instruction manual dega upa ii l

image

Contents

1. st a l s v9ud _ E T MESES A u vx i ae ON S 2 ES pe cs sm S a 82 E k X AW OW AW voaavct SUR Hes qm Ma ca S P Ce JN oe C go ER Tal on 17 Shen ks TS ar zZ nis NE TL gt pz nis C Ju A JN d IET 1 D x A 8 gt cle ca 8 lt ON ad me TL raih S I JA rpi N Z 2S mz oa dcn ON ese ss ens i x usd dr ESL e cg 9 lel adhe 1 Z T s ON amp ig sin ty y03 wile lt 78 Sx k l I QO E 1 gt x S YENA a IN a S V av JUNE e L Vos e di OU 6 LJ _ E ool JN gt A em O O T IS LT fe T es Jo 7 2 am E PB qul H L VS VU Hy 1 6 oig Ay VAN VOR ec
2. DEGA UPA IIL x channel number Shielded 3 x 1 mm max 600m Shielded 3 x 1 5 mm max 1100m DEGA DV DEGA UPA IIL x channel number Shielded 4 x 1 mm max 100m UTP cat 5e max 100m yellow DEGA Tc Il DEGA UPA IIL Shielded 4 x 1 mm max 100m UTP cat 5e max 100m DEGA Zc DEGA UPA IIL v OPERATION OF THE COMPACT CONTROLLER Two buttons are used for the operation of the compact controller the button and the button Switching between the channels displayed transmitters using the IL button it is possible to switch between the occupied channels Resetting the acoustic alarm press the button thereby deactivating the internal piezo buzzer for 20 minutes the ALARM relay switches to the idle mode If after 20 minutes the event for which the acoustic alarm was activated still persists the sounder starts up again and the ALARM relay is switched on It is possible shut down the acoustic alarm 3 times in a row and subsequently it will no longer be active for the duration of the alarm Note Resetting the acoustic alarm causes only temporary deactivation of the acoustic alarm The other signalling features relays LEVEL1 LEVEL2 etc remain functional Service mode If it is necessary to replace the transmitter without announcing failure or alarms it is possible to freeze the status of all the relays of the compact controller for up to 60 minutes This is achieved by
3. INSTRUCTION EGA MANUAL k we Compact Evaluation Controller DEGA UPA II L ISO 9001 2008 Quality Management Systems Syst me de Qualit www sgs com Content Page 2 For your protection Page 2 Technical data and information Page 3 Operational and external conditions Page 3 Basic types Page 4 Accessories Page 5 Description of the product Page 7 Installation assembly and disassembly Page 9 Operation of the compact controller Page 9 Functions of the compact controller Switching on the compact controller The idle mode The gas alarm status i e exceeding the limits of detection levels 1 4 The PEL status of the gas alarm Failure Detection of critical temperatures Detection of flooding Emergency valve Solenoid valve Status of the required service intervention calibration of sensors Functions of the DEGA UPA II LS controller Functions if the DEGA UPA Il L MULTI controller Page 12 Operation and maintenance Operation Maintenance Monitoring of the calibration periods Page 13 15 Appendices Appendix No 1 Example of the connection of the compact DEGA UPA II L controller Appendix No 2 Example of the connection of the compact DEGA UPA II L S controller Appendix No 3 Example of the connection of the compact DEGA UPA II L MULTI controller Page 16 General warranty terms and conditions Reproduction of this manual or any part thereof in any form without the prior written permission of DEGA
4. MAINTENANCE For proper operation of the detection system which also includes the controller it is requisite to periodically undertake specifically the following servicing of the transmitters connected to the controller a calibration at least once every 6 12 months i e setting the detection limits checking the responsiveness of the sensor checking the system s functionality The precise interval is dependent on the level of contamination of the environment the degree of accuracy required and the level of occurrence of the selective gases in the environment Calibration should be carried out only by authorised service centres holding a valid certificate of competency or by the manufacturer b Functional checking at least once every 3 12 months Functional checks are performed utilising the test gas at the concentration that is intended for it this must not exceed the limit range of the transmitter We recommend gases with a certified 1st grade of purity Recommendation For ideal functioning it is recommended to carry out the calibration and the functional checks once every 6 months or the calibration once every 12 months and the functional check once every 3 months The means for testing the fire alarm transmitters must not be utilised for these checks v APPENDICES Appendix No 1 Example of the connection of the DEGA UPA II L compact controller
5. CZ s r o QJ is prohibited DEGA CZ s r o reserves the right to alter the specifications of the hardware and software described in this manual at any time and without prior notice DEGA CZ s r o bears no liable for any damage resulting from the use of this device v FOR YOUR PROTECTION OOOO EI E Watch out for static electricity Prior to installing or handling the product ensure that you do not have an accumulated static charge Touch a grounded metal object to trigger the discharge of any accumulated electric charge Otherwise the product could suffer damage In the event of any failure of the equipment unplug it immediately If you notice an unusual odour or smoke emanating from the product unplug it from the mains and from all peripherals Continued operation could result in injury or property damage After disconnecting the product deliver it to an authorised service centre or the manufacturer for inspection Do not use the product in the vicinity of flammable gases or in areas where there is a potential occurrence of these gases Do not use electronic equipment in the vicinity of flammable gases this could potentially cause a fire or an explosion The product is not designed for use in industrial or commercial spaces nor in Ex hazardous areas Do not disassemble the product and ensure against its contact with water Contact with internal components of the product may cause an electric shock In the case of any failure refer the ser
6. INS MN 7c X8 8 gc V 9 mu 5 gol 8 d mo COME i aL 7 E E To D T E E ag V NTE 29 3 EM E dm 7 Sdn I Na q L 5 Q J E Appendix No 2 Example of the connection of the DEGA UPA II L S compact controller Em a v MEE BS srez ry P pe LUN rs z 7S Ba EI 3 r Ol Vil ras EP vt Z ea YW YOSSI JN ee v 3d be 2 GE S2 Je oe WEN ce A ty E J RM t5 Vc S e ves JN az UR x OC PZ a rp Be UN P8 MESS ET ot 2 e a7 i on 8 A 5 21 E zog w ae T S YDH b i A prs FE Ed K fe UN Eg Z
7. When the TWA concentration is exceeded the icon and DANGER sign are lit up and the switching on of the LEVEL4 and the ALARM relays and the activation of the internal acoustic alarm PEL in English TWA Time weighted Average This function is activated only in the case of the detection of toxic gases e g carbon monoxide CO etc Note Levels of PEL alarms for individual gases for specific transmitters are set by default in accordance with the specifications of the transmitter and can be adjusted in accordance with the customer s requirements Note This function is not included in the DEGA UPA II L S version FAILURE ERROR In the event of any failure of the compact controller or of its accessories the yellow LED ERROR comes on the ERROR relay switches to the C3 NC3 position the acoustic alarm is activated the ALARM relay is switched on by contacts C4 NO4 and the appropriate symbol commences flashing on the display In the event of the failure of the DEGA UPA II L compact controller only a Ea symbol flashes on the display Inthe event of the failure of the gas liquid transmitter only a key symbol together with the icon flash on the display together with the number of the channel on which the transmitter that signalled the failure is located Pi Pei symbol and the sud icon flash on the display In the event of a failure of the critical temperature sensor DEGA Tc II only the key E symbol and the ico
8. coil of the switching power of up to 7 VA The valve is connected by means of a two wire cable to the terminals marked DEGA HV and DEGA HV A voltage pulse is transmitted in the following cases power failure failure of the gas transmitters exceeding level 4 of concentration Note Connect the emergency valve of the DEGA HV DN15 DEGA HV DN20 or DEGA HV DN25 type to the compact controller Solenoid valve The relay of the compact controller can also be used for controlling the solenoid valves of the without voltage closed type with a 230VAC coil Connect one wire of the valve coil to the neutral wire Connect the other wire to the NO terminal of the relay NO RES Connect the C terminal of relay 8 C RE8 to the live wire Valve closure occurs in the following instances power failure failure of the gas transmitter s exceeding level 4 of concentration Note The requirement for controlling the solenoid valves must be specified in the order THE STATUS OF THE REQUIRED SERVICE INTERVENTION CALIBRATION OF TRANSMITTERS The compact detector in conjunction with the NBX II transmitter is provided with automatic monitoring of the calibration periods of the gas transmitters Following the expiration of 12 months since the last calibration of the transmitters the user is alerted to the necessity of recalibra tion This status is displayed by long flashes of ERROR LED flashing Fa and the e NilsyVile mselel iapim icon The compact c
9. pressing the and the buttons for at least 5 seconds The display then shows only the length of time up to the reactivation of the compact controller 60 minutes after entering the service mode the compact controller switches back to normal If we wish to manually move out of service mode to normal operation we press the and MAJ buttons again for 5 seconds Press the AJ button in the service mode to test the functions of the compact controller all signalling elements and display will be illuminated 8 seconds the acoustic alarm will be activated 2 seconds sequential switching of all the relays Changing the setting of the critical temperature In the event of the requirement for changing the settings of values 1 and 2 of the critical temperature in the service mode press the button for 5 seconds The level indicating the critical temperature 1 set will appear on the display Press LZ to set the temperature lower pressing to set the temperature in the range of 0 99 C Save the temperature set by pressing the button for 5 seconds This will lead you to setting level 2 of the critical temperature Critical temperature 2 must be set at least one C higher than critical temperature 1 This adjustment is again carried out using the A andthe buttons After selecting the correct temperature save the setting by pressing the button for 5 seconds and return to the service mode v FUNCTIONS OF THE COMPACT CONTROLLER The description of the
10. relay functions corresponds to the basic model of compact data the DEGA UPA II L logger in the DEGA UPA II L S and the DEGA UPA II L Multi versions the configuration of the relay is conducted differently and this is described at the end of this chapter SWITCHING ON THE COMPACT CONTROLLER ON After switching on the power supply the LCD display shows the current version of the installed firmware and subsequently all the indication features are tested After this sequence the compact controller counts down the time required for the stabilisation of the connected transmitters 20 180 s in accordance with the warm up time of the individual transmitters If everything is O K the compact controller goes into normal operation and the ERROR relay is switched to the C4 NO4 contacts position indicating its proper operation Note Blocking after switching on is necessary for the stabilisation of the sensor and for preventing an accidental power outage that could cause excitation of false alarms IDLE MODE READY The compact controller remains in this mode during most of its operation The information displayed on the LCD display is relative to the transmitter the number of which is displayed below the e NN 3B icon with blue LEDs lit up next to the displayed channel Displaying concentration values from other transmitters or the current temperature from the DEGA Tc Il temperature sensor can be achieved by pressing L2 In the event that
11. the technical standards or the applicable safety regulations in the Czech Republic damage to the product during transportation caused by improper handling or handling of the product in a manner contrary to the advice provided in the instruction manual DEGA products that have been used in association with other than original DEGA products including consumables and accessories bearing additional parts or consumables e g a foil label seal etc that are detrimental to normal wear and tear during operation together with wear and tear of the product and its parts caused by their normal use 5 Claims regarding a product defect that can be dealt with reasonably quickly and without additional consequences will be resolved by remedying the defect repair or by replacement of the product part because in such a case it is a contradiction of the standard norms that the entire product shall be replaced 8 616 paragraph 4 of the Commercial Code 6 The buyer who exercises the right of warranty repair is not entitled to the return of the parts that have been replaced 7 The warranty period can be extended for up to 48 months and its validity can be extended beyond the standard length on the basis of the conclusion of an individual warranty contract Further information may be obtained through a specific business meeting 8 For the complete version of the general business conditions and of the claims procedure go to www dega cz Manufacturer DE
12. GA CZ s r o K Zizkovu 640 9 190 00 Prague 9 Czech Republic Tax ID CZ 279 029 43 Company ID 279 02 943 Telephone cz 420 774 447 660 5 Fax 420 227 203 512 E mail info dega cz Web www dega cz 2012 DEGA CZ S R O USER MANUAL VER 07DEGAUPAIIL201 210 4f DEGA x S RoHs C 2
13. I 7 R E E xem ears REEL s PE a E 8c np e K rae T IWZOW7 aW vosarE Keuna E ww perse Nee i Jg Gg e JA seed SIN IDEE rm Dee A x GCL IN O Eg U e nN G z aa bs z t s 3 2 ule ES UR S DIZA S MEE og od aie Tr N gt z cS NN A ON a 1 ef 6I U 2 cp J Y ei i XY I S We s ae JN lt lt IS o P e Ci U QU C t If T X 2 A GI U en MT 88 D E zi q Th yoo i 61 e Ll CN JN IS UL 5 dl 08 3d LJ 21 e O0 0 T C Ta CA LL ks xu ED m Z UAI _ lt T CSI a TT cae pol ON e AB OW 3 x OX Ta sci INS amp Xv YAN v qx a Ze cm S ec e d 9 UJ Z n i 09 7 25 B I ro DATA ES 2g UL N ire lt 7 22 p me 1 Fe DK yo E Sdn 1 24 A cU f um v GENERAL WARRANTY TERMS AND CONDITIONS When following the instructions for installation operation and maintenance the manufacturer guarantee 24 months from the date of receipt for the product Should the product purchased be put into operation by an entity other than the seller the warranty period commences from the date that the product is put into operation provided that the buyer ordered its commissioning within three weeks of its receipt The customer expressly acknowledges that during the warranty period that extends beyond the length of the warranty period that is specified in the Commercial Code the statutory warranty s he can neither require replacement of the product nor may s h
14. IS Fo D OF al LN cA TIT ET J a SN VOICI Az JN Ez mm i zt Wgp E lt I 3 Bos S y3 2 JN VUS QO 2 OS ss Z 2 Li O O ro ON Ps D A YW VO3U LZAEA ud X aT scab He gu Hr Z t O ru oN FS bI vule S E p e ool ta E O Al C sq IND amp VM re axa amp 8 7 UD gc v e 4 4 5c 8 d rg oo SM e raU A p M cc Ex ic Aut E9 L1 Fe pe zal Sdn dz wl ae A D Appendix No 3 Example of the connection of the DEGA UPA II L MULTI compact controller S VOI
15. R 14 Input terminal block for the channel for transmitter 4 15 Terminal block for relay 8 16 Terminal block for relay 7 17 Terminal block for relay 6 18 Terminal block for relay 5 19 Terminal block for relay 4 20 Terminal block for relay 3 21 Terminal block for relay 2 22 Terminal block for relay 1 ee 18 17 16 15 ravi LE L K de m 11 12 IES UL 24 RS 232 terminal block 25 RS 485 terminal block 26 Terminal block for the DEGA Tc II temperature sensor 27 Terminal block for the DEGA HV emergency valve 28 Connector for connecting DEGA UPA II UPS in development 23 Jumper for switching communication RS 485 RS 232 DESCRIPTION OF THE PANEL 4 aa T LESS S 6 DEGA UPA ii 3 1 The LED indicator of the serial number of the connected gas detection transmitter 2 The OPTION button for switching between the channels transmitters displayed 3 The RESET button for the acoustic alarm 4 The LCD display 5 The LED indicator POWER ERROR 6 The LED indicator for detection alarm levels 1 4 DESCRIPTION OF THE LCD DISPLAY CHANMEL GAS ELEMENTS CO NH CO C H CH CONCENTRATION Cl O OTHER mg Im TWA ed F n CALIBRATION REQUIRED DANG FER ALARM1 ALARM 2 ALARM 3 ALARM 4 10 9 1 Warning concerning the requisite calibration 2 The channel currently displayed 3 The type of gas or substance det
16. TL External reset button of the acoustic alarm When using DEGA UPA II L 12 24 accessories it is possible to connect an external acoustic or optical signalling device 12V DC max 4 A i e it is possible to use up to 8 x devices connected in parallel the DEGA MR MY MG MSL and DEGA S v DESCRIPTION OF THE PRODUCT 28 27 wi 25 1 Power supply unit 2 Dual terminal block for the power supply 230 VAC 3 Terminal block for the external connection of optical acoustic signalling 12V DC max 100 mA Note When using DEGA UPA II L 12 24 accessories it is possible to connect an external acoustic or optical signalling device 12V DC max 4 A i e it is possible to use up to 8 x devices connected in parallel the DEGA MR MY MG MSL and DEGA S 4 Internal acoustic alarm sounder 5 Terminal block for the DEGA Zc II flood sensor Note non active in the DEGA UPA IILS version 6 Terminal block for the DEGA TL reset button 7 LEDs of channel 1 ALARM ERROR 8 Input terminal block for the channel for transmitter 1 9 LEDs of channel 2 ALARM ERROR L3 EH 22 WA 20 19 AA ENGI NES AB o gE AB AB E aE M ene DITE HHRHH THR LULU DEGA UPA DEGA LZ a r a8 Tree La at 10 10 Input terminal block for the channel for transmitter 2 11 LEDs of channel 3 ALARM ERROR 12 Input terminal block for the channel for transmitter 3 13 LEDs of channel 4 ALARM ERRO
17. e or flooding nor the control of the emergency valve Relays 1 8 have following functions RE1 i i RE Switching when exceeding level 1 of gas leakage on channel 1 PAGE 3 DEGA UPA II L MULTI the highest version of the compact evaluation controller is utilised to supply power for four gas transmitters and for a full independent evaluation of detection levels 1 4 independently for each of the transmitters It is designed as a compact device for mounting on DIN rail in racks or in DEGA boxes The status of all the transmitters including failures is indicated on the controller by means of a built in LCD display and LED indicators The controller is fitted with acoustic signalling and a reset button for the acoustic alarm and with the function of automatic monitoring of the calibration periods In conjunction with an external temperature sensor the DEGA Tc II it is possible to evaluate up to two levels of critical temperature In conjunction with an external flood sensor the DEGA Zc II flooding can be detected In conjunction with the circuit for controlling the emergency valve DEGA UPA II V itis possible using a current pulse to close the emergency valves e g DEGA HV DNx Relays 1 8 have the following functions Any function of each relay can be set in accordance with the individual customer s requirements the function of individual relays can be specified to the manufacturer or set up using the DEGA CONFIG configura
18. e withdraw from the contract 1 When claiming a product defect it is necessary to submit a proof of purchase that contains the following information name and surname name and business name address and the warranty card if the buyer received one from the seller The validity of the warranty shall not be affected by non compliance with the obligations related to the issuance of the warranty card 2 Claims concerning the product for a warranty repair only complete devices are accepted may be filed during the warranty period only with the seller from which it was purchased subsequently the seller is required to forward the product to an authorised service centre or to the manufacturer 3 Acondition for the recognition of the rights under the warranty is the installation of the product having been undertaken by an authorised person in possession of a valid certificate from the manufacturer 4 This warranty is not applicable to a product that has not been put into operation by the manufacturer or by a certified employee in possession of a valid certificate issued by the manufacturer damage caused by fire water static electricity power surges in the electric supply or in the public network accident improper use of the product wear and tear contamination of the product and its subsequent cleaning damage caused by improper installation any adjustment modification or improper manner of use inconsistent with the instruction manual
19. ected 4 Icon for failure required service intervention 5 Icon for the temperature sensor 6 Icon for flooding 7 The summary gas alarm 8 Icon for the exceeding of the maximum average concentration TWA 9 Units in which the measuring is conducted 10 Concentration displayed This function is active only in the event of connecting an external DEGA TCIIA temperature sensor an external DEGA Zcll flood sensor INSTALLATION ASSEMBLY AND DISASSEMBLY The compact controller is designed for mounting on a DIN rail in a rack or in the DEGA box At the customer s request it is possible to supply the LCD display for mounting on the door of the rack CAUTION The controller is supplied with 230VAC voltage connected to L and N terminals When using the DEGA UPA II 24 12 accessories the controller is supplied with 24VDC voltage the positive pole is connected to the L terminal and the negative pole to the N terminal In the event of connecting this version to a 230VAC power supply the controller will be destroyed Four independent gas detection transmitters the flood sensor and the temperature sensor can be connected to the device a the gas detection transmitter of the DEGA NBx yL Il type is a linear transmitter communicating by means of an analogue current loop 4 20 mA It is supplied in versions designed for the detection of natural gas methane propane butane butane carbon monoxide CO combustible gases carbon d
20. ioxide CO2 and more than 100 other gases in accordance with the customer s requirements b the gas detection transmitter of the DEGA NSx type with a semiconductor sensor communicating by means of a 4 20 mA current loop It only transmits information in regard to two concentration levels c the DEGA NSx CL DEGA NSx EL DEGA NSx IL are linear transmitters for use in potentially explosive atmospheres Ex zone 1 communicating through an analogue 4 20 mA current loop They are supplied in versions for the detection of natural gas methane propane butane butane carbon monoxide CO combustible gases carbon dioxide CO2 and more than 100 other gases in accordance with the customer s requirements d the DEGA DV transmitter is a special version of the transmitters probes that monitor the concentration of ammonia in water Utilised for a 2 level detection e the DEGA Tc II temperature sensor is an external critical temperature sensor with a linear range of 0 99 C f the DEGA Zc II flood sensor is an external flood sensor for the indication of flooding of the premises e g the boiler room the warehouse etc CONNECTING TRANSMITTERS TO ALL TYPES OF DEGA UPA II L S MULTI CONTROLLERS Transmitter Terminal Terminal Controller Shielded 3 x 1 mm max 600m Shielded 3 x 1 5 mm max 1100m DEGA NBx yL II DEGA UPA IIL x channel number Shielded 3 x 1 mm max 600m Shielded 3 x 1 5 mm max 1100m 3 LLL DEGA NSx yL II
21. n flash on the display In the event of the failure of the flood sensor DEGA Zc II only the key P Note In the case of the DEGA UPA II L S version the ERROR relay is not switched on and is used as a level 2 alarm on channel 2 DETECTION OF CRITICAL TEMPERATURE only in the event of the DEGA Tc II temperature sensor being connected When exceeding the critical temperature which is normally set as 45 C at level 1 and 60 C at level 2 the E icon and sign are lit up and the contact of the relay associated with a critical temperature level is switched on including the alarm relays for the lower levels Reaching level 2 of critical temperature leads to the activation of an internal piezo buzzer and the switching on of the ALARM relay Note This function is not included in the DEGA UPA II L S version DETECTION OF FLOODING only in Mu event of the flood sensor of the DEGA Zc II being connected In the event of the detection of flooding the MA icon and DANGER sign lights up on the LCD display and the TEMP2 relay contact is switched on Note In the DEGA UPA II L S version this function is not included Note If both flooding and a critical temperature are detected the TEMP2 relay is used for detection of both flooding and level 2 of the alarm of critical temperature EMERGENCY SOLENOID VALVE Emergency valve The circuit for controlling emergency valves is designed to control the solenoid emergency valves with a 12 V DC
22. ods In conjunction with an external temperature sensor the DEGA Tc II it is possible to evaluate up to two levels of critical temperatures Flooding can be detected by means of an external flood sensor DEGA Zc II In conjunction with the circuit for controlling the emergency valve DEGA UPA II V it is possible using a current pulse to close the emergency valves e g DEGA HV DNx Relays 1 8 have the following functions RES Switching when exceeding levela of gas leakage Ra O UU Rt Switching when exceeding levels of gas leakage Eves mts Switching when exceeding level2 of gas leakage Evez RES Switching when exceeding levelt of gas leakage LEVEL m The else relay E ma witch RE8 RE7 RE6 RE5 RE4 RE3 RE2 E1 DEGA UPA II L S a special version of the compact evaluation controller is utilised to supply power for four gas transmitters and for a full independent evaluation of 2 levels detection independently for each of the transmitters It is designed as a compact device for mounting on DIN rail in racks or in DEGA boxes The status of all the transmitters including failures is indicated on the controller by means of a built in LCD display and LED indicators The controller is fitted with acoustic signalling and a reset button for the acoustic alarm and with the function of automatic monitoring of the calibration periods Note This type of controller does not enable the detection of the critical temperatur
23. oller b 12V 4A in the event of a 24VDC supply to the controller in the event of installing the DEGA UPA II 24 12 accessories Ingress protection IP 20 Relay contact ampacity resistance load 8A 250 V 50Hz 8A 30V DC inductive load 1 6A 30V DC Dimensions W x H x D 245 x 72x 121mm Weight 0 7kg v OPERATIONAL AND EXTERNAL CONDITIONS CSN 33 2000 5 51 Operating temperature range 20 C to 85 C Relative humidity of the ambient air max 95 Altitude ACT The occurrence of humidity AD1 The incidence of solid foreign bodies AE1 The occurrence of corrosive or polluting substances AF1 Vibrations AH1 The types of materials processed or stored BE1 Working environment BE1 non explosive atmosphere BNV CSN EN 60079 10 The compact controller is intended primarily for internal spaces to be mounted in racks or in DEGA boxes v BASIC TYPES The DEGA UPA II L a compact evaluation controller is utilised to supply power for four gas transmitters and for the full evaluation of the 1 4 level of detection including the PEL detection It is designed as a compact device to be mounted on a DIN rail in racks or in DEGA boxes The status of all the transmitters is indicated on the controller including failures by means of a built in LCD display and LED indicators The controller is fitted with acoustic signalling and a reset button for the acoustic alarm and the function of the automatic monitoring of the calibration peri
24. ontroller remains in operation Following the expiration of 18 months from the most recent calibration of the transmitters for security reasons the func tion of the entire compact controller is blocked This status is displayed as a blinking ERROR LED a flashing d and the ENEEIER eD icon All the relays are in the C NO position The functions of the compact controller in the special S version In this version the compact controller is equipped with only 2 level detection of gases whereby each transmitter controls 2 separa te relays with levels 1 and 2 In this version it is not possible to connect the transmitter of the critical temperature The ERROR relay is used for switching on level 2 of alarm on channel 2 and the ALARM relay is used for switching on level 1 of alarm on channel 2 The internal acoustic alarm remains functional All the other features are the same as for the DEGA UPA II L version The functions of the compact controller in the special MULTI version In this version the settings of the relay switching are fully configurable by means of the DEGA CONFIG configuration software The relay configuration options are described in the User Guide for the DEGA CONFIG software All the other features are the same as for the DEGA UPA II L version v OPERATION AND MAINTENANCE 1 OPERATION This compact controller does not require any special maintenance during operation The surface can be cleaned with a cloth as needed 2
25. the concentration exceeds the maximum level that the connected transmitter is able to detect the HI symbol is displayed in place of the values In the event of concentrations greater than 999 it shows the symbol t indicating multiples of thousands e g the number 1t1 stands for 1100 or 4t5 stands for 4500 of 99t stands for 99000 THE GAS ALARM STATUS i e exceeding levels 1 4 of the detection limit Should level 1 of concentration be exceeded the appropriate level of alarm lights up on the LCD display and the LED panel and the relevant relay will be switched on and the LCD display will show the concentration measured by the transmitter channel by which level 1 of concentration was exceeded If multiple transmitters exceeded level 1 of concentration the transmitter with the highest level of alarm is displayed Note 1 Acoustic signalling is activated by default when level 4 of alarm is reached In accordance with the customer s requirements this can also be set to a lower level Note 2 By default levels of alarm 1 4 for individual transmitters are set in accordance with the specifications of the transmitter and they can be altered in accordance with the customer s requirements Note 3 In the UPA II L S version the compact controller is equipped only with two level gas detection and the ALARM relay is utilised for level 1 of alarm on channel 2 The PEL STATUS OF THE GAS ALARM i e exceeding the time weighted average
26. tion software i e any relay can be set as the alarm for gas detection levels 1 4 from any transmitter or for transmitter failure or for the detection of temperature and or of flooding and for optical and acoustic signalling or for any combination thereof For all the above types of controllers the following statuses of relay contacts are applicable The idle status of all the relays The idle status of the ERROR relay with the exception of the ERROR relay pU MEE ae Positions of the Status contacts contacts Active relay alarm C NO Idle status the system works without any faults Active relay alarm v ACCESSORIES DEGA UPA II BOX A box with a lock for the installation of the controller outside the rack i e on a wall etc DEGA UPA II UPS An uninterruptible power supply 30 60 minutes in development DEGA UPA II 24 12 Power supply for the controller 24V DC DEGA UPA II V Circuit for control of the emergency valve using a current pulse we recommended the DEGA HV DNx emergency valve DEGA Zc II External flood sensor cannot be used with version DEGA UPA II L S DEGA Tc II External temperature sensor cannot be used with version DEGA UPA II L S DEGA HV DNx Emergency valve can be used in conjunction with DEGA UPA II L V cannot be used with version DEGA UPA II L S External acoustic and optical signalling DEGA MR MY MG MSL Rotating beacon red yellow green column DEGA S Sounder DEGA
27. vicing of the product exclusively to a certified service centre Contact with water can create a short circuit in the product and consequent damage to property or personal injury Utilise only certified DEGA accessories The device is certified and is technically and functionally suitable for authentic DEGA accessories In the event that the device is utilised with other products the manufacturer shall not liable for any damages that this may cause Use cables of the appropriate types To ensure compliance with the parameters of the product to connect the product to other devices or to the power supply utilise exclusively the cables recommended and described in the Technical Data and Information section v TECHNICAL DATA AND INFORMATION Supply voltage 230V AC 50 Hz in the case of the utilisation of the DEGA UPA II 24 12 accessories the supply voltage is 24V DC Cable for connecting the DEGA Tc Il temperature sensor the UTP cat 5e max length 100 m or shielded 4x1 mm2 cable Cable for connecting the DEGA Zc II flood sensor the UTP cat 5e max length 100 m or shielded 4x1 mm2 cable Cable for connection of the DEGA TL Il external reset button cable 2x1mm2 max length 100m Output 8 x relay potential free switching contacts RS 485 RS 232 Control of the DEGA HV DNx emergency valve in the case of mounting the DEGA UPA II V accessories Output of the optical acoustic signalling a 12V 100mA in the event of a 230VAC supply to the contr

Download Pdf Manuals

image

Related Search

Related Contents

MC 2100 Bedienungsanleitung - Motz  Assemblage du CZ21 Précautions et entretien Bien débuter avec le  LTB Audio Systems USB Pro 5.1 Surround Sound Headphone System User's Manual  Bingo! - PilotoLOCO.com  XTnano Operation Manual  Conceptronic 1100072 cleaning wipe for office  Téléchargez le PDF  BALANCE PROFESSIONNEL ÉLECTRONIQUE MOD. RB  Pediatric & Adult Operator`s Manual    