1. 1 3 Installation To guarantee UPS normal operation before connecting devices to the UPS please verify that ground and neutral lines of the connected devices are not short circuited see Figure 1 Line Neutral GND A Ep NEUTRAL UPS Figure 1 Devices An neutral line and ground line are short circuited please add isolation transformer between UPS and devices see Figure 2 Line Neutral GND Isolation transformer Device Figure 2 M aruson Technology Corporation 2 ULTIM A SERIES 1K 3KVA 2012 Jan A Never connect neutral line of input to neutral line of output Otherwise it will cause the damage of the ee see Figure 3 L gales UPS Wiring BOX TO LOAD Figure 3 Do not connect appliances or devices which would overload the UPS system to the UPS output sockets Place cables in such a way that no one can step on or trip over them The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the building wiring outlet shockproof outlet Please use only VDE tested CE marked power cables to connect the loads to the UPS system When installing the equipment make sure the sum of the leakage current of the UPS a
2. 6 SPECIFI CATIONS A sosnane sense aea aare a candesnenensuueaiceameauanconuns 17 M aruson Technology Corporation 1 ULTIMA SERIES 1K 3KVA 2012 Jan 6 Specifications MODEL ULT 1K L ULT 2K L ULT 3K L CAPACI TY 1000 VA 800 W 2000 VA 1600 W_ 3000 VA 2400 W INPUT 160VAC 140VAC 120VAC 110VAC 5 or 80VAC 70VAC 60VAC 50 VAC 5 based on load percentage 100 80 80 70 70 60 60 0 Voltage 168VAC 148VAC 128VAC 118VAC 5 or 84VAC 74VAC 64VAC 54 VAC 5 Range based on load percentage 100 80 80 70 70 60 60 0 300 VAC 5 or 150 VAC 5 290 VAC 5 or 145 VAC 5 Single phase with ground 0 98 Output voltage 208 220 230 240VAC or 110 115 120 127VAC AC Voltage Regulation Synchronized Ra Synchronized Range 47 53 Hz or 57 63 Hz 50 Hz 0 25 Hz or 60Hz 0 3 Hz urrent Crest Ratio 3 THD Linear Load 4 THD Linear Load 6 THD Non linear Load 7 THD Non linear Load Zero Time 4 ms Typical EFFICIENCY 88 5 89 peak 89 3 90 peak 83 7 86 peak 88 2 89 peak 12V 9Ah Harmonic Distortion 1 0A 27 4 VDC 1 54 7 VDC 1 82 1 VDC 1 Battery Type l Numbers Depending on the capacity of external batteries Charging Current 1A 2A 5A Default 1A 2A 4A 8A Default harging Voltage 27 4 VDC 1 54 7 VDC 1 82 1 VDC 1 PHYSI CAL Standard Pimensions 400 X 146 X 205 397 x 145 x 220 421 x 190 x 318 Model DxWxH
3. OO M aruson Technology Corporation 12 01 Output Voltage Setting gue HLS chu M aruson Technology Corporation For 208 220 230 240 VAC models you may choose the following output voltage 208 present output voltage is 208Vac 220 present output voltage is 220Vac 230 present output voltage is 230Vac 240 present output voltage is 240Vac For 110 150 120 127 VAC models you may choose the following output voltage 110 present output voltage is 110Vac 115 present output voltage is 115Vac 120 present output voltage is 120Vac 127 present output voltage is 127Vac ON Mute Button Press the Down key or Up key to set the acceptable high point and acceptable low point of input voltage HLS High loss voltage in Line mode For 208 220 230 240 VAC models the setting range is from 260V to 300V For 110 115 120 127 VAC models the setting range is from 130V to 150V LLS Low loss voltage in Line mode For 208 220 230 240 VAC models the setting range is from 160V to 190V For 110 115 120 127 VAC models the setting voltage is from 80V to 95V OFF Enter Button Select Button ENA ECO mode enabled DIS ECO mode disabled ON Mute Select Button 3 2 LCD Panel Input Battery Voltage Info Press the Down key or Up key to set the acceptable high point and acceptable low point of input voltage HLS High loss voltage in ECO mode For 208 220 230 240 VAC
4. mm Net Weight kgs 28 8 Long Dimensions Runtime DxWxH mm 400 X 146 X 205 397 x 145 x 220 421 x 190 x 318 Model _ Net Weight kgs 13 5 peration Humidity 20 90 RH 0 40 C non condensing oise Level Less than 45dBA 1 Meter Smart RS 232 Port Card Supports Windows ere als Windows 7 Linux Unix and ntelligent Slot Power management from SNMP manager and web browser Derate capacity to 80 when the output voltage is adjusted to 208VAC M aruson Technology Corporation 17 ULTIMA SERIES 1K 3KVA 2012 Jan 1 Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly Save this manual properly and carefully read the following instructions before installing the unit Do not operate this unit before reading through all safety information and operating instructions carefully 1 1 Transportation Please transport the UPS system only in the original packaging to protect against shock and impact 1 2 Preparation Condensation may occur if the UPS system is moved directly from cold to warm environment The UPS system must be absolutely dry before being installed Please allow at least two hours for the UPS system to acclimate to the environment Do not install the UPS system near water or in moist environments Do not install the UPS system where it would be exposed to direct sunlight or near a heater Do not block ventilation holes in the UPS housing
5. models the setting range is from 7V to 24V of the nominal voltage For 110 115 120 127 VAC models the setting range is from 3V to 12V of the nominal voltage LLS Low loss voltage in ECO mode For 208 220 230 240 VAC models the setting range is from 7V to 24V of the nominal voltage For 110 115 120 127 VAC models the setting voltage is from 3V to 12V of the nominal voltage 11 ULTIMA SERIES 1K 3KVA 2012 Jan Battery Info lt M aruson Technology Corporation 8 3 1 Buttons Operation Button Function Turn on the UPS Press and hold ON Mute button for at least 2 seconds to turn on the UPS Mute the alarm After the UPS is turned on in battery mode press and hold this button for at least 5 seconds to disable or enable the alarm system But it s not applied to the situations when warnings or errors Occur Down key Press this button to display previous selection in UPS setting mode Switch to UPS self test mode Press ON Mute buttons simultaneously for 5 seconds to enter UPS self testing while in AC mode Turn off the UPS Press and hold this button at least 2 seconds to turn off the UPS in battery mode UPS will be in standby mode under normal power or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Switch LCD message Press this button to change the LCD message for input voltage input freq
6. 012 Jan M aruson Technology Corporation 10 ULTIMA SERIES 1K 3KVA 2012 Jan
7. TECHNOLOGY CORP Power Solutions All Y our N eeds ULTIMA SERIES 1K 3KVA On Line UPS USER MANUAL M aruson Technology Corporation 18557 East Gale Avenue City of Industry California 91748 U S A Tel 1 626 912 8388 Fax 1 626 912 8680 Toll Free 1 888 M ARUSON E Mail Info MarusonUSA com Website www MarusonUSA com All trademarks are the property of their respective owners M aruson Technology Corporation ULTIMA SERIES 1K 3KVA 2012 Jan Table of Contents 1 IMPORTANT SAFETY WARNING windensscstecntcsnscnsvndncsavsdesauatsendusuvassdssnnddsasasdeotenesdauscsaunenanasn 2 del Irans portato Nai 2 A E AR LR 2 De Ss la tala tomes r E E NA a a a a N a Dy 2 TA OCU Na RE N TAA 3 125 Maintenance Service and FQuleS 3 ind n a ds iaa 3 21 1 NSTALLATION AND SETUP tsasersiscccscdcssoncscduetscnsaszandsninddsaiucdendssscensunadsnusdcctvacssetiessuaiven 5 22 Vn R d Panel MC o e ooo 5 DoD otup DU Sana caca 6 3 OPERAT ONSiinarca aia ia 8 Bz BUCEOMS Operas dd decai 8 eZ CD PING esa daira tant gts eata toad ecantt art te uence atic teeta uton oe suiouc E E E add ace kaa 8 Se AVADE API PP PE ca PO O pacts OI att nua edtuane Shae paNeE 10 324 LCD Display Wording NA aaa 10 B20 UPS A de 10 3 6 Operating Mode Descrip aia 12 FAFS Rererenice COMP 13 3 0 Warninda MACAO Sais ida AA 13 A TROUBLESHOOTING cosacos 14 5 STORAGE AND MAINTENANCE sisisdvanciccnsctutscasuscdcsvssevatvecabssuusawsscnsicouidndeiescecauecisvnckenets 16
8. down start up and status monitoring connect one end of the communication cable to the RS 232 port and the other to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS status through the PC The 2K L model is equipped with intelligent slot for SNMP RS 232 USB or AS 400 card When installing with the communication card in the UPS it will provide advanced communication and monitoring options Step 1 Tog Step 2 4 Step 3 i Remove cover of intelligent Insert communication card Screw card tightly and slot into the slot complete installation Step 4 Network Connection Network Fax Phone surge port IN OUT Connect a single modem phone fax line into surge protected IN outlet on the back panel of the UPS unit Connect from OUT outlet to the equipment with another modem fax phone line cable M aruson Technology Corporation 6 ULTIMA SERIES 1K 3KVA 2012 Jan TO exte rna aa Step 5 Turn On the UPS Press the ON Mute button on the front panel for two seconds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 6 Install Software For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown You may insert provided CD into CD ROM to install the monitoring software If not please fol
9. l l l Pl program rakia cutet contro better mode D Table 9 Dseole Battery numbers setting 7 M aruson Technology Corporation 7 ULTIM A SERIES 1K 3KVA 2012 Jan 05 Bypass Mode Enable Disable Interface Setting S E gt ENA Bypass mode enabled DIS Bypass mode disabled Press the Down key or Up key to set the acceptable high voltage point and acceptable low voltage point HLS Bypass high voltage point LLS Bypass low voltage point n For 208 220 230 240 VAC models 230 264 setting the high voltage point from 230Vac to 264Vac 170 220 setting the low voltage point from 170Vac to 220Vac For 110 115 120 127 VAC models 120 132 setting the high voltage point from 120Vac to 132Vac 85 115 setting the low voltage point from 85Vac to 115Vac 00 Exit Setting 3 6 Operating Mode Description Mode Online mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at online mode ECO mode Energy saving mode When the input voltage is within voltage regulation range UPS will bypass voltage to output for energy saving Battery mode When the input voltage is beyond the acceptable range or power failure and my OC the alarm is sounding every 4 seconds le e3u UPS will backup power from battery en O P ULTIMA SERIES 1K 3KVA 2012 Jan
10. la Vac output voltage Vdc battery voltage Hz frequency Load information al Indicates the load level by 0 25 26 50 51 75 and 76 100 C L WN m m WW gt E LES ones S r UU gt po 0 m n Pr Ln U cr i L r E Indicates overload SHORT Indicates the load or the UPS output is short circuit 3 5 UPS Setting de operation information There are three parameters to set up the Indicates the UPS connected to the mains Parameter 1 UPS Indicates the battery is working Parameter 1 For program alternatives There are 6 programs to set up Refer to Indicates the bypass circuit is working below table Indicates the ECO mode is enabled setting options or values for each program Parameter 2 and Parameter 3 are the Indicates the Inverter circuit is working Indicates the output is working Battery information Parameter 2 Parameter 3 Indicates the Battery level by 0 25 26 50 51 75 and 76 100 ear AULT Indicates the battery is fault LOW BATT Indicates low battery level and low battery voltage Input amp battery voltage information m4 m Vac Indicates the input voltage or frequency ar E a ee e l LI LAL uz Indicates battery voltage in 1K model ds Vac Input voltage Hz input frequency Vdc battery voltage Indicates battery charge discharge voltage and current A only available for 2K model M aruson Technology Corporation 9 ULTIMA SERIES 1K 3KVA 2
11. low steps below to download and install monitoring software from the internet 1 Go to the website http www power software download com 2 Click the ViewPower software icon and then choose your required OS to download the software 3 Follow the on screen instructions to install the software 4 When your computer restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock Step 7 External Battery Connection Follow the below chart to make external battery connection 7 f b a tt e ry y E b a tt e ry Step 8 External Battery Capacity Configuration in Software To calculate accurate backup time of external batteries it s necessary to configure battery numbers in software The standard calculated capacity for one battery is 9Ah If connecting to 100Ah batteries then it s equal to 11 in parallel 100Ah 9Ah 11 sets Wiewpower corigarcacn UPSsetarg Control View omwat Lenguage llelp E ti User type Acministrator E a S Mon loved 1195 192168 10777 gt 058 el 15A5CIAS_PDM A Local sbutdowr temote shutdown Paremetersseting urdicsing irfecmaticn Greer poorer fanvlinn a Fable y Tale ddal W Enable Q Daevle zatory deep eschoras protection mble stoole site foult detection emble 2savle S oa g g Y o y a 2 Ed z rr o o o 8 F l l Bypass notallowed L Enable 9 S zole
12. measures necessary when sounding 1 The load is still supplied working with batteries but directly from AC power Remove wristwatches rings and other metal objects via bypass Use only tools with insulated grips and handles 2 The load is no longer When changing batteries install the same number and same type of batteries supplied by power Do not attempt to dispose of batteries by burning them This could cause battery Battery backup time is shorter Batteries are not fully Charge the batteries for at explosion than nominal value charged least 5 hours and then Do not open or destroy batteries Escaping electrolyte can cause serious injury to the check capacity If the skin and eyes and may be toxic problem still persists Please replace the fuse only with the same type and amperage in order to avoid fire consult your dealer hazards Batteries defect Contact your dealer to Do not dismantle the UPS system replace the battery M aruson Technology Corporation 15 ULTIMA SERIES 1K 3KVA 2012 Jan M aruson Technology Corporation 4 ULTIMA SERIES 1K 3KVA 2012 Jan 2 Installation and Setup 4 Troubleshootinc NOTE Before installation please inspect the unit Be sure nothing inside the package is If the UPS system does not operate correctly please solve the problem by using the table damaged Please keep the original package in a safe place for future use below Possible Cause 2 1 Rear Panel View No i
13. nd the connected devices does not exceed 3 5mA 1 4 Operation Do not disconnect the mains cable on the UPS system or the building wiring outlet shockproof socket outlet during operations since this would cancel the protective earthing of the UPS system and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets and output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet In order to fully disconnect the UPS system first press the OFF Enter button to disconnect the mains Prevent fluids and other foreign objects from entering the inside of the UPS system 1 5 Maintenance Service and Faults The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel Caution risk of electric shock Even after the unit is disconnected from the mains building wiring outlet components inside the UPS system are still connected to the battery and electrically live and dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors Only persons adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons mus
14. ndication and alarm even The AC input power is not Check if input power cord ULT 1K L though the mains is normal connected well firmly connected to the a gt mains oe E AE The AC input is connected Plug AC input power cord A WES to the UPS output to AC input correctly ON 08 20 Lg 0 i EY NALES E A D Line and neutral Rotate mains power socket a lo gN ja The icon Land ve flashing on conductors of UPS input by 180 and then connect LCD display and alarm is sounding are reversed to UPS system every second and flashing The external or internal Check if all batteries are battery is incorrectly connected well connected The icon on LCD display and alarm is sounding every second Fault code is shown as 27 and the Battery voltage is too high Contact your dealer BATT FAULT or the charger is fault icon is lighting on LCD display and alarm is continuously sounding Fault code is shown as 28 and the Battery voltage is too low Contact your dealer PE has or the charger is fault icon EMAU ig lighting on LCD 3 display and alarm is continuously sounding tocar A ni OVER LOAD UPS is overloaded Remove excess loads from UPS output a la ie en UPS is overloaded Devices Remove excess loads from connected to the UPS are UPS output IEC Type fed directly by the ULT 3K L electrical network via the AAA AA EE A Bypa
15. ode Bus start fail 11 12 Inverter soft start fail Inverter voltage high 12 3 8 Waming Indicators Over temperature Inverter voltage Low Inverter output short Battery voltage too high Bus unbalance 04 x Battery voltage too low BT OMNIA E Eni OVER LOAD Warming Icon flashing Alam Low battery OW BATT Sounding every second Sounding twice every second Battery is not connected Sounding every second Site wiring fault Over temperature Charger failure Out of bypass voltage range ar Sounding every second gt gt Dia a Bee M aruson Technology Corporation 13 Sounding every second Sounding every second Sounding every second Sounding every second ULTIMA SERIES 1K 3KVA 2012 Jan External battery connection only available for L models RS 232 communication port Modem Phone line Network surge protection Intelligent slot Output circuit breaker Output terminal eS oP e 2 2 Setup the UPS Step 1 UPS Input Connection Plug the UPS into a two pole three wire grounded receptacle only Avoid using extension cords The input plug is a 18 3C for 1K 2K and 1 5mm 3C or 14 3C for 3K Step 2 UPS Output Connection Simply plug devices to output sockets During power failure UPS will provide power to connected devices Step 3 Communication Connection Communication port RS 232 port Intelligent slot o o To allow for unattended UPS shut
16. ss After repetitive overloads Remove excess loads from the UPS is locked in the UPS output first Then shut Bypass mode Connected down the UPS and restart devices are fed directly by it the mains Fault code is shown as 43 and The The UPS shut down Remove excess loads from OVER LOAD ie automatically because of UPS output and restart it Icon is lighting on LCD overload ak the URS output display and alarm is continuously sounding Fault code is shown as 14 and the The UPS shut down Check output wiring and if IEC Type Schuko Type India Type con is lighting on LCD automatically because connected devices are in display and alarm is continuously short circuit occurs on the short circuit status 1 Output receptacles sounding UPS output 2 AC input 3 Input circuit breaker M aruson Technology Corporation ULTIMA SERIES 1K 3KVA 2012 Jan M aruson Technology Corporation 14 ULTIMA SERIES 1K 3KVA 2012 Jan Bypass mode When input voltage is within acceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm will sound every 10 seconds Standby mode UPS is powered off and no output supply power but can still charge batteries 3 7 Faults Reference Code Fault Event Fault Fault Event Fault Code C
17. t be kept well away from the batteries M aruson Technology Corporation 3 ULTIMA SERIES 1K 3KVA 2012 Jan 5 Storage and Maintenance Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer ES Be sure to deliver the used battery to a recycling facility or ship it to your dealer in the replacement battery packing material Storage Before storing charge the UPS for minimum 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 40 C 45 C Every 2 months M aruson Technology Corporation 16 ULTIM A SERIES 1K 3KVA 2012 Jan Caution risk of electric shock The battery circuit is not isolated from the input Possible Cause voltage Hazardous voltages may occur between the battery terminals and the Fault code is shown as 1 2 3 4 A UPS internal fault has Contact your dealer ground Before touching please veny Marne voltage s present 11 12 13 and 41 on LCD display occurred There are two Batteries may cause electric shock and have a high short circuit current Please take and alarm is continuously possible causes the precautionary measures specified below and any other
18. uency battery voltage output voltage and output frequency It will return back to default display when pausing for 10 seconds Setting mode Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in standby mode or bypass mode Up key Press this button to display next selection in UPS setting mode Switch to bypass mode When the main power is normal press ON Mute and Select buttons simultaneously for 5 seconds Then UPS will enter to bypass mode This action will be ineffective when the input voltage is out of acceptable range Backup Time Info Fault Info Mute Operation Output amp Battery Voltage Info gt Load Info AS Mode Info ULTIMA SERIES 1K 3KVA 2012 Jan 3 3 Audible Alarm Backup time information Battery Mode Sounding every 4 seconds Indicates the backup time in pie chart Low Battery Sounding every second IE Indicates the backup time in numbers YU j H hours M minute S second ault information Indicates that the warning and fault occurs Indicates the warning and fault codes the codes are listed in Sounding twice every second Continuously sounding Bypass Mode Sounding every 10 seconds details in 3 5 section 3 4 LCD Display Wording I ndex Lui epean Abbreviation Display Content Meaning Cd Indicates that the UPS alarm is disabled rm Output amp battery voltage information H H tae Indicates the output voltage frequency or battery voltage la

Download Pdf Manuals

image

Related Search

Related Contents

Tecumseh AE4460U-AA1CXW Drawing Data  Manual de usuario Descarga archivo pdf  CODi Protege  Origine, tableau nutritionnel, ingrédient… Toutes les nouveautés du  (取扱説明書) 家庭用重【便ポスト  TERMO DE RETIRADA DO EDITAL DO PREGÃO  REC Day on the Hill a Success - East  Une nouvelle approche du désherbage en milieu urbain et  ficha técnica de mejillones tigre tg 3x1 kg  FERROCIANURO DE POTASIO  