1. Indoor unit numbers which had been given prior to the setting change will be displayed UNT No Indoor unit numbers which had been given prior to the setting change will be displayed UNIT No UNIT No No RAV SM561KRT E EN 1074007701 m 10 INDOOR UNIT OPERATION WHEN CONNECTED TO MULTIPLE UNITS When you want to know position of the indoor unit using the address To confirm the unit numbers in a group control Operation while the air conditioner stops The indoor unit numbers in a group control are successively displayed and the corresponding indoor fan is turned on Push buttons simultaneously for 4 seconds or more e Unit No H1 is displayed e The fans of all the indoor units in a group control are turned on Every pushing button the indoor unit numbers in the group control are successively displayed e The firstly displayed unit numbers indicates the address of the main unit e Only fan of the selected indoor unit is turned on Push button to finish the procedure All the indoor units in group control stop To confirm all the unit numbers from an arbitrary wired remote controller Operation while the air conditioner stops The indoor unit numbers and position in the same refrigerant cycle line can be confirmed An outdoor unit is selected the indoor
2. TOSHIBA CARRIER CORPORATION PROF OK FILM OUTPUT PLEASE CORRECT AS MARKED L AND SEND BACK FOR THE NEXT PROOF C PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT 1074007701 Toshiba 1074007701 COVER 2 7 16 04 13 38 TOSHIBA RAV SM561KRT E EN 1074007701
3. Parts to be procured locally Connecting pipe Liquid side Connecting cable 6 35 mm diam Nominal diam 1 4 thick 0 8 mm HO7RN F or 2451 66 1 5 mm or more RAV SM561KRT E Thermal insulation for refrigerant pipe 9 52 mm diam Nominal diam 3 8 thick 0 8 mm 10 mm or more thermal insulating foam polyethylene RAV SM801KRT E Thermal insulation for drain pipe Connecting pipe Gas side 1 mm or more foam polyethylene 12 7 mm diam Nominal diam 1 2 thick 0 8 mm RAV SM561KRT E Drain pipe Outer 16 mm diam l Tapes 15 9 mm diam Nominal diam 5 8 thick 1 0 mm RAV SM801KRT E Grounding cable 2 0 mm diam or more ROOF OK FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED MIHI THEN MAKE FILM OUTPUT EN 1 Toshiba 1074007701 01 01 10 2 7 16 04 13 30 TOSHIBA RAV SM561KRT E 1074007701 1 PRECAUTIONS FOR SAFETY e Ensure that all Local National and International regulations are satisfied e Read this PRECAUTIONS FOR SAFETY carefully before Installation e The precautions described below include the important items regarding safety Observe them without fail e After the installation work perform a trial operation to check for any problem Follow the Owner s Manual to explain how to use and maintain the unit to the customer e Turn off the main power supply switch or breaker before the unit maint
4. 13 31 TOSHIBA RAV SM561KRT E EN 1074007701 8 TEST RUN In case of wired remote controller Procedure 4 Description Keep button pushed for 4 seconds or more TEST is displayed on the display part and the selection of mode in the test mode is permitted Push J button At this time all indoor unit s displays flash Using __E _ button select the operation mode COOL or HEAT e Do not run the air conditioner in a mode other than COOL or HEAT e The temperature controlling function does not work during test run e The detection of error is performed as usual After the test run push 0 2 button to stop a test run Wired remote controller display part is same as procedure 1 Push Fa check button to cancel release from the test run mode TEST disappears on the display and the status returns to a normal 9 TROUBLESHOOTING Confirmation and check When a trouble occurred in the air conditioner the check code and the indoor unit No appear on the display part of the remote controller The check code is only displayed during the operation If the display disappears operate the air conditioner according to the following Confirmation of error history for confirmation Check code ROOF OK make FILM OUTPUT PLEASE CORRECT AS MA
5. CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT PROOFED 9 Toshiba 1074007701 01EN 01 10 10 7 16 04 13 30 TOSHIBA RAV SM561KRT E EN 1074007701 Toshiba 1074007701 01 01 10 11 7 16 04 6 REFRIGERANT PIPING Piping with outdoor unit e Shape of valve differs according to the outdoor unit For details of installation refer to the Installation Manual of the outdoor unit Air purge Using a vacuum pump perform vacuuming from the charge port of valve of the outdoor unit For details follow to the Installation Manual attached to the outdoor unit e Never use the refrigerant sealed in the outdoor unit for air purge REQUIREMENT For the tools such as charge hose etc use those manufactured exclusively for R410A Refrigerant amount to be added For addition of the refrigerant add refrigerant R410A referring to the attached Installation Manual of outdoor unit Be sure to use a scale to charge the refrigerant of specified amount REQUIREMENT e Charging an excessive or too little amount of refrigerant causes a trouble of the compressor Be sure to charge the refrigerant of specified amount e A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the nameplate attached to the service panel of the outdoor unit It is necessary to troubleshoot the compressor and refrigeration cycl
6. L2 Ln Some group control system configuration requires manual address change after automatic address setting e System configuration that requires address change is the combined system where twin and triple system of multiple units are controlled by group control with single remote controller Group Control on Combined System For example Block of dotted lines Single system Twin system Twin system represents each system Example of random setting Address 1 1 1 Address 2 1 2 Address 3 3 1 Address 3 1 2 Address 2 2 2 System address Group address When the power is turned on the above addresses Remote controller are set by automatic address setting However system indicated R C address and indoor unit address are randomly set and thus Unit on which automatic address is set the address setting should be changed by manual address Example of setting so that system address and indoor unit address address setting Indoor address are matched change After changed by manual Address 1 1 1 Address 2 1 2 Address 2 2 2 Address 3 1 2 Address 3 2 2 address setting e Change and check of address should be carried out by the following procedures ROF PROOFED BY FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED 1 E N THEN MAKE FILM OUTPUT Toshiba 1074007701 01EN 11 22 19 7 16 04 1
7. from flashing to being lit the setting is completed If there are some other indoor units of which setting is to be changed repeat the procedure 2 5 to change the setting After the above setting is completed push button to select indoor unit No which had been given prior to the setting change and then specify the CODE No 12 13 and 14 with the temperature C v button successively to confirm the changes made Check of address change Prior to the change 3 3 1 After the change 2 2 2 The setting change which has been made can be cleared by pushing button In this case perform the setting again from Procedure 2 After checking the changes made push button the changes will be confirmed If E button is pushed the display will disappear and air conditioner will be in ordinary stop state The commands from the remote controller cannot be received for approximately 1 minute after pushing button e f the commands from the remote controller is not received even after 1 minute has elapsed the address setting may be incorrect In this case perform the setting again from Procedure 1 as the automatic address setting has been made again OK FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT 20 TOSHIBA 3 3 Indoor unit numbers which had been given prior to the setting change will be displayed
8. que acompanha a unidade exterior Lees deze installatiehandleiding zorgvuldig door voordat u de airconditioner gaat installeren Deze installatiemethode beschrijft de installatiemethode van de binnenunit e Zie voor de installatie van de buitenunit de installatiehandleiding bij de buitenunit ro Evyxeipi io npiv e vkaraoraor rou KArparicTIKOU To Evyeipidio mepivpagel 2 mou e TTA TOSHIBA RAV SM561KRT E 1074007701 n ADOPTION OF NEW REFRIGERANT e This Air Conditioner is a new type which adopts a new refrigerant HFC R410A instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer UTILISATION DU NOUVEAU REFRIGERANT e Ce climatiseur est d un type in dit qui utilise le nouveau refrigerant HFC R410A au lieu du refrigerant traditionnel R22 afin d viter la destruction de la couche d ozone EINF HRUNG EINES NEUEN K HLMITTELS e Dies ist ein neuartiges Klimagerat Anstatt des herk mmlichen K hlmittels R22 verwendet es das neue ozonschicht schonende K hlmittel R410A A
9. unit numbers in the same refrigerant cycle line are successively displayed and then its indoor unit fan is turned on Push the timer time Firstly the line 1 item code Address Change is displayed Select outdoor unit Using SET button determine the selected line address e The indoor unit address which is connected to the refrigerant cycle line of the selected outdoor unit is displayed and the fan is turned on and all display of indoor unit turned on Every pushing UNIT button the indoor unit numbers in the same refrigerant 4 line are successively displayed e Only fan of the selected indoor unit operates To select another line address Push CL button to return to procedure e The indoor address of another line can be successively confirmed F button to finish the procedure OK FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT ROF PROOFED BY EN 21 Toshiba 1074007701 01EN P11 22 22 7 16 04 13 31 TOSHIBA RAV SM561KRT E EN 1074007701 E Toshiba 1074007701 01EN P11 22 23 MEMO ROF PROOFED BY OK Make FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT 7 16 04 TOSHI B 3 3 A RAV SM561KRT E EN 1074007701
10. 3 31 TOSHIBA RAV SM561KRT E EN 1074007701 10 INDOOR UNIT OPERATION WHEN CONNECTED TO MULTIPLE UNITS To change all the indoor addresses from an arbitrary wired remote controller When the setup operation with automatic address has finished this change is available Contents Using an arbitrary wired remote controller the indoor unit address can be changed for each same refrigerant cycle line Change the address in the address check change mode Operation while air conditioner stops 3 EN UNIT No gay JA Display panel will flash as shown on the drawing below when pushing buttons at the same time for 4 seconds or more Make sure that the displayed CODE No is 10 If the displayed CODE No is not 10 push button to erase the display and perform the setting again from the beginning The commands from the remote controller cannot be received for approximately 1 minute after pushing button Display may differ depending on When executing group control the indoor unit numbers that is displayed first ine becomes the main unit Every pushing UNIT button the indoor unit numbers in the group control are successively displayed Select the indoor unit of which setting is to be changed At this time the fan of the sele
11. An insufficient power supply capacity or inappropriate installation may cause fire e Use the specified cables for wiring connect the terminals securely fix To prevent external forces applied to the terminals from affecting the terminals Conform to the regulations of the local electric company when wiring the power supply Inappropriate grounding may cause electric shock e Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas If a combustible gas leaks and stays around the unit a fire may occur OK FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT ROF PROOFED BY EN 3 7 16 04 13 30 m Toshiba 1074007701 01 1 10 5 7 16 04 2 INSTALLATION PROCEDURE Installation diagram of indoor unit Insulate the refrigerant pipes separately with insulation not together 65 mm or more Insert the cushion between the indoor unit and wall and lift indoor unit to make work easier Min 6 mm thick heat resisting polyethylene foam The auxiliary piping can be connected the left rear left rear right or bottom Do not allow the drain hose to sag Cut the piping hole sloped slightly i Make sure to run the drain hose sloped downward Rear left Left Mounting screw Mounting the installation plate For installation of th
12. DOZIONE DI UN NUOVO REFRIGERANTE e Questo condizionatore d aria di un tipo nuovo che adotta un nuovo refrigerate HFC R410A al posto del refrigerante convenzionale R22 per prevenire la distruzione dello strato di ozono dell atmosfera terrestre ADOPCION DE NUEVO REFRIGERANTE e Este aparato de aire acondicionado es un modelo reciente que incorpora el nuevo refrigerante HFC R410A en lugar del refrigerante convencional R22 para asi evitar danos en la capa de ozono ADOPCAO DO NOVO REFRIGERANTE e Este ar condicionado um modelo novo que adopta um novo refrigerante HFC R410A em vez do refrigerante convencional R22 para evitar a destruic o da cama de ozono TOEPASSING VAN EEN NIEUW KOELMIDDEL e Deze airconditioner is een nieuwe type dat werkt met een nieuw koelmiddel HFC R410A in plaats van met het conventionele koelmiddel R22 als bijdrage om de aantasting van de ozonlaag te reduceren YIOOETHZH NEOY e KALUATLOTIKO amp var v o WUKTIKO HFC otn Oon OUUBATLKOU WUKTIKOU R22 Bonrjosr rou ROF PROOFED BY OK FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT Toshiba 1074007701_TOC 2 7 16 04 13 38 TOSHIBA RAV SM561KRT E EN 1074007701 m CONTENTS Accessory parts an
13. RAV SM561KRT E EN 1074007701 1 PRECAUTIONS FOR SAFETY e After unpacking the unit examine it carefully if there are possible damage e Do not install in a place that might increase the vibration of the unit e To avoid personal injury with sharp edges be careful when handling parts e Perform installation work properly according to the Installation Manual Inappropriate installation may result in water leakage electric shock or fire e When the air conditioner is installed in a small room provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level e Install the air conditioner securely in a location where the base can sustain the weight adequately e Perform the specified installation work to guard against an earthquake If the air conditioner is not installed appropriately accidents may occur due to the falling unit e f refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may generate e After the installation work confirm that refrigerant gas does not leak If refrigerant gas leaks into the room and flows near a fire source such as a cooking range noxious gas might generate e Electrical work must be performed by a qualified electrician in accordance with the Installation Manual Make sure the air conditioner uses an exclusive power supply
14. RKED PROOFED BY AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN FILM OUTPUT 15 299899 Indoor unit No in which an error occurred TOSHIBA RAV SM561KRT E EN 1074007701 Toshiba 1074007701 01EN _P11 22 16 7 16 04 13 31 m 9 TROUBLESHOOTING Confirmation of error history When a trouble occurred on the air conditioner the trouble history can be confirmed with the following procedure The trouble history is stored in memory up to 4 troubles The history can be confirmed from both operating status and stop status When pushing and buttons at the same time for 4 seconds or more the following display appears If Service check is displayed the mode enters in the trouble history mode e 01 Order of trouble history is displayed in CODE No window e Check code is displayed in CHECK window e Indoor unit address in which an error occurred is displayed in UNIT No Every pushing of button used to set temperature the trouble history stored in memory is displayed in order The numbers in CODE No indicate CODE No 01 latest 04 oldest REQUIREMENT Do not push button because all the trouble history of the indoor unit will be deleted After confirmation push E button to return to the usual display 1 Check the troubles ac
15. Toshiba 1074007701_COVER 3 7 1 SAIBA P INSTALLATION MANUAL MANUEL D INSTALLATION INSTALLATIONS HANDBUCH MANUALE D INSTALLAZIONE MANUAL DE INSTALACION MANUAL DE INSTALACAO INSTALLATIEHANDLEIDING 2 2 AIR CONDITIONER SPLIT CLIMATISEUR TYPE SPLIT KLIMAGERAT SPLIT SYSTEM CONDIZIONATORE D ARIA TIPO MULTIAMBIENTI APARATO DE AIRE ACONDICIONADO TIPO SPLIT AR CONDICIONADO TIPO SPLIT AIRCONDITIONER GESPLITST TYPE KAIMATIZTIKO MHXANHMA AIAIPO YMENO Z T YMOS lt High Wall Type gt lt Type mural haut gt lt Wandmontierter Typ gt lt Tipo a condotto nascosto gt lt Modelo de pared gt lt Tipo Mural gt lt Hoog Wandtype gt lt Tuttoc YWnAou Toixyou Heat Pump Model Modele a thermopompe Ger te mit Heizung Modello con pompa di riscaldamento HFC Modelo con bomba de calor Modelo de bomba t rmica Model met warmtepomp Movr Ao pe AvrAia Indoor Unit Unit int rieure R41 OA Raumeinheit Unita interna Unidad interior Unidade interior Binnenunit Eowtepikn PROF OK FILM OUTPUT PLEASE CORRECT AS MARKED RAV SM561 KRT E AND SEND BACK FOR THE NEXT PROOF RAV SM801KRT E Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the indoor unit NE For installation of the outdoor unit follow the Installation Manual
16. ach indoor unit cannot be operated individually e Use RBC TWP30E and 50E of branch pipe kit optional for twin combination e For piping connection refer to this manual and the installation manual of outdoor branch pipe kit Wiring diagram for twin combination Wiring of each indoor unit should be HO7RN F or 245IEC66 1 5 mm or more Wiring of remote controller should be VTCF 0 5 2 0 Address can be set automatically Address setting will be executed for 5 minutes after the power is turned on There is no need to change the address setting The main unit is indoor unit that receives START STOP signal from the wireless remote control 1 Remote Controller 10 oor unit connecting line Control line Other connecting line Power supply CAUTION Make sure to check the wiring before turning on the power When connecting by twin combination make sure that no wiring is made to No 3 terminal block of sub unit Air conditioner may not work after the power is turned on Group combination When executing group control on multiple unit system Group control of up to 8 units is available with single remote controller Use wired remote controller for group control e For wiring and wiring procedures for individual system using the same refrigerant refer to the installation manual of each combination e Wiring between systems should be done by the following procedures Connec
17. art of the terminals Incomplete connection or fixation may cause a fire etc 2 Be sure to connect earth wire Grounding work Do not connect the earth wire to gas pipe city water pipe lightning rod or the earth wire of telephone Incomplete grounding causes an electric shock 3 For electric work strictly follow the Local Regulation in each country and the Installation Manual and use an exclusive circuit Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire CAUTION e This indoor unit has no power cord e f incorrect incomplete wiring is carried out it will cause an electrical fire or smoke e Be sure to install an earth leakage breaker that is not tripped by shock waves If an earth leakage breaker is not installed an electric shock may be caused e Be sure to use the cord clamps attached to the product e Do not damage or scratch the conductive core and inner insulator of power and inter connecting cables when peeling them e Be sure to comply with local regulations on running the wire from outdoor unit to indoor unit size of wire and wiring method etc e Use the power cord and Inter connecting cable of specified thickness type and protective devices required REQUIREMENT e For power supply wiring strictly conform to the Local Regulation in each country e For wiring of power supply of the outdoor units follow the Installation Manual of each outdoor unit Never
18. attached to the outdoor unit Veuillez lire attentivement ce Manuel d installation avant d installer le climatiseur Ce manuel d crit la proc dure d installation de int rieure e Pour installer l unit ext rieure reportez vous au Manuel d installation fourni avec ext rieure Bitte lesen Sie dieses Handbuch sorgf ltig bevor Sie mit der Installation des Klimager tes beginnen In diesem Handbuch wird die Installation der Raumeinheit beschrieben Um die Au Beneinheit zu installieren folgen Sie den Anweisungen in Handbuch das der beiliegt Prima di installare il condizionatore d aria leggere con attenzione questo manuale d installazione e Questo manuale descrive il metodo d installazione dell unit interna Per l installazione dell unit esterna fare riferimento al manuale d installazione fornito insieme all unit esterna Lea atentamente este Manual de instalaci n antes de proceder a la instalaci n del aparato de aire acondicionado e Este manual describe el m todo de instalaci n de la unidad interior e Para la instalaci n de la unidad exterior consulte el Manual de instalaci n que acompa a a la unidad exterior Leia atentamente o presente Manual de Instala o antes de instalar o Ar Condicionado e O presente manual descreve o m todo de instalar a unidade interior e Para a instala o de uma unidade exterior siga o Manual de Instala o
19. connect 220 240V power to the terminal blocks B etc for control wiring Otherwise the system will fail e Perform the electric wiring so that it does not come to contact with the high temperature part of the pipe The coating may melt resulting in an accident e After connecting cables to the terminal blocks provide a trap and fix cables with the cable clamp e Run the refrigerant piping line and control wiring line in the same line e Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes 1 Connect the connecting cable to the terminal as identified with their respective numbers on the terminal block of indoor and outdoor unit HO7RN F or 245IEC66 1 5 mm or more Mount a leakage breaker Insulate the unsheathed redundant cords conductors with tape For inter unit wiring do not use a wire jointed to another on the way Fix the cable with cord clamp A O N OK FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT ROF PROOFED BY EN 11 7 16 04 13 31 Toshiba 1074007701 01EN _P11 22 12 TOSHIBA RAV SM561KRT E 1074007701 m ELECTRICAL WORK Wiring between units 1 Connect the wires between the units correctly Errors made in the connections can result in the unit malfunctioning 2 Connect the control wires between the outdoor unit and indoor unit a
20. cording to the above procedure 2 Ask an authorized dealer or qualified service maintenance professional to repair or maintain the air conditioner 3 More details of the service code are explained in Service Manual Incase of wireless remote control Check the indication of the display panel on the main unit Typical example O Power supply is not turned on Check cable connection and correct it Miscabling between sensor unit and indoor unit No indication even if the remote control is operated Defective connection between sensor unit and indoor unit MEM Miscabling or defective connection between indoor unit and outdoor units 0 o Protective device of outdoor unit works Check outdoor unit __ Flashes alternatively 0 Protective device of indoor unit works Check indoor unit Flashes alternatively 1 Ask an authorized dealer or qualified service maintenance professional to repair or maintain the air conditioner 2 More details of the service code are explained in Service Manual PROOFED BY OK FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT 1 6 E N Toshiba 1074007701 01 11 22 17 7 16 04 13 31 TOSHIBA RAV SM561KRT E EN 1074007701 INDOOR UNIT OPERATION WHEN CONNECTED TO MULTIPLE UNITS Twin combination Two indoor units can be operated with single outdoor unit However e
21. cted indoor unit is turned on and LED indicator on the indoor unit will light up and the locations of indoor units of which setting is to be changed can be checked Specify the CODE No 12 with the temperature button Indoor unit numbers which had been CODE No 12 System address given prior to the setting change will be displayed Change the system address from 3 to 2 with the timer time button Push button If the display changes from flashing to being lit the setting is completed OK FILM OUTPUT PLEASE CORRECT AS MARKED ROF PROOFED BY PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT 19 Toshiba 1074007701 01EN _P11 22 20 7 16 04 13 31 TOSHIBA RAV SM561KRT E EN 1074007701 AND SEND BACK FOR THE NEXT PROOF m Toshiba 1074007701 01EN P11 22 21 7 16 04 10 INDOOR UNIT OPERATION WHEN CONNECTED TO MULTIPLE UNITS ROF PROOFED BY Specify the CODE No 13 with the temperature button CODE No 13 Indoor address Change the indoor address from 3 to 2 with the timer time button Push button If the display changes from flashing to being lit the setting is completed Specify the CODE No 14 with the temperature button CODE No 14 Group address Change the set data from 0001 to 0002 with the timer time 163154 Set data Main unit 0001 Sub unit 0002 Push button If the display changes
22. d parts to be procured locally REFRIGERANT PIPING cerent 8 1 PRECAUTIONS FOR SAFETY ELECTRICAL 0 2 2 11 2 INSTALLATION PROCEDURE TEST ttm 14 SELECTION OF INSTALLATION PLACE 9 TROUBLESHOOTING eren ntes 15 4 INSTALLATION OF INDOOR UNIT 10 INDOOR UNIT OPERATION WHEN 5 DRAIN PIPING WORK 2 CONNECTED TO MULTIPLE UNITS eere 17 ROF PROOFED BY Toshiba 1074007701_TOC 3 OK FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT 7 16 04 TOSHI B 3 39 RAV SM561KRT E EN 1074007701 ITALIANO DEUTSCH FRANCAIS ENGLISH La d O lt NEDERLANDS PORTUGUES EAAHNIKA Accessory parts and parts to be procured locally Accessory parts E mcm ee ervice contac Installation plate address label Wireless remote Installation Manual control Owner s Manual Remote control holder Screw for remote control holder Mounting screw 24 mm x 25 mm CUT ES Wired remote controller is an optional part sold separately _
23. e indoor unit use the paper template included o plate 2 Hook Indoor unit Hook Y Indoor unit Weight Mounting screw When the installation plate is directly mounted on the wall 1 Securely fix the installation plate to the wall by screwing it through the upper and lower fixing holes 2 To mount the installation plate on a concrete wall with anchor bolts utilize the anchor bolt holes as illustrated in the above figure 3 Attach the installation plate horizontally to the wall CAUTION When installing the installation plate with mounting screw do not use the anchor bolt hole Otherwise the unit may fall down and result in personal injury and property damage 25 mm hole Mounting screw 24 x 25 mm Anchor bolt Projection 15 mm or less Clip anchor local parts PROOFED OK FILM OUTPUT PLEASE CORRECT AS MARKED 4 N AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT 3 30 TOSHIBA RAV SM561KRT E EN 1074007701 n 3 SELECTION OF INSTALLATION PLACE A WARNING e Install the air conditioner where there is sufficient strength to withstand the weight of the unit If the strength is not sufficient the unit may fall down resulting in injury CAUTION Upon approval of the customer install the air conditioner in a place that satisfies the following conditions e Place where the unit can be installed
24. e malfunction Open the valve fully Open the valve of the outdoor unit fully A 4 mm hexagonal wrench is required for opening the valve For details refer to the Installation Manual attached to the outdoor unit Gas leak check Check with a leak detector or soap water whether gas leaks or not from the pipe connecting section or cap of the valve REQUIREMENT Use a leak detector manufactured exclusively for HFC refrigerant R410A R134a etc Thermal insulation process Apply thermal insulation for the pipes separately at liquid side and gas side For the thermal insulation to the pipes at gas side be sure to use the material with heat resisting temperature 120 C or higher Using the attached thermal insulation material apply the thermal insulation to the pipe connecting section of the indoor unit securely without gap REQUIREMENT Apply the thermal insulation to the pipe connecting section of the indoor unit securely up to the root without exposure of the pipe The pipe exposed to the outside causes water leak ROF FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED MI THEN MAKE FILM OUTPUT 10 EN 3 30 TOSHIBA RAV SM561KRT E EN 1074007701 n ELECTRICAL WORK A WARNING 1 Using the specified cables ensure to connect the wires and fix wires securely so that the external tension to the cables do not affect the connecting p
25. enance e Ask the customer to keep the Installation Manual together with the Owner s Manual CAUTION New air conditioner installation e THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT R410A WHICH DOES NOT DESTROY OZONE LAYER The characteristics of R410A refrigerant are easy to absorb water oxidizing membrane or oil and its pressure is approx 1 6 times higher than that of refrigerant R22 Accompanied with the new refrigerant refrigerating oil has also been changed Therefore during installation work be sure that water dust former refrigerant or refrigerating oil does not enter the refrigerating cycle To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are charged from those for the conventional refrigerant Accordingly the exclusive tools are required for the new refrigerant R410A For connecting pipes use new and clean piping designed for R410A and please care so that water or dust does not enter Moreover do not use the existing piping because there are problems with pressure resistance force and impurity in it CAUTION To disconnect the appliance from main power supply This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm The installation fuse 25A D type must be used for the power supply line of this conditioner WARNING e Ask a
26. he pipe is bent incorrectly the indoor unit could be unstable on the wall After passing the connecting pipe through the pipe hole connect the connecting pipe to the auxiliary pipes and insulate as necessary ROF PROOFED BY OK FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT 6 EN Toshiba 1074007701 01EN _P01 10 7 7 16 04 13 30 TOSHIBA RAV SM561KRT E EN 1074007701 5 DRAIN PIPING WORK CAUTION e Bind the auxiliary pipes two and connecting cable with tape tightly In case of left side pipe exit and rear left exit bind the auxiliary pipes two only with facing tape Auxiliary pipes Installation plate 4 Indoor unit e Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit e Carefully connect the auxiliary pipes and connecting pipes to each other and cut off the insulating tape wound on the connecting pipe to avoid double taping at the joint then seal the joint with vinyl tape etc e n order to reduce the possibility of condensed water being produced within the indoor unit make sure to insulate both the connecting pipes Use a suitable form of insulation material specifically design designed for refrigeration pipe work e When bending a pipe ensure care is taken to prevent pipe damage 1 Run the drain hose sloped downwards Do not rise the drai
27. horizontally e Place where a sufficient servicing space can be ensured for safe maintenance and check e Place where drained water will not cause any problem Avoid installing in the following places e Place exposed to air with high salt content Seaside area or place exposed to large quantities of sulfide gas hot spring Should the unit be used in these places special protective measures are needed e Place exposed to oil vapor oil smoke or corrosive gas e Place where organic solvent is used nearby e Place close to a machine generating high frequency e Place where the discharged air blows directly into the window of the neighboring house For outdoor unit e Place where noise of the outdoor unit is easy to transmit When installing the air conditioner on the boundary with the neighbor pay due attention to the level of noise e Place with poor ventilation e Where the ceiling height is more than 3 m e Where the floor wall ceiling structure is unable to support the weight of the unit 4 INSTALLATION OF INDOOR UNIT A WARNING e Install the air conditioner certainly at a place to sufficiently withstand the weight If the strength is insufficient the unit may fall down resulting in human injury e Perform a specified installation work to guard against an earthquake An incomplete installation can cause accidents by the units falling and dropping Locate the unit so as to provide uniform circulation of chilled air Av
28. m with a wire joint Wire joints White 2 pieces are included in the attachments to the remote controller sold separately or the wireless remote control kit sold separately Cabling diagram Never touch remote controller wiring with another 200 240V wiring Otherwise the system will fail Terminal block for remote controller Approx 200 mm ote con W White bl f ind t cabling of indoor uni B Black Remote controller unit or sensor part Remote controller cable Connecting part Remote controller Local procure unit or cable from sensor part Remote controller cabling ME Cable from remote controller unit Wire joint Wiring diagram This wiring diagram is single combination about twin combination see 17 page Remote controller Remote controller cable Indoor side Indoor Outdoor connecting cable Outdoor side Single phase 220 240 e For details of cabling installation of the wired remote controller refer to the Installation Manual attached to in the wired remote controller OK FILM OUTPUT PLEASE CORRECT AS MARKED ROF AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED tee THEN MAKE FILM OUTPUT EN 13 Toshiba 1074007701 01EN P11 22 14 7 16 04 13 31 TOSHIBA RAV SM561KRT E EN 1074007701 8 TEST RUN Before test run e Before turning on the power supply carry out the following procedure 1 Using 500V megger check 1MQ or more exists be
29. n authorized dealer or qualified installation professional to install maintain the air conditioner Inappropriate installation may result in water leakage electric shock or fire e Turn off the main power supply switch or breaker before attempting any electrical work Make sure all power switches are off Failure to do so may cause electric shock e Connect the connecting cable correctly If the connecting cable is connected in a wrong way electric parts may be damaged e When moving the air conditioner for the installation into another place be very careful not to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle If air or any other gas is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it may resultingly causes pipe burst and injuries on persons e Do not modify this unit by removing any of the safety guards or by by passing any of the safety interlock switches e Exposure of unit to water or other moisture before installation may cause a short circuit of electrical parts Do not store it in a wet basement or expose to rain or water ROF OK MAKE FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED 5 555 5 THEN FILM OUTPUT 2 EN Toshiba 1074007701 01EN 01 10 3 7 16 04 13 30 TOSHIBA RAV SM561KRT E EN 1074007701 Toshiba 1074007701 01 01 10 4 TOSHIBA
30. n hose f l X 50 mm Do not put the drain hose end into water Do not form the drain hose into the waved shape Do not put the drain hose end into the drainage ditch 2 Itis not possible to add water to the drain pan to confirm correct drainage To do this the unit must be operated in the COOL mode 3 When connecting extension drain hose insulate the connecting part of extension drain hose with pipe insulation Pipe insulation Drain cm Inside the room N Extension drain hose CAUTION Arrange the drain pipe to allow proper drainage from the unit Incorrect drainage can result in condensation problems This structure of this air conditioner is designed condensed water which may form on the back of the indoor unit into the drain pan Therefore do not store the power cables and other parts within the drain guide ROF OK MAKE FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED 5 555 55 5 THEN MAKE FILM OUTPUT Toshiba 1074007701 01EN _P01 10 8 Wall Drain guide Space for pipes 7 16 04 13 30 TOSHIBA RAV SM561KRT E EN 1074007701 m PROOFED BY 6 REFRIGERANT PIPING 1 Use copper pipe with 0 8 mm or more thickness In case pipe size is 215 9 with 1 0 mm or more 2 Flare nut and flare works are also different from those of the conventional refrigerant Take out the flare nut attached
31. n size Hi OK FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT 8 E N ROF Toshiba 1074007701 01EN _P01 10 9 7 16 04 13 30 TOSH BA RAV SM561KRT E EN 1074007701 6 REFRIGERANT PIPING Tightening connection CAUTION e Do not apply excessive torque Otherwise the nut may crack depending on the conditions Unit Nem Outer diam of copper pipe Tightening torque 6 4 mm diam 14 to 18 1 4 to 1 8 kgfem 9 5 mm diam 33 to 42 3 3 to 4 2 kgf m 12 7 mm diam 50 to 62 5 0 to 6 2 kgf m 15 9 mm diam 68 to 82 6 8 to 8 2 e Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak but also a trouble of the refrigeration cycle Flare at indoor unit side Flare at outdoor unit side Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers Then tighten the nut with a spanner and torque wrench as shown in the figure Half union Flare nut Externally Internally threaded side threaded side Use a wrench to secure Use a torque wrench to tighten OK FILM OUTPUT PLEASE
32. oid locating the unit as shown in the bad marked figures below Good location Bad location Bad location Evenly hot or cooled Shaded area well hot or cooled Shaded area well hot or cooled If a good location is not possible use a fan to circulate the air evenly throughout the room ROF OK FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED EN gt Nem THEN MAKE FILM OUTPUT Toshiba 1074007701 01 01 10 6 7 16 04 13 30 TOSHIBA RAV SM561KRT E EN 1074007701 m 5 DRAIN PIPING WORK Piping and drain hose installation In case of right side exit e Cut out the knockout portion by the slits with a knife or pair of wire cutters as necessary Slit Body right In case of downward pipe exit e Cut out the knockout portion by the slits with a knife or pair of wire cutters as necessary Slit Body right Piping via left hand connection Bend the connecting pipe so that it is laid within 43 mm above the wall surface If the connecting pipe is laid exceeding 43 mm above the wall surface the indoor unit could be unstable when set on the wall When bending the connecting pipes always use a suitable bending tool to avoid damaging the pipes Bend the connection pipe within a radius of 30 mm To connect the pipe after installation of unit figure To the front of the flare 59 Use the handle of a screwdriver etc If t
33. s shown in the figure below Wiring connections Air inlet grille Front panel Cord clamp l Earth line Terminal cover Screw Connecting cable 1 Remove a screw and then remove cover of the electric parts box 2 Strip wire ends 10 mm 3 Match wire colors with terminal numbers on indoor and outdoor units terminal blocks and firmly screw wires to the corresponding terminals 4 Connect the ground wires to the corresponding terminals 5 Fix the cable with cord clamp 6 Fix cover of the parts box and the terminal block surely with the fixing screws Make a loop on the cable for margin of the length so that the electric parts box can be taken out during servicing 3 1 M 15 9 a 4 Xoo DE See E Grounding cable 30 Connecting cable Earth line Connecting cable OK Make FILM OUTPUT PLEASE CORRECT AS MARKED ROF AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED tee THEN MAKE FILM OUTPUT 12 EN Toshiba 1074007701 01EN P11 22 13 7 16 04 13 31 TOSHIBA RAV SM561KRT E EN 1074007701 ELECTRICAL WORK Wired remote controller cabling e Strip off approx 14 mm the cable to be connected e Non polarity 2 core cable is used for cabling of the remote controller e Twist cable of the remote controller to be connected with cable of the remote controller unit or sensor and press fit the
34. t the remote controller terminal plate A B on the indoor unit to which the remote controller is connected to the terminal plate A B on each of other indoor units by linking them with each other with remote controller wiring e Automatic address setting commences when the power is turned on After 3 minutes Setting will be indicated on the display panel to show that the address is being set PROOFED BY OK FILM OUTPUT PLEASE CORRECT AS MARKED AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED THEN MAKE FILM OUTPUT EN 17 7 16 04 13 31 Toshiba 1074007701 01EN P11 22 18 TOSHIBA RAV SM561KRT E EN 1074007701 m 10 INDOOR UNIT OPERATION WHEN CONNECTED TO MULTIPLE UNITS Automatic address setting takes approximately 5 minutes until completion Group Control of Single System Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit Indoor unit up to 8 units JJ ma oO m 2 o i gt gt m 2 5 5 e 2 2 0 o Ir o 2 3 m D Control line Other connecting line e Length of wires for remote controller L should be 200 m in case of using wireless remote receiver 300 m another controller or less e Length of wires for remote controller should be 200 m or shorter in total i e L1
35. to the main unit of the air conditioner and use it CAUTION IMPORTANT 4 POINTS FOR PIPING WORK 1 Remove dust and moisture from the inside of the connecting pipes 2 Tight connection between pipes and unit 3 Evacuate the air in the connecting pipes using VACUUM PUMP 4 Check the gas leakage Connected points Permissible piping length and head They vary according to the outdoor unit For details refer to the Installation Manual attached to the outdoor unit Insert a flare nut into the pipe and flare the pipe As the flaring sizes of R410A differ from those of refrigerant R22 the flare tools newly manufactured for 410 are recommended Up However the conventional tools be used by adjusting projection margin of the 4 _ Projection margin in flaring Unit mm Rigid Clutch type R410A tool used Conventional tool used R22 R410A R22 6 4 to 15 9 Same as left 1 0 to 1 5 0 5 to 1 0 Outer diam of copper pipe Imperial Wing nut type Outer diam of copper pipe R410A R22 6 4 or 9 5 1 5 to 2 0 1 0 to 1 5 12 7 or 15 9 2 0 to 2 5 1 5 to 2 0 e Flaring diam meter size A Unit mm Outer diam of copper pipe s R410A In case of flaring for R410A with the conventional flare tool pull it out approx 0 5 mm A more than that for R22 to adjust to the specified flare size The copper pipe gauge is useful for adjusting projection margi
36. tween the terminal block 1 to 3 and the earth If 1MQ or less is detected do not run the unit Do not apply to the remote controller circuit 2 Check the valve of the outdoor unit being opened fully e To protect the compressor at activation time leave power ON for 12 hours or more be for operating How to execute a test run Using the remote controller operate the unit as usual For the procedure of the operation refer to the attached Owner s Manual A forced test run can be executed in the following procedure if the operation stops by thermo OFF This method is limited to when wired remote controller is installed In order to prevent a serial operation the forced test run is released after 60 minutes have passed and returns to the usual operation CAUTION When the remote controller is used for the first time it accepts an operation approx 5 minutes after the power supply has been turned on It is not a trouble but is because the setup of the remote controller is being checked For the second power ON time and after approx 1 minute is required to start the operation by the remote controller Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices ROF 0 FILM OUTPUT PLEASE CORRECT AS MARKED PROOFED BY AND SEND BACK FOR THE NEXT PROOF PLEASE CORRECT AS MARKED eMe THEN MAKE FILM OUTPUT 14 EN Toshiba 1074007701 01EN P11 22 15 7 16 04