1. Code Description In Hexadecimal 8000 No active error 1102 Discharge Temperature high 1108 Internal thermostat detector working 49C 1110 Outdoor unit fail 1300 Pressure low 1302 Pressure high High pressure probe working 63H 1503 Protection against freeze or battery high temperature 1504 Protection against freeze or battery high temperature 1504 Over heating protection 1509 High pressure error ball valve closed 1520 Super heating anomaly due to low temp of discharge TH4 2500 Erroneous operation of drain pump 2502 Erroneous operation of drain pump 2503 Drain sensor anomaly DS 4030 Serial transmission error 4100 Compressor pause due to excess of current initial block 4101 Compressor pause due to excess of current overload 4102 Phase detection opened 4103 Anti phase detection 4108 Phase opened in phase L2 or connector 51CM opened 4118 Error in the anti phase detector electronic board 4124 Connector 49L opened 4210 Cut due to over current of compressor 4220 Voltage anomaly 4230 Radiator panel temperature anomaly TH8 5101 Ambient temperature probe anomaly TH1 indoor unit 5102 Liquid probe anomaly TH2 5102 Cond Evap probe anomaly TH5 5104 Error detection in discharge temperature 5105 Outdoor probe error TH3 5106 Outdoor probe errorTH7 5107 Outdoor probe errorTH6 5110 Outdoor probe errorTH8 5202 Connector 63L opened 5300 Current probe error 6600 MNET duplicated add
2. Present value in unit once indoor unit is powered and ME AC LON 1 is in configured online mode Default Service Type Acknowledged Update Rate The value is defined by cpSndHrtBt Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf Intesis Software S L All rights reserved z URL http www intesis com n tes IS E email info intesis com 9 Sol are IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 nv9 nviFanSpeed network input SNVT switch nviFanSpeed This input network variable is used to change fan speed of the indoor unit Valid Range See section 6 for detail on indoor unit model differences and function availability Unit Command NV content AUTO state 0 LOW state 2 1 AND 0 s value lt 25 MID 1 state 2 1 AND 25 value x 50 MID 2 state 2 1 AND 50 value lt 75 HIGH state 2 1 AND 75 value x 100 nv10 nvoFanSpeed network output SNVT switch nviFanSpeed This output network variable indicates present fan speed of the indoor unit Valid Range See section 6 for detail on indoor unit model differences and function availability Unit Status NV content AUTO state 0 value 0 LOW state 1 value 25 MID 1 state 1 value 50 MID 2 state 1 value 75 HIGH state 1 value 100 Default Value Present value in unit once indoor unit is power
3. 100 Default Value Present value in unit once indoor unit is powered and ME AC LON 1 is in configured online mode Default Service Type Acknowledged Update Rate The value is defined by cpSndHrtBt Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf X i URL http www intesis com a Intesis Software S L All rights reserved ntes IS E email info intesis com 11 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 aand ict nv13 nviSetPoint network input SNVT temp p nviSetPoint This input network variable controls temperature setpoint of the indoor unit As per LonMark standard SNVT temp p uses SI units Celsius as in general all LonMark compliant SNVTs do there is no native Fahrenheit support in LonWorks Though user might want to represent this value at user level interface in other non SI units e g Fahrenheit LonWorks visualisation and network management tools TAC Vista LonMaker generally allow transforming a value contained in a SNVT temp p into the Fahrenheit scale for end user convenience Valid Range See section 6 for detail on indoor unit model differences and function availability 16 319C nv14 nvoSetPoint network output SNVT temp p nvoSetPoint This output network variable indicates present temperature setpoint of the indoor unit As per LonMark standard SNVT temp p uses SI units Celsius as i
4. S L All rights reserved ntes IS E email info intesis com software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 PCA RP GA Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO LOW MID1 MID2 HIGH 1 3 4 5 6 17 28 19 30 19 30 19 28 HIGH speed may not be available in some older versions of this AC type PCA RP KA Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO AUTO LOW MID1 MID2 HIGH 0 1 2 3 4 5 6 17 28 19 30 19 30 19 28 PEA RP200 Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO LOW MID2 no vanes 17 28 19 30 19 30 19 28 PEA RP400 Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO single fan speed no vanes 17 28 19 30 19 30 19 28 PEAD JA Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO AUTO LOW MID1 MID2 no vanes 17 28 19 30 19 30 19 28 PEAD RP Temperature Set P
5. the indoor unit Valid Range Unit Status NV content ON value 100 state 1 OFF value 0 state 0 Default Value Present value in unit once indoor unit is powered and ME AC LON 1 is in configured online mode Default Service Type Acknowledged Update Rate The value is defined by cpSndHrtBt Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf Intesis Software S L All rights reserved z URL http www intesis com n tes IS E email info intesis com 8 Sol are IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 nv7 nviMode network input SNVT hvac mode nviMode Valid Range This input network variable is used to change the operation mode of the indoor unit See section 6 for detail on indoor unit model differences and function availability Unit Command NV content AUTO HVAC AUTO 0 HEAT HVAC HEAT 1 DRY HVAC PRE COOL 5 COOL HVAC COOL 3 FAN HVAC FAN ONLY 9 FAN Any other n nv8 nvoMode network output SNVT hvac mode nviMode Valid Range This output network variable indicates present operation mode of the indoor unit See section 6 for detail on indoor unit model differences and function availability Unit Status NV content AUTO HVAC AUTO 0 HEAT HVAC HEAT 1 DRY HVAC PRE COOL 5 COOL HVAC COOL 3 FAN HVAC FAN ONLY 9 Default Value
6. 0 seconds 277Vrms continuous Lonworks Media Compatible with TP FT 10 channels FTT 10 and FTT 10A Compatible with LPT 10 Link Power Transceivers Lonworks Network polarity Polarity insensitive AC Unit connection 58 mm LonWorks Port oe Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf X i URL http www intesis com a Intesis Software S L All rights reserved ntes IS E email info intesis com 25 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 5 AC Unit Types Prefix first part of the AC unit model number Line MFZ KA Domestic MLZ KA Domestic MSZ FA Domestic MSZ FD Domestic MSZ GA22 MSZ GA25 MSZ GA35 Domestic MSZ GABO MSZ GA60 MSZ GA71 Domestic MSZ GB Domestic MSZ GC Domestic MSZ GE Domestic PCA RP GA Mr Slim PCA RP KA Mr Slim PEA RP200 Mr Slim PEA RP400 Mr Slim PEAD JA Mr Slim PEAD RP Mr Slim PEFY P20 140VMA E City Multi PEH RP200 250 Mr Slim PKA RP35 50HAL Mr Slim PKA RP60 71 100KAL Mr Slim PKA RP100FAL Mr Slim PLA RP AA2 Mr Slim PLA RP BA Mr Slim PSA Mr Slim SEZ KA Mr Slim SEZ KD Mr Slim SLZ KA Mr Slim Any AC unit with a model number not specified in this list in column Prefix is not compatible with the interface and can not be used
7. 3 IntesisBox ME AC LON 1 v 1 6 10 User s Manual Rev 3 Intesisg IntesisBox ME AC LON 1 v 1 6 10 User Manual rev Intesis Software S L 2009 All Rights Reserved Information in this document is subject to change without notice No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or any means electronic or mechanical including photocopying and recording for any purpose other than the purchaser s personal use without the written permission of Intesis Software S L Intesis Software S L Mila i Fontanals 1bis 1 08700 Igualada Spain TRADEMARKS All trademarks and tradenames used in this document are acknowledged to be the copyright of their respective holders Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf X i URL http www intesis com a Intesis Software S L All rights reserved ntes IS E email info intesis com 2 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 LonWorks Interface for Mitsubishi Electric air conditioners Compatible with all models of Domestic amp Mr Slim lines Order Code ME AC LON 1 Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf Intesis Software S L All rights reserved URL http www intesis com ntes IS E email info intesis com 3 IntesisBox is a registered trademark of Intesis Software SL t
8. Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf X i oer URL http www intesis com a Intesis Software S L All rights reserved ntes IS E email info intesis com Sol are tel 34 938047134 IntesisBox is a registered trademark of Intesis Software SL IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 6 Available features for each type of AC Unit Each AC unit model has particular features with regard to following functionalities Number of different operation modes Number of different fan speeds Number of different vane positions Range of temperature set points which may also depend on the mode of operation of the unit heat cool In case that network variables nviMode nviFanSpeed nviVanePos or nviSetpoint are written to a value that is not supported by the AC unit under control the AC unit will ignore the setting In general this situation should be avoided only those values supported by the AC unit under control should be written in the appropriate input NV This list shows the available features in each supported AC type MFZ KA Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL AUTO AUTO LOW MID1 MID2 HIGH _ 0 1 2 3 4 5 6 16 31 16 31 16 31 16 31 MLZ KA Temperature Set Point Mode
9. Fan Speed Vane Pos_ Heat Cool Dry Auto HEAT DRY COOL AUTO AUTO LOW MID1 MID2__ 0 1 2 3 4 5 6 16 31 16 31 16 31 16 31 MSZ FA Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL AUTO AUTO LOW MID1 MID2 0 1 2 3 4 6 16 31 16 31 16 31 16 31 MSZ FD Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL AUTO AUTO LOW MID1 MID2 HIGH 0 1 2 3 4 5 6 16 31 16 31 16 31 16 31 MSZ GA22 MSZ GA25 MSZ GA35 Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL AUTO AUTO LOW MID1 MID2 0 1 2 3 4 5 6 16 31 16 31 16 31 16 31 MSZ GA50 MSZ GA60 MSZ GA71 Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL AUTO AUTO LOW MID1 MID2 0 1 2 3 4 5 6 16 31 16 31 16 31 16 31 MSZ GB Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL AUTO AUTO LOW MID1 MID2 0 1 2 3 4 6 16 31 16 31 16 31 16 31 MSZ GC Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL AUTO AUTO LOW MID1 MID2 HIGH _ 0 1 2 3 4 5 6 16 31 16 31 16 31 16 31 MSZ GE Temperature Set Point Mode Fan Speed Vane Pos_ Heat Cool Dry Auto HEAT DRY COOL AUTO AUTO LOW MID1 MID2 HIGH 0 1 2 3 4 5 6 16 31 16 31 16 31 16 31 Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf a URL http www intesis com Intesis Software
10. ble on DIN rail wall or even inside the indoor unit in some models of AC e External power not required e Direct connection to LONWORKS TP FT 10 bus e Direct connection to the AC indoor unit The cable for this connection is also supplied e Configuration from any LONWORKS commissioning tool e Total Control and Supervision e Real states of the AC unit s internal variables e Allows to use simultaneously the IR remote control and LONWORKS meAcLon1 Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf X i URL http www intesis com a Intesis Software S L All rights reserved l ntes IS E email info intesis com 5 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 2 Connection The interface comes with cable connectors for direct connection to the AC indoor unit and with a plug in terminal block of 2 poles for connection to a LonWorks TP FT 10 bus Disconnect mains power from the AC unit Open the front cover of the indoor unit in order to have access to the electronic circuit In the electronic circuit locate the socket connector marked as CN92 in Mr Slim models or CN105 in the rest of models Using the cable that comes with the interface insert one of its connectors the one installed in the shortest uncovered part into the socket of the ME AC LON 1 and the other connector the one installed
11. d by cpSndHrtBt User Manual rev 3 Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf Intesisg Intesis Software S L All rights reserved IntesisBox is a registered trademark of Intesis Software SL URL http www intesis com email info intesis com tel 34 938047134 13 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 nvi5 nvoSpaceTemp network output SNVT_temp_p nvoSpaceTemp This output network variable indicates present ambient temperature measured by the indoor unit As per LonMark standard SNVT temp p uses SI units Celsius as in general all LonMark compliant SNVTs do there is no native Fahrenheit support in LonWorks Though user might want to represent this value at user level interface in other non SI units e g Fahrenheit LonWorks visualisation and network management tools TAC Vista LonMaker generally allow transforming a value contained in a SNVT temp p into the Fahrenheit scale for end user convenience If Fahrenheit end user representation is desired cpTempMagnitude nv4 can be adjusted so that NV nvoSpaceTemp makes slight changes into the set of discrete values it represents so that when nvoSpaceTemp actual value is converted into the Fahrenheit scale by the visualisation network management tool it gives a Fahrenheit value as close as possible to an integer in the Fahrenheit scale See description for cpTempMagnitude nv4 in section 3 3 Valid Range See section 6 fo
12. ed and ME AC LON 1 is in configured online mode Default Service Type Acknowledged Update Rate The value is defined by cpSndHrtBt Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf X i URL http www intesis com a Intesis Software S L All rights reserved ntes IS E email info intesis com 10 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 nvii nviVanePos network input SNVT count nviVanePos This input network variable changes vane position of the indoor unit Valid Range See section 6 for detail on indoor unit model differences and function availability Unit Command NV content AUTO state 0 HORIZ state 2 1 AND 0 lt value x 10 POS2 state gt 1 AND 10 value x 30 POS3 state 2 1 AND 30 value x 50 POS4 state 2 1 AND 50 lt value x 70 VERT state 2 1 AND 70 value x 90 SWING state 2 1 AND 90 value nv12 nvoVanePos network output SNVT count nvoVanePos This output network variable indicates present vane position of the indoor unit Valid Range See section 6 for detail on indoor unit model differences and function availability Unit Status NV content AUTO state 0 HORIZ state 1 value 10 POS2 state 1 value 30 POS3 state 1 value 50 POS4 state 1 value 70 VERT state 1 value 90 SWING state 1 value
13. el 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev INDEX 1 PFESENtAtlON csiri iers r rse dk kn RE EN EEEREN AEE ANER EEEN NENE ANER 5 2 COMME CUO senesne isinira OET ne reine YER E For ENEON viene ven ERE OEA VEEE ENONSE 6 3 LonWorks Interface Specification essssssssssssssssssssseeneseeneneeme memes 7 3 1 Functional Profile iere teitex rem egre ex xem EXE deca deawl aatede A 7 3 2 Network Variables Interface iere coe ete ken axe cesi ties Pa Fr ko na ae a Ria 8 3 3 Configuration Properties eene nene nnn nune naa dana ang Fe Ra Ed 22 4 Specifications ixcessissexe ska x sieges E EARARERREREA AKURERERDA KR KRRPAKNTKRRPRTRKRPEREEAU 25 5 AC Umit TYDES E 26 6 Available features for each type of AC Unit eee eee cetera eee nena eee 27 7 emen 30 Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf URL http www intesis com a Intesis Software S L All rights reserved ntes IS E email info intesis com 4 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 1 Presentation The ME AC LON 1 interface allows a complete and natural integration of Mitsubishi Electric air conditioners into LonWorks networks Compatible with all models of Domestic and Mr Slim line e Reduced dimensions 93 x 53 x 58 mm e Quick and easy installation Mounta
14. in the largest uncovered part to the socket CN92 or CN105 of the AC unit s electronic circuit You can place the ME AC LON 1 inside or outside the AC indoor unit depending on your needs remember that ME AC LON 1 must be also connected to the LonWorks TP FT 10 network Close the AC indoor unit s front cover again Electronic circuit of AC indoor unit CN92 or ME AC LON 1 CN105 b Cable Do not modify the length of the cable supplied with the interface it may affect to the correct operation of the interface Use this hole to fix the cable using the staple and screw provided with the interface Connection cable supplied with the CN105 for Domestic line CN92 for Mr Slim line Consult list of models at the end of interface the document to identify to which line belongs every model AC Unit IntesisBox ME AC LON 1 90 mm SERVICE Lon LONWORKS TP FT 10 Bus Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf URL http www intesis com Intesis Software S L All rights reserved n tes IS E email info intesis com 6 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 3 LonWorks Interface Specification Program Id for firmware release v1 6 10 is 9F FD 51 56 00 06 04 02 Previous older firmware releases have program id 9F FD 51 56 00 06 04 01 3 1 Functional Profile UFPTmeAcLon v2 nviO
15. istered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Me U vanua nv20 nviRmLock network input eeprom SNVT_switch nviRmLock This input network variable is used to disable indoor unit s remote control Value is stored in ME AC LON 1 s eeprom Valid Range Unit Command NV content Remote Control value gt 0 AND state 21 DISABLED Remote Control value 0 OR state 0 ENABLED nv21 nvoRmLock network output SNVT_switch nvoRmLock This output network variable shows current status of remote control disablement Valid Range Unit Status NV content Remote Control value 100 state 1 DISABLED Remote Control value 0 state 0 ENABLED Default Value state 0 value 0 Default Service Type Acknowledged Update Rate This network variable is updated always that its value changes Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf Intesis Software S L All rights reserved z URL http www intesis com n tes IS E email info intesis com 17 IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 nv22 nviOnTimeReset network input SNVT switch nviOnTimeReset This input network variable is used to reset the operation time counter shown in nvoOnTime Valid Range Unit Command NV content RESET nvoOnTime value gt 0 AND s
16. led i e it will be never updated on change Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf Intesis Software S L All rights reserved z URL http www intesis com ntes IS E email info intesis com 21 IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 83 Configuration Properties nvO cpAcModel From firmware version v1 5 9 this cp has been deprecated There is no need to setup the AC unit any more onto ME AC LON 1 device nvi cpWindowTime network input UCPTopenWindowTimeout config prop cpWindowTime This configuration property is used to indicate the timeout that will take for ME AC LON 1 to switch OFF indoor unit after window has been open Value contained in UCPTopenWindowTimeout has the same format as SNVT time min the UCPT type is referenced to this SNVT Valid Range 0730 minutes Factory Settings 0 minutes will switch OFF indoor unit immediately after opening window nv2 cpSndHrtBt network input SCPTmaxSendTime config prop cpSndHrtBt This configuration property defines the maximum time between the previous and next update for following network variables nvoOnOff nvoMode nvoFanSpeed nvoVanePos nvoSetPoint Value contained in SCPTmaxSendTime has the same format as SNVT time sec the SCPT type is referenced to this SNVT Valid Range 0765535 seconds Factory Settings 100 0 seconds Doc Intesi
17. n general all LonMark compliant SNVTs do there is no native Fahrenheit support in LonWorks Though user might want to represent this value at user level interface in other non SI units e g Fahrenheit LonWorks visualisation and network management tools TAC Vista LonMaker generally allow transforming a value contained in a SNVT temp p into the Fahrenheit scale for end user convenience If Fahrenheit end user representation is desired cpTempMagnitude nv4 can be adjusted so that NV nvoSetPoint makes slight changes into the set of discrete values it represents so that when nvoSetPoint actual value is converted into the Fahrenheit scale by the visualisation network management tool it gives a Fahrenheit value as close as possible to an integer in the Fahrenheit scale See description for cpTempMagnitude nv4 in section 3 3 Valid Range See section 6 for detail on indoor unit model differences and function availability 16 319C Default Value Present value in unit once indoor unit is powered and ME AC LON 1 is in configured online mode Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf X i URL http www intesis com a Intesis Software S L All rights reserved ntes IS E email info intesis com 12 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 Default Service Type Acknowledged Update Rate The value is define
18. nOff nvoOnOff SNVT switch SNVT switch nviMode nvoMode SNVT hvac mode SNVT hvac mode nviFanSpeed nvoFanSpeed SNVT switch SNVT switch nviVanePos nvoVanePos SNVT switch SNVT switch nviSetPoint nvoSetPoint SNVT temp p SNVT temp p nvoSpaceTemp SNVT temp p nviWindowContact nvoWindowContact SNVT switch SNVT switch nviDisable nvoDisable SNVT switch SNVT switch nviRmLock nvoRmLock SNVT switch SNVT switch nviOnTimeReset nvoOnTime SNVT switch SNVT time hour nvoAlarm SNVT switch nvoErrCode SNVT count nvoVersion SNVT str asc Configuration O OE cpAcModel SNVT_count nvO cpWindowTime SNVT time min nvi cpSndHrtBt SNVT time sec nv2 cpSndHrtBtTemp SNVT time sec nv3 cpTempMagnitude SNVT count nv4 Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf X i URL http www intesis com a Intesis Software S L All rights reserved ntes IS E email info intesis com software tel 34 938047134 IntesisBox is a registered trademark of Intesis Software SL IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 3 2 Network Variables Interface nv5 nviOnOff network input SNVT switch nviOnOff This input network variable is used to switch On and Off the indoor unit Valid Range Unit Command NV content ON value gt 0 AND state 1 OFF value 0 OR state 0 nv6 nvoOnOff network output SNVT_switch nvoOnOff This output network variable indicates present On Off status of
19. nt or Infrared remote controller and this remote controller is setup in the Fahrenheit scale cpTempMagnitude should be set to Fahrenheit setting so that the values in nvoSetPoint fit with the ones in the remote controller Value contained in UCPTtempMagnitude has the same format as SNVT count the UCPT type is referenced to this SNVT Valid Range 0 Celsius default Set of values for SVWVT temp p will be 10 C to 38 C in steps of 1 C 1 Fahrenheit Set of values for SNVT_temp_p will be 50 F 51 9989F 53 996 F 55 0049F 57 0029F 59 F 60 998 F 62 996 F 64 994 F 66 992 F 68 F 69 0089F 71 0069F 73 0049F 75 002 F 77 F 78 998 F 80 9969F 82 994 F 84 9929F 87 0089F 89 006 F 89 9969F 91 0049F 93 002 F 95 F 96 998 F 98 996 F 100 004 F Factory Settings 0 Celsius Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf X i URL http www intesis com a Intesis Software S L All rights reserved ntes IS E email info intesis com 24 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 4 Specifications Dimensions 93 x 53 x 58 mm Weight 85g Operating Temperature 25 85 C Stock Temperature 40 85 C Operating Humidity 25 90 RH 50 C non condensing Stock Humidity 95 RH 50 C non condensing Isolation voltage 1000Vrms during 6
20. oint Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO LOW MID2 no vanes 17 28 19 30 19 30 19 28 PEFY P20 140VMA E Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO AUTO LOW MID1 MID2 no vanes 17 28 19 30 19 30 19 28 AUTO operation mode is only available when using outdoor units PURY or PQRY PEH RP200 250 Temperature Set Point Mode Fan Speed Vane Pos_ Heat Cool Dry Auto HEAT DRY COOL FAN AUTO single fan speed no vanes 17 28 19 30 19 30 19 28 PKA RP35 50HAL Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO _ AUTO LOW MID1 MID2 0 1 2 3 4 5 6 17 28 19 30 19 30 19 28 PKA RP60 71 100KAL Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO _ AUTO LOW MID1 MID2 0 1 2 3 4 5 6 17 28 19 30 19 30 19 28 PKA RP100FAL Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO LOW MID2 1 3 4 5 6 17 28 19 30 19 30 19 28 PLA RP AA2 Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO _ LOW MID1 MID2 1 3 4 5 6 17 28 19 30 19 30 19 28 PLA RP BA Temperature Set Point Mode Fan Speed Vane Pos_ Heat Cool Dry Auto HEAT DRY COOL FAN AUTO AUTO LOW MID1 MID2 HIGH 0 1 2 3 4 5 6 17 28 19 30 19 30 19 28 Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3
21. ols TAC Vista LonMaker generally allow transforming a value contained in a SNVT temp p into the Fahrenheit scale for end user convenience formally stated and SNVT_temp_p US representation In case of using Fahrenheit end user representation the set of discrete values for nvoSetPoint and nvoSpaceTemp might become troublesome for representation Internally the AC unit works with Celsius temperatures and so do nvoSetPoint and nvoSpaceTemp resulting in strange temperature values when converted to Fahrenheit e g 230C converts to 73 49F 24 C converts to 75 29F In order to have more natural Fahrenheit values cpTempMagnitude lets the integrator specify whether those SNVT temp p values are meant to be converted into Fahrenheit scale at control visualisation level In case that Fahrenheit is configured in cpTempMagnitude the discrete values that nvoSetPoint and nvoSpaceTemp will show up will be specifically adjusted as close as possible to integer Fahrenheit values So for instance instead of representing a value of 239C 73 49F in a SNVT temp p it will represent a 22 789C 73 0049F giving better proximity to a Fahrenheit integer 739F in this case In any case if using Fahrenheit for control visualisation of SNVT temp p variables rounding will be needed for the final value if integers are desired this happens because of the limited resolution of SNVT temp p itself If using ME AC LON 1 along with a Mitsubishi Wall mou
22. pdf a URL http www intesis com Intesis Software S L All rights reserved l ntes IS E email info intesis com 28 IntesisBox is a registered trademark of Intesis Software SL oe tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 PSA Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO LOW MID2 no vanes 17 28 19 30 19 30 19 28 SEZ KA Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO LOW MID2 no vanes 17 28 19 30 19 30 19 28 SEZ KD Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO AUTO LOW MID1 MID2 no vanes 17 28 19 30 19 30 19 28 SLZ KA Temperature Set Point Mode Fan Speed Vane Pos Heat Cool Dry Auto HEAT DRY COOL FAN AUTO _ LOW MID1 MID2 1 3 4 5 6 17 28 19 30 19 30 19 28 Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf a URL http www intesis com Intesis Software S L All rights reserved l ntes IS E email info intesis com 29 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 7T Error Codes
23. r detail on indoor unit model differences and function availability 10 389C Default Value Present value in unit once indoor unit is powered and ME AC LON 1 is in configured online mode Default Service Type Acknowledged Update Rate The value is defined by cpSndHrtBtTemp Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf URL http www intesis com a Intesis Software S L All rights reserved ntes IS E email info intesis com 14 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 nvi6 nviWindowContact network input SNVT switch nviWindowContact This input network variable is used to change the window contact status of the indoor unit Once contact is ON window is open indoor unit will be switched OFF after a timeout configured at cpWindowTime nv1 Valid Range Unit Command Window OPEN Window CLOSED NV content value gt 0 AND state 21 value 0 OR state 0 nvi7 nvoWindowContact network output SNVT_switch nvoWindowContact This output network variable indicates the window contact status of the indoor unit Valid Range Unit Status Window OPEN Window CLOSED NV content value 100 state 1 value 0 state 0 Default Value state 0 value 0 Update Rate This network variable is updated always that its value changes Doc Intesi
24. ress definition 6602 MNET Line transmission hardware error 6603 MNET BUS busy 6606 MNET Line transmission error 6607 MNET transmission error 6607 MNET without ack 6608 MNET transmission error 6608 MNET without response 6831 IR remote control transmission error reception error 6832 IR remote control transmission error transmission error 6840 Transmission error with the indoor outdoor unit reception error 6841 Transmission error with the indoor outdoor unit transmission error 6844 Error in inter connection cable in the indoor outdoor unit indoor unit number deactivated 5 min or more 6845 Error in inter connection cable in the indoor outdoor unit cabling error disconnection 6846 Initial timer deactivated 8001 ME AC LON 1 device communication error 65535 Status of error has not been obtained from AC unit yet initialization value In case you detect an error code not listed contact your nearest Mitsubishi Electric technical support service Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf X i URL http www intesis com a Intesis Software S L All rights reserved ntes IS E email info intesis com 30 software tel 34 938047134 IntesisBox is a registered trademark of Intesis Software SL
25. sBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf URL http www intesis com Intesis Software S L All rights reserved n tes IS E email info intesis com 15 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 nv18 nviDisable network input eeprom SNVT switch nviDisable This input network variable is used to disable enable ME AC LON 1 device Value is stored in ME AC LON 1 s eeprom Once disabled the only input NV active will be this one the rest of input NVs will be disabled To enable again the device just write in this NV the appropriate value state Valid Range Unit Command NV content ME AC LON 1 value gt 0 AND state 21 DISABLED ME AC LON 1 value 0 OR state 0 ENABLED nv19 nvoDisable network output SNVT_switch nvoDisable This output network variable indicates whether ME AC LON 1 is disabled Valid Range Unit Status NV content ME AC LON 1 value 100 state 21 DISABLED ME AC LON 1 value 0 state 0 ENABLED Default Value state 0 value 0 Default Service Type Acknowledged Update Rate This network variable is updated always that its value changes Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf URL http www intesis com Intesis Software S L All rights reserved n tes IS E email info intesis com 16 software IntesisBox is a reg
26. sBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf X i URL http Awww intesis com a Intesis Software S L All rights reserved ntes IS E email info intesis com 22 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 nv3 cpSndHrtBtTemp network input SCPTmaxSendTime config prop cpSndHrtBtTemp This configuration property defines the maximum time between the previous and next update for network variable nvoSpaceTemp Value contained in SCPTmaxSendTime has the same format as SNVT time sec the SCPT type is referenced to this SNVT Valid Range 0765535 seconds Factory Settings 900 0 seconds Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf URL http www intesis com Intesis Software S L All rights reserved ntes IS E email info intesis com 23 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 nv4 cpTempMagnitude network input UCPTtempMagnitude config prop cpTempMagnitude As per LonMark standard all variables using type SNVT temp p are based in SI units Celsius as in general all LonMark compliant SNVTs do there is no native Fahrenheit support in LonWorks Though for nviSetPoint nvoSetPoint and nvoSpaceTemp user might want to use the Fahrenheit scale at user level interface LonWorks visualisation and network management to
27. sisBox is a registered trademark of Intesis Software SL tel 34 938047134 rev 3 IntesisBox ME AC LON 1 v 1 6 10 User Manual nv25 nvoErrCode network output SNVT count nvoErrCode This output network variable indicates the present error code indicated by the indoor unit Valid Range Unit Status NV content No error 8000 Error Error code e 0001 7999 indoor unit error code nvoAlarm 100 1 e 8001 ME AC LON 1 Communication Error nvoAlarm 100 1 e 65535 Status of error has not been obtained from AC yet initialization value Default Value 8000 No error Default Service Type Acknowledged Update Rate This network variable is updated always that its value changes Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf URL http www intesis com Intesis Software S L All rights reserved n tes IS E email info intesis com 20 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 nv26 nvoVersion network output polled SNVT str asc nvoVersion This polled output network variable indicates the firmware version of ME AC LON 1 device Valid Range Up to 30 ascii characters string Default format is V x yy zz where x yy zz stands for the firmware version on the device Default Value N A Default Service Type N A non bindable Update Rate This network variable is pol
28. tate 21 nv23 nvoOnTime network output eeprom SNVT time hour nvoOnTime This output network variable indicates the operation time for the indoor unit Value is stored in ME AC LON 1 s eeprom This value can be used for the maintenance of indoor unit s filter as well as for monitoring the operation time of the unit Valid Range 0765535 hour Default Value N A Default Service Type Acknowledged Update Rate This network variable is updated always that its value changes Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf URL http www intesis com Intesis Software S L All rights reserved n tes IS E email info intesis com 18 software IntesisBox is a registered trademark of Intesis Software SL tel 34 938047134 IntesisBox ME AC LON 1 v 1 6 10 User Manual rev 3 nv24 nvoAlarm network output SNVT switch nvoAlarm This output network variable indicates failure in the communication between ME AC LON 1 device and the AC indoor unit Valid Range Unit Status NV content ON value 100 state 1 OFF value 0 state 0 Default Value state 0 value 0 Default Service Type Acknowledged Update Rate This network variable is updated always that its value changes Doc IntesisBox ME AC LON 1 v1 6 10 User Manual eng r3 pdf Intesis Software S L All rights reserved z URL http www intesis com n tes IS E email info intesis com 19 Inte

Download Pdf Manuals

image

Related Search

Related Contents

Philips AVENT SCF996  GPA-400 stereo guitar power amp user manual  intext:Installationsanleitung filetype:pdf  Manuel du jeu  PS / PSA / PSW... Opération  HOL-VIS07 Microsoft Windows Vista. Desktop Optimization Pack  Guarantee Card NC 100 Microlife NC 100 Microlife NC 100  MH-500 – 500g/0.1g User Manual    User Manual  