1. Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller TEL User Manual SPC3 3300 Page 13 CONTROLS A Wilson Mohr Company 3 5 5 External Relay Operation Assignment to a digital input DI for external switching of the alarm relay ON and or OFF This function has priority to gas alarm and or manual switching in the menu Status Relay Symbol Description n Function R01 Relay No Relay Selection DI ON External On 0 If digital input closed relay switches ON DI OFF External Off 0 If digital input closed relay switches OFF 3 5 6 Delay Mode of the Relay Delay time ON starts when the alarm is released and or delay time OFF starts when the alarm returns to normal condition ae Setting Symbol Description Status Function R 01 Relay No Relay Selection 0s Delay Time ON 0 Mode ON Relay is only activated at the end of the defined time sec 0 sec No delay 0s Delay Time OFF 0 Mode OFF Relay is only deactivated at the end of the defined time sec 0 sec No delay 3 6 Menu SP Parameters Display and change of parameters assignment of alarms to alarm relays and activati
2. Latching mode Horn function External relay operation Delay ON time Delay OFF time SP mode 2 Gas type Measuring range SP signal Threshold 1 Threshold 2 Threshold 3 Threshold 4 Hysteresis Delay ON time Delay OFF time C A mode Assigned failure lt gt alarm Assigned alarm lt gt alarm relay Assig SP sig lt gt analog output l 1 SP 01 On Board Sensor SP 02 external Transmitter Polygard is a registered trademark of MSR Customer Services 858 578 7887 amp 888 GO INTEC INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 Fax 858 578 4633 amp 888 FX INTEC www inteccontrols com vows IMEL CONTROLS A Wilson Mohr Company SPC3 3300US Specification subject to change without notice Printed in USA 140916 PolyGard Single Point Combustible Gas Controller TEL User Manual SPC3 3300 Page 26 CONTROLS A Wilson Mohr Company 6 Configuration and Parameter Card Commission Project No ee S Customer Commissioning Company er xu Commissioning Date Cd Service Technician 6 1 Configuration Card of System Parameters Service Software Mainten Service AV Overlay Time Costumer Power Fault Version ance Phone Time Av System Pass ON Relay Date LEL Time Time Default _GC03_ 06 06 08 858 578 7884 120 120 1800 US 1234 30s o ee a Calib
3. Gross senivity Data iiiter De o e E ERE RETE IRAE E A XERRA UR tiet 29 9 4 Exchange of Sensor Element eere p ee HIER AI m dtp ice tes 30 9 Specification Gas Sensor ceret ener Ei eue asini cune e Vra Tune Leo ok a Re esee T oie deem mennan 30 10 Notes and General Information 0 ccccececesceeeee cece eeeeeeeeeenee sees eee ea ceases seeeeee sens seaneeseeeseeeeeseeeneeseeeneees 31 10 1 Intended Product Application aeree eee dee did a eee ee 31 10 2 Installers Responsibilities ececccccccecceeeeeeeeceeeeeee caer ee eeeeaaeanaeceeeeeeeeegeceaaaeceeeeeeeeseeceeeeeteesenanes 31 10 3 Maintenance cu nie ee ea ese ee en tte ee o ee el en ee 31 10 4 Limited Warranty vise 5 21 eec nl adie I dn a aa aa alee 31 Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller TEL User Manual SPC3 3300 Page 04 CONTROLS A Wilson Mohr Company Single Point Gas Controller SPC3 1 Description The PolyGard SPC3 Gas Controller is used for measuring monitoring and warning of combustible gases and vapours in the ambient air in the LEL range A catalytic sensor SP01 is integrated in the gas controller for combustible gases In addit
4. inier epe pee dicet oer Cere sei RE RE Re Ro B0E 17 3 6 9 A Alarm Assigned to Alarm Relay iriaren sirnana eene eene emere 17 3 6 10 SP Signal Assigned to Analog Output ssssssse eene 17 3 7 Menu System Parameters et tnn Hn guinea animum 18 3 7 1 Seice MOJE 3 n vtae e Demi cnet les iden 19 9 2 Software Version dte neto ect get t ER esce eel 19 3 7 3 Maintenance Concept niitide e vio td e rd ael Ede de ue e e ano t aee a Fed ce uo dee d dese dae 19 37 4 Average Friction note ote tae ee a e Lad eee te cab ee le o e Ee du ee 19 37 5 System Time System Date eeri dala nade aene ee Me aep on E dd 20 3 7 6 Customer Password Gode 1 2 Ur ined a RE I eed e ae de t ded ane 20 Stel Analog Output aae necne Inte dn dn a e E Ee PP a Rata en 20 3 7 8 Define the Failure Relay iei i E ED RR Re EHE RR EXER DRE AE AERAR 20 3 7 9 Power On Timie uie e Ee ci AED n ci eed ede n EM e eut 21 4 Mounting Electrical Connection ce cece esse eee eeee eee eeeeen seen nee enne enne nenne nennen nnn nennt nnn nnn nena 22 41 Electncal Gonnectiom i e eee eee de AA eee qe 22 42 Connection Diagram eee tette e er E Tet dea dee EH adea datas ate ete E ee 23 4 3 Connector Block Overview SPC3 Module ssssssessseeeneeenee nennen enne 24 Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC INTE
5. 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller TEL User Manual SPC3 3300 Page 19 CONTROLS A Wilson Mohr Company See 3 7 7 m pem 3 7 1 Service Mode When the service mode is active ON the alarms are not transmitted to the alarm relays in case of calibration or service work The service mode is reset automatically after 60 minutes or manually in the menu Service Mode ar Default Symbol Description Status Function Off Service Mode Off Off Alarms activate the associated alarm relays On Alarms are not transmitted to the alarm relays 3 7 2 Software Version s gs Default Symbol Description Status Function GCO03 Software XX Versi n XX Software Version 3 7 3 Maintenance Concept Integrated in the SPC3 system there is a control of the maintenance intervals required by law or by the customer At commissioning or after maintenance the number of days until the next due maintenance is entered Reset of the maintenance message service phone no When the days counter reaches zero the failure signal is activated the following morning at 9 o clock and the phone no of the service technician occurs in the display The remaining days until the next maintenance can be rea
6. 8 PME status AlAnM I I A E E AE ETE E E ESE E E E E A 8 EA E E E a Fie EP E A E T A T A T E ean hee ails 9 3 3 1 Manual Operation of the Relays ssssssssessseeneeeenen enne nnne rennen nnne 9 3 4 Menu Meas ririg Vales ceni n eee ee eere eg dete digas et e ipe edes 10 3 5 Menu Relay Parameters ci ene Ba etl eb tt atelier ire 10 3 5 1 Relay MOdG6 i etate ie i te e i em e a EL ER ee be a d iet 11 3 5 2 Relay Bunction static Flasn iu cL t RE t pte ei heat Pet 11 3 5 3 Latching Mode 2 et te ead high ei edendi bet bae e oen 11 3 5 4 Homi Function EN MP E EA A AAE AAA ae OE AANA NA AAAA ON ANNAT 12 3 5 5 External Relay Operation eec te e m i eed 13 3 5 6 Delay Mode of the Relay ee bee e ee lien die ia dpa ru 13 3 6 Menu SP Parameters iecit eiecit sand or ende uenis cand ee aene e a mi den ea 13 3 6 1 Activate Deactivate SP ie gebe HP ep dp tede tam M Uu GI Roc dae 15 36 2 Selection Gas Typ ich dtp itn E i cn eeepc EA ch perti E aco P nta gren 15 3 6 3 Measuring Rage em i ird e ted es Etc tede interiit 16 SGA cS BP Slgh l sii iiiter i ua c te t to decli Ua dert aree ee sati aed 16 3 6 5 ihreshold Hystetesis uiii te duet ie e ERE E S eR ORE RET na etre nn 16 3 6 6 Delay ot Alarm ON Or OEE ede t Ebert eure e t e et per ete tuae e teneo ES 16 3 0 7 Comtrol MOd6 i mede i RR Pt beside ex eae ave bv E eek tas top a kage sete 17 3 0 8 SP Fault Assigned to Alarim
7. NEL User Manual SPC3 3300 Page 06 CONTROLS A Wilson Mohr Company 2 3 Code Level Code Level 1 Default Password 1234 Code Level 2 Password 9001 All changes of setups and set point values are protected by a four digit numeric code password The code level 1 permits the operation of the SPC3 this code level is intended for the customer The code can be changed individually via code level 2 see section 3 7 6 In code level 2 all setups and set points are released this code level is only for the service technician Code level 2 cannot be changed or deleted The release of the code level is deleted if no button is pushed within 15 minutes All menu windows are visible without entering a code 3 Menu Overview The operation of the Single Point Gas Controller SPC3 is effected by a simple and logical menu structure which is easy to learn The operating menu contains the following levels e Starting menu e Main menu e Submenu 1 and 2 Starting menu Main menu Submenu 4 Display and reset of errors See from point 3 1 Displays the status of actual alarms See point 3 2 Display of the relay status Manual operation of the relays Reset function of the relays See from point 3 3 Displays the measuring values See point 3 4 Display and change of the relay parameters See from point 3 5 Display and change of the sensor point parameters Activate or Deactivate SP Assignment of the alarms to the alarm rela
8. of SP No Ex Gas type Ex See 3 6 2 LEL Gas unit See 3 6 2 CV Current value CV Current value of gas concentration AV Average value Average value 10 measured values within the time unit Control mode Display of selected control mode CV or AV Not active Status SP Not active SP not active Error Fault SP Current signal 3 mA or 22 mA 3 5 Menu Relay Parameters Display and change of the parameters for each alarm relay d Polygard is a registered trademark of MSR Customer Services 858 578 7887 amp 888 GO INTEC Main menu HHIHH Select relay No Relay mode See 3 5 1 Relay function See 3 5 2 Activate latching mode See 3 5 3 Definition of horn function See 3 5 4 Definition of external relay operation See 3 5 5 Set delay time ON See 3 5 6 Set delay time OFF See 3 5 6 SPC3 3300US Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller TEL User Manual SPC3 3300 Page 11 CONTROLS A Wilson Mohr Company 3 5 4 Relay Mode Definition of relay mode Setting P Symbol Description Status Function R01 Relay No Selection of relay De Relay Mode De De energized Alarm ON Relay ON energized y energized Energized Alarm ON Relay OFF 3 5 2 Relay Function St
9. signals is defined in this menu Symbol Description AM Function SP 01 Sensor Point Selection of SP No Linear Transmitter with linear output signal Linear SP Signal Linear Non linear Transmitter with non linear output signal only AT series from MSR E 3 6 5 Threshold Hysteresis For each sensor point four alarm thresholds are available for free definition If the gas concentration is higher than the adjusted alarm threshold the associated alarm is set If the gas concentration falls below the alarm threshold inclusive hysteresis the alarm is again reset Unused alarm thresholds have to be defined at measuring range end point in order to avoid false alarms At O2 measurement an alarm is released by a decreasing measuring signal Symbol Description rodea Function SP 01 Sensor Point Selection SP No 10 Threshold 1 Gas concentration gt Threshold 1 Alarm 1 40 Threshold 2 Gas concentration gt Threshold 2 Alarm 2 10 96 Threshold 40 Threshold 3 Gas concentration gt Threshold 3 Alarm 3 LEL 100 Threshold 4 Gas concentration gt Threshold 4 Alarm 4 5 Hysteresis Gas concentration lt Threshold X Hysteresis Alarm X OFF 3 6 6 Delay of Alarm ON or OFF Definition of alarm ON and or alarm OFF delay The function applies to all alarms of an SP m Default Symbol Description Status Function SP 01 Sensor Point Selection of SP No Gas concentrati
10. 40 0 90 0 70 SPC3 3300US Specification subject to change without notice Printed in USA 140916 PolyGard Single Point Combustible Gas Controller User Manual SPC3 3300 8 4 Exchange of Sensor Element Consider static electricity See point 3 Page 30 e Sensor should always be installed without power applied e Unplug old sensor element from the PCB e Take the new sensor out of the original packing e Plug the sensor element into the PCB at X3 e Make calibration see 8 9 Specification Gas Sensor Sensor performances Gas type Combustible gases and vapours Sensor element Catalytic bead pellistor Measuring range 0 100 LEL Pressure range Atmosphere 10 96 Storage temperature range 5 C to 30 C 41 F to 86 F Storage time Max 6 months Mounting height Depending on gas type Accuracy 1 96 of reading Long term zero drift 5 signal loss year Long term sensitivity drift lt 2 measuring range month Response time too 10s Methane Temperature drift lt 1 Life expectancy gt 3 years normal operating environment Humidity range 15 95 RH non condensing Temperature range 10 C to 40 C 14 F to 104 F Calibration adapter Fig 6 Type CONKIT COMB AT BS lt E Polygard is a registered trademark of MSR Customer Services 858 5
11. 78 7887 amp 888 GO INTEC pS a Z Fax 858 578 4633 amp 888 FX INTEC INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com IMEL CONTROLS A Wilson Mohr Company SPC3 3300US Specification subject to change without notice Printed in USA 140916 PolyGard Single Point Combustible Gas Controller TEL User Manual SPC3 3300 Page 31 CONTROLS A Wilson Mohr Company 10 Notes and General Information It is important to read this user manual carefully in order to understand the information and instructions The PolyGard SPC3 gas monitoring control and alarm system may only be used for applications in accordance to the intended use The appropriate operating and maintenance instructions and recommendations must be followed Due to permanent product developments MSR reserves the right to change specifications without notice The information contained herein is based on data considered to be accurate However no guarantee or warranty is expressed or implied concerning the accuracy of these data 10 1 Intended Product Application The PolyGard SPC3 is designed and manufactured for controlling for saving energy and keeping OSHA air quality in commercial buildings and manufacturing plants i e detection and automatic exhaust fan control for automotive maintenance facilities enclosed parking garages engine repair shops warehouses with forklifts fire stations tunnels etc 10 2 Insta
12. 8 2 1 Zero Point Calibration Attention Prior to calibration the sensor has to be powered and fully stabilized for at least 4 hour e Connect digital voltmeter to bridge pins bridge for zero point calibration e Connect the calibration adapter to sensor element e Apply sensor element zero calibration gas 150 ml min 1 Bar 14 5 psi 10 or other clean air source e Wait two minutes until the signal is stable adjust signal with zero potentiometer Zero until the signal is 0 mV 1 mV and stable 4 mA Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller User Manual SPC3 3300 8 2 2 Notes 8 2 3 Gain Calibration Ex calibration gas is toxic never inhale the gas Symptoms Dizziness headache and nausea Procedure if exposed Take the victim into fresh air at once call a doctor Open window SP 01 in menu Measuring Value Connect calibration adapter carefully to the sensor element Apply sensor element span calibration gas 30 60 LEL 150 ml min 1 Bar 14 5 psi 10 Page 29 IMEC CONTROLS A Wilson Mohr Company Wait two minutes until the measuring value is stable adjust the value with potentiomete
13. AC DC 0 5 A potential free SPDT Alarm relay R2 30 VAC DC 0 5 A potential free SPNO SPNC Binary output R3 R4 30 VDC 0 05 A open collector output Visualization Display Two lines each 16 characters Status LED 4 Normal operation Fault Alarm 1 Alarm 2 Operation 4 push buttons menu driven Operation Environment Humidity 15 90 RH non condensing Working temperature 10 C to 40 C 14 F to 104 F Storage temperature 5 C to 30 C 41 F to 86 F Pressure range Atmospheric 10 Physical Enclosure stainless steel type 5 Stainless steel V2A Colour Natural brushed Dimensions W x H x D 113 x 135 x 45 mm 4 48 x 5 35 x 1 8 in Weight Approx 0 6 kg 1 32 Ibs Protection class IP 55 Installation Wall mounting pillar mounting Enclosure plastic version type 0 7 Plastics GWPLAST Colour RAL 7032 light grey Dimensions type 0 W x H x D 87 x 127 x 56 mm 3 43 x 5 0 x 2 2 in Dimensions type 7 W x H x D 114 x 156 x 75 mm 4 49 x 6 14 x 2 95 in Weight Approx 0 4 kg 0 9 Ibs Protection IP 55 Installation Wall mounting Cable entry Standard 2 x M 20 Wire connection Screw type terminals min 0 25 to 2 5 mm 14 to 30 AWG Guidelines EMC Guidelines 89 336 EEC CE Options Analog input external transmitter Analog input 1 4 20 mA input res
14. C Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Specification subject to change without notice Printed in USA 140916 PolyGard Single Point Combustible Gas Controller TEL User Manual SPC3 3300 Page 03 CONTROLS 5 ero unnm 24 5 1 COMMISSIONING a ooi vedi aida ad Ged a CEDE e C Bel n Re dad deb af i cus da e a ed ed 24 5 2 Checklist Commlissioriirig iudici c e ie aid it avin deat i edt el at rea de en 25 6 Configuration and Parameter Card eseeeeeeeeeeeeeen nennen nnne nnne rien nin in nnn innen nin nnns 26 6 1 Configuration Card of System Parameters sssssssssseeeeeeeeene mener enn 26 6 2 Configuration Card of Alarm Relays noes anina aai ennemi en nennen enn nnns 26 6 3 Configuration Card of Measuring Parameters sssssssseeeee ene 26 MES edIOIld4cocebe 27 LEMECCK NDIDIM 28 8 1 IB tego eMe ETC E 28 8 2 GCalibratl mnics uo HIP RE e ER RO ee E ERO i OE TEE By ce 28 8 2 1 Zero Point Calibration 1 c en ee teed saa eere pud ade eene Ea ek deve deuda hn dd nado da 28 8 2 2 Gain Calibration Rame eise ee a ee is e HE d RUE eee 29 8 2 3 Calculation Calibration Gas lt 7 Target Gas alternative calibration ssssssss 29 9 39
15. C Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller EL User Manual SPC3 3300 Page 20 CONTROLS A Wilson Mohr Company 3 7 5 System Time System Date Time and date have no memory back up therefore after each power supply OFF ON time and date restart Input and correction of time and date Selection of the time and date format er Default Symbol Description Status Function US Time format US EU Display of time and date in EU format US Display of time and date in US format hh mm ss Input of the correct time EU format hh mm ss am Input of the correct time US format TT MM JJ Input of the correct date EU format MM TT JJ Input of the correct date US format hh mm ss Time TT MM JJ Date 3 7 6 Customer Password Code 1 Change the system password for level 1 ET Default Symbol Description Status Function 1234 Cusjomer 1234 1234 Define the customer s password with 4 characters Password 3 7 7 Analog Output The Single Point Gas Controller has one analog output AO01 with 0 4 to 20 mA 0 2 to 10 V signal The signal of SP01 or and SP02 can be assigned to the analog output The assignment is effected in the menu SP Parameters for each SP The sensor point sends the sig
16. C3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 User Manual SPC3 3300 PolyGard Single Point Combustible Gas Controller EL Page 21 3 7 9 Power On Time CONTROLS A Wilson Mohr Company Gas sensors need a running in period until the chemical process of the sensor reaches stable conditions During this running in period the current signal can lead to an unwanted releasing of a pseudo alarm Therefore the power on time is started at the SPC3 after having switched on the power supply While this time is running out the Gas Controller does not activate any alarms The power on status occurs in the starting menu Symbol Description 30s Power On Time Default Status 30s Function XX Define the power on time sec Polygard is a registered trademark of MSR Customer Services 858 578 7887 amp 888 GO INTEC INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 SPC3 3300US Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice PolyGard Single Point Combustible Gas Controller TEL User Manual SPC3 3300 Page 22 CONTROLS A Wilson Mohr Company 4 Mounting Electrical Connection The Gas Controller is fixed to
17. H7 nc 1 124 VDC 8 COM_1 9 COM 2 Analog output X4 R r 2 10 NO NC 2 0 V o g 11 24 VDC Analog Output Signal R1 SPDT 30 VAC DC 0 5 A Selecttable via Jumper R2 SPNO SPNC 30 VAC DC 0 5A 0 4 20mA 0 2 10 V R3 R4 Open Collector 30 VDC 50 mA The analog input function is determined by the hardware Each PCB has got a label with the specific type Polygard is a registered trademark of MSR Customer Services 858 578 7887 amp 888 GO INTEC INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 Fax 858 578 4633 amp 888 FX INTEC www inteccontrols com SPC3 3300US Specification subject to change without notice Printed in USA 140916 PolyGard Single Point Combustible Gas Controller NEL User Manual SPC3 3300 Page 24 CONTROLS A Wilson Mohr Company 4 3 Connector Block Overview SPC3 Module 1 2 e i X4 4 Anal Out o Q 0 fel 4 OFO OJ 8 3 e K 9 2 5 10 1 Dn y X5 Anal Output Fig 4 Fig 5 Selection of the analog output signal Jumper O 20 96 Jumper V A Output signal Not set Not set Set Not set Not set Set Set Set 5 Commissioning 5 1 Commissioning Prior to commissioning the wiring of the SPC3 including all field devices must be completely terminated Check the optional external transmitter input signal it has to be the same as indicated on the label of the PCB See fig 05 Select the contact for relay 2 with jumper NC NO
18. R MEL electronic coNTROLS 9 Noms Alam 2 SOg PolyGard Single Point Controller SPC3 3300 Single Point Gas Controller for Combustible Gases Serial Number E 1008 User Manual October 2008 September 16 2014 Revision Polygard is a registered trademark of MSR Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com A Wilson Mohr Company SPC3 3300US Specification subject to change without notice Printed in USA 140916 PolyGard Single Point Combustible Gas Controller EL User Manual SPC3 3300 Page 02 CONTROLS 1 Description ic cestcct estes nccdccicdecsazetiectccccecacdsciedeccadctuecdecieiee tet case cancetectacieSacas at TT 4 2 Operating Irnistruction inne inerte DER PREDA ED Ini IR LM inen 5 2 1 Description Keypad User Interface sssssssssssssssssssseseeeenerere nennen nee 5 2 2 Setting Changing Parameters or Set points ssssssssesseene eene 5 2 3 Code Levels acuti die d eed dudo Edge idee cud ed eee ded Rud c ep dev ah 6 EE EeuvBijae E 6 3 1 gt Fault Management eoriet no hee he m he opem hime 7 3 1 1 Acknowledge a Fault e REPRE t E Ea c eee ene 7 3 1 2 Error Memory ii reet RR e RE RD DR ERR EP DA ERE 7 94 3 SyStemiBITO S soie tec hee etate ied rege ett etate este ge ters Ratete Mee etave es A
19. See fig 2 3 and 5 Select the analog output signal with jumper V A and 0 20 See fig 5 After switching the power supply ON and at the end of the Power ON Time the SPC3 is ready for use The SPC3 is delivered with standard parameters and set points The registration of the optional external gas transmitter and the assignment of the alarm relays to the individual alarms must always be performed during commissioning Additionally all other parameters have to be checked and adapted to the local conditions The standard parameters can be taken from the following configuration and parameter card We recommend registering the individual parameters and set points into the list We recommend checking the parameters and set points according to the following check list Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller User Manual SPC3 3300 5 2 Checklist Commissioning Time and date Parameter of average function Password level 1 customer s password Function analog output Define fault relay Power ON time Service phone no Maintenance date 2 4 Relay R Relay mode Function static flash
20. ain menu System Error can only be opened via code level 2 In the error memory the last 15 faults are listed for the service technician even if they were already acknowledged in the menu System Error The deletion of each individual message is effected in the same way as the reset of a fault Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller EL User Manual SPC3 3300 Page 08 CONTROLS A Wilson Mohr Company 3 1 3 System Errors The following system error messages are recorded SP 02 gt 22 mA Current signal at analog input gt 22 mA 11 VDC External Transmitter Cause Short circuit at analog input or transmitter not calibrated transmitter defective Solution Check cable to transmitter make calibration replace the transmitter SP 02 3 mA Current signal to analog input 3 mA 1 3 VDC External Transmitter Cause Wire breaking at analog input or transmitter not calibrated transmitter defective Solution Check cable to transmitter make calibration replace the transmitter GC Error Internal communication error I O Board to LCD Board Cause Internal error Solution Change the Gas Controller module Maintenance Syste
21. are not assigned to any alarm relay Default Symbol Description Status Function SP 01 Sensor Point Selection of SP No A1 01 01 Alarm 1 activates alarm relay R 01 1 A2 02 02 Alarm 2 activates alarm relay R 02 A3 03 03 Alarm 3 activates alarm relay R 03 A4 04 00 Alarm 4 doesn t activate any alarm relay 3 6 10 SP Signal Assigned to Analog Output The sensor point signal can be assigned to the analog output At this the signal defined in the control mode current or average value is transmitted Analog output see also 3 7 7 ae Default Symbol Description Status Function SP 01 Sensor Point Selection of SP No 0 A 0 0 SP Signal not assigned to analog output 1 SP Signal assigned to analog output 1 Polygard is a registered trademark of MSR Customer Services 858 578 7887 amp 888 GO INTEC INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 SPC3 3300US Specification subject to change without notice Fax 858 578 4633 amp 888 FX INTEC Printed in USA 140916 www inteccontrols com PolyGard Single Point Combustible Gas Controller EL User Manual SPC3 3300 Page 18 CONTROLS A Wilson Mohr Company 3 7 Menu System Parameters Displays and changes the system parameters of the Gas Controller module m A a A A A A A A A A A m Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578
22. arm relay R3 open collector This alarm output is defined as horn relay by this parameter with the following possibilities to reset e By pressing any of the 4 push buttons only possible in the starting menu e Automatic reset at the end of the fixed time e By an external push button assignment of the appropriate digital input The horn function is only activated if at least one of the two parameters time or digital input is set Special function Response After acknowledging the output by push button or externally time starts When this time has run out and the alarm is still acting the relay is set again Setting Status R 03 Relay No Selection of relay Symbol Description Function 0 Reset of the relay after time having run out or by push button Quitt Mode 0 1 Reset of the relay by push button after time having run out and when alarm is still acting relay is set again Response function Time for automatic reset function or response function Time 120 _ 0 no reset function DI 0 Assignment which digital input resets the output Acknowledge the horn output On Alarm 3 oi Gas concentration higher Jiower than threshold Time On Relay 3 Of Acknowledging On signal Or Special function Response Return of the horn rela On Alarm 3 s Gas concentration higher lower than threshold Time Time On Relay 3 off Acknowledging On signal of
23. atic Flash Definition of relay function ae Setting Symbol Description Status Function R01 Relay No Selection of relay 0 Relay function static 0 Function 0 gt 0 Relay function flashing Time period in sec Impulse Break 1 1 3 5 3 Latching Mode Definition of latching function ar Setting Symbol Description Status Function R01 Relay No Selection of relay No Latching mode non active Me Latching Mode No Yes Latching mode active Acknowledging a latching relay in the menu Status Relay is only possible if the gas concentration is again lower than the alarm threshold including hysteresis In this case the status latching occurs in the display Example Alarm relay R2 with latching mode On Alarm 2 m Gas concentration higher lower than threshold Display in the Menu R2 R2 R2 R2 R2 R2 Status Relay Off On On On Latching Off On Relay 2 off Reset in the Menu Status Relay Off Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller EL User Manual SPC3 3300 Page 12 CONTROLS 3 5 4 Horn Function The internal horn is connected to al
24. ce INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller User Manual SPC3 3300 4 2 Connection Diagram Connection diagram with Option external Transmitter 4 to 20 mA Fig 2 now INTEL CONTROLS A Wilson Mohr Company SPC X3 Digital X5 Input DIO 1 ext Buzzer Option external 7 Bus B 2 R3 Transmitter 6 Bus A 24V 3 SP 02 5 4 20mA_Inp gy 4 4 20 mA 4 Analog Out R4 5 Warning 24 VDC 3 24 VDC_Out T elno 1 Flash light 0VDC peeH 2 l0 VDC R1 1 7 NC 1 1124 VDC 8 COM_1 9 COM2 Analog output X4 R r 2 10 NO NC 2 0 V o e 11 ssaa 24 VDC Analog Output Signal R1 SPDT 30 VAC DC 0 5 A Selecttable via Jumper R2 SPNO SPNC 30 VAC DC 0 5 A 0 4 20mA 0 2 10 V R3 R4 Open Collector 30 VDC 50 mA Connection diagram with Option external Transmitter 0 2 to 10 V Fig 3 SPC X3 Digital X5 Input DIO 1 ext Buzzer Option external 7 Bus B 2 i R3 Transmitter 6 Bus A 24V 3 SP 02 poo 0 2 10 V a 4 0 2 10V 4 Analog_Out m 5 Warning 24 VDC 3 24 VDC_Out ay e No 1 Flash light 0 VDC 2 lo VDC R1
25. d from the menu Maintenance in The service phone no can be entered individually in the next menu Symbol Description inia Function XXX Maintenance in Remaining days until the next maintenance XXX Maintenance interval 912 Reset of the maintenance message by entering the number of days until the next maintenance 0853 Phone No Input of the individual service phone no 3 7 4 Average Function For each active sensor point the Single Point Gas Controller calculates the arithmetic average value out of 10 measurements got within the time unit defined in the menu AV Time This average value is indicated in the menu Measuring Values next to the current value At each sensor point the control mode current or average value is defined for the alarm evaluation The alarm evaluation of the control mode average value is overlaid by the current value when the current value exceeds the alarm threshold defined in the menu AV Overlay The overlay is delayed by the time factor defined in this menu Whit time factor O sec the overlay is not active Symbol Description vidua Function 120s AV Overlay 120s sec Delay time of average value overlay 100 LEU 100 LEU LEL Alarm threshold of average overlay 1800 s AV Time 1800 s sec Time for the calculation of the average value Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTE
26. e SP vows INTEL CONTROLS A Wilson Mohr Company ee Setting Symbol Description Status Function SP 01 Sensor point Selection SP No Not Active Sensor point activated at the controller Ade Rr igus active Not active Sensor point not activated at the controller SP01 On Board sensor SP02 Externer Transmitter optional 3 6 2 Selection Gas Type Assign gas type to attached gas transmitters Symbol Description Ud Gas type Unit an d SP 01 Sensor point CO Carbon monoxide ppm 0 300 Ex Combustible gases LEL 0 100 NO Nitrogen oxide ppm 0 50 NO Nitrogen dioxide ppm 0 25 NH3 Ammonia ppm 0 300 O Oxygen AVN 0 25 CO Carbon dioxide ppm 0 2000 SO Sulphur dioxide ppm 0 100 H2S Hydrogen sulphide ppm 0 200 CL Chlorine ppm 0 100 ETC Ethylene oxide ppm 0 20 VOC Air quality 96 0 100 R401 Refrigerant gas ppm 0 2000 R402 Refrigerant gas ppm 0 2000 Ex Gas type Ex R408 Refrigerant gas ppm 0 2000 R409 Refrigerant gas ppm 0 2000 R404 Refrigerant gas ppm 0 300 R416 Refrigerant gas ppm 0 300 R502 Refrigerant gas ppm 0 300 R410 Refrigerant gas ppm 0 300 R411 Refrigerant gas ppm 0 300 R11 Refrigerant gas ppm 0 300 R123 Refrigerant gas ppm 0 300 R134 Refrigerant gas ppm 0 300 R22 Refrigerant gas ppm 0 300 TEM Temperature C 0 50 RH Humidity RH 0 100 CO Carbon dioxide ppk 0 5000 TOX Tox
27. e sensor also has a similarly heated inactive compensator element Both elements are part of a Wheatstone measuring bridge Environmental influences such as temperature ambient moisture or thermal conductivity of the monitored ambient air affect both elements to the same extent so that the influences on the measuring signal are almost completely compensated The integrated measuring amplifier converts this sensor current into a linear selective output signal The measuring amplifier zero point measuring bridge and the zero point and amplification of the analog output signal are calibrated by potentiometers Attention There is a small quantity of corrosive liquid in the sensor element If in case of damage persons or objects touch the liquid you have to clean the affected areas as fast and carefully as possible with tap water Out of use sensors must be disposed in the same way as batteries 8 2 Calibration Required instruments to calibrate the transmitter e Test gas bottle with synthetic air or Ex free ambient air e Test gas bottle with Ex gas methane etc in the range of 30 60 96 of the measuring range e Gas pressure regulator with flow meter to control the gas flow to 150 ml min e Calibration adapter with tube silicone free e g Viton Type Calibrset CONKIT COMB AT See fig 06 e Digital voltmeter with range 0 10 VDC accuracy 1 96 e Small screwdriver Note Please observe proper handling procedures for test gas bottles
28. ic gas ppm 0 XX 1 Recommendation without obligation 2 Decreasing signal at oxygen measurement Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Specification subject to change without notice Fax 858 578 4633 amp 888 FX INTEC INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller TEL User Manual SPC3 3300 Page 16 CONTROLS A Wilson Mohr Company 3 6 3 Measuring Range The measuring range can be defined arbitrarily between 10 and 10000 The measuring ranges in the table gas type are only recommendations without obligation The measuring range for SP01 integrated gas sensor is factory set the measuring range for SP02 must agree with the signal 4 to 20 mA 0 2 to 10 V of the attached gas transmitter 4 mA 0 2 V Display 0 ppm 20 mA 10 V Display of the ultimate value of the measuring range 3 6 4 SP Signal Gas transmitters using electro chemical or catalytic beat gas sensors normally produce a linear 4 to 20 mA 0 2 to 10 V signal proportional to the gas concentration Semiconductor gas sensors produce a non linear exponential signal This signal leads to a non linear 4 to 20 mA 0 2 to 10 V signal of the gas transmitter The Single Point Gas Controller SPC3 is prepared for both types of gas transmitters The classification of
29. ion an external gas transmitter SP02 can be connected to the controller for controlling toxic or combustible gases or even Freons Four alarm thresholds are free adjustable for each Sensor Point SP Every alarm threshold can be assigned to one of the maximum 4 alarm outputs RX The Gas Controller can interface via the 0 4 to 20 mA or 0 2 to 10 V output signal with any compatible electronic analog control DDC PLC control or automation system The free adjustable parameters and alarm threshold make a very flexible use in the gas measuring possible Simple and comfortable commissioning is possible due to factory adjusted parameters The configuration parameter settings and operation is easy to do without programming knowledge The PolyGard Single Point Gas Controller SPC3 must not be used in potentially explosive atmospheres Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller NEL User Manual SPC3 3300 Page 05 CONTROLS A Wilson Mohr Company 2 Operating Instruction The complete configuration parameterization and service are made via keypad user interface in combination with the display screen Security is provided via two password level
30. istance 200 Q 0 2 10V input resistance 25 KQO overload and short circuit proof Power supply for external analog transmitter 24 VDC max 50 mA Buzzer Acoustic pressure 83 dB A distance 200 mm 0 7 ft Frequency 2300 Hz Serial Interface Transceiver RS 485 19200 Baud Heating Temperature controlled 342 C 38 F 3 6 F Ambient temperature 20 C 4 F Power supply 18 20 VDC Power consumption 0 3 A 7 5 VA Polygard is a registered trademark of MSR Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 SPC3 3300US Specification subject to change without notice www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller TEL User Manual SPC3 3300 Page 28 CONTROLS A Wilson Mohr Company 8 Gas Sensor 8 1 Description The integrated sensor works according to the catalytic bead principle The monitored ambient air diffuses through a sintered metal disk in the sensor Here the explosive gases are burned by catalytic means at a heated detector element pellistor The resulting combustion heat also heats up the detector element This heating changes the resistance of the detector element which is proportional to the partial pressure of the explosive gases In addition to the catalytic detector element th
31. llers Responsibilities It is the installer s responsibility to ensure that all PolyGard SPC3 are installed in compliance with all national and local regulations and OSHA requirements All installations shall be executed only by technicians familiar with proper installation techniques and with codes standards and proper safety procedures for control installations and the latest edition of the National Electrical Code ANSI NFPA70 It is also essential to follow strictly all instructions as provided in the user manual 10 3 Maintenance We recommended checking the PolyGard SPC3 system regularly Due to regular maintenance differences in efficiency can easily be corrected Limited Warranty Re calibration and part replacement may be implemented in the field by a qualified technician and with the appropriate tools Alternatively the easily removable plug in transmitter card with the sensor may be returned for service to INTEC Controls 10 4 Limited Warranty MSR Electronic GmbH and INTEC Controls warrants the PolyGard SPC3 for a period of two years 12 months normal exposure for the sensor from the date of shipment against defects in material or workmanship Should any evidence of defects in material or workmanship occur during the warranty period INTEC Controls will repair or replace the product at their own discretion without charge This warranty does not apply to units that have been altered had attempted repair or been subject to abu
32. m maintenance is necessary Cause Maintenance date exceeded Solution Make the maintenance 3 2 Status Alarm Display of the actual alarms in plain text in the order of their arrival Only those sensor points are displayed where at least one alarm is active Changes are not possible in this menu Symbol Description Function Sensor SPa SP Point No A1 Alarm 1 ON A2 Alarm 2 ON A3 Alarm 3 ON A4 Alarm 4 ON AX Status alarm Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller TEL User Manual SPC3 3300 Page 09 CONTROLS A Wilson Mohr Company 3 3 Status Relay The SPC3 has two alarm relays R01 R02 and two open collector outputs RO3 R04 In the following description they are referred to as alarm relays Display of the actual status of alarm relays Manual operation of the alarm relays sigi Setting Symbol Description Status Function R 01 Relay No 01 Select Relay No OFF Relay OFF No gas alarm ON Relay ON Gas alarm OFF Status relay OFF Manual OFF Relay manual OFF Manual ON Relay manual ON 3 3 1 Manual Operation of the Relays The manual operation of the alar
33. m relays is managed in the menu Status Relay If a relay is in the manual ON or OFF status the orange red alarm LED at the Gas Controller is lit continuously The external operation of the alarm relay via an assigned digital input has priority to the manual operation in the menu Status Relay and to gas alarm Relays manually operated in the menu Status Relay are deleted again by selecting the function Automatic Acknowledging the relays in latching mode is also effected in this menu Select the relay Select the function of manual operation Manual ON Relay ON Select the function Manual OFF Relay OFF Automatic Delete manual operation Reset Reset of a latching mode Take over the function Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 User Manual SPC3 3300 PolyGard Single Point Combustible Gas Controller TEL Page 10 3 4 Menu Measuring Values CONTROLS A Wilson Mohr Company In this menu the current value CV and average value AV with gas unit and gas type for each active sensor point SP is displayed as well as the defined control mode CV or AV mode Symbol Description M Function SP 01 Sensor P No Selection
34. nal which is defined in the menu C A Mode The output signal mA V and starting point 0 20 is selected at the I O Board by means of jumper See fig 5 Out of the signals of all assigned sensor points the Single Point Gas Controller determines the minimum the maximum or the average value and transmits it to the analog output The definition which value is transmitted is effected in the menu Analog Output 1 The analog output can be calibrated at 4 and at 20 mA only in mA mode Therefore an ampere meter measuring range 25 mA can be attached to the AO and the respective factor has to be changed until the analog output corresponds to 4 and or 20 mA During calibration evaluation of the sensor point signals is not possible This calibration is effected by the factory The factors shall not be changed 3 ds Default Symbol Description Status Function Select Min Displays the minimum value of all assigned SP Max Max Max Displays the maximum value of all assigned SP Output Mode me Average Displays the average value of all assigned SP 4 0 Calibration 4 0 4 Calibration factor at 4 mA 20 0 20 0 20 0 Calibration factor at 20 mA 3 7 8 Define the Failure Relay Definition of the failure relay See also fault management 3 1 ee Default Symbol Description Status Function OX Fault Relay R04 ROX Define the fault relay Polygard is a registered trademark of MSR SP
35. on Threshold Alarm is only activated at the end S Delay Time ON I0 of the fixed time sec 0 sec No Delay Gas concentration Threshold Alarm is only deactivated at the os Delay Time OFF 0 end of the fixed time sec 0 sec No Delay Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller User Manual SPC3 3300 3 6 7 Control Mode voor UMEL CONTROLS A Wilson Mohr Company Definition of the alarm evaluation by means of current CV or average value AV E Default Symbol Description Status t Function SP 01 Sensor Point Selection of SP No CV Evaluation CV CV Control by the current gas value AV Control by the average gas value Current average value function see 3 7 4 3 6 8 SP Fault Assigned to Alarm Definition which alarms are activated in case of a fault at the sensor point rur Default Symbol Description Status Function SP 01 Sensor Point Selection of SP No Alarm 1234 A 0 Alarm not ON at SP failure Faut 0000 Failure SP 0000 1 Alarm ON at SP failure 3 6 9 Alarm Assigned to Alarm Relay Each of the 4 alarms can be assigned to any alarm relay Unused alarms
36. on of Sensor Points SP Main Menu Selection of SP n Activate or deactivate SP See 3 6 1 Define gas type See 3 6 2 Define measuring range See 3 6 3 Adjust signal form of the transmitter See 3 6 4 Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller EL User Manual SPC3 3300 Page 14 CONTROLS A Wilson Mohr Company Define threshold 1 See 3 6 5 Define threshold 2 See 3 6 5 Define threshold 3 See 3 6 5 Define threshold 4 See 3 6 5 Hysteresis See 3 6 5 Set delay time ON See 3 6 6 Set delay time OFF See 3 6 6 Define control mode See 3 6 7 Assign SP fault to alarm See 3 6 8 Assign alarm to alarm relay See 3 6 9 and 3 6 10 Assign SP signal to analog output See 3 6 10 Ill HHHH Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller User Manual SPC3 3300 3 6 1 Activate Deactivat
37. r Gain until the value corresponds to the calibration gas concentration Remove calibration adapter with a careful light turn Check the sensor for correct mounting By limiting the gain factor calibration will not be possible any more when the sensitivity of the sensor reaches a residual sensitivity of 30 Then the sensor has to be replaces Calculation Calibration Gas lt gt Target Gas alternative calibration UWeas KALgas X Keas Ucas Example 8 3 Polygard is a registered trademark of MSR Customer Services 858 578 7887 amp 888 GO INTEC INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 UWeas Target gas LEL KALgas Calibration gas LEL Kcas Ucas Factor relative sensitivity LEL calibration gas Factor relative sensitivity LEL target gas Calibration gas 30 LEL Methane Target gas Propane 30 LEL Methane x 100 63 47 61 LEL Propane Cross senivity Data Gas type Acetone Acetylene Benzene Cyclohexane Ethyl Alcohol Ethyl Acetate Ethylene Ethane n Butane n Heptane n Hexane Hydrogen Isopropyl Alcohol Methane Methanol n Octane Propane n Pentane JP8 JET A Sensitivity1 96 96 LEL methane Chemical mark LEL 96 viv 2 60 2 40 1 20 1 30 3 30 2 20 2 30 3 00 1 80 1 05 1 10 4 00 2 20 CH 100 440 500USA CHOR NNNM FENCE GNE Fax 858 578 4633 amp 888 FX INTEC www inteccontrols com 6 70 0 95 2 10 1
38. ration Mode 4 20 Eu 6 2 Configuration Card of Alarm Relays Relay Static Latching Horn No Flash Mode Function D 1 1 1 Time Quitt D D Di Di D Default Energized os No o o o o J o o o R01 R02 R03 R04 6 3 Configuration Card of Measuring Parameters sp sp Gas Meas sp Thresholds Ner SS Pe Signal a2 LAs LAs T ISR ee e reer 20 00 00 fault active 01 Delay Time Assigned SP Assigned Alarm Sec AV Fault lt gt Alarm Alarm Rela ON OFF At A2 ABT as A1 A2 AS A4 Pie Se eo ee Fd SON Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller User Manual SPC3 3300 7 Specifications SPC3 INTEL CONTROLS A Wilson Mohr Company Electrical Power supply 18 28 VDC AC reverse polarity protected Power consumption without options 120 mA max 2 9 VA Analog output signal Selectable Current Voltage Starting point 0 or 20 0 4 20 mA load x 500 O 0 2 10 V load 2 50 kO Proportional overload and short circuit proof Alarm relay R1 30 V
39. s OQ Alarm 1 Alarm 20 IJ gt 4 m 2 1 Description Keypad User Interface Enter Main Menus scrolls through Main Menus and Sub Menus increase or decrease a value Navigates through menus on the same level moves cursor when inputing data Exit programming mode and saves settings return to previous level or menu Enter Sub Menus accepts and stores data silence horn if assigned LED orange Flashes when alarm one or more alarms are active Permanently on when one of the relays is manually operated LED red Flashes when alarm two or more alarms are active Permanently on when one of the relays is manually operated LED yellow Flashes at system or sensor failure or when maintenance needed LED green Power LED 2 2 Setting Changing Setups or Set points Open desired menu window Code window opens if no code level approved After inputting the valid code the cursor jumps on the first position segment to be changed gt Push the cursor onto the position segment which is to be changed a Change the setup set point Save the changed value Finish Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller
40. se accidental or otherwise The warranty also does not apply to units in which the sensor element has been overexposed or gas poisoned The above warranty is in lieu of all other express warranties obligations or liabilities This warranty applies only to the PolyGard SPC3 MSR Electronic GmbH and or INTEC Controls shall not be liable for any incidental or consequential damages arising out of or related to the use of the PolyGard SPC3 If the PolyGard SPC3 needs to be returned to INTEC Controls for service an RMA number must be obtained prior to sending Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916
41. the wall through the 4 marked mounting holes at the back side of the housing These mounting holes are accessible after opening the housing For mounting you additionally have to plug off the PCB See fig 01 The mounting holes are covered with the enclosed caps after the end of the installation We recommend considering the following when choosing the mounting position e The installation height depends on the gas type to be detected For gases whose specific weight is higher than that of air the installation is near the ground For gases with a specific weight lower than that of air installation has to be at the highest point possible e Cables are inserted from below e Keep a minimum distance of 150 mm on the right side in order to open the stainless steel housing e Customers instructions 85 mm 42mm A E Mounting l v Fig 01 Standard plastic housing Stainless steel housing 4 1 Electrical Connection The technical requirements and regulations for wiring electrical security as well as project specific and environmental conditions etc must be observed when mounting The electrical installation may only be completed by a qualified electrician in full compliance with pertinent regulations Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without noti
42. y See from point 3 6 m a 8 8 8 m Display and change of the system parameters See from point 3 7 Polygard is a registered trademark of MSR SPC3 3300US Customer Services 858 578 7887 amp 888 GO INTEC Fax 858 578 4633 amp 888 FX INTEC Specification subject to change without notice INTEC Controls 12700 Stowe Dr Suite 100 Poway CA 92064 www inteccontrols com Printed in USA 140916 PolyGard Single Point Combustible Gas Controller TEL User Manual SPC3 3300 Page 07 CONTROLS A Wilson Mohr Company 3 1 Fault Management The integrated fault management records the last 15 faults with date and time stamps in the menu System Errors Additionally a record of the faults occurs in the Error Memory which can be selected and reset only by the service technician An actual fault is displayed in plain text in the starting menu The failure relay which is defined in the system parameter Failure relay is activated The yellow LED in the front of the gas controller flashes In case of fault of a sensor point SP the alarms defined in the menu SP Parameter are activated additionally 3 1 1 Acknowledge a Fault Attention Acknowledging a fault is only possible after having removed the cause Select menu System Errors Example Failure SP 01 lt 3 mA Reset the fault Fault reset Fault reset Cause not eliminated Reset not possible 3 1 2 Error Memory The menu Error Memory in the m