Insight Power SNMP Card
Contents
1. battery condition e Multiple server shutdown The shutdown software included provides automatic shutdown either pre programmed by administrator or when critical power events also Notification of users via SNMP Traps and e mail through SMTP Network Time Protocol supported Telnet support for configuration BOOTP DHCP supported NetBIOS Name Service supported MD5 HTTP security System Application InsightPower is an interface between UPS and the network It can obtain the status from a UPS and issue commands to it InsightPower supports two kinds of protocol SNMP and HTTP for user access Through the SNMP NMS and Web Browser user can obtain the UPS status issue commands to UPS and setting up InsightPower through the network InsightPower also provides shutdown software for various OS The shutdown software that runs under various OS can link to InsightPower automatically through the network and communicate with InsightPower via SNMP protocol The shutdown software retrieves UPS information from InsightPower Shutdown software will then proceed to the shutdown process in order to prevent the abnormal shutoff of host or server due to power events UPS NMS Station or g Web Browser InsightPower SNMP Card Power Line Ethernet Shutdown S W Shutdown S W Shutdown S W Operating Operating Operating System 1 System 2 System N Figure 1 1 System Application Diagram 4 InsightPower Chapter 2 First Ins
2. 00 00 00 00 00 000 3 00 00 00 00 00 00 000 4 00 00 00 00 00 00 000 5 00 00 00 00 00 00 000 6 00 00 00 00 00 00 000 7 00 00 00 00 00 00 000 8 00 00 00 00 00 00 000 0 Back To Previous Menu Please Enter Your Choice gt Figure 2 10 Setting Trap Receivers Upgrade Firmware InsightPower supports TFTP Client protocol for upgrading new version firmware You need a TFTP server or just run the EzSetting in the CD to upgrade the firmware 1 TFTP Server IP 172 016 176 141 2 Upgrade Now 0 Back To Previous Menu 14 InsightPower Please Enter Your Choice gt Figure 2 11 Upgrade Firmware Soft Restart Simply restart the InsightPower Reset All To Default Clear all of the settings in EEPROM Exit Without Save Exit and disregard the changes Save And Exit Preserve your changes in EEPROM and exit InsightPower Chapter 4 Managing InsightPower Running the Web Browser Internet Explorer 1 Make sure that you have a TCP IP network already installed 2 If there is no DHCP network service on the network contact your network administrator to get an IP address for you workstation that has the same network s address as the InsightPower IP address The default IP address of InsightPower is 192 168 1 100 3 Start your Web Browser Enter the URL http nhost_name or http ip_ address in the address box The InsightPower will then ask for your account and pa
3. After the user defined Estimated OS Shutdown Delay the output power is switched off InsightPower Client or SNMP ShutdownAgent must be used on the server for it to be properly shutdown The Estimated OS Shutdown Delay includes the assigned countdown delay in the shutdown software plus the duration of OS shutdown process When shutdown software receives the Smart Shutdown signal the low battery reaction settings will be used to process the shutdown procedure UPS Shutdown Schedule Only UPS InsightPower device supports two kinds of shutdown schedule 1 Weekly Schedule 2 Special Day Schedule Set both of these options to plan your UPS schedule shutdown and restart time UPS Shutdown Software InsightPower Client If your InsightPower device needs to work with shutdown software to protect your servers which are powered by the UPS and you want to control the 18 InsightPower schedule shutdown and restart from InsightPower device then please visit the Configure page and enable the Perform Smart Shutdown in Schedule option You can also set the schedule at shutdown software side And because the shutdown software will send the control command to UPS through SNMP to shutdown the UPS we have to add the server IP address with write permission in the SNMP Table of InsightPower device Note Before managing the UPS Shutdown Schedule please make sure that the Date and Time configured in InsightPower is correct
4. LAN then please run the EzSetting utility to configure the User Limitation to Allow Any Terme Zone GMT 08 Beijing Tape bet Tiere Server Nae or 172 106 2004 Dd Tire Server Sarre or F wOsret Tow Coe oO 17 2007 Teme 00 00 lt x nes t a recommended t proves a static P Adie arwi Gst Te BOOTP OLP Cent opion Ifan te fret tme orfigae por aj Posar dae pema ee a aa here h he Dat fare felt ad Gren a Time Sarsa for Pe Gmie Proft INTP protocol f pomsbis 4 How to refresh the NetBIOS table in Windows operating system Answer Sometimes the IP address of InsightPower will be changed but keep the same host name although Windows will update its NetBIOS table periodically but we can force it to purge its cache immediately by typing the following command nbtstat R After that you can connect to the InsightPower by its host name 5 How to get the IP address and MAC address from my computer Answer In Windows system please type ipconfig all in DOS prompt For Unix system please use ifconfig in the shell 6 Unable to ping or connect to the adapter Answer 1 Check all network connections 2 Ensure that your PC and the InsightPower are on the same network segment If you don t have a router this must be true 3 It may be that your arp table contains invalid entries You can clear the arp table by rebooting or by typing the following command at the command prompt or Run dialog box arp d 4 You
5. None 7 000 000 000 000 None 8 000 000 000 000 None 0 Back To Previous Menu Please Enter Your Choice gt Figure 2 8 SNMP Trap 13 InsightPower Time Server There are 2 ways to provide current time and date to InsightPower one is set the system time manual but it is not an ideal way The other one and ideal way is setup a time server for InsightPower InsightPower supports SNTP which MS Windows XP has been supported If you have installed the InsightPower Client from the bundled CD you can just assign the host in the Time Server IP address Because InsightPower Client has the ability to act as a time server for InsightPower device Instead of that you need to install the Simple TCP IP Services from Add Remove Windows Components SSS So e e a aa ea e Time Server SSS SSS 525552 S22 SSS2 gt 4 1 Time Selection SNTP 2 Time Zone 8 hr 3 1st Time Server 172 016 176 141 4 2nd Time Server jesse tri 5 Manual Date 01 01 2000 MM DD YYYY 6 Manual Time 00 00 00 hh mm ss 0 Back To Previous Menu Please Enter Your Choice gt Figure 2 9 Time Server Wake On LAN InsightPower supports the magic packet to wakeup workstations in 2 conditions power restore or system startup with a delay time ee ee a ee al a et ee Wake On LAN ee SSeS aS SSS SS aa a p Index MAC Address Delay Trigger Conditions 1 00 0c 08 34 4d 57 001 Power Restore System Startup 2 00
6. UPS Shutdown during Power Crisis Only UPS InsightPower responds to 2 different kinds of UPS shutdown events AC failed Battery Low Goes to the Configure in the UPS Management menu Logging in as an Administrator Set the options in UPS Shutdown Action section then press the Submit button UPS Shutdown Software InsightPower Client If your InsightPower device needs to work with shutdown software to protect your servers which are powered by the UPS then you should clear all of the settings of UPS schutdown action in the InsightPower device Instead of that set the reaction shutdown at software side And because the shutdown software will send the control command to UPS through SNMP to shutdown the UPS we have to add the server IP address with write permission in the SNMP Table of InsightPower device Note Once InsightPower detects there is at least one shutdown software running the event driven shutdown would be canceled Wake Computer Up Please check the BIOS settings and enable WOL option Then go to the Wake On LAN page in the Network menu Please note that this feature should only available for the servers in the same LAN with InsightPower device Email Notification This page describing of UPS email notification setting to let administrator configure Mail server and Mail receivers in order to receive notification or report from InsightPower by email once power event was occurred 1 SMTP Server Name or IP This item
7. command as in the DOS prompt Messages will then are displayed on the screen afterwards key in the administrator account default account is admin and password default password is password The InsightPower configuration main menu will be displayed on the screen Please refer to the Text Mode Configuration section for more information Note InsightPower will terminate the telnet connection if there is no data transmittion in 1 minute Text Mode Configuration UPS Web Version 1 0 User Manager System Configuration SNMP Access Control SNMP Trap Time Server Mail Server Wake On LAN Upgrade Firmware Soft Restart Reset All To Default Reset Hub To Default Exit Without Save Save And Exit ONTMODMDIDAUAWNHE Please Enter Your Choice gt 1 Figure 2 4 InsightPower Main menu User Manager SSS SSS SS SSS Se ae User Manager SaaS eae ae See eeS Administrator 1 Account admin 2 Password orale Roe dea 3 Limitation Only in This LAN Device Manager 4 Account device 5 Password PIAS 6 Limitation Only in This LAN Read Only User 10 InsightPower 8 Ne 7 Account user Password Limitation KKKKKKKK Only in This LAN 0 Back To Previous Menu Please Enter Your Choice gt Figure 2 5 InsightPower User Manager menu No Function Description Default 1 A
8. is the Hostname of a SMTP Mail Server that will be used to send email messages from the InsightPower If entering a Hostname you are also required to enter the DNS IP in the System Configuration Sender Mail Address This item is the e mail sender address in the following format name company com Password This item is the password of Mail Server Default has no entry and only required if Mail Server needed for authentication to send mail 19 InsightPower 4 Receiver This column is for entering the email address of the individual you wish the InsightPower to send mail to 5 Event Level This item is for selecting the Severity level of notification you wish to send to each Mail Receiver configured to be sent Mail Type Events or Events Status SNMP Access Control Setting InsightPower supports SNMP protocol You can use SNMP NMS to manage UPS through the network The IP address of the workstation must be entered in the InsightPower write access table to prevent unauthorized users from configuring InsightPower via SNMP protocols Power Fail Restore Simulation To make sure the network configuration is correct InsightPower provides 2 test buttons to simulate power fail and power restore events After pressing the test buttons InsightPower send the related SNMP trap to the assigned target hosts and simulate the power event values to SNMP response data The power fail simulate will be terminated automatically in 30 minutes to prevent
9. InsightPower UPS SNMP Card User s Manual InsightPower Table of Contents Chapter 1 Introduction Model Differences Features System Application Chapter 2 First Installation Trouble Shooting Chapter 3 Configuration Configuring the InsightPower by EzSetting Configuring the InsightPower throught COM Port Configuring the InsightPower throught Telnet Text Mode Configuration User Manager System Configuration SNMPv1 Access Control SNMP Trap Time Server Wake On LAN Upgrade Firmware Soft Restart Reset All To Default Exit Without Save Save And Exit Chapter 4 Managing InsightPower Running the Web Browser Internet Explorer UPS Information UPS Management gt gt Configure UPS Management gt gt Control Smart Shutdown UPS Shutdown Schedule UPS Shutdown during Power Crisis Wake Computer Up Email Notification SNMP Access Control Setting Power Fail Restore Simulation Updating UPS SNMP Device Firmware from Windows Chapter 5 Shutdown Software Installation of InsightPower Client in Windows Installation of SNMP Shutdown Agent in Windows Chapter 6 Specification Technical Specification PIN Assignment DIP Switch Definition LED Indicator oOoOnmuan ikrwWW OO InsightPower Chapter 1 Introduction Model Differences There are 2 models for SNMP card One is InsightPower SNMP card with golden finger connector the other one is mini SNMP card Their outlines are as the following e InsightPower SNMP Card Network Port lt CO
10. M Port lt Dip Switch lt There is an additional COM port for InsightPower SNMP card with golden finger This COM port is used to do the configuration or connect to a environmental sensor box e mini SNMP Card Dip Switch lt i Network Port lt Due to the limitation of PC board size mini SNMP card has no COM port other than that the other features are all the same The settings of Dip Switch are different too In the normal mode InsightPower SNMP card needs to set the dip switches to the OFF position but the mini SNMP card needs to set to the ON position Features e Network connection through RJ45 connector Allows connection of the UPS directly to the ethernet network through a RJ45 connector without using RS232 ports on the computer and without loading any individual UPS management software on the network server e Network UPS management Allows remote management of the UPS from any workstation through Internet or Intranet e Remote UPS monitoring via SNMP HTTP Allows monitoring of the UPS using Delta MIB Management Information Base Internet Browser e Configure UPS and system functions from any client password protected InsightPower Set UPS and system parameters from any SNMP management station or through Internet Browsers using HTTP forms and objects e Keep event logs amp metering data in EEPROM Provides a history data of UPS power events power quality UPS status and
11. arch all of the UPS in the LAN All of the UPS SNMP DEVICE will be listed in the Device List See 2 1 If you want to search the InsightPower devices in a different domain network just change the subnet and subnet mask addresses then press the Discover button to list them E lnsightPowes ExTetting v1 5 5 AM ra Press Discover button to search all of the SNMP devices in the LAN Discover j Then select one of device in the Device List which you would lhe to configure or upgrade it But before to do tut please provide the account name and password by pressing the Modify buten Ser gt gt Configurator is used bo sip the P ackiress ratmaik enable or dabble networking services Upgrade button used to load the device firmware file then fareme t w te solected device xe Lit P Adress 1721 86 233 Pi 56 087 INVERTERIWER Lt atten oag AGI an raw tem Of SNMP device iF F 112 DX to the Device List manually Host Name LA Password ar Mer Pi D a Modfy Set he account and paseword r he selected davee Remove Remove the selected device gt from the Device List Figure 2 1 EzSetting screen If the InsightPower device can not be found check the networking port UDP 3456 in the OS Open it if it is blocked Select the device in the device list to configure the network parameters then press the Modify button to provide your account and password The default account and password are admin and password See 2 2 InsightPow
12. ation are in the same LAN 11 Open EzSetting from CD and refer to next chapter for configuring InsightPower by EzSetting 12 You need to change the Host Name IP Address 13 Because there is no BOOTP DHCP server in your network environment you need to disable BOOTP DHCP option in the System Configuration group 14 Please refer to next Chapter Configuring the InsightPower by EzSetting section for more detail information on configuring the InsightPower in an easy way Trouble Shooting 1 How to provide a SNTP Simple Network Timer Protocol server for InsightPower Answer There are 2 ways to provide a network time server for InsightPower The easiest way is to install the InsightPower Client software you can find it in the bundled CD The other one is to install the Simple TCP IP Services of Networking Services from Add Remove Windows Components You may need a Windows CD while installing Don t forget to provide the IP address of the host in the Time Server page 2 How to make sure the network connection is established between my workstation and InsightPower Answer Check the networking connection by typing the following command ping HostName or IP from your workstation InsightPower 3 In the internet explorer can see the Login page but cannot login Answer Please check the IP addresses of the SNMP card and the PC which you try to login If both of the IP addresses are not in the same
13. can connect to the InsightPower ONLY if your PC and the InsightPower are using IP Addresses from the same address block Normally private LANs use IP Addresses from ONE of the following blocks which are reserved for this purpose 10 0 0 0 10 255 255 255 172 16 0 0 172 31 255 255 192 168 0 0 192 168 255 255 The InsightPower s default IP address 192 168 1 100 is from the last block If your LAN is using a different address block then you will NOT be able to connect to the UPS Adapter via the LAN In this case your choices are o Use Terminal Mode configuration to set the InsightPower s IP Address o Use the TCP IP arp utility to provide a temporary IP Address to the InsightPower o Change your PC s IP Address to allow connection via the LAN InsightPower 7 Unable to perform SNMP get operations Answer Check the SNMP settings stored in the InsightPower The IP Address of the PC you are using must be entered in one of the SNMP Access Control NMS IP fields with Read or Read Write permission The Community String on the PC and InsightPower must match 8 Unable to perform SNMP set operations Answer Check the SNMP settings stored in the InsightPower The IP Address of the PC you are using must be entered in one of the SNMP Access Control NMS IP fields with Read Write permission The Community String on the PC and UPS Adapter must match 9 Unable to receive traps at your management station Answer Check the SNMP Trap se
14. dministrator Account Administrator gets the whole rights to admin 2 Administrator Password modify he asighiPowerand URS password settings 3 Administrator Limitation oe login area ohtine administator 6 aivin This LAN 4 Device Account Device Manager is permitted to change device the network setting but has the ability to 5 Device Password configure the UPS settings password 6 Device Limitation Restrict login area of the device manager Only in This LAN T User Account Read Only User can observe the UPS user 8 User Password information only password 9 User Limitation Restrict login area of the general user Only in This LAN System Configuration ee System Configuration CB aaa te ee 1 IP Address 192 168 001 100 2 Subnet Mask 255 255 255 000 3 Gateway IP 192 168 001 254 4 DNS IP 192 168 001 001 5 BOOTP DHCP Client Enable 6 HTTP Server Enable 7 Telnet Server Enable 8 FTP Server Enable 9 HTTP Server Port 80 a Telnet Server Port 23 b SNMP Get Set Port 161 c SNMP Trap Port 162 d Host Name NetBIOS INSIGHTPOWER e System Contactor f System Location g Status Stable 3 0 Back To Previous Menu Please Enter Your Choice gt Figure 2 6 System Configuration Menu No Function Description Default 1 IP Address The InsightPower IP address 192 168 001 100 2 _ Subnet Mask The sub net mask setti
15. down amp Restart UPS Only Sends a single shutdown or restart command to the UPS or combine the shutdown and restart commands to the UPS Once the UPS receives the command it executes the commands with the assigned delay time Smart Shutdown The configuration of Smart Shutdown is located in the Configure web page The Smart Shutdown is used to launch the smart shutdown mechanism immediately InsightPower Outlet Control Some UPS models are allowed to control their output receptacle banks individually These commands are used to turn on or off with a delay time for each output banks Power Fail Restore Simulation These buttons are used to simulate the power fail and power restore signals by the SNMP card itself They will not affect the UPS but will affect the shutdown software Users can verify the shutdown installation by pressing these buttons instead of unplugging the input power cord System Time 03 27 2008 Thursday 13 31 42 Rack to Home UPS Management gt gt Control Battery Test Battery Test Type 10 seconds Test v Subent IPS Shutdown Delay fv 160 Seconds tart Delay 60 Minutes Subrat r ated OS S 300 Seconds Span reer Cancel Shutdown Dank 1iTurn Off in Pmr Seconds Smtch Banki tch_Bank1 2 Turn Off in 60 Seconds Switch_Bank2 Power Fi Restore Simulation Power Fail Test Powar Restore Test Smart Shutdown Initiates a signal for the server to shutdown
16. er 8 AGennistrater Account Account admin Default admin Password Dof uk password Figure 2 2 Provide the account and password Click on the Configuration button and setup the essential network parameters See 2 3 Configuration System identification System Configuration Host Name NetBIOS 1P2 IP Adress System Contactor Subnet Mask System Location Gatrway IP Date Time ONS IP snTP OMarnual BOOTP OMCP Chant l Disabie Time Zone GMT 08 Beijing Taipei HTTP Server G ODisable ist Time Server Name or IP 172 136 186 116 Tehet Server enabke ODmable 2nd Time Server Name or IP HTTP Server Port S0 Set Current Time Date 07 26 2006 AMMADO Telnet Server Port 23 Time 12 00 00 hh mm ss User Limitation Adminstrator in The AN Allow Any R 4al a cawel A Revet to Default cancer Device Manager in The Lan Allow Any It is recommended to provide a static IP Address and Read Only User in The LAN O Allow disable the BOOTP DHCP Client option ay bf it is the first time to Configure your InsightPower device pioase a5sign an unique name in the Host Name field and Given a Time Sarver for the device throught SNTP protocol if possible Figure 2 3 Configure the system parameters Configuring the InsightPower throught COM Port a 2 ALD O Prepare a workstation Microsoft Windows 9x Me NT4 0 2000 2003 XP or later installed Use the RJ45 to DB9 seria
17. ettings in the InsightPower Client software In this case you still can configure the schedule shutdown restart and event driven shutdown from InsightPower Client software Installation of SNMP Shutdown Agent in Windows 1 Insert the InsightPower CD ROM into the CD ROM drive 2 Run the SNMP ShutdownAgent Setup exe program on the CD ROM 3 After set up is complete please continue to provide the IP address of InsightPower device The SNMP Shutdown Agent open the specific UDP port and listen for SNMP traps when the operating system initiates 22 InsightPower Chapter 6 Specification Technical Specification Network Connection RJ 45 jack connector Operating Temperature 0 40 C Operating Humidity 10 80 PIN Assignment Cens Nein Ne DIP Switch Definition Golden finger SNMP card No SW1 SW2 Function Mode ssid Mini SNMP card swi sw2 Function Mode ON SNMP Normal Mode the UPS doesn t response to its RS232 port OFF SNMP Stop Mode PC can communicate with the UPS through its RS232 port LED Indicator No Yellow LED Green LED Function Mode 1 Flashing 0 2 sec Normal operation 2 Flashing 1sec UPS Disconnect 3 OFF Hardware or network error 23
18. from forgetting press the Power Restore Test button Updating UPS SNMP Device Firmware from Windows To perform firmware upgrade use the EzSetting exe program on the CD ROM This program is compatible with Windows operating system E lasightPowes ExTettiing v1 5 5 Prove Deecover button to search all of the SMP devices in the LAN Recover Then select one of device in the Device List which you would lhe t configure or upgrade it But before to do fiat please provide the account name and password by pressing the Modify buton Seret Sy Configuration is used b sip the P ackiress netmask enable or dinable Configurator _ heatworking services Upgrade button s uted to bad the Gove firmware file then raceme t w e x Te solected dwie uy Password Version Mocda Prodkxt Mer MCP LOOOR Ma Dx Lidt Inverter 90 20 AI an naw tam of SNMP device t the Device List manually Mody Set Te accourt and pateword r the selected davee Remove the selected device gt fom te Device List 1 Device List Displays the addresses of the UPS SNMP DEVICE present in the local network 2 Discover Search for the InsightPower devices in the local network 3 Add Lets you add the IP address of an UPS to the Device List manually 4 Modify Lets you modify the parameters of the device selected in the Device List 5 Remove Removes the selected device from the Device List 6 Configuration Provides an easy wa
19. l cable that provided from package connect between the InsightPower COM port and the COM port on the workstation Set both the DIP switches of the InsightPower device to OFF position normal mode From the workstation running Microsoft Windows 9x Me NT4 0 2000 2003 XP or later and click on the HyperTerminal icon of the accessory programs group Enter a name and choose an icon for the connection Select direct COM port connection Setup the COM port parameters 2400 bps 8 data bits no parity 1 stop bit and no flow control Set both the DIP switches of the InsightPower to ON position configuration mode Messages will then are displayed on the screen afterwards key in the administrator account default account is admin and password default password is password The InsightPower configuration utility main menu will be displayed on the screen Please refer to the Text Mode Configuration section for more information InsightPower Configuring the InsightPower throught Telnet 1 2 3 Connect the InsightPower to the network Prepare a workstation Microsoft Window Max OSX or Linux installed which is connected to the same LAN Make sure both the DIP switches of the InsightPower to OFF position normal mode From the Windows workstation running DOS Prompt and type telnet HostName or IP to open the telnet connection with InsightPower For other operating system user please run the OS shell and type the same
20. munity string first to identify the incoming packet is read only or not If they are identical then InsightPower responses the inquiring value SSS SSS SS SS SSS SS SS e SNMP Access Table Saat banttmtneinny 0 Index NMS IP Community Permission 1 01 Other SNMP NMSs public Read Only 2 02 172 016 176 141 insightpower Read Write 3 03 000 000 000 000 Not Access 4 04 000 000 000 000 Not Access 5 05 000 000 000 000 Not Access 6 06 000 000 000 000 Not Access 7 07 000 000 000 000 Not Access 8 08 000 000 000 000 Not Access 0 Back To Previous Menn Please Enter Your Choice gt Figure 2 7 SNMP Access Table SNMP Trap If you want to use a PC and perform the SNMP manager trap function in order to manage UPS through InsightPower the IP address of the PC must be added to the SNMP Trap list The Event Level field is used to decide what kind of power events should be send to the target address There are 3 levels of power events Information Warning and Severity If you select the Information then all of the power events will be send to the target IP address warning level will send the Warning and Severity events to the target address SSS ae eee a a e r e SNMP Trap a ta at e Index Target IP Community Event Level 1 172 016 176 142 insightpower Information 2 172 016 176 143 private Warning 3 172 016 176 144 public Severity 4 000 000 000 000 None 5 000 000 000 000 None 6 000 000 000 000
21. nable or disable the UPS buzzer If it is selected to disable then the UPS will not alarm permanently The setting value will be kept on the UPS side Sets the Buzzer Alarm to Silence will mute the UPS until next power event occurs Voltage Sensitivity Decide the detection rate for the input voltage The setting value will be kept on the UPS side Low Battery The UPS has already built in a low battery level but if you want to send the low battery signal earlier Please enable this item and input the threshold for the low battery level This value will not change the built in value in the UPS but the setting value will be kept on the SNMP card side UPS Shutdown Action These options are used to turn the UPS off when Power Fail or Battery Low occurred But if there is a InsightPower Client connected then the countdown will not be started until the connection of InsightPower Client is released to prevent from turning the PC power off unattended The setting value will be kept on the SNMP card side Smart Shutdown Estimated Shutdown OS Delay is used to predict the longest shutdown time of all of the connected operating systems The setting value is kept in the SNMP card side Battery Replacement Date The setting values are kept in the UPS side UPS Management gt gt Control Battery Test Sends the battery test command to the UPS There are 3 commands 10 seconds Test Test Until Battery Low and Abort Test Shut
22. ng 255 255 255 000 3 Gateway IP The network default gateway 192 168 001 254 4 DNS IP Domain Name Server IP address 192 168 001 001 5 BOOTP DHCP Client Enable Disable BOOTP DHCP protocol Enable 6 HTTP Server Enable Disable HTTP protocol Enable 7 _ Telnet Server Enable Disable telnet protocol Enable 3 FTP Server Enable Disable FTP protocol Enable For batch configuration purpose 11 InsightPower HTTP Server Port HTTP networking port 80 Telnet Server Port Telnet networking port 23 SNMP Get Set Port SNMP polling and response port 161 SNMP Trap Port SNMP trap port 162 Host Name NetBIOS Host name for Windows INSIGHTPOWER System Contactor Alphanumeric string System Location Alphanumeric string emoja eje Status Stable Status change confirmation check time 12 InsightPower SNMPv1 Access Control If you wish to use a workstation with SNMP Manager installed or if you wish to set more restrictive InsightPower access you can use the access table to add the IP address of the PC s on which you wish to modify the access permissions Figure 2 7 The communication protocol between shutdown software InsightPower Client and the InsightPower device is SNMP the administrator needs to maintain this table for all workstations to keep UPS and workstations work correctly The index 01 is a special design for all read only workstations InsightPower checks com
23. ssword input the correct account and password then UPS management Web home page will be shown on the screen 4 If the Login web page can be displayed but unable to login with the correct account and password The reason may caused by the IP address where you login is different with the SNMP card IP address please refer to Chapter2 Trouble Shooting Note InsightPower will logout user automatically if there is no data transmittion through HTTP connection more than 30 minutes UPS Information Includes the information of identification status battery input output and bypass These web pages will be refreshed every 10 seconds UPS Management gt gt Configure 03 27 2008 Thursday 12 17 10 Reboot After Power Restore F Enable Subma j Boot Delay After Power Restore130 Seconds Submit Buzzer Control F Enable Subma Alarm Silence Subma Normal Subma Enable lt 30 Submit D Enable 0 Seconds t w C Enable 0 Seconds Subma Smart Shutdown Delay 300 Seconds a Z Enable Subma To perform Smart Shutdown please visit the Control page 12 30 2006 MM 0D YYYY ste 12 31 2009 mM DD YYYY Submit gt 2 n O InsightPower Auto Restart If the UPS is turned off during the input power failed then next time when the power restores the UPS can decide to restart automatically or not The setting value will be kept on the UPS side UPS Buzzer Buzzer Control is used to e
24. tallation Please check your network environment if there is a BOOTP DHCP server in your LAN then begin from step 1 otherwise start from step 9 1 Connect the InsightPower device in your LAN 2 Open the internet browser and link to the InsightPower device by typing the default host name InsightPower in the address edit box 3 Login as administrator with admin account and password for default password 4 Open the User Manager page to manage your accounts and passwords 5 There is a limitation in the User Manager page to restrict the login users to login in the same LAN or not Select Only in This LAN option to restrict this login account can only login in the same LAN with the SNMP card selecting Allow Any allows this account to login from anywhere Switch to the System Configuration page and change the default Host Name Configure the IP address Subnet Mask Gateway IP for InsightPower device If there is no DNS server then you need to assign IP address for mail server if you want to be notified e mail 8 We recommend you to disable the BOOTP DHCP option and assign a valid static IP address 9 Open the Time Server page to synchronize the InsightPower device and time server Please refer to next section on how to construct your SNTP server NO If you have no BOOTP DHCP server in your LAN then follow belows 10 Make sure both of the InsightPower device and your workst
25. ttings in the InsightPower The IP Address of the PC you are using must be entered in one of the Target IP fields The Community String on the PC and InsightPower must match 10 Forget the administrator s account and password Answer Connect the configuration cable in console port and set both of the DIP switches of InsightPower to ON position configuration mode and key in the rstadmin while the account and password are prompted in 30 seconds Now the account and password of administrator are reset to default values InsightPower Chapter 3 Configuration The easiest way to configure the InsightPower is running EzSetting you can find the software in the CD Please see below sub section for more information If you have configured the essential network parameters successfully you can launch the internet browser or telnet to the device which you just assigned to do detail configuration The first thing is to open the User Manager page and change your accounts and passwords Configuring the InsightPower by EzSetting 1 Prepare a workstation Microsoft Windows 9x Me NT4 0 2000 2003 XP or later installed Make sure both the DIP switches of InsightPower to OFF position default normal mode to enable network transmission Make sure the workstation and InsightPower device are in the same LAN Put the provided CD in the CD ROM drive and find the InsightPower EzSetting then launch it Press the Discover button to se
26. y to do the initial configuration through networking UDP port 3456 If you cannot get the device information please check and open the UDP port from your OS 7 Upgrade Sends the program loaded with the Browse button to the selected 20 InsightPower device of the Device List 21 InsightPower Chapter 5 Shutdown Software There are 2 kinds of shutdown software to help you to protect servers from power crisis One is InsightPower Client the other one is SNMP ShutdownAgent Both of them have the ability to shutdown servers gracefully The major difference is SNMP ShutdownAgent can only receive SNMP traps of power fail and battery low signals but InsightPower Client can observe UPS parameters record power events and values for you Installation of InsightPower Client in Windows 1 Insert the InsightPower CD ROM into the CD ROM drive 2 Run the InsightPower Client Setup exe program on the CD ROM 3 After set up is complete please continue to provide the host name or IP address of InsightPower device and community string which has been set in the SNMP Access Control menu The InsightPower Client service connects to the device automatically when the operating system initiates Please note that when the InsightPower Client connects to InsightPower SNMP Card the schedule and UPS Shutdown Action settings in the SNMP Card would be ignored until the connection of InsightPower Client is released to prevent from conflicting with the s