CDL Pocket Quick Reference Guide
Contents
1. Cool Designs Ltd jJ i E s Pocket Quick Reference Guide Ow the TOSHIBA RBC AMT32E RBC AMS41E Remote Controllers Cool Designs Ltd lt Raising the Standards Air Conditioning Distribution Tos Leading Innovation gt gt gt Quick Reference Guide To assist service engineers working on Toshiba air conditioning equipment there is a large quantity of data available via the standard remote controller either the RBC AMT32E or the RBC AMS41E this data is NOT available via an Infrared remote or the RBC AS21E2 simplified remote controller Accessing the data is a simple process of pressing a sequence of buttons on the remote controller Fault Code Guide Current fault codes are displayed automatically on the left of the remote controller Four figure display in Black fault code history can be accessed by pressing Test and Set The two yellow buttons together and holding for 4 seconds Each controller will hold four fault codes per unit controlled the first displayed fault code is the youngest and the fourth will be the oldest To scroll through the faults use the TEMP A V buttons e Refer to the Technical Handbook for fault code diagnosis and descriptions Data Retrieval Guide System data can be obtained by pressing Test and CL together and holding for 4 seconds Codes are displayed on the right of the remote display
2. Raising the Standards Air Conditioning Distribution divisio m CarbonNeutral com m e TOSHIBA Leading Innovation gt gt Contact details Cool Designs Ltd Technical Support 07590775510 Monday Friday 07 30 to 19 30 Toshiba Air Conditioning 24 7 technical support 0870 843 0333 Option 7 Text back service 07624 803 017 Type fault code in lower case no spaces Try our on line training videos on YouTube Cool Designs Ltd reserves the right to change the product specifications data and images without notice 02015 Bical Raising the Standards in Air Conditioning Distribution WINNER OF THE VESA
3. To scroll through the codes use the TEMP A V buttons Data is displayed on the left of the remote controller Data is available for 0 1 2 3 amp A Series Digital Super Digital Inverter VRF equipment SMMS SHRM SMMSI amp SHRMi deem lt Cool Designs Ltd divisio Raising the Standards in Air Conditioning Distribution CarbonNeutral com Digital Super digital 0 1 2 3 series data Room Temp Control Temp 9C 60 TE Sub cooled Liquid Temp C Room Temp Remote Controller C TO Ambient Temp C 02 Return Air Temp C 62 TD Discharge Temp C 03 TCCoil Vapour Temp C 63 TS Suction Temp C 04 65 THS Inverter Heat Sink Temp C Coil Liquid Temp C Digital Super digital 4 series Room Temp Control Temp C 60 TESub cooledliquid Temp C 01 TA Return Air Temp C 62 TDDischargeTemp C TC Coil Vapour Temp C 63 _ TS Suction Temp Coil Liquid Temp C 65 _ THS Inverter Heat Sink Temp C 7 Fan Speed rpm Operation Current A Discharge Temp Indoor If fitted C VRF indoor data for Mini SMMS SMMS SMMSI amp SHRM equipment Room Temp Control Temp 9C Indoor Discharge Temp If Used 9C PMV Position 0 10 01 Room Temp Remote Controller C TA Return Air Temp 9C D Number of Co
4. covery Controlled 9 TO Outdoor Ambient Temp C Pressure release A PMVi 20penng Discharge Temp Release B PMV4Openng B FollowerUnitReleae C CompressoriCurent A OutdoorUnitSze HP Compressor 2 Current A Note Would be replaced with 1 2 3 or 4 to Compressor 3 Current A obtain data from respective outdoor unit Outdoor Fan Current A would be replaced with either 5 6 7 8 to obtain data from outdoor units 1 2 3 or 4 For descriptions that are more detailed please refer to the relevant technical service manual Compressor IPDU 2 Heat Sink Temp 9C Compressor IPDU 3 Heat Sink Temp C Outdoor Fan IPDU Heat Sink Temp 9C gare Designs Ltd 2015 divisio Raising the Standards Air Conditioning Distribution WINNER B CarbonNeutral com EUTRAL Common Configurable Control Options Accessed via Toshiba hard wired remote controller RBC AMT32E and RBC AMS41E Relocation of room temperature sensing from return air to remote controller sensor Press and hold the TEST SET amp CL Buttons simultaneously for 4 seconds The Engineering Menu is accessed at item code 10 Use the Temperature A V Buttons to navigate to item code 32 Use the Timer A V Buttons to adjust the value from 0000 to 0001 Press SET to acknowledge the change Press Test t
5. nnected Indoor Units No TCJ Coil Liquid Temp C Indoor Capacity x 10 HP TC2 Coil PMV Pipe Temp C Number of Outdoor Units No TC1 Coil Vapour Temp Od Outdoor Capacity 10 HP VRF Outdoor data for Mini SMMS SMMS amp SHRM equipment Td1 Compressor 1 Discharge Temp TU Low Pressure Saturated Temp C c Compressor 1 Current A 1 Td2 Compressor 2 Discharge Temp C Pd High Pressure Sensor MPa A Compressor 2 Current A TS Suction Temp C Compressor 1 2 ON OFF TE Outdoor Heat Exchanger Temp C Outdoor Fan Mode 0 31 TL Liquid Temp 9C Outdoor Unit Size HP Note Would be replaced with 1 2 3 or 4 to obtain data from respective outdoor unit Ps Low Pressure Sensor MPa PMV1 2 Opening 0 100 dT re Cool Designs Ltd el W Raising the Standards in Air Conditioning Distribution _ CarbonNeutral com ui TOS BA Leading Innovation gt gt gt VRF Outdoor data for SMMSi SHRMi equipment Pd High Pressure Sensor MPa Ps Low Pressure Sensor MPa Td1 Compressor 1 Discharge Temp C Td2 Compressor 2 Discharge Temp C Compressor 1 Revolutions rps Compressor 2 Revolutions rps Compressor 3 Revolutions rps Outdoor Fan Mode Compressor IPDU 1 Heat Sink Temp C C 8 TL LiquidTemp C Heating Cooling Re
6. o exit the Engineering Menu The display will go blank and then flash SETTING whilst the system reconfigures When SETTING stops flashing press ON OFF Button to restart the operation Automatic restart after power failure Press and hold the TEST SET amp CL Buttons simultaneously for 4 seconds The Engineering Menu is accessed at item code 10 Use the Temperature A V Buttons to navigate to item 28 Use the Timer A V Buttons to adjust the value from 0000 to 0001 Press SET to acknowledge the change Press Test to exit the Engineering Menu The display will go blank and then flash SETTING whilst the system reconfigures When SETTING stops flashing press ON OFF Button to restart the operation _ Cool Designs Ltd Raising the Standards in Air Conditioning Distribution TOSHIBA Leading Innovation gt gt gt Simplified Instructions for the RBC AMS41E Remote Controller Setting Present Time and Day of Week Press and hold SCHEDULE for 4 seconds setting appears on screen Press DAY until the correct day of the week is indicated Press TIME up and down keys to set current time Press SET to confirm entries Day and time now set Setting ON and OFF Times scheduled operations E T LE Press PROGRAM display will flash PG 01 Press DAY until Monday is selected then Press SET Press SET PG 01 will stop flashing Press TIME up and down keys until required ON TIME is displayed Press SCHEDULE until Sl blinks symbol deno
7. tes start operation Press SET Press UNIT PG 02 will appear Press SET PG 02 will stop flashing Press TIME up and down keys until required OFF TIME is displayed 10 Press SCHEDULE until blinks denotes stop operation 11 Press SET and then PROGRAM The bar now underlining MONDAY indicates that times have now been entered Copying From Monday to Remaining Days of Week E LN LE Ee Press PROGRAM display will flash PG 01 Press DAY key and select Monday Press SET Press UNIT key until PG CP appears program copy Press SET Press DAY and select Tuesday Press SET Monday times have now been copied into Tuesday to continue copying return to step 4 Press PROGRAM The times have now been programmed into the controller N B To activate the programmed times press SCHEDULE will flash Press SET remains displayed scheduled programming now activated To deactivate the programmed times press SCHEDULE will flash Press CL disappears from screen inc lt Cool Designs Ltd Raising the Standards in Air Conditioning Distribution Time Temperature and Mode Selection when Programming the RBC AMS41E Setting Present Time and Day of Week Press and hold SCHEDULE for 4 seconds setting appears on screen Press DAY until the correct day of the week is indicated Press TIME up and down keys to set current time Press SET to confirm entries Day and time now set Setting Scheduled Operations with Mode and Temperature f
8. unctionality 12 Press PROGRAM display will flash PG 01 13 Press DAY until Monday is selected then Press SET 14 Press SET PG 01 will stop flashing 15 Press TIME up and down keys until required ON TIME is displayed 16 Press MODE key selecting desired mode of operation 17 Press TEMPERATURE up amp down arrows to set desired temperature 18 Press SCHEDULE until 1 blinks symbol denotes start operation 19 Press SET 20 Press UNIT PG 02 will appear 21 Press SET PG 02 will stop flashing 22 Press TIME up and down keys until required OFF TIME is displayed 23 Press SCHEDULE until EO blinks symbol denotes stop operation 24 Press SET and then PROGRAM The bar now underlining MONDAY indicates that times have now been entered Copying From Monday to Remaining Days of Week 9 Press PROGRAM display will flash PG 01 10 Press DAY key and select Monday 11 Press SET 12 Press UNIT key until PG CP appears program copy 13 Press SET 14 Press DAY and select Tuesday 15 Press SET Monday times have now been copied into Tuesday to continue copying return to step 4 16 Press PROGRAM The times have now been programmed into the controller N B To activate the programmed times press SCHEDULE will flash Press SET LO J remains displayed scheduled programming now activated To deactivate the programmed times press SCHEDULE LS will flash Press CL La disappears from screen Cool Designs Ltd oa 2
Download Pdf Manuals
Related Search
Related Contents
vie quotidienne et droits sociaux des adultes en [U7.06.01] Opérateur CALC_IFS_DNL NI-FBUS Hardware and Software User Manual Demander la notice d`utilisation Digitus DN-19 MA-42U mounting kit Instruction Manual L`identification, - PetMarket Magazine Epic Fitness FMTL39940 Treadmill User Manual Bon-Aire i3000 Use and Care Manual User`s Manual and Operating Instructions Copyright © All rights reserved.