and wirings must be firmly tightened and no signs of visible oxidation or erosion EA07 TI TI 170A 8VlS ZH dV a n 3 0 P m OO m x lt WARNING High Temperature m Y JJ e 334 4 4A 654 7 SBSC DO OE D CDU CN C i E n AR AJ v 66 9 m m NI 1400 se m L e _ E 8 S O0 HOIVIS Figure 2 Diagram X Use only original