1. Electrical Controls cables City Multi R2 WR2 Series System Indoor Units and Air Curtains s can operate on heating or cooling simultaneously e g some indoor units are cooling whilst other indoor units and air curtain are heating at the same time The City Multi R2 WR2 Series heat recovery system with Heat Pump Air Curtain s consists of e Oneor more Thermoscreens VRF PHVR Heat Pump heating amp cooling Air Curtains e A Mitsubishi Electric PAC AH M G AHU Controller or PAC AH M H AHU Controller one for each air curtain A Mitsubishi Electric PAR 21MAA Remote Controller one for each AHU Controller One or more Mitsubishi Electric City Multi R2 WR2 Series Compressor Unit Mitsubishi Electric BC Controller Mitsubishi Electric Indoor Unit s NB Can be used on a full air curtain basis if required up to 100 diversity e Mitsubishi Electric BMS System or Centralised Controller if required supplied by Thermoscreens Ltd supplied by others 9901037 2 Page 3 of 33 DESIGN INFORMATION Each Thermoscreens Heat Pump Air Curtain needs to operate with a Mitsubishi Electric PAC AH AHU Controller There are two versions that can be used PAC AH M G and PAC AH M H the supply of which is dependent on the EU state country where the installation is being carried out The rated size of the PAC AH AHU Controller needs to be matched to the size of the heat pump air curtain Each size of AHU Controller comes wi
2. thermoscreens PHV RECESSED HEAT PUMP AIR CURTAINS INSTALLATION OPERATION amp MAINTENANCE INSTRUCTIONS For use with CITY MULTI VRF units PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING INSTALLATION Thermoscreens Ltd St Mary s Road Nuneaton Warwickshire England CV11 5AU MITSUBISHI A TM ELECTRIC Email sales thermoscreens com AIR CONDITIONING SYSTEMS Tel 44 0 24 7638 4646 Fax 44 0 24 7638 8578 www thermoscreens com 9901037 2 Page 1 of 33 cke a Marat AIA ermanente C fo II Thermoscreens Mitsubishi Electric Thermoscreens City Multi Heat Pump Air Curtains can be used with Mitsubishi Electric City Multi Y WY Series Heat Pump or City Multi R2 WR2 Series Heat Recovery systems City Multi Y WY Series Heat Pump Air Curtain System City Multi Y WY Series Heat Pump Air Curtain Schematic 1 em iar PH em ym Yol CW JI TOLEA e VV i IE i PAC AH AHU 1 Controller LEV s I l X IEFLLLLLLLIF lee che T Power l Fan e L Air Curtain Heat Pump mM D ll d d IN Remote 3 Speed Fan Switch Mitsubishi Electric l PAR 21MAA Compressor Unit E remote E controller E TEE d f in Mitsubishi Electric BMS Control Indoor Units Refrigeration pipework Electrical Controls cables City Multi Y Series System Indoor Units and Air Curtains s all operate on heating at the same time or all operate o
3. Joy Ajddns e5211329 3 eseud Jed viet OOSTAHd AYA eseud Jad v8 OOOTAHd JA weg suey pue S19 e9H 211794 0001nN0 31419313 IHSIEGNSLIA 1s0JJeq 103 jddns 6e511329 3 8907 9901037 2 zz Wiring to PAC AH AHU Controller and Controls Wiring The Mitsubishi Electric PAC AH AHU Controller needs to be located within 7m from the air curtain cables are 8m long It would normally be placed lying flat within the ceiling void but it could be fixed to a wall using the four mounting feet It must be accessible for future service work if necessary It comes pre wired with various 8m long cables for T power supplies thermistor sensors LEV s alarms etc which have Ee to be connected to the air curtain Each of the pre wired cables has a E label attached to it at the end of the cable showing where it has to be connected at the air curtain The following table lists the connections e to be made between the PAC AH AHU Controller and the Air ET FI Curtain Please note there are two types of AHU Controller PAC AH M G and PAC AH M H and wiring of some cables and components is different for each type This is indicated in the table below See also wiring diagram on Page 16 for PAC AH M G and Page 17 for PAC AH M H Controller Termination at Cable Component Termination at Air Type PAC AH Curtain wired to terminals E N L curtain to PAC AH 230v ac POWER SUPPLY wired to terminals D
4. Ajddns e21329 3 Page 16 of 33 9901037 2 1911011409 NHY H IW HV 9Vd Utm UIEUDO ary dung 189H HAHd AYA NVEDVIO ONIYIM Page 17 of 33 KUER VIN TZ MV umoys paads Y IN L6 e V d ue4 WINIPAN E ils m uey peeds e Dun JOU H LNO JN17 O X E Zz O O a d O XQ000ZAHd JUN 104 VL Z eir Sl ESE m XCOOSTAHd F8N 105 V8 T XGOOOTAHd HUA 49 VE T z S ZHOS UAT AOEZ Ua S T1 B eg San pepeeu Udy JOU ae 7 pue Z1 HH ONtpT eu ua Ale ixne 8 19016 E ul 9JeS al 3 8U U1J19 pue zy WO s 11 5 al 9 dund JDBUUODSIP paJuinbaJ Jou 3 18 c sjuauwa 3 6uneasH 2143129 3 1501490 1 TI l uenvbiado Tzott II MA6 MOE X yun wz MAGL MAS ZX Wun UST H MAS MASTXE Wun WT AN a DR A ARE SLN3N373 A AA sous la M Es O SOSS EE AAA 19d A COCO SS o E O l aan CGNO LATA ll SS l AA He OVe lalala IHS E TN zn ZHOS YAT AOEZ 10 geed use TT ac zHos ud A00P ONIWHIM JIC p 23097 E ONIHIM3IIS r J0J Aiddne e214329 3 l l a ia cl cia e dee Jee d EE MT A ARS H1uv3 6 eunuta p vm IVuln3N 8 jeune p dk ef seuun 118 3e SAT JAI JUaue ad Z jJeuruJe JO EHE rege Puedo s uleqind Ip UBYM JUO BAI JAI p9UuX1IIMS T JeuruJa aseyd Jed v ST OOOZAHd AHA asn dund a3esuspuo gt
5. PAR 21MAA Remote Controller To Switch On and Off Turn the air curtain on by pressing the ON OFF Button on the PAR 21MAA Remote Controller and the air curtain fans will start within a few seconds If a 3 Speed Fan owitch is fitted adjust the fan speed to suit using the slider switch As set up by the Commissioning Engineer the air curtain will operate in AUTO mode automatically heating or cooling as required with a target temperature of 24 C all other buttons on the Remote Controller are locked out NB The air curtain may produce condensate during hot weather so a condensate disposal system must be fitted PAR 21MAA Remote Controller 3 Speed Fan Switch Turn the air curtain off by pressing the ON OFF Button on the PAR 21MAA Remote Controller and the air curtain fans will stop If the PAR 21MAA Remote Controller is not locked the following functions operate HEAT Mode Press the Mode Button on the Remote Controller until HEAT appears on the display Adjust the target temperature using the A or V TEMP Button between 22 C and 28 C maximum Allow time for the air stream to heat up AUTO Mode only if a condensate disposal system is fitted Press the Mode Button on the Remote Controller until AUTO appears on the display Adjust the target temperature using the A or W TEMP Button to 24 C This is the normal mode of operation for the heat pump air curtain and it should run in this set up with no further adjustments automatic
6. brushed and vacuum cleaned Refit the filters opposite to removal The filters are very durable but may need to be replaced after a number of service intervals Vacuum clean and remove any build up of dust dirt and debris within the air curtain especially on the face of the coil and the electric heating elements Note Fan motors are permanently lubricated and require no additional lubrication If the Air Curtain has been used in Cooling S Loosen by 4 turns the rear row of Remove the front row of drain tray drain tray fixing screws along the fixing screws along the whole whole length of the tray Do not length of the drain tray Keep the remove these screws completely screws 9901037 2 Page 29 of 33 The drain tray now angles down along its front edge and the inside surface of the tray can be easily cleaned Remove all debris from the drain tray outlet spout and condensate hose Check there are no kinks in condensate hoses If a peristaltic condensate pump is fitted change the rubber pump head tube Refit drain tray opposite to removal Once the air curtain has been cleaned visually inspect the air curtain components Ensure pipe temperature sensors are located in their pockets and any foam insulation covering these pockets is un damaged Check the location of the thermal overheat cut out and air sensor and that the thermal overheat cut out switch has not tripped see oection Commissioning Page 22 Check all elec
7. can occur service Manual to understand error code because of a fault within the air curtain fault then inspect and repair air curtain if there is a fault If the Heat Pump Air Curtain system is still not operating correctly call for a Mitsubishi Electric Service Agent 9901037 2 Page 31 of 33 z Warranty If any problems are encountered with the heat pump air curtain please contact your Mitsubishi Electric Service Agent Care has been taken in compiling these instructions to ensure they are correct although Thermoscreens Ltd disclaims all liability for damage resulting from any inaccuracies and or deficiencies in this documentation Thermoscreens Ltd retain the right to change the specifications stated in these instructions Thermoscreens Ltd St Mary s Road Nuneaton Warwickshire England CV11 5AU Email sales thermoscreens com Tel 44 0 24 7638 4646 Fax 44 0 24 7638 8578 www thermoscreens com 9901037 2 Page 32 of 33 Thermoscreens Ltd St Mary s Road Nuneaton Warwickshire CV115AU United Kingdom Telephone 444 0 24 7638 4646 Fax 44 0 24 7638 8578 EC DECLARATION OF CONFORMITY as defined by the EC Council Directive on Machinery 2006 42 EC the Low Voltage Directive 73 23 EEC the Electromagnetic Compatibility Directive 89 336 EEC and the Pressure Equipment Directive 97 23 EC Herewith we declare that the air movement equipment designated below on the basis of its design and construction in the form b
8. holes in the casing one at the top of the unit and a lower one at the rear both fitted with rubber plugs see Figure 1 Page 11 The photo shows the plastic hose going through the lower rear condensate outlet hole It is possible to gravity drain condensate from these recessed air curtains via the lower condensate outlet hole at the rear of the unit which is c 40mm minimum above the top surface of the ceiling within the ceiling void see Figure 1 Means of condensate disposal must then be provided within the ceiling void The plastic hose should be pushed through this lower hole at the rear after removing the plug and connected to the condensate disposal system within the ceiling void Alternatively a suitable condensate pump not supplied by Thermoscreens can be supplied and fitted by the installer to remove condensate directly from the unit The condensate pump must be of sufficient capacity see Table below and if located above the drain tray self priming and capable of providing the appropriate suction head so the pump will lift condensate out from the top of the air curtain Suitable condensate pumps with a suction head are Peristaltic or Rotary Diaphragm type We recommend the Blue Diamond rotary diaphragm type with cooling signal sensor drainStik manufactured by Charles Austen Pumps Ltd www miniblue co uk Maximum likely Air Curtain Condensate flow rate litres hour VRF PHV1000R DXE HO 60 It is recommended
9. necessary to re set the voltage tappings on the transformers inside the fan speed controller to achieve a compromise between airstream performance and noise levels This is explained in the instructions that come with the optional fan speed controller If it is intended that the air curtain is to ever operate in cooling mode switch the Mode Button on the PAR 21MAA remote controller to COOL and adjust the target temperature to 14 C minimum setting using the W TEMP Button Wait for the air curtain air stream to go cold Check the inside of the drain tray is clean there is no debris in the outlet spout there are no kinks in condensate hoses the condensate pump if fitted will operate or the gravity condensate drain if used is functional It is unlikely that condensate will fill the drain tray straight away so it will be necessary to fill the tray manually with water to see if the condensate removal system is working satisfactorily If an alarm sensor is fitted in the drain tray check it operates to stop the air curtain cooling if the drain tray becomes too full Test the air curtain for a time in cooling mode with the recessed grille core fitted and if environmental conditions permit check that condensate is being collected and disposed of or pumped away by the condensate pump No condensate should leak out of the air curtain At the end of the cooling test remove the recessed grille core and check that the inside of the air curtain has remained dr
10. that the electrical supply to the Air Curtain is switched off before starting any commissioning work Air Curtain Checks Check that the components inside the air curtain are as shown in the picture below Check that the thermal overheat cut out switch has not tripped Push down on the red button on the top of the thermal overheat switch if it has tripped it will click back on Connections on electric lements Thermal overheat cut out switch oa Air Inlet BEE O A Sensor 12v DC em T relay oet the inner aluminium air vanes within the air curtain air discharge so they point straight downwards over the doorway A PAR 21MAA Remote Controller should be connected and used to carry out commissioning even if the air curtain is to operate under the control of a BMS System or Centralised Controller Disconnect the remote control plug from inside the E PAC AH AHU Controller to use the remote controller Plug it back in again if a BMS Centralised Controller is to be used and the PAR 21MAA is disconnected after commissioning NB If the air curtain is used in AUTO mode under the control of k a BMS System or Centralised Controller it is necessary to also have a PAR 21MAA Remote Controller connected 3 Mitsubishi Electric Compressor Unit For Y Series systems ensure that the appropriate dip switch has been set in the compressor unit so that the PAR 21MAA Remote Controller will operate in AUTO mode and to enable Auto Re Sta
11. will lift condensate out from the top of the air curtain Suitable condensate pumps with a suction head are Peristaltic or Rotary Diaphragm type We recommend the Blue Diamond rotary diaphragm type with cooling signal sensor drainStik manufactured by Charles Austen Pumps Ltd www miniblue co uk lt is recommended that the condensate pump has the facility so it only operates when the air curtain is in cooling mode by detection of water in the drain tray or by detecting a cooling differential in the airflow It should also have a pump overrun to empty the drain tray as much as possible when the air curtain is switched off The condensate disposal system should have an alarm system with appropriate sensor fitted in the drain tray that will give a volt free signal open circuit alarm This will stop 9901037 2 Page 5 of 33 the air curtain cooling if the condensate drain tray is in danger of flooding air curtain fans will continue to operate Other indoor units on the same City Multi system are unaffected if the air curtain condensate alarm occurs There is a plastic fixing bracket with 8mm diameter hole attached to the drain tray inside the air curtain so a condensate sensor can be fixed in the tray by the installer The hole can be enlarged if necessary to suit the type of sensor used so it is located in the tray at the appropriate position see the manufacturer s instructions that come with the condensate pump for further information The 230v A
12. 1 D2 start Air Curtain 230v ac OPERATION SIGNAL M G and M H 8m 2 core cable pre Defrost signal from PAC AH to wire to terminals 5 amp 6 plugged into CN52 on operate contactor in air curtain for PAC AH pcb defrost electric heaters if used M G and M H 8m 2 core cable pre Thermistor Gas temperature Fit sensor bulb into Hot Gas wired to terminals sensor identified Black pocket on refrigerant gas T21 T22 THERMISTOR pipe at top of air curtain after GAS A a brazing pipe connections M G and M H wire to terminals Thermistor Liquid temperature 8m 2 core cable with sensor 111 T12 THERMISTOR sensor identified White bulb factory fitted within air LIQUID curtain M G only wire to terminals Thermistor Return Air 8m 2 core cable with sensor T1 amp T2 THERMISTOR temperature sensor identified bulb factory fitted within air INLET AIR Red curtain M H only wire to terminals Thermistor Return Air 8m 2 core cable with sensor T1 amp T2 THERMISTOR temperature sensor identified bulb factory fitted within air OUTLET AIR Red curtain M H only Terminals T31 T32 Nothing connected to T31 or T32 Not Applicable Linear Expansion Valve s LEV s M G and M H 8m 6 core cable pre wired to 6 way colour coded LEV terminals Install in liquid line near to air curtain ei N M G and M H 8m 2 core cable pre Condensate alarm from condensate Connect to condensate pump plugged
13. 33 The Thermoscreens Air Curtain requires a permanent mains electrical supply from a local switched isolator Electrical power to the PAC AH AHU controller is then fed from the air curtain Electrical power to the Mitsubishi Electric compressor unit s and BC Controller is fed separately in the normal way see separate Mitsubishi Electric instructions If the defrost cycle electric heaters inside the air curtain are to be used during the heating mode defrost cycle the electrical supply to the air curtain needs to be 3 phase 3L N E If the defrost cycle electric heaters are not required they can be permanently disconnected at installation and a single phase electrical supply 1L N E fed to the air curtain instead see Installation Electrical Supply Warning Air curtain fans continue to operate during heating mode system defrost to maintain an air stream across the doorway With the defrost cycle electric heaters operating the discharge air temperature from the air curtain is kept to a few degrees below that of the indoor ambient air temperature during the duration of system defrost If the electric heaters are disconnected discharge air temperatures could be very cold approximately 6 C during the defrost and defrost times will also be extended particularly with the R2 Series System Defrost does not occur with WY and WR2 systems so the defrost cycle electric heaters should be disconnected on these systems There are various control cables
14. AN mode never in AUTO or COOL mode lt is important this is done at commissioning if the air curtain is not to operate in cooling mode and is not fitted with a condensate disposal system 9901037 2 Page 24 of 33 SG Filter Dirty Indicator The air curtain is fitted with a Filter Dirty Indicator It is located at the left hand end of the air discharge grille and signals when the air curtain inlet grille filters should be vacuum cleaned or the air curtain requires servicing NB The filter dirty indicator on the PAR 21MAA Remote Controller does not function wired to a PAC AH AHU Controller da t A la j 1 E d i j g T 1 T P EL HEP e The indicator states are outlined below Indicator State Indicator Light Action Required Reset Button GREEN FLASH _ On 0 5s Off 3s RED ON On permanently RED FLASH On0 5s Off0 5s Service filters The filter indicator schedule is based on fan operating hours For the default schedule shown schematically below the inlet grille filter should be vacuum cleaned every 120hrs of fan operation every 1 to 2 weeks and a full service should take place every 480hrs of fan operation RED ON Quick reset RED ON Quick reset Fan operating hours 4 RED ON Quick reset m hrs RED FLASH Hold 5s to reset i The factory set default schedule is suitable for most applications However the actual frequency of cleaning required will depen
15. C single phase electrical supply to operate the condensate pump will come from the air curtain Warning The air curtain condensate collection system is designed to remove condensate with the air curtain operating in cooling mode during normal summer weather conditions in countries with a temperate climate In case of extreme weather conditions or failure of the condensate disposal system which can occur it is vital that the design of the floor beneath the air curtain and its surface is such that it will not become slippery or damaged if it became wet This is similar to the conditions that might be experienced with heavy rainfall in at an open doorway or wet pedestrian foot traffic so careful consideration must be paid to the design of the floor and its surface finish If it is intended that the air curtain should not be operated in cooling mode and a condensate disposal system pump is not fitted the BMS System Centralised Controller or PAR 21MAA manual Remote Controller must be configured at commissioning so that COOL or AUTO mode can never be selected see Section Commissioning It is still recommended however that the floor design and surface be as described above in case cooling mode is used in the future and to cope with heavy rainfall or wet pedestrian foot traffic Note It could still be possible for an end user to unlock a PAR 21MAA Remote Controller if they found out how to and switch it into cooling not realising that condensat
16. H o ejeld Jojeedes CN s ju uM Jouog 6 i pue Addnsjeoupeld a s 10 UONISOA eAneuJo a 4 y UOT n yv E pioa Bul 1989 woy 19 U 0 Jie JO jun Jo epis wou eooueJeog 08 Eis al Page 11 of 33 9901037 2 Fitting the Recessed Grille The recessed grille consists of a frame and grille core with filter attached to it Fix the four fixing brackets to the grille frame using an M4 screw to fit each fixing bracket Note which fixing brackets go where see photo there are two shapes Remove the grille core from the grille frame by unfastening the two conical bolts fitted at each end of the grille core using an 8mm spanner Then push the grille core sideways against the spring loaded pins on one side and the grille core with filter now comes clear of its frame Note The grille core with filter attached will still be tethered to the frame via safety cords and will hang down on these cords Locate the four M6 bolts that will hold the grille fixing brackets to the air curtain two inside each end of the unit and remove these M6 bolts Lift the frame into position so the air discharge section of the grille will align with the air discharge vanes from the air curtain see Figure 1 and photos on Page 7 Screw an M6 bolt through the slot in each grille fixing bracket until all four are located in place Adjust the height of the grille frame via the slots in the fixing brackets so the frame fits ne
17. OOO Ae Pe Reset the Filter Dirty Indicator after cleaning by a quick press of the Reset Button even if the indicator has not gone red aa T qd iis B Servicing the Air Curtain suggest every 3 Months or if the Filter Dirty Indicator shows FLASHING RED Always disconnect and isolate the mains electricity supply both at the local electrical supply to the Air Curtain and to other Mitsubishi Electric equipment in the City Multi system before servicing maintaining or repairing the Air Curtain Note All servicing maintenance and repairs to the air curtain must be carried out by an approved Service Agent Towards the rear of the recessed grille nearest the doorway and at each end of the grille there are two conical bolts that prevent the grille being removed without the use of tools Loosen these two conical bolts using an 8mm spanner Then push the grille core towards the doorway against spring loaded pins on one side and the grille core with filler now comes clear of its frame Note The grille core with filter attached will still be tethered to the frame via safety cords and will hang down on these cords 9901037 2 Page 28 of 33 The grille filter can now be unclipped from the grille and brushed and vacuum cleaned screws inset into the frame see photo Loosen each of these screws by 2 turns E Ze Pull the void filter outwards at the bottom and then remove from the air curtain lt can then be
18. ady to start DANGER Beware of Fans Starting Turn the air curtain on using the ON OFF Button on the PAR 21MAA Remote Controller and the air curtain fans will start straight away owitch the Mode Button on the PAR 21MAA to heating mode and adjust the target temperature to 28 C maximum setting using the ATEMP Button If the 3 Speed fan switch is installed check that the fans run at Low speed Medium speed and High speed by operating the slider switch Check there is no mechanical noise coming from the fans at each of the three fan speeds and that all fans are working If the 3 Speed fan switch is not to be installed a wire link will have been fitted to the fan speed terminals on the air curtain Set the wire link to one of the three fan speeds LOW MED or HIGH appropriate to the site conditions see also Page 19 Check Heating and Cooling Performance In heating mode check that the air stream from the discharge grille warms up across the whole length of the air curtain after approximately 20 minutes of operation and that the air stream reaches right down across the doorway with the door open or closed If necessary the inner aluminium vanes in the air curtain air discharge can be angled either inwards or outwards if this gives better penetration warming of any incoming draughts The fan speed can also be adjusted High Medium or Low to suit the 9901037 2 Page 23 of 33 conditions If an optional fan speed controller has been installed it may be
19. air curtain once it is located in position Ensure there is sufficient height clearance within the ceiling void to do this hanging rods Holes are provided in the top face of the casing see Figure 1 for positions to allow the unit to be suspended on M10 threaded rods not provided All suspension points must be used uc Du tee rra Number of Air Curtain Weight kg pan lag suits Four of the threaded rods the two at each end of the unit enter the casing from above and are attached to fixing brackets near the bottom of the unit see photo above looking up into the air curtain The two centre threaded rods on PHV1500 and PHV2000 units are attached to the top face of the casing Ensure each of the threaded rods is secured onto a suitable structure that can support the weight of the unit see table above When fitting the threaded rod ensure that it does not interfere with internal components Threaded rod should engage into fixing holes by a minimum of 20mm and locking nuts fitted to prevent the rod rotating and coming away from its fixing point Note When installing the air curtain ensure that the underside of the casing is between 40mm and 65mm above the exposed bottom face of the ceiling tile plasterboard see Figure 1 The recessed grille and other air curtain components have adjustment within this range although aim to achieve the minimum 40mm if possible It is the sole responsibility of the installe
20. ake sure the thermistor gas sensor has not been inserted into its pocket on the gas pipe at the top of the air curtain before brazing Remove it if it has or it will burn when the pipe connection is brazed For the City Multi system the LEV needs to be brazed into the liquid line as close as possible to the air curtain 2m maximum The picture shows an example of this On the VRF PHV2000R DXE HO there are two LEVs to be fitted in parallel see Mitsubishi Electric AHU Controller instructions The LEV s should be located in the ceiling void in an accessible position For the City Multi VRF R2 and WR2 Series system pipework from each air curtain must connect to one pair of ports on the Mitsubishi Electric BC Controller The exception to this is the VRF PHV2000R DXE HO air curtain that requires 2 pairs of ports on the BC Controller to achieve the correct output Do not combine pipework from two or more air curtains together into one set of pipework and then connect this to one pair of ports NB A maximum P140 Index is possible from 1 pair of ports contact Mitsubishi Electric 9901037 2 Page 13 of 33 zz To gain access inside the Air Curtain To gain access for connection of the electrical supply controls wiring and to work on the unit during commissioning it is necessary to remove the grille core of the recessed grille Remove the grile core from the grille frame by unfastening the two conical bolts fitted at each end of the grille cor
21. al and controls cables and in accordance with the Instructions that come with the Mitsubishi Electric City Multi equipment This work must only be undertaken by a Mitsubishi Electric approved Contractor Refrigerant installation pipework sizes need to be as follows Discharge Line ere Air Curtain Liquid Lin VRF PHV1000R DXE HO in VRF PHV1500R DXE LO cA in VRF PHV2000R DXE LO VRF PHV2000R DXE HO in NOTE Contact Mitsubishi Electric for MT EE lengths numbers of fittings etc The installation must be done in accordance with the Mitsubishi Electric Service Manual It is intended that refrigerant pipe connections to the air curtain are made using brazed joints and these must be carried out in a professional and safe manner If installation pipe sizes for the discharge gas line and liquid line are different from the pipe connection sizes on the air curtain suitable pipe reducers must be used for the connection R410A refrigerant systems can operate at pressures up to 610 psi c 42 Bar These brazed joints may well be located in a public area and a weakness leading to an explosion could be extremely dangerous The air curtain with its coil is manufactured in accordance with the Pressure Equipment Directive and the installation must be carried out to a good standard of workmanship Use a heat sink on the copper pipes when brazing to reduce the transfer of heat to the inside of the air curtain where sensitive components are located M
22. ally heating or cooling as required FAN Mode Fan only no heating or cooling Press the Mode Button on the Remote Controller until FAN appears on the display COOL Mode only if a condensate disposal system is fitted Press the Mode Button on the Remote Controller until COOL appears on the display Adjust the target temperature using the A or V TEMP Button between 20 C and 14 C minimum Allow time for the air stream to chill Do not necessarily use the lowest target temperature possible as this uses a lot more energy and carbon resources The temperature of the air returning to the air curtain is constantly displayed on screen 9901037 2 Page 27 of 33 SERVICING THE HEAT PUMP AIR CURTAIN z Vacuum Clean the Air Inlet Grilles Filters Weekly or when the Filter Dirty Indicator shows PERMANENT RED With the air curtain switched OFF a vacuum cleaner with an extension tube and brush attachment at its end should be used to clean the face of the air inlet grille and the filter at the back of the grille This is important to minimise the build up of dust and lint on the air filter which will affect the performance of the air curtain This is a simple service task that can be carried out by the Cleaner or Janitor on a weekly basis from floor level without having to access the air curtain at high level This should be done weekly as a regular service task and or when the Filter Dirty Indicator BNN shows permanent red B OONNNNM AA O
23. atly against the cut out in the ceiling Tighten each M6 bolt in place locking the grille frame in the correct position up against the underside of the finished ceiling The grille core will now be hanging down on its safety cords exposing all the components up inside the air curtain Within the air curtain there are sliding air separator plates two on the PHV2000 and one on the PHV1500 and PHV1000 These need to be adjusted up or down to stop the discharge air re circulating back into the air curtain Release the M6 bolts at each end of the plate extend the sliding plate down so it will just touch the topside of the grille along its whole length when the grille core is fitted and tighten the bolts see photo and Figure 1 It is necessary to temporarily fit the grille core to gauge the required height of the air separator plate s Re fit the grille core by locating each spring loaded pin in its locating hole push against the spring loaded pins so the fixed pins at the other side of the grille core locate in their fixing holes in the frame Tighten and secure the conical bolts fitted at each end of the grille core to lock it in position Note Access for electrical connections and all servicing is by removing the grille core Once work on the ceiling is finished remove the protective plastic film from the recessed grille frame 9901037 2 Page 12 of 33 Refrigerant Pipework This must be carried out before connection of any electric
24. d on the environment Two alternative filter indicator schedules are available and can be selected by changing the jumper position marked 1 2 or 3 on the Filter Indicator pcb Filter Indicator Schedul Double ECCE Half Filter Indicator Schedule ve quency Default QUERY Inlet grille vacuum interval 120 hrs 240 hrs Filter service interval 240 hrs 480 hrs 960 hrs 9901037 2 Page 25 of 33 To access the Filter Indicator pcb to change jumper position Switch off the electrical power to the Heat Pump Air Curtain Remove the recessed grille core from the air curtain see To gain access inside the Air Curtain Page 14 Unfasten the two screws as indicated The Filter Indicator pcb is now accessible to change the jumper position Once the filter indicator pcb jumper has been re positioned re fit the filter indicator and replace the recessed grille core m Hand over to End User Before leaving site it is important that there is a Hand Over Meeting to hand over the heat pump system and air curtain installation to the end user or their representative This should include a full and clear explanation of how the system operates and a demonstration showing the air curtain running Be sure to explain the Filter Indicator Schedule that the air inlet grille must be regularly vacuum cleaned and the unit serviced at regular intervals If the air curtain is to be operated under manual control it is important that the
25. e using an 8mm spanner Then push the grille core sideways against the spring loaded pins on one side and the grille core with filter now comes clear of its frame Note The grille core with filter attached will still be tethered to the frame via safety cords and will hang down on these cords 3 Electrical Supply to the Air Curtain This must be carried out AFTER the connection of the refrigerant pipework All electrical wiring and connections MUST be carried out by a competent qualified electrician in accordance with the latest edition of the IEE wiring regulations and or local statutory regulations see also Wiring Diagrams on Pages 16 and 17 e A local isolator having a contact separation of at least 3mm on all poles must be fitted in the electrical supply to the air curtain and located in an accessible position adjacent to the unit 3 phase if defrost electric heaters are required 1 phase if defrost electric heaters are not required e The appliance must be connected using cables having an appropriate temperature rating heat resistant e Ensure that the supply cables circuit breakers and other electrical installation equipment are correctly sized for the air curtain being installed See Table overleaf e A 20mm size cable gland or conduit connector should be used for the Electrical Supply into the air curtain e This appliance must be Earthed 9901037 2 Page 14 of 33 400V 3ph 50Hz It 230V 1ph 50Hz if defrost electric hea
26. e would then flood out of the drain tray It may therefore be considered prudent to install a condensate disposal system even if it is intended that the unit should only be used in HEAT or FAN mode If a Building Management System BMS or Centralised Controller is to be used for control of the air curtain please contact Mitsubishi Electric for more details The air curtain is designed only for use with a Mitsubishi Electric City Multi VRF system for use on R410A The complete Thermoscreens Mitsubishi Electric heat pump system including fridge pipework wiring controls etc must be installed only by an approved Mitsubishi Electric refrigeration contractor The air curtain is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety High Output HO and Low Output LO in this document refers to the heat pump heating or cooling capacity of the Air Curtain not to any electrical rating HO air curtains have a 3 row coil LO air curtains have a 2 row coil These instructions must be read in conjunction with the Mitsubishi Electric instructions that come with other components of the heat pump system e g Compressor Unit BC Controller PAR 21MAA Remote Controller BMS System Centralised Controller etc They should be kept by
27. end user understands how the Mitsubishi Electric PAR 21MAA Remote Controller and 3 Speed Fan Switch operate That the PAR 21MAA Remote Controller has been locked so only the ON Off button functions and the air curtain operates in AUTO mode with a fixed target temperature of 24 C If a condensate disposal system has not been fitted it is vital they understand that the air curtain must not be run in COOL or AUTO mode and that the PAR 21MAA Remote Controller has been locked so only the ON Off button functions and the air curtain operates only in HEAT mode with a fixed target temperature of 24 C If the air curtain is to be operated under the control of a BMS System or Centralised Controller explain all the settings and demonstrate the operation of the system If a condensate disposal system has not been fitted it is vital they understand that the air curtain must not be run in COOL or AUTO mode that it must only be operated in HEAT or FAN mode If a condensate disposal system has been fitted and they are going to run the air curtain in COOL mode not just AUTO mode explain that the target temperature should be adjusted to a comfortable level of cooling not necessarily to the lowest target temperature possible as this uses a lot more energy and carbon resources Ensure that all instructions and manuals are handed to the end user or their representative 9901037 2 Page 26 of 33 USER INSTRUCTIONS FOR THE AIR CURTAIN For manual control using a
28. into CN31 on pump alarm system alarm terminals which must PAC AH pcb open circuit alarm and stops unit be volt free open cct alarm 9901037 2 Page 18 of 33 Remote 3 Speed Fan Switch A remote 3 speed fan switch is supplied with the air curtain so the end user can remotely select High Medium or Low fan speeds to suit the local conditions The 3 Speed Fan Switch should be mounted on a wall with the Mitsubishi Electric PAR 21MAA Remote Controller if used so the end user will then have On Off temperature control and fan speed control all from one location The 3 speed fan switch is wired to terminals FAN HIGH MED and LOW in the Air Curtain using 230v mains rated 4 core double insulated cable of size 0 75mmY If the remote 3 Speed fan switch is not to be used a permanent wire link must be fitted across the fan terminals in the air curtain or the fans will not operate when the system is started This will result in an error message from the compressor unit after a time The picture opposite shows a wire link fitted across terminals FAN and MED and the air curtain would operate at Medium Fan Speed whenever the heat pump system is switched on Note Fan speed selection using the PAR 21MAA Remote Controller is not available The fan speed control logic within the PAC AH AHU Controller is not suitable for the operation of an air curtain and so is not used The finished wiring to the air curtain will be as shown in the
29. m i E investigate possible cause of internal wiring or controls fault Air curtain has been running for less SR Give system sufficient time to than 20 minutes and is still warming up Ur reach operating condition or cooling down Air curtain is set to Fan Only on PAR 21MAA Remote Controller BMS System or Centralised Controller Check schedule on Controller and amend if necessary Adjust the target temperature on the BMS System Centralised Controller or PAR 21MAA Remote Controller Select the correct mode for the Target temperature is set incorrectly i e too low for heating or too high for cooling Air curtain discharge air stream is not heating or cooling when required conditions on the BMS oystem Centralised Controller or the PAR 21MAA Remote Controller RU 4 Rectify alarm circuit which Condensate Alarm circuit is open circuit un Moor must be closed circuit for air and air curtain will not COOL curtain to operate in cooling Service air curtain as Air Curtain filters and or coil is dirty described in Section The operating mode is set incorrectly i e set on COOL when heating is required Servicing Pages 28 to 30 Error Code 2502 or 2503 indicating Inspect air curtain condensate Mitsubishi condensate alarm from condensate tray and condensate pump Electric pump alarm system service or repair if necessary system is Refer to Mitsubishi Electric indicating an A variety of error codes
30. n cooling at the same time The City Multi Y Series Heat Pump Air Curtain system consists of e One or more Thermoscreens VRF PHVR Heat Pump heating amp cooling Air Curtains e A Mitsubishi Electric PAC AH M G AHU Controller or PAC AH M H AHU Controller one for each air curtain e A Mitsubishi Electric PAR 21MAA Remote Controller one for each AHU Controller e One or more Mitsubishi Electric City Multi Y WY Series Compressor Unit e Mitsubishi Electric Indoor Unit s NB Can be used on a full air curtain basis if required up to 100 diversity e Mitsubishi Electric BMS System or Centralised Controller if required supplied by Thermoscreens Ltd supplied by others 9901037 2 Page 2 of 33 City Multi R2 WR2 Series Heat Pump Air Curtain System City Multi R2 WR2 Series Heat Recovery Heat Pump Air Curtain Schematic BC Controller Darrnanar ala el ri RFQ CIIAN l rermanen rical su ppIy i l A y I Rar i i PAC AH AHU gt PAC AH AHU Controller Controller X LEV s Defrost electric heaters if used I I Be N l Lensa l A l 1 per air l curtain Fan q mE a IDefrost signal Cond alarm MN GM N e l Mitsubishi Electric I PAR 24MAA Compressor Unit Remote p E3 remote 3 Speed eege controller qnm Fan Switch BE i i Kat Mitsubishi Electric BMS Control Indoor Units Refrigeration pipework
31. ode see text for more information The following optional equipment is also available for the air curtain Fan Speed Controller for low speeds For your records Date of urchase eee ees Place of burchaee enm Serial Number For warranty purposes proof of purchase is necessary so please keep a copy of your invoice 9901037 2 Page 8 of 33 INSTALLATION OF THE HEAT PUMP AIR CURTAIN The air curtain is designed to be recessed within ceiling voids or bulkheads within a building and located horizontally over a doorway It must not be installed outside of the building SG Location The air curtain must be mounted so the recessed grille is between 1 8m minimum and 3 5m maximum above floor level and situated as close to the doorway as possible The Air Discharge section of the recessed grille must be nearest to the doorway and the Air Inlet section furthest from the doorway Beware of doorway top edges structural beams door opening closure devices etc which may interfere with the air stream and affect the location of the unit The air curtain must be installed level or condensate may leak out particularly if it tilts down at the left hand side looking out of the doorway from inside It is better to tilt down slightly at the right hand side as the drain tray spout is this side DOORWAY Ensure there will be adequate clear space above the top of the unit within the ceiling void to safely allow for pipework brazing operati
32. ons The PHVR Recessed Heat Pump air curtain has a rectangular air ventilation hole with Void Filter on one side of the unit see photo of unit on Page 7 This air ventilation hole will be inside the ceiling void once the air curtain is installed and air from the void needs to enter it for the correct operation of the unit There must be a clearance gap of 80mm minimum between this ventilation hole and any obstruction bulkhead within the ceiling void to allow ventilation air from the void to easily enter the air curtain Furthermore the ceiling void must be sufficiently large and freely ventilated so there will be an adequate supply of ventilation air m hr to the unit see table below If the ceiling void is enclosed around the air curtain it will need an air ventilation grille of effective free area cm as given in the table below and an adequate air path within the void for air to enter the rectangular air ventilation hole Required air flow within Effective free area of ventilation grille ceiling void m hr for an enclosed ceiling void cm 9901037 2 Page 9 of 33 CG Ceiling Suspension Make the cut out in the ceiling to the dimensions given in Figure 1 being as accurate as possible The air curtain can be manoeuvred straight up through the M10 ceiling cut out Alternatively the ceiling can be fitted threaded after the air curtain is installed Bear in mind it will be necessary to carry out pipework brazing operations above the
33. photo adjacent wiring is shown with a 3 phase electrical supply for enabled defrost heaters Note the use of 20mm conduit with thermistor sensors and low voltage cables routed in a separate conduit to that used for mains rated cables m PAR 21MAA Remote Controller If the air curtain is to be manually controlled by the end user a Mitsubishi Electric PAR 21MAA remote controller not supplied by Thermoscreens must be supplied and fitted by the installer This is wired to the PAC AH AHU Controller using 2 core cable Refer to the Mitsubishi Electric instructions that come with the PAR 21MAA remote controller for installation and wiring of the controller A PAR 21MAA Remote Controller is also required for commissioning purposes and if using AUTO mode with a BMS System or Centralised Controller u M NET Communications Cable The M NET communications cable is wired to the PAC AH AHU Controller in accordance with Mitsubishi Electric instructions Avoid isolators in the communications cables as this can lead to transmission problems 9901037 2 Page 19 of 33 u Condensate Disposal System If it is intended to use the air curtain in cooling mode a condensate disposal system is required The air curtain is supplied with a 1m length of 12mm bore plastic hose ready fitted to the outlet spout of the drain tray The plastic hose can be found curled up inside the air curtain at the right hand side of the unit There are two condensate outlet
34. r to ensure that the building fixing points and suspension system used are suitable for the air curtain being installed 9901037 2 Page 10 of 33 NIVLYND HIV dINNd LV3H HAHd JO SNOISN3MIG I 20117 E padund esou eyesuepuoo 10 ajo c E cc uonoeuuo jueJeDujeM z i au pinbr SS uonoeuuo 1ueJeBujey P4 Sec JOH y Grt Gtr Gt uu uipIM Bue ur Ea O X 7 d q P e GEZ Geo SSL uu uibue1 MO MI sajoy po doup Ije esf e SHUN ulz UIg JO 9 HUN WY JO v 0622 0691 0611 wu o Leo OA S601 008 V N ww g fie E E Ovzz CH OSLL uuu y Ba Es v 3xa do00cAHd 3Xd Y00SLAHd 3Xd H000LAHd WW g BE g 8 p eS Pi V mm sje u DUUIAA IOIDUOC Su pue jddns eon MP L B 9 g TA a uuc9 orp l y 13431 9NI TI3O zs P eJuB o do uo AyAe46 asoy ejesuepuoo 104 BJO
35. riate position If a condensate pump is being used see the manufacturers instructions that come with the pump for further information The 230v AC single phase electrical supply to operate a condensate pump should come from the air curtain see wiring diagram For a condensate pump with cooling mode start and pump overrun as recommended above use Terminals 7 Permanent Live 8 Neutral 9 Earth which provides a permanent 5A fused supply Terminal 1 Switched Live can be used if a Switched Live is required This will energise when the air curtain is operating Heat Fan or Cool and de energise when it is switched off This is also a 5A fused supply 3 Optional Fan Speed Controller An optional fan speed controller is available to provide a greater range to the three fan speeds in the air curtain Three fan speeds are still used but the speeds can be reduced to lower levels than the standard fan motor offers The controller is useful if noise levels are an issue on site as the fan speeds can be reduced accordingly The controller can be fitted to the air curtain retrospectively It does not fit inside the air curtain but comes with 2m cables so it can be hidden remotely from the unit or even inside one of the optional sheet metal covers Separate instructions come with the fan speed controller showing how it is connected to the air curtain and commissioned 9901037 2 Page 21 of 33 COMMISSIONING THE HEAT PUMP AIR CURTAIN Ensure
36. rought onto the market by us in accordance with the relevant safety health and performance requirements of the Machinery If alterations are made to the machinery without prior written permission from us this declaration becomes invalid Designation of Equipment Series Type Relevant EC Council Applied Harmonised Standards Basis of Self Attestation Responsible Person Date Signed 9901037 2 THERMOSCREENS AIR CURTAINS with CITY MULTI SYSTEM VRF PHV1000DXE HO VRF PHV1000RDXE HO VRF PHV1500DXE LO VRF PHV1500RDXE LO VRF PHV1500DXE HO VRF PHVI500RDXE HO VRF PHV2000DXE LO VRF PHV2000R DXE LO VRF PHV2000DXE HO VRF PHV2000RDXE HO the Machinery Directive 2006 42 EC the Low Voltage Directive 73 23 EEC as amended by 93 68 EEC the Electromagnetic Compatibility Directive 89 336 EEC as amended by 91 31 EEC and 93 68 EEC the Pressure Equipment Directive 97 23 EC Machinery EN 292 1 EN 292 2 EN 294 EN 394 EN 414 LVD EN 60335 1 EN 60335 2 30 EN 60335 2 40 EMC EN55011 EN 61000 3 2 EN 61000 3 3 EN 61000 4 2 EN 61000 4 4 EN61000 4 5 EN61000 4 11 EN61000 6 4 PED EN 13134 EN 13133 Quality Assurance to BS EN ISO 9001 2000 B S I Registered Firm Certificate Number FM 85224 Mr M Francis Managing Director Thermoscreens Limited 17 une 2009 iy e emt y F j Page 33 of 33
37. rt after power failure if required PUMY P model SW2 5 ON for AUTO mode PUHY P YHM and PQHY P YHM model SW4 5 ON for AUTO mode SW1 9 and SW1 10 on for Auto Re Start after power failure 9901037 2 Page 22 of 33 SG Mitsubishi Electric PAC AH AHU Controller Remove the access covers of the PAC AH AHU Controller and check that the dip switch settings are correct for the controller These need to be set as follows VRF PHV1000DXE HO een ew oe gt mr a oe Pio an VRF PHV1500DXE HO Black rectangle indicates VRF PHV1500DXE LO VRF PHV2000DXE LO VRF PHV2000DXE HO N moveable head of dip switch ie PE e e m EE These settings are the same for DAC AH MG and DAC AH MH AHU Controllers Starting the System Carry out a final inspection to ensure that all wiring is in accordance with the wiring diagram on Page 16 for a PAC AH M G or Page 17 for a for PAC AH M H and that all connections have been properly made Ensure that the refrigerant system is complete there are no leaks and there is sufficient charge of refrigerant RA10A Switch on the electrical supply to the compressor unit and other City Multi system components Wait 30 seconds and switch on the electrical supply to the air curtain at the local isolator The system will boot up and when the screen on the PAR 21MAA Remote Controller becomes active it will repeat the message PLEASE WAIT After several minutes when the PLEASE WAIT message has stopped the system is re
38. sed auxiliary Y terminal 14NO as shown in the adjacent picture or into a suitable terminal block NB Defrost does not occur with WY and WR2 systems so the defrost cycle electric heaters should always be disconnected on these systems 9901037 2 Page 15 of 33 191011409 NHY D IW HV 9Vd Ulm ueno ary dung 19H YAHd SYA WVHOVIG ONIYIM ZHOS UAT ADEZ JO ZHOS UdE A00t HUTT J00pinO Joy Ajddng e214323 3 It l aja NE NE NM NEM mm mm mm mm mm pm mm mm mm 19D NIICIS1 3 ZH0S UdE A00t eseud Jed viet 000ZAHd JN eseud Jed viet OOSTAHd JA aseyd Jed yg OOOTAHd JUN SUeJ pue SJ93eaH 21329J 3 1s0JJeq 104 Ajddng j e211323 3 e201 OPTIONAL LOW SPEED CONTROLLER HIuv3 vUN umoys peedsg ue uunipelw U23IMS uey peeds e 6uisn 0u H 1010 DINTI Xd000ZAHd YA 404 vi X0A00STAHd JHA 404 V8 T X0A000TAHd JHA 495 VE T ZHOS UAT AOEZ U9U1 S T1 p p u Uday JOU Je 7 pue Zi ONVT euruJe3 Aveyixne ul J9Jes 8JIM 3 8UILUJI9 pue zv WO 9JIM ajdind 3 euuoosip paJuinbaJ Jou se sjuawa 3 6uneaH 213293 1501490 1I MA6 MIO EX FUN ue MIS L MAIS ZX dun Huet MAGS 7 MASTXE PUN WT 6 JeuluaL g eulula 1 seuun 118 3e SA JAN 3ueueuuag Z eul JO Bunejado si ulen 11e uauM A UO BAIT JAN p9U21IMS T JeuruJe y asn duung e3esuepuo Joy
39. ters are required if defrost electric heaters are not used Rated Electrical Rated Current per Rated Electrical A EUR Power Input kW phase A Power Input kw Rated Current A Air Curtain If the defrost electric heaters are not to be used they can be disabled by disconnecting the neutral to the contactor coil inside the air curtain see below and wiring diagrams on Pages 16 amp 17 Note If the defrost electric heaters are disconnected discharge air temperatures could be very cold approximately 6 C Defrost times could also be extended particularly with the R2 Series System Fie 9 NW i L2 ia s Sa S KL gi 4 e i wi E q 4 T mmi 71 Cen The photo above shows the completed The photo above shows the completed wiring to terminals L1 L2 L3 N and wiring to terminals L1 N and Earth Earth for a 3 phase electrical supply for a single phase electrical supply 400v 3ph 50Hz if defrost electric 230v 1ph 50Hz if defrost electric heaters are used heaters are not used NB Electric heaters must be disabled for 1 phase Do not use cable size of more than 2 5mm or connecting the cable is difficult See also wiring diagram on page 16 or page 17 If the defrost electric heaters are to be disabled this can be done by disconnecting the purple neutral wire from terminal A2 on the contactor inside the air curtain The disconnected purple wire should be terminated safely into unu
40. th different size LEV s and number of LEVs so they need to be matched to the air curtain The table shows the AHU Controller to be selected and performance data for the air curtain Air Curtain No Off Pump Output kw Volume PAC AH125M G Type P632411X01 Or 8 1 PAC AH125M H PAC AH125M G Type P632411X01 Or 10 6 PAC AH125M H PAC AH140M G Type P632414X01 Or 15 1 13 6 PAC AH140M H PAC AH140M G Type P632414X01 or 16 4 14 8 PAC AH140M H PAC AH250M G Type P632411X01 or 21 4 19 3 PAC AH250M H Maximum heat pump output refers to the heating or cooling output from the air curtain air stream Figures are derived from laboratory testing with reference to test standard EN14511 They are with the air curtain operating at high fan speed outdoor air temperature 7 6 C db wb indoor air temperature 20 C db for heating outdoor air temperature 35 27 C db wb indoor air temperature 27 C db for cooling Contact Mitsubishi Electric for performance at other outdoor and indoor conditions The air curtain normally operates under automatic temperature control set on the PAR 21MAA remote controller and can also run at part load The following City Multi compressor units can be connected For Y WY Series systems PUHY E P200 1250Y S HM A PQHY P200 600Y S HM A PUMY P100 140V Y HMB PUHY HP200 500Y S HM A For R2 WR2 Series systems PURY E P200 800Y S HM A PQRY P200 600Y S HM A 9901037 2 Page 4 of
41. that are wired on site to the PAC AH AHU Controller and the Thermoscreens Air Curtain that provide control for the operation of the unit These e Start Stop of air curtain fans e Operation of LEV s for control of heating or cooling output e hermistor sensors e PAR 21MAA Remote Controller for end user manual control if used e On Off of electric heaters inside the air curtain during system defrost if used e Condensate alarm derived from condensate pump alarm sensor if used e M Net communications link to the Mitsubishi Electric Compressor Unit see also wiring diagrams The Thermoscreens Air Curtain is supplied with an integral condensate drain tray to enable the air curtain to be used in cooling mode during warm weather if so desired If it is intended to use the air curtain in cooling mode a condensate drain system is required It is possible to gravity drain condensate from these recessed air curtains via the lower condensate outlet hole which is c 40mm above the top surface of the ceiling within the ceiling void Means of condensate disposal must then be provided within the ceiling void Alternatively a suitable condensate pump not supplied by Thermoscreens can be supplied and fitted by the installer to remove condensate directly from the unit The condensate pump must be of sufficient capacity see Page 20 and if located above the drain tray it should be self priming and capable of providing the appropriate suction head so the pump
42. that the condensate pump has the facility so it only operates when the air curtain is in cooling mode by detection of water in the drain tray or by detecting a cooling differential in the airflow It should also have a pump overrun to empty the drain tray as much as possible when the air curtain is switched off The plastic hose should be pushed through either of the two condensate outlet holes after removing the plug and connected to the condensate pump using the adapter supplied with the pump It may be necessary to extend the hose if the pump is remotely located Whether a gravity drain system is used to remove the condensate or a condensate pump there should be an alarm system with appropriate sensor fitted in the drain tray that will give a volt free signal open circuit alarm This will stop the air curtain cooling if the 9901037 2 Page 20 of 33 condensate drain is in danger of flooding bringing up error code 2502 or 2503 and the air curtain fans will continue to operate Other indoor units on the same City Multi system are unaffected if the air curtain condensate alarm occurs There is a plastic fixing bracket with 8mm diameter hole attached to the drain tray inside the air curtain so a condensate sensor can be fixed in the tray by the installer Remove the drain tray at one end to gain better access to the plastic fixing bracket Enlarge the hole if necessary to suit the type of sensor used so it is located in the tray at the approp
43. the building facilities manager for future reference 9901037 2 Page 6 of 33 UNPACKING THE HEAT PUMP AIR CURTAIN The following items are supplied and packaged within the Thermoscreens air curtain box VRF Recessed Heat Pump Air Curtain Remote 3 Speed Fan Switch Air Discharge The Recessed Grille is packed in a separate box but comes with the air curtain Recessed Grille with Filter If anything is missing or damaged please contact your place of purchase immediately ZA Air Discharge The Mitsubishi Electric PAC AH M G AHU Controller or PAC AH M H AHU Controller comes in its original Mitsubishi Electric box It is delivered with the Thermoscreens air curtain and Recessed grille It is factory pre wired as much as possible to reduce installation time on site PAC AH M G or M H AHU Controller Check with the cross reference labels on the Thermoscreens air curtain box and the Mitsubishi Electric AHU Controller box that the correct AHU Controller is matched with the correct air curtain Other components for the heat pump system are as described above on the System ochematics on pages 2 and 3 9901037 2 Page 7 of 33 The Installer will also need to supply and install the following PAR 21 MAA Remote Controller Condensate Disposal System and Condensate Pump if non gravity drain If Air Curtain is to be manually controlled If Air Curtain is to be operated in COOL or also needed for commissioning AUTO m
44. trical connections and terminals within the unit are tight and that crimp connections have not become loose After all the components have been re fitted switch on the electrical supplies and fully function test the air curtain to ensure correct operation see Section Commissioning Check the condensate pump operates if fitted Reset the Filter Dirty Indicator after the service by pressing the Reset Button for at least 5 seconds even if the indicator has not ao gone flashing red and hand back the unit to the end user M KR A mmm o fm m nn TZ I PR 9901037 2 Page 30 of 33 SS Fault Conditions If the Thermoscreens Heat Pump Air Curtain System does not operate as expected refer to the fault finding table below Symptom Possible Cause Action Required Electrical power is not switched on to the Mitsubishi Electric City Multi system and at the local electrical isolator next to the Thermoscreens Air Curtain Switch on power to all components in the heat pump system and wait 30 seconds Switch on air curtain using the PAR 21MAA Remote Controller BMS System or Centralised Controller Air curtain Air curtain is not switched On fans do not operate Air Curtain fans are not wired to operate with either a 3 Speed Fan Switch or a wire link on fan terminals in air curtain Wire in 3 Speed Fan Switch or wire link see wiring diagram Problem with air curtain fan motor s or elen Weil diagra
45. y and that all condensate was collected by the removal system To conserve energy and carbon resources it is recommended to set up the BMS System Centralised Controller or PAR 21MAA Remote Controller so it can operate in AUTO Mode at a target temperature of 24 C This is the normal mode of operation for the heat pump air curtain and it should run in this set up with no further adjustments automatically heating or cooling as required If the end user is to operate the air curtain with a PAR 21MAA Remote Controller set up the No 1 locking function on the controller so they can only switch the air curtain ON or OFF with no control of mode or target temperatures See user instructions for the Mitsubishi Electric PAR 21MAA Remote Controller BEWARE It is possible for the air curtain to go into cooling mode on a warm day if the BMS System Centralised Controller or PAR 21MAA Remote Controller is set in AUTO mode as described above A condensate disposal system must therefore be fitted if the air curtain is set in AUTO mode If it is intended that the air curtain should only operate in heating mode never in cooling mode the PAR 21MAA Remote Controller must be set to HEAT mode with an appropriate heating target temperature say 24 C and locked so only the ON OFF function on the Remote Controller works If it is to be operated from a BMS System or Centralised Controller this should be configured such that the air curtain can only operate in HEAT or F
Download Pdf Manuals
Related Search
Related Contents
AS-200 ADVERTISING SCAN HELIX BOARD 12 FIREWIRE MKII - access Manual de referencia Autodesk AutoSketch 10, Commercial Full, EN SINEAX V624, Convertisseur de mesure programmable pour Télécharger - Apollo Valves S-BIOMOUSE - SMS Ingenierie PENDULO - Salquisa Samsung Samsung GT-E2121 Lietotāja rokasgrāmata Copyright © All rights reserved.