Home

Tender Document () - Government of Nova Scotia

image

Contents

1. 15 1 Provincial Legislation 15 1 1 Hospitals Act is an Act relating to Hospitals and in particular Section 71 1 of the Hospitals Act provides that the hospital records and particulars of patients are confidential and shall not be made available to any person or agency except with the consent or authorization of the patient concerned Section 71 of the Hospitals Act prevails over the disclosure provisions of the FOIPOP Act such that the availability of patient records and particulars falls under the Hospitals Act and not under the FOIPOP Act The Personal Health Information Act PHIA is an Act respecting the collection use disclosure and retention of personal health information The purpose of this Act is to govern the collection use disclosure retention disposal and destruction of personal health information in a manner that recognizes both the right of individuals to protect their personal health information and the need of custodians to collect use and disclose personal health information to provide support and manage health care Page 25 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 15 1 3 PIDPA Nova Scotia s Personal Information International Disclosure Protection Act was created to protect the personal information of Nova Scotians from being disclosed outside Canada PUDPA affects Nova Scotian public bodies and public body service providers 15 1 4 FOIPOP Freedom o
2. STANDARDS This installation and the equipment proposed must meet the following standards The current edition of the CSA standard Canadian Electrical Code C22 1 The equipment shall be CSA approved meeting all the requirements set forth in the following CSA Medical standards CAN CSA C22 2 No 601 1 Medical Electrical Equipment Part 1 General Requirements for Safety respecting latest revisions interpretations amendments supplements amp applicable collaterals 12 1 This equipment system shall be in compliance with CSA Standard CAN CSA C22 2 No 601 1 2 Medical Electrical Equipment Part 2 Collateral Standard Electromagnetic Compatibility Requirements and Tests The vendor MUST provide to Biomedical a copy of documented proof of testing and its results if requested The system and all its components MUST be labelled as CSA approved to the medical standards referenced above Any system equipment proposed that is not approved to the medical standards indicated above and not properly labelled as such will not be accepted until such time that this is performed and reviewed to the satisfaction of the Biomedical Engineering Department Any system equipment that requires special acceptance testing to be certified to CSA standards must have had this carried out prior to shipment to the Health Centre by an agency that has been accredited with the Standards Council of Canada Copies of any inspection reports for this special inspecti
3. to be delivered to Finance in a separate sealed envelope clearly identified as pricing information Additional Terms amp Conditions Successful Vendor must agree to comply with and be bound by IWK General Terms and Conditions for Purchase Orders in Appendix 1 Governing Laws This agreement and all items pertaining to it shall be governed and interpreted in accordance with the laws of the province of Nova Scotia Page 5 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS e Vendor Questions Any questions regarding this RFP must be directed through the RFP Coordinator who has been specified in this document The RFP Coordinator will direct the vendor to the most appropriate contact Information offered from sources other than the direction given by the RFP coordinator is not official and may be inaccurate ALL vendor questions must be submitted to the RFP Coordinator no later than the date specified in the Acquisition Schedule that follows After this date the RFP Coordinator will post the questions amp Answers on the following website for all vendors to see https www gov ns ca tenders Closing Date The RFP Coordinator must receive all proposals at the address specified no later than 3 00 p m local time on the date identified in the acquisition schedule Failure to submit a proposal by the deadline specified will result in the rejection of the vendor s proposal Submission of the Pro
4. definition phone e mail etc organization charts would be helpful in addition Required Response Maximum amp typical response amp delivery time periods else negotiated penalty gt Minimum phone response within 60 minutes Mandatory Actual guaranteed phone response time mins IWK Health Centre CRRT RFP August 25 2014 Final Page 19 of 44 IWK Health Centre Hfx NS Typical parts sources amp ph factory service support e g parts amp factory service support depots Required Response sales amp applications support personnel source Required Response Actual guaranteed phone response time mins service support personnel source Required Response Location of service support personnel Indicate who will be responsible for shipping costs for repairs Clarify if specialized shipping containers are required Required Response Supply Delivery amp Installation Vendors must describe the various initial supply schedule data including expected date of delivery amp any terms of the quote Please reference Required Response This is a supply amp install acquisition Bidders must furnish the equipment amp associated consumables etc Bidders are also required to perform all installation set up calibration amp testing required for the equipment to be used except where indicated Required Response The succes
5. details Required Response Haemodialysis HD High Flux Dialysis HFD High Volume Hemofiltration HVHF Intermittent Haemodialysis IHD Intermittent Hemofiltration HD Plasma adsorption perfusion PAP Therapeutic Plasma Exchange PEX Slow Low Efficient Daily Dialysis SLEDD Pre Post Dilution amp Anticoagulant Pumps Specific System Performance The CRRT systems should be proven to be exhibit the following core functionality or provide the functional control equivalent Please provide the fluid balance accuracy N B shall have a minimum accuracy of 10 Mandatory Please detail upgrade capacity including software updates features and associated costs Required Response Please detail all Data Storage amp Logging options including costs N B Includes data cards centralized storage and Monitoring Required Response Please detail the Low Flow Rates associated with each type of treatment minimum maximum Rate Required Response Please detail the High Flow Rates associated with each type of treatment Minimum Maximum Rate Required Response Does the system have limitations with respect to low flow rates based on internal catheter diameter flow rate pressure and therapy type If so please provide this information and detail the impact with respect to treating pediatric patients Required Response Please detail
6. hard copy and one CD DVD copy of the service manual for each system amp all major components proposed The service manual must contain but not limited to Mechanical amp electronic schematics Electronic component layouts Mechanical component breakdown Complete electronic electrical amp mechanical parts list Circuit descriptions amp theory of operation Calibration PM procedures amp schedules Troubleshooting procedures Equipment specifications Installation requirements manuals System wiring diagrams Error code listing w descriptions problems amp how to access these Codes Passwords to access all service and configuration menus and functions Note Service manual should be the same service manual as delivered to field service technicians Service manuals should also contain an updated list of service bulletins service manual updates and PM procedures 22 2 Operators Manuals The following departments must receive a hard copy of the operator s manual s for each system purchased except where noted 22 2 1 Biomedical Engineering 22 2 2 Require a hard copy for each of the systems proposed 22 2 3 Require a CD DVD copy for each of the systems proposed 22 2 4 Information Technology IT Require any documentation that relates to networking interfacing software packages etc Page 35 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 23 SERVICE CAPABILITIES 23
7. the CRRT system must be proven to exhibit the functionality control described in this specification by clinical trial prior to endorsement for issue of contract Systems not averaging at least a Good rating with medical and nursing staff during clinical trials may be Mandatory summarily dismissed by IWK at its sole discretion Further a rating of Fail by one of the medical staff for any score sheet entry will result in that bid being reviewed with the potential for of being summarily dismissed Specific Requirements amp Functionality The CRRT systems must be proven to be exhibit the following core functionality or provide the functional control equivalent Integrated Heparin Pump Mandatory Slow Continuous Ultra filtration SCUF Mandatory Continuous Venovenous Hemodiafiltration Mandat CVVHDF anuatory Continuous Venovenous Haemodialysis Mandat CVVHD POSAR Continuous Venovenous Hemofiltration CVVH Mandatory Blood Leak Detector Mandatory Blood Air Bubble Detector Mandatory Temperature control and monitoring Mandatory Return Line Clamp Mandatory Filter Pressure Sensor Mandatory Access Line Pressure Sensor Mandatory Return Line Pressure Sensor Mandatory Page 11 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS Identify additional functionality provided by the proposed CRRT System Please provide
8. Act and may be required to release information relating to this RFP and or the resultant contract IWK would endeavor to consult the affected proponent s to the extent permitted by law The vendor agrees that it shall not seek information regarding this purchase or any proposals or decisions relating to this purchase by application under the Freedom of Information and Protection of Privacy Act Nova Scotia The vendor acknowledges that all information and records relating to this procurement process may be released to the vendor only at the discretion of the IWK and subject to the procurement process applicable law and confidentiality concerns IWK reserves the right to a cancel the process at any stage b cancel the process at any stage and issue a new RFP for the same or similar deliverables c reject any or all proposals and d reject any and all proposals submitted and to negotiate with the compliant proposal offering the best value in any manner necessary to serve the best interests of IWK Neither the responsive proposal that scores the highest number of rated points nor the one that contains the lowest price will necessarily be accepted or considered the best value proposal The IWK will not pay for the information solicited by any RFP All costs incurred by a vendor in the preparation of a proposal are the responsibility of the vendor The IWK makes no representation or assurance regarding Page 39 of 44 IWK Health Centr
9. General Terms amp Conditions Updated May 31 12 Appendix 2 Manufacturer Disclosure Statement for Medical Device Security MDS2 Appendix 3 Vendor Confidentiality Agreement Appendix 4 User Notification of Hazards Recalls Defect Notices Computer amp Software Viruses Worms and Technical Service Bulletins Page 4 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 2 TERMS amp CONDITIONS These Instructions to Bidders Equipment Requirements and Terms amp Conditions are for the furnishing installation start up calibration and the testing of medical equipment for the IWK Health Centre Courier only address Charter Place Offices 1465 Brenton Street 5 Floor Finance Halifax NS B3J 3T3 hereafter referred to as BUYER or IWK RFP Proposal Evaluations Proposals will be evaluated on the basis of but not limited to 1 price 2 conformance to Equipment Requirements and Terms amp Conditions 3 conformance to Biomedical and Information Technology requirements equipment features specifications performance and reliability 4 vendor experience 5 the experience of users with the equipment and vendors 6 delivery amp installation schedule 7 warranty terms 8 service capabilities 9 user training and support services 10 operating costs and overall responsiveness to this Request for Proposal RFP Criteria Selection The order in which the above selection criteria are listed
10. is not necessarily indicative of their relative importance It is expected that vendors submitting proposals will demonstrate extensive and substantial qualifications capabilities and experience in manufacturing installing and servicing the equipment sought including successful provision of similar goods and services to comparable institutions Vendor Selection The BUYER intends to select a vendor on the basis of proposals received in response to this RFP and any other information it obtains from other sources regarding the equipment and the vendor The BUYER reserves the right to make its final decision independent of any or all of the above factors Independent Servicing The BUYER reserves the right to solicit service contract bids from qualified independent service organizations in the interest of reducing its technical support costs Acceptance Testing The system shall be subject to and must pass acceptance testing performed by the IWK Health Centre Compliance with Applicable Standards The system equipment or device will be tested for compliance with applicable CSA medical standards for electrical safety and manufacturers specifications Pricing All quotations shall be firm for at least 180 days Pricing shall be net of any taxes proposed quoted pricing is to be in Canadian s and Items such as delivery freight costs set up fees in servicing taxes etc are to be shown as separate line items Note All pricing proposals are
11. power system needs ACCEPTANCE TESTING 21 1 The proposed system shall be subject to and must pass acceptance testing performed by the IWK Health Centre The system will be tested for compliance with applicable CSA medical standards for electrical safety and manufacturers specifications The system shall be subject to and must pass acceptance testing performed by IT personnel if applicable Before going live the system shall successfully demonstrate its backup and recovery procedure to resume operation after a disaster As bound by the provincial guidelines for Nova Scotia and Health Canada devices will be checked that they meet the device license and or establishment license requirements as defined and set forth in the Medical Devices regulations stated earlier Any proposals for equipment that do not meet the requirements of these new Medical Devices Regulations or CSA medical standards will not be considered in the tendering process In addition if applicable the physicians from each department have to accept that all the features in the system are fully functioning to their satisfaction Page 34 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 22 DOCUMENTATION Manuals DO NOT have to be included in this RFP submission but must be included if the Health Centre requests an evaluation When the system s is purchased the following documentation must be included 22 1 One 1
12. system provide Onscreen Details Explanation of Alarms and instruction on how to resolve Please provide details Required Response How does the system Manage and prioritize multiple on screen Alarms How are they organized as to prevent overwhelming the user e g Highest Priority First Please provide details Required Response Does the machine clearly identify the most likely cause of an alarm and avoid presenting the user with erroneous potential secondary alarms triggered by the primary alarm event Please provide Details Required Response Please describe any additional Human Factor Design Features used to increase user friendliness usability increase patient safety and reduce the probability of use errors Required Response Engineering amp Safety Requirements Detail any amp all engineering amp safety requirements Include at least Power electrical requirements typical consumption amp isolation Required Response N B Include any requirements for UPS power conditioner etc EMI EMC specifications Required Response Safety requirements amp concerns amp other Required Response IWK Health Centre CRRT RFP August 25 2014 Final Page 13 of 44 IWK Health Centre Hfx NS All equipment must be proven as adequately robust to withstand the rigours of Tertiary care Mandatory intensive care environments Proposed sy
13. 1 The vendor shall provide a description of local and regional factory based service capabilities including the following The number and qualifications of service engineers Their training Their base locations The locations of backup service engineers The location of primary and backup spare parts locations The time for delivery of parts after notification 23 2 The vendor shall indicate the company s response times are to the following Response to service calls placed Service rep on site response PROBLEM NOTIFICATIONS 24 1 The following will be provided for the life of the system 24 1 1 Immediate notification of any alerts affecting any part of the system 24 1 2 Notification of manufacturer s technical service bulletins 24 1 3 Immediate notification of any software or hardware threats viruses worms etc for any other threats to any computer based equipment software that may be used These notifications will automatically be sent directly to Biomedical by a means agreeable to both parties The manufacturer shall arrange for free access to the manufacturer s web site for downloading of any applicable updates software patches corrections etc that are required in maintaining a reliable effective and safe working system All problem notification shall be provided at no additional cost to the Health Centre If the Health Centre should agree to purchase the equipment being proposed then as a condition of sale t
14. IWK Health Centre 5850 5980 University Ave D P O Box 9700 A Halifax Nova Scotia IWK Health Centre Canada B3K 6R8 IWK Health Centre for Children Women amp Families REQUEST FOR PROPOSAL RFP the provision of CONTINUOUS RENAL REPLACEMENT THERAPY CRRT SYSTEMS Issued FRIDAY SEPTEMBER 8 2014 by IWK HEALTH CENTRE HALIFAX N S 5850 5980 University Ave Post Office Box 9700 Halifax Nova Scotia Canada B3K 6R8 TIVK Health Centre http www iwk nshealth ca index cfm IWK Health Centre for Children Women amp Families IWK Health Centre Hfx NS Request for Proposal RFP Continuous Renal Replacement Therapy CRRT Systems Located in Halifax Nova Scotia the IWK Health Centre provides quality care to children youth women and families in the three Maritime Provinces of eastern Canada and beyond The IWK is a tertiary care hospital dedicated to education research family centered care and health promotion The Health Centre has a total of 271 beds consisting of 74 adult beds 76 beds for babies 78 children s beds amp 43 off site residential program beds The Children s Health Program at the IWK has both a pediatric nephrology and intensive care programs that see patients who require different forms of dialysis treatment in both ambulatory and inpatient settings These treatment options are performed on a wide range of pediatric patients infant to late teen Currently most acute dialysis services ar
15. NICAL SERVICE BULLETINS USER NOTIFICATION OF HAZARDS RECALLS DEFECT NOTICES COMPUTER amp SOFTWARE VIRUSES WORMS and TECHNICAL SERVICE BULLETINS IWK Health Centre 5850 5980 University Ave i P O Box 9700 Halifax Nova Scotia MK Health Centre Canada B3k 6R8 Vendor shall automatically notify Biomedical Engineering at the IWK Health Centre of any product hazards recalls defect notices software or hardware viruses worms and any technical service bulletins issued that relate to any of the equipment quoted being manufactured and or delivered to BUYER under the terms of this RFP Any of these notifications shall be made to Biomedical Engineering Department within five 5 days of the earliest announcement in any nation by the manufacturer or device regulatory body This agreement shall remain in effect for the life of the equipment and or system Vendor understands that failure to comply with this requirement may lead to a one 1 year BUYER ban on the purchase of all products from Vendor The undersigned hereby acknowledges that he she and all representatives of his her company will adhere to the above protocol Signature Name Title Date Page 44 of 44 IWK Health Centre CRRT RFP August 25 2014 Final
16. R reserves the right to make their decision independent of any or all of the above factors If an on site clinical evaluation of the equipment is not possible the vendor shall include arrangements for site visits by Health Centre representatives which will include e Three 3 reps from the applicable department e One 1 Biomedical Engineering rep 28 3 The vendor will indicate the reference sites that will be included in these site visits REFERENCES 29 1 IWK may make such investigation as it deems necessary to determine the ability of any Proponent to provide products and services and may utilize the results of such investigation in awarding the Contract 29 1 1 A list of references Canadian References preferred from similar institutions that are presently using the equipment proposed complete with the name and telephone numbers of the contacts for the following must be included with this proposal If proposed equipment is a different configuration specify the difference 29 1 2 Clinical User 29 1 3 In house service representative 29 1 4 IT contacts if applicable PROPOSAL COST 30 1 Proposals are to be F O B Hospital 30 2 Pricing quoted is to be in Canadian funds TERMS OF PAYMENT 31 1 Include the proposed equipment payment terms including any cancellation fees and any alternatives that result in a cost saving to the BUYER 31 2 Include a proposed method for determining price changes if any if a delivery date l
17. Version Mandatory Preferred TCP IP Version 4 Mandatory Wireless Communications Protocol an Mandatory Preferred 802 11 A B G N See Note 3 Mandatory Interoperability Standards amp Protocols Protocol Version Mandatory Preferred HL7 2 X Mandatory HL7 3 0 Supported CCOW 1 5 Preferred Operating System amp Hardware Operating System Windows See Notes 2003 2008 Dell Hp 1 amp 2 See Notes Desktop Windows 7 Dell 1 amp 2 Preferred Platform Make An Mandatory Preferred Intel Server Preferred Application Database Platform Database jaa Mandatory Preferred Intel SQL 2005 Preferred Storage Requirements Mandatory AA Component aa Preferred Provide expected storage needs for this system Include requirements E Mandato for first year as well as expected increases over the next 5 years ry Storage Estimates Storage Technologies Archiving Identify any Data Archiving techniques that are provided with your Capabilities system And or can be applied to your system Security Standards Confidentiality Integrity Availability Identify the type and capacity of storage provided with your system Mandatory Preferred Mandatory Component Consideration Preferred Comply Identify the Authentication Model that your product leverages List also the pass
18. ail All CRRT equipment and supplies disposables must be proven to be certified to all appropriate CSA and recognized standards for dialysis Including but not limited to the CAN CSA 60601 2 16 14 Particular requirements for the basic safety and essential performance of haemodialysis haemodiafiltration and Mandatory CAN CSA 60601 2 16 14 Pass Fail haemofiltration equipment CAN CSA ISO8638 12 CAN CSA ISO 8637 12 etc CAN CSA ISO 13958 11 Page 14 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS Only tentative winning bidders will be asked and required to detail all CSA standards used to design amp test their products including actual Compliance Test detail reports All equipment components require this approval If Required equipment systems are supplied without such Response required certification amp labelling the supplier is responsible for all testing amp modification costs to make the equipment system acceptable by CSA standards All power cords including the plug power bars amp power outlets must be hospital grade amp CSA Mandatory approved Warranty One year full warranty parts plus labour minimum N B A 2 year total warranty for the entire system is preferred The IWK reserves the right to select first from solutions that provide such coverage providing all mandatory requirements are met Labour coverage durat
19. al record e g medical record acc evice identification number c Diagnostic therapeutic e g photo radi jata with identifying characteristics d Open unstructured text entered by devici B oe Maintaining ePHI Can the device a Maintain ePHI temporarily in volatile memory i e until clea on by power off or reset b Store ePHI persistently on local media c Import export ePHI with other systems Mechanisms used for the transmitting importing exporting of ePHI Can the device Display ePHI e g video display ae Generate hardcopy reports or images containing Retrieve ePHI from or record ePHI to removable media e g disk DVD CD ROM tape CF SD card memory stick Transmit receive or import export ePHI via dedicated cable connection e g IEEE 1073 serial port USB FireWire Transmit receive ePHI via a network connection e g LAN WAN VPN intranet Internet Transmit receive ePHI via an integrated wireless connection e g WiFi Bluetooth infrared Other P Page 42 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS APPENDIX 3 VENDOR CONFIDENTIALITY AGREEMENT IWK Health Centre 5850 5980 University Avenue P O Box 9700 Halifax Nova Scotia A B3K 6R8 TWK Health Centre VENDOR Vendor address VENDOR acknowledges during the course of performing it s obligations hereunder VENDOR and their employees officers directors or other Cl
20. by the Health Centre s Biomedical Engineering IT as well as the respective physicians of each department receiving a system or after the first clinical application CONSUMABLE PRODUCTS 27 1 The vendor shall identify all consumable items used with this equipment e g Filters etc and provide guaranteed prices for these items for a period of five 5 years after acceptance of the systems by the BUYER 27 2 Prices for consumable items shall be subject to negotiation with BUYER before contract award under this RFP 27 3 Indicate whether supplies that are to be used with this equipment are to be purchased only from the manufacturer or from other companies as well specify 28 EVALUATION Page 37 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 28 1 The BUYER may select and inviting vendors to do presentations demonstrations evaluations and or clinical on site trials It shall be understood that this decision will be made based upon but not limited to the following price conformance to equipment requirements and terms amp conditions conformance to biomedical amp information technology requirements equipment features specifications vendor experience the experience of other users with the equipment and vendors delivery amp installation schedule warranty terms service capabilities user training and support services operating costs and overall responsiveness to this RFP The BUYE
21. dditional charge to the Health Centre All training is to outline safe practises for handling cleaning amp reprocessing of equipment particularly with a view to potentially contaminated equipment Page 32 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 19 TECHNICAL SERVICE TRAINING amp TOOLS 19 1 The IWK Health Centre s Biomedical Clinical Engineering outside the warranty period provides the majority of in house service on electro medical equipment This is to be supported by the successful proponent Separate factory level technical service training for two staff members from Biomedical Engineering shall be included as an option priced per person including all travel costs The IWK s training shall be comparable to the regular technical training provided to the manufacturer s own technical support staff 19 2 1 The vendor shall include details on the following Program length and format Course location Course content Qualifications of instructors Written materials provided Tuition fee Flight accommodation meals amp ground transportation Service tools documentation etc that may be provided with tuition Detail any amp all specialized maintenance equipment test equipment adapters proprietary tools required to fully maintain the equipment throughout its estimated life cycle This same detail along with the associated pricing or annual license fees is also
22. e CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS the outcome of proposals and specifically reserves the right to terminate the tendering process without consequence or liability All bid materials will become the property of the IWK unless otherwise specified by the vendor The vendor represents and warrants that none of the bid materials infringe any intellectual property rights of third parties The IWK reserves the right to provide clarification on existing requirements contained in any RFP Should additional requirements be identified they will be submitted to all vendors in writing as an addendum to this document References identified in the proposal may be contacted by the IWK to substantiate the proposal s solutions capabilities and reliability as well as proponent performance and overall service Proponents are expected to cooperate fully in helping IWK to verify Proponent claims The successful Proponent will be required to execute a contract in the IWK standard form The Proponent s proposal shall be attached as a schedule and incorporated by reference into this standard form agreement to the extent applicable All proposed services equipment goods furniture as applicable must comply with all relevant laws codes and standards and where appropriate be approved to applicable standards e g CSA standards All vendors and any subcontractors performing work at the IWK must be registered in the Provinc
23. e agenda is to be included in the bid showing equivalency to the regular technical training provided to the manufacturer s own technical staff A 50 discount from published rates will apply for any additional training within 2 years of Mandatory installation All training is to outline safe practises for handling cleaning amp reprocessing of equipment particularly with a view to potentially contaminated equipment Mandatory Maintenance amp Support Page 17 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS Schedules for projected end of production EOP amp end of support EOS life are to be provided for all quoted equipment EOS life is to be greater than or equal to seven 7 years from date of purchase gt N B Equipment purchased that has an EOS date within less than seven 7 years will be subject to remedial action if this EOS date is excluded or incorrect in the response to this tender Mandatory Vendors are to provide ready access to knowledgeable staff for problem solving support during IWK s normal business hours Vendors are to detail any amp all charges associated with service support consultation including both service representative visits amp phone consultations for in house staff Mandatory Vendors are to include upon_product shipment two 2 user s manuals plus one 1 service manual or like documentatio
24. e of Nova Scotia under the Corporations Registration Act or the Partnerships and Business Names Registration Act All prices costs are to be quoted in Canadian dollars and exclusive of any taxes Items such as delivery set up fees in servicing taxes etc are to be shown as separate line items The IWK qualifies for government and educational discounts from various vendors All applicable discounts are to be identified in the price section It is a condition precedent to the IWK s acceptance of any tender that the vendor confirms that they have no outstanding or pending litigation action claim demand or cause of action against the IWK which in any way relates to the subject matter of the RFP or which relates to the supply of goods and services to the IWK Avendor s proposal must be signed by an authorized signing officer of or authorized person for the vendor certifying that all information contained in the proposal is accurate and agreeing to comply with all of the terms conditions and provisions of the RFP All Proponents must provide full disclosure of any and all funding of in kind programs that have been provided to IWK Furthermore all Proponents must disclose the name s of and person s employed at IWK who is under contract or represents the Proponent in any capacity which may be viewed as a conflict of interest Vendors must clearly identify any Third Party software or hardware components if applicable
25. e provided by the Regular Dialysis Unit nursing team incurring on call and overtime charges that are dependent upon minimal staffing The new CRRT model will support both the PICU and the Pediatric Nephrology programs by allowing trained pediatric intensive care nurses to provide CRRT therapy to critically ill PICU inpatients The new model is intended to transfer the responsibility of CRRT done on PICU inpatients to PICU nurses trained in CRRT with an aim of reducing overtime costs increasing the utilization of CRRT in PICU when evidence indicates diagnosis would benefit from its utilization and support timeliness of the service given more nurses will be trained in its implementation and management CRRT is becoming a gold standard in PICU patient care leading to better health outcomes and aligns with our IWK mandate providing tertiary care with continuity of care within the PICU We are requesting proposals for the acquisition of Two 2 Continuous Renal Replacement Therapy CRRT Systems for the Pediatric Intensive Care Department Page 2 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS FOR ALL INTERESTED VENDORS All interested vendors should forward their proposals if they meet the following requirements as outlined in the following required specifications Please forward Four 4 copies of all information which will include Three 3 hard copies and one 1 electronic copy on DVD or CD to the atte
26. ed by these regulations then the vendor must include the current Device License for each piece of equipment indicated in this system 14 1 4 Copies of the licenses for the current year must be included in this proposal Any proposals that DO NOT meet these requirements will not be accepted 14 2 Patient Management Software LU On August 31 2009 the Medical Devices Bureau of Health Canada sent out notices to manufacturers importers and distributors of medical devices software that patient management software is classified as a medical device and is subject to compulsory licensing under the Food and Drugs Act and Medical Devices Regulation Patient management software can fall into one of two classes They are defined as Class I Any patient management software used only for archiving or viewing information or images and not involved in the primary acquisition manipulation and transfer of data is considered a Class medical device Although Class I medical devices do not require a license any manufacturer distributor or importer must have an Establishment License Page 24 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS Class II Patient management software involved in data manipulation data analysis data editing image generation recording of measurements graphing flagging of results or performing calculations is considered a Class II medical device and must have it s own lice
27. erence by the BUYER Provide as many details and information as necessary to avoid unnecessary follow ups and unwanted frustrations with the vendor that may jeopardize the sale L Any mandatory requirement requested by the BUYER in this RFP is an essential need that must be met by the vendor Failure to meet a mandatory requirement may be grounds for disqualification and shall be established by any of the following conditions 1 Vendor states that a mandatory requirement cannot be met 2 Vendor fails to include information necessary to substantiate that a given mandatory requirement has been met 3 A response of will comply is not sufficient 4 Responses must indicate present capability 5 Representations that future developments will satisfy the requirement are not sufficient 6 The vendor presents the information requested by this RFP in a matter inconsistent with instructions stated by any portion of this RFP 7 Customer references or site visits report the vendor s inability to comply with one or more of the mandatory requirements and 8 The vendor fails to include the customer references required 3 2 Second Section Supporting Documentation e The second section of the proposal shall include any brochures references support documentation training schedules Medical device Licenses etc 3 3 Third Section Pricing All pricing proposals are to be delivered in a separate sealed envelope clearly identified as pricing informatio
28. es to the existing equipment in order to keep systems at the same version levels The vendor shall propose optional pricing incentives that may allow forklift upgrades etc to any of the existing systems presently in use The IWK will also entertain any leasing options that may be available from the vendor It shall be understood that proposals submitted to the IWK will be evaluated on the basis of but not limited to the following Proposals will be evaluated on the basis of but not limited to 1 price 2 conformance to Equipment Requirements and Terms amp Conditions 3 conformance to Biomedical and Information Technology requirements equipment features specifications performance and reliability 4 vendor experience 5 the experience of users with the equipment and vendors 6 delivery amp installation schedule 7 warranty terms 8 service capabilities including but not limited to the availability of factory level service training and detailed service manuals 9 user training and support services 10 operating costs and overall responsiveness to this Request for Proposal RFP The basis of this evaluation will decide which vendor s will be invited to provide any presentations demonstrations evaluations and or on site clinical trials etc It is the right of the BUYER that this decision will be made independent of any or all of the above factors NOTE Submitting a proposal in response to this RFP const
29. f Information and Protection of Privacy Act An act respecting the right of access to documents of public bodies in Nova Scotia and a right of privacy with respect to personal information held by public bodies in Nova Scotia 15 2 Federal Legislation 15 2 1 PIPEDA Personal Information Protection and Electronic Documents Act An act to support and promote electronic commerce by protecting personal information that is collected used or disclosed in certain circumstances by providing for the use of electronic means to communicate or record information or transactions and by amending the Canada Evidence Act the Statutory Instruments Act and the Statute Revision Act 15 3 Patient Information Impact Assessment 15 3 1 MDS Manufacturer Disclosure Statement for Medical Device Security The vendor must provide with this proposal a Patient Information Impact Assessment for possible privacy related consequences of equipment and or system that use or disclose personal patient information or data including electronic Protected Health Information ePHI The Manufacturer Disclosure Statement for Medical Device Security MDS provides manufacturer s model specific description of the following The equipment or system s ability to maintain and or transmit ePHI The security features amp safeguards associated with the equipment or system 15 3 2 The vendor shall submit a fully completed MDS form for the equipment or syste
30. he VENDOR must comply agree and sign the Notification Agreement as shown in Appendix 4 SERVICE CONTRACTS 25 1 The pricing section shall include vendor proposed service agreements for a One 1 Three 3 and five 5 year periods Include all agreement terms conditions and fees minimum and maximum remedial maintenance response time credit to the BUYER if the selected vendor fails to meet guaranteed response time availability of trained technicians and parts system hardware enhancements and upgrades software maintenance engineering support software license and any other factors that should be considered by the BUYER in evaluating the vendor s proposal The price for each yearly period shall be clearly indicated and binding Page 36 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 25 1 1 Full service package 24 hours 7 days 25 1 2 Full service package 8 00am to 5 00pm 5 days 25 1 3 First screen shared service package Biomedical 25 1 4 Preventative Maintenance package 25 1 5 Time and Materials service 26 WARRANTY 26 1 The vendor shall provide a description of warranty contracts including your standard warranty and any special extended warranties offered Provide a description of proposed watranty terms including any partial less than one year or extended warranties 26 2 It should be understood that the warranty period shall not begin until all proposed system s are approved
31. ient approved personnel or independent contractors may become aware of have access to information from Client that is not publicly known including but not limited to information relating to the identity condition history care or treatment of Client s patients and Client personnel information or Client business information VENDOR agrees to ensure that all of VENDOR employees officers directors or other Client approved personnel or independent contractors engaged by VENDOR who become aware of have access to such information shall treat all information as strictly confidential Such information shall not be disclosed to any non VENDOR employees or representatives or entity without prior written approval of Client The obligation of confidentiality in this paragraph shall apply regardless of whether the subject information was supplied to VENDOR or whether the information was learned by VENDOR inadvertently during the course of its performance or otherwise The obligation of confidentiality in this paragraph shall survive the termination of this agreement regardless of the method or timing of its termination VENDOR Vendor Vendor Rep Name print Vendor Rep Name Signature Vendor Rep Title Print Page 43 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS APPENDIX 4 USER NOTIFICATION OF HAZARDS RECALLS DEFECT NOTICES COMPUTER amp SOFTWARE VIRUSES WORMS AND TECH
32. including optional vendor modules that are not included as part of the vendor s pricing response Page 40 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 18 Provincial Initiative It is understood that any agreement and or purchase that results from this tender are available to all Nova Scotia District Health Authorities DHAs 1 through 9 for a twelve 12 period following the contract award at their discretion While the exact resultant configuration may not be appropriate for any given DHA it is expected that the vendor will afford the same pricing and or discount structure to all districts Each district will be responsible for issuing their own P O The IWK encourages the use of electronic commerce for business transactions therefore vendors are requested to include a description of their capabilities and experience with electronic commerce Vendors should also include any discount structure they offer with this Vendors submitting bids involving the collection use or disclosure of personal information are required to certify that the vendor s business is fully compliant with the Personal Information Protection and Electronic Documents Act Canada All prices are to be FOB destination freight included upon delivery to the IWK The vendor shall identify any component of their shipment that includes hazardous materials requiring the IWK to take any environmental or personnel precau
33. ion Months Mandator j y Parts coverage duration Months The vendor shall not start the warranty period until the equipment has been placed into clinical use Note 1st day of clinical usage following all user training outlined in B 3 1 Mandatory Quote warranty extensions on a per year basis Required as applicable Response Training On site training must be provided for all applicable personnel On site in servicing must be supplied for all affected clinical Biomedical Engineering amp SPD staff members In servicing shall be scheduled at a time mutually agreeable to the IWK amp the successful vendor before Mandatory commencement of the evaluation period The IWK reserves the right to waive training on equipment with which it is already familiar Any amp all associated costs are to be detailed in the Cost Proposal Page 15 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS The provision of clinical training prior to and immediately following installation is mandatory Specify and list all the clinical in servicing provided in the cost proposal for clinical staff Mandatory The vendor must provide a detailed clinical implementation and training plan for items B 3 1 Mandatory and B 3 2 Two 2 follow up on site training subsequent CRRT procedures at a mutually agreed upon date is mandatory the vendor is to supply a follow up o
34. ists Required Response The Vendor must provide a Minimum of 2 Pediatric References using this equipment in an intensive care setting Canadian Preferred Required Response With regards to B 6 2 and B 6 3 The IWK reserves the right to disqualify at its sole discretion any bids for which it cannot obtain satisfactory references Mandatory Future development upgrade paths for obsolescence protection for the various system Mandatory components are to be detailed if known Technology Upgrades Further to clause B 4 1 if the vendor changes manufacturing support status of the proffered model s and introduces a replacement model that would also meet the clinical requirements described in this RFP after a purchase order has been placed but before installation the vendor will offer IWK the option of supplying the newer model at no additional cost Mandatory Page 21 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 8 SOFTWARE IF APPLICABLE LJ All software options and fees are to be priced out separately and included in pricing section The vendor will list ALL software components available on the SPECT CT GAMMA CAMERA with separate pricing indicated in the pricing section of the proposal The vendor must clearly outline any licensing fees associated with software support upgrades and the frequency of payment for these These licen
35. itutes the vendor s acceptance of procedures terms amp conditions evaluation criteria and other administrative instructions of this RFP Vendor s ACCEPTANCE Signature Title Please Print Page 8 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 5 INSTALLATION TESTING OF PROPOSED SYSTEM AND COMPONENTS 5 1 1 Vendor is responsible for unpacking assembling and performance testing of the CRRT equipment prior to user training and clinical use 5 1 2 Vendor shall allow Biomedical Engineering to perform acceptance testing as per Health Centre Policy Verification of Medical Device License CSA Standards Approval Electrical Safety Performance Testing 6 ACQUISITION SCHEDULE LH The BUYER reserves the right to change the acquisition schedule or issue amendments to the RFP at any time The BUYER also reserves the right to cancel and or reissue the RFP stee event DATE DURATION E eee eU E aa iii i pii September 30 2014 October 10 2014 To be agreed upon with successful vendor Page 9 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 7 EQUIPMENT The proposed Continuous Renal Replacement Therapy CRRT Systems must meet IWK Mandatory requirements and general specification requirements Indicate compliance YES NO and add comments in this section to assess the proposed system Equipment Technical Specifications and Requi
36. llowing as a minimum but more details Auditing are preferred Data and Time of access Patient Identifier Staff member that accessed the information Identify how your system deals with changes corrections to data If a change is made after the fact does your solution allow an audit to identify the original information recorded Data Integrity Mandatory If your system does not inherently achieve this what techniques can be used in conjunction with your system to ensure Data Integrity This may be in the form of Data Archiving Technology that can be leveraged Please identify your Disaster Recovery processes to ensure that in the event of a failure we understand the timeline of unavailability of the solution These processes need to cover the rebuilding and or Mandatory Disaster restoration of Operating System Applications and all Recovery collected Data back to the last backup completed What is the extent of potential data loss Availability The IWK leverages EMC Networker Backup products to provide local and offsite backups of systems on our Preferred network Identify redundancy options with your system that can mitigate both hardware and software faults They can Redundancy include items like redundant power supplies and hard Preferred drives as well as hot standby or active failover components that may be available with your solution Mandatory Integrity Application Support and Deploymen
37. m being proposed in this RFP The pdf file is available at the following web address http www himss org content files MDS2FormInstructions pdf 15 3 3 See Appendix 2 for a sample of the MDS form 15 3 4 Privacy Impact Assessment Please note the IWK Health Centre requires that a Privacy Impact Assessment PIA be completed by the vendor of choice prior to the signing of a purchase agreement 15 3 5 Vendor Confidentiality Agreement 15 3 6 The vendor will be required to sign a Vendor Confidentiality Agreement for servicing See Appendix 3 for a sample of the Form Page 26 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 16 SOFTWARE 16 1 Include the vendor s manufacturer s policy on notification of hardware and software 16 2 Updates on this equipment system through its life expectancy during both warranty and after warranty Page 27 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 17 IT SERVICES TECHNICAL STANDARDS The following tables and notes outline the IWK Health Centre technical standards for vendors who are supplying software and or hardware as part of their proposal Please indicate your compliance in the appropriate column of the tables and written responses to the associated notes in the space provided Attach additional supporting technical specifications and documentation to your response Communications Protocol
38. n e The third section of the proposal shall be a line item price quotation that separately lists all of the components of the proposed equipment system installation costs and any other costs associated with this acquisition Installation costs should be included in the price All pricing is to be installed freight prepaid and included in price proposal including rigging and inside delivery Page 7 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS e Each line item for each quotation must have both the standard list price as well as any discounted price This shall include service and equipment e Pricing for all options and accessories shall also be included in this section of the proposal SPECIAL INSTRUCTIONS 4 1 It shall be understood that all legal amp financial responsibilities in complying with the Health Products amp Food Branch Inspectorate HPFBI Health Canada regulations as they apply to the sale amp distribution of medical devices shall be the sole responsibility of the vendor Vendors submitting RFP s shall do so with a proposal that addresses the following While it is preferred that a single vendor meet ALL of the requirements of each department the BUYER reserves the right to select multiple vendors systems at its discretion Should equipment being proposed be the same as existing systems the vendor shall consider proposal options that will allow for upgrad
39. n per installation site Electronic copies of the manuals are to be provided with the bid for analysis The manuals collectively should contain at least the following Mandatory Detail any amp all specialized maintenance equipment test equipment adapters proprietary tools required to fully maintain the equipment throughout its estimated life cycle This same detail along with the associated pricing or annual license fees is also to be included in the Price Proposal Required Response Validated cleaning amp sterilization instructions Required Response Technical specifications Required Response Circuit documentation amp theory of operation Required Response Calibration amp preventive maintenance procedures Required Response Trouble shooting guides and error codes Required Response Proprietary Tools equipment Test Circuits Jigs Extender Boards calibration devices test equipment Required Response Diagnostic amp service software Required Response passwords access codes Required Response schematics amp diagrams Required Response IWK Health Centre CRRT RFP August 25 2014 Final Page 18 of 44 IWK Health Centre Hfx NS Special maintenance equipment requirements Required Response Proprietary tools diagnostic service software test circuits access codes passwords required to fully service su
40. n site in servicing as described in Mandatory B 3 1 and B 3 2 at a time mutually agreeable to the vendor and the Health Centre within a two year period following the go live date Describe all on going training amp education Required opportunities provided Response Each vendor shall include and specify all available training material Preference will be given to vendors that are able to supply Required interactive multi media training application Response programs E g Video telecommunication presentations multimedia Page 16 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS Application in service training for all subsequent hardware and or software upgrades or updates installed on the system will be supplied at the Mandatory time of the update installation at no additional charge to the Health Centre The IWK Health Centre s Biomedical Clinical Engineering outside the warranty period provides the majority of in house service on Mandatory electro medical equipment This is to be supported by the successful proponent Separate factory level technical service training for staff members from Biomedical Engineering shall be included as an option priced per person including all travel costs The IWK s training shall be comparable to the regular technical training provided to the manufacturer s 5 Mandatory own technical support staff Note A cours
41. nse BA Companies in doubt as to whether their software is a Class I or Class II device can contact Health Canada s Medical Devices Bureau for a ruling To initiate an action for a ruling send an email containing a basic description of your company and the software in question very brief together with contact information for someone in your company who can discuss the application with Health Canada The email can be sent to DEVICE_LICENSING hce sc gc ca Health Canada will contact you to discuss the process and any additional information required More information can be found on the Health Canada website 14 2 1 The vendor will identify which patient management software packages offered fall under the definition of Class I as defined above For those devices the vendor will provide their establishment licence no 14 2 2 The vendor will identify which patient management software packages offered fall under the definition of Class II as defined above For those devices the vendor will provide the medical device licence nos for each 14 2 3 Copies of the licenses for the current year shall be included with this proposal 15 PATIENT PRIVACY amp INFORMATION SECURITY IF APPLICABLE L It is essential that the Health Centre ensure that the privacy aspects and protection of information have been properly addressed as it relates to the following provincial and federal ACTS The vendor shall indicate compliance to the following
42. ntion of Purchasing Manager IWK No later than 3 00pm September 30 2014 Delivery Address Charter Place Offices 1465 Brenton Street 5 Floor Finance Halifax NS B3J 3T3 No facsimiles will be accepted Any questions regarding this RFP shall be conducted through the RFP Coordinators Indicated Any questions clarifications or discussions regarding this RFP must be conducted through the RFP coordinators below Blair Myers Ted MacLaggan Purchasing Manager Manager Biomedical Engineering Blair Myers iwk nshealth ca ted maclaggan iwk nshealth ca Ph 902 470 8917 Ph 902 470 8837 Page 3 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS TABLE OF CONTENTS Table of Contents Terms amp Conditions Vendors Proposal Format Special Instructions Installation Testing of proposed system and components Implementation Training amp Support Acquisition Schedule Equipment Software if applicable Start Up of System Accessories Delivery amp Installation Standards Date amp Time Medical Device Regulations Patient Privacy amp Information Security if applicable Software OANANNDNBRWNH Training Site Requirements amp Layout Acceptance Testing Documentation Service Capabilities Problem Notifications Service Contracts Warranty Consumable Products Evaluation References Proposal Cost Terms of Payment Substitution Proposal copies Appendix 1 IWK
43. od that any agreement and or purchase that results from this tender will be made known to and be available to all Nova Scotia Health Districts 1 through 9 for a twelve 12 month period following the contract award at each DHA s discretion While the exact resultant configuration may not be appropriate for any District it is expected that the vendor will afford the same pricing and or discount structure to all districts Each district will be responsible for issuing their own separate Purchase Order and or contract for services product Page 6 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS e NOTE It is a condition precedent to the IWK Health Centre s acceptance of any tender that the Vendor confirm that they have no outstanding or pending litigation action claim demand or cause of action against the WK Health Centre which in any way relates to the subject matter of the RFP or which relates to the supply of goods and services to the WK Health Centre BA Vendors will not be allowed to alter proposal documents after the deadline for submission 3 VENDORS PROPOSAL FORMAT All proposals submitted shall follow the format as outlined below 3 1 First Section Compliance Documentation e The first section of the vendor s proposal shall include details and compliance claims as they relate to the following sections of this RFP The vendor shall reference the same line item numbers for easy ref
44. on MUST be submitted to Biomedical Engineering at the time of delivery Vendors must comply with CSA Z317 13 12 Infection control during construction renovation and maintenance of healthcare facilities The vendor must provide proof of certification to the above standards Page 23 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 13 DATE amp TIME 13 1 The equipment system must be capable of properly recognizing any future date transitions and time and capable of performing correct date calculations 13 2 The equipment system shall be able to handle dates for a period of not less than fifty years after purchase 13 3 If there are any limitations to the date recognition these must be clearly identified and submitted with this proposal 14 MEDICAL DEVICE REGULATIONS 14 1 Medical Devices aa Any system equipment sold in Canada must now meet the Medical Device Regulations as set forth by the Health Protection Branch at Health Canada 14 1 1 The manufacturer must meet one or all of the following conditions providing license numbers where requested 14 1 2 In accordance with these regulations if the equipment being proposed is classified as Class I as defined by these regulations then the vendor must include their current Establishment License with this proposal 14 1 3 In accordance with these regulations if the equipment being proposed is classifieds Class II II or IV as defin
45. onger than one 1 year from the proposed delivery date is requested by BUYER Page 38 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 32 SUBSTITUTION 32 1 The vendor shall include a proposed method that allows the BUYER to substitute at its discretion new equipment introduced by the vendor after the award but before delivery that more suitably meets BUYER s clinical requirements Specifically address potential cost differences The vendor shall make no substitutions without agreement by BUYER 33 PROPOSAL COPIES 33 1 Please include 3 complete copies of this proposal for the following e Biomedical Engineering e Diagnostic Imaging e Purchasing Please include at least 1 electronic copy of this proposal on CD DVD or USB Drive APPENDIX 1 IWK GENERAL TERMS amp CONDITIONS UPDATED MAY 31 12 1 The IWK acknowledges that any information submitted in confidence by a vendor if disclosed to third parties could reasonably be expected to cause financial harm or harm the competitive position of the vendor Any information contained in a proposal that is considered confidential by the vendor must therefore be clearly identified as confidential The IWK and its representatives shall to the extent permitted by law respect the confidential nature of any information so identified Please note that as a public body IWK is subject to the Freedom of Information and Protection of Privacy
46. posal constitutes the vendor s acceptance of the procedures evaluation criteria and other administrative instructions of the RFP It is NOT acceptable to fax the Proposal The BUYER assumes no responsibility for delays in Canada Postal Service or any delivery or courier service that the vendor may select Time extensions will not be granted Vendor Contact Each vendor shall appoint an individual to act in an official capacity on behalf of the vendor for this acquisition The following information shall be included in the proposal o Name of the Vendor Representative Representative s Title Name of the Company Company Address Telephone Fax Number Cell Phone Pager Number E mail address Scheduling amp Amendments The BUYER reserves the right to change the acquisition schedule or issue amendments to the RFP at any time Right to Cancel The BUYER reserves the right to cancel and or reissue the RFP if so required Withdrawing Proposals Vendors may withdraw a proposal that has been submitted at any time up to the proposal closing date and time To accomplish this a written request signed by the authorized representative of the vendor must be submitted to the RFP Coordinator After withdrawing a previously submitted proposal the vendor may submit another proposal at any time up to the closing date and time Indemnity As a governmental unit the WK cannot provide an indemnity in the contract Provincial Initiative It is understo
47. pport the equipment must be provided upon product shipment and if necessary included as an option in the pricing proposal Mandatory The proponent agrees that the Proprietary tools service manuals diagnostic service software test circuits access codes passwords provided with Biomedical Clinical Engineering Factory Service Training may be shared with other employees of the IWK Health Centre Mandatory The vendor free of charge is to supply regular updates service bulletins throughout the equipment s lifecycle detailing any changes to the service manual as detailed in B 4 3 Mandatory Vendors are to include upon product shipment a minimum of two license copies of all service support software tools as required to provide Biomedical Engineering Service amp Support The software tools should be comparable to the software tools available to the vendor s service Mandatory The vendor shall provide service contract pricing options within the pricing proposal The service contract pricing should include PM Only full PM Repair and shared service options Biomedical Dept Front Line for 1 3 and 5 years Mandatory Bidders are to specify where sales amp service support originate Bidders are to have readily accessible sales amp technical support Bidders are to describe their various sales amp service mechanisms including but not limited to Mandatory Current contact names together with role
48. rements Worksheet Section A Overall System Components and Requirements General Requirements amp Performance Systems must be proven safe amp suitable to intended pediatric and adult clinical applications Systems must also be proven to have adequately robust construction to withstand the rigours of the intense tertiary quaternary care hospital environment Mandatory The system of the vendor of choice shall be proven acceptable per all requirements of this specification document via in house equipment trial in order to confirm selection Mandatory Systems must be proven capable of safely and effectively performing both low flow and high flow pediatric and adult CRRT procedures Bidders are invited to detail additional Mandatory procedures and features particular to paediatric applications for which use of their systems is indicated Page 10 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS Controls and system alarms must be proven to be clear intuitive amp easy to use understand Minimization of daughter screens and keystrokes is critical in order to support quality control IWK reserves the right to select first from devices that Mandatory are compliant with CAN CSA 60601 1 6 Medical electrical equipment Part 1 6 General requirements for basic safety and essential performance Collateral standard Usability If short listed
49. sful Bidder must install amp configure all system equipment amp software Required Response All building system requirements are to be relayed in the Technical Proposal for consideration Unless otherwise specified amp or negotiated IWK Health Centre or its agents will perform all building systems renovations amp upgrades Required Response IWK Health Centre CRRT RFP August 25 2014 Final Page 20 of 44 IWK Health Centre Hfx NS Vendor must supply a list of disposables including cost average cost treatment and pricing options Required Response History amp Upgrades Vendors must supply product history for IWK s assessment including a detail of all recalls over the previous five 5 years as well as any amp all litigation associated with the proffered products s both completed amp incomplete N B The IWK reserves the right to disqualify at its sole discretion any bids for which it deems have unsatisfactory recall issues and or resolution Required Response Vendors must provide references amp current install base details for proffered products for IWK s assessment Please include both clinical amp technical references Vendors are requested to comment on this listing to show how their products have proven their worth prior to this current application Vendors are to include past or present IWK users of their products on their reference l
50. sing fees are to include any necessary fees associated with servicing software networking archival support etc NOTE New regulations are required for Medical Device licensing of Patient Management Software See the section on Medical Device Regulations START UP OF SYSTEM 9 1 The successful vendor will be responsible for costs related to start up and testing of the system including but not limited to a Manuals Support b Performance Assurance amp Associated Supplies Disposables c CSA Field Inspections 10 ACCESSORIES 10 1 The vendor shall provide the description and cost of any relevant disposables and accessories required and or available 10 2 Provide information on other options configurations and features available including pricing in the pricing section of the proposal 10 3 Specification or data sheets for all equipment components are to be provided including weights and dimensions of all components environmental tolerances and power and utility requirements Page 22 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 11 DELIVERY amp INSTALLATION 11 1 The vendor shall confirm that they are in agreement with the equipment delivery date and the timeline set in the Acquisition Schedule outlined earlier in this document 11 2 If this cannot be achieved please clearly state the delivery installation and training times required for the proposed equipment system
51. stem must withstand typical hospital reprocessing techniques Written validated cleaning sterilization instructions shall be provided with the tender response Adequate Mandatory sterilization procedures amp or alternative measures e g drapes etc are to be provided in order to conserve the sterile field Vendors shall provide industry standard safety Required measures Response Vendor as applicable shall provide a list of required information technology infrastructure of data drops device server requirements specification recommended Required interfaces Server Operating System Response Requirements SQL Server Requirements Version Requirements and all associated minimum requirements SECTION B ADMINISTRATION amp SUPPORT REQUIREMENTS Standards amp Device Licensing a All equipment must have Health Canada s Health Protection Branch Therapeutic Device HPB TPD Licensing as required Bidders shall confirm their products have such licensing else provide an explanation as to why it is not required Mandatory All equipment must be proven to be certified to all appropriate CSA standards e g CSA 60601 1 and respecting latest revisions interpretations amendments supplements amp applicable collaterals by a recognized agency Must confirm compliance with respect to electromagnetic immunity and emissions cf CSA 60601 1 2 Mandatory CAN CSA 60601 1 2 Compliant Pass F
52. t Mandator Sy en server and workstation component Hardware Do Workstation Server components have to be purchased from your company or can the IWK leverage our existing Workstation and Server Preferred Vendors Provide details surrounding Server and Workstation software Mandatory installation processes Will the Software function with only User rights on the Workstations Software 7 2 X Is the software Windows XP and Windows 7 compliant What Antivirus products are approved for your network attached p Mandatory workstations and servers Page 29 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS ae IWK Currently leverages Symantec Endpoint 12 Is this a supported Preferred product on servers and workstations Will the IWK be able to leverage Microsoft System Centre to Deploy Preferred software to workstations Is your software professionally packaged in MSI files that support fully i automated deployments If not does the executable have switches for Preferred Installation silent installs and right assignments It is the IWK s preference to have Windows Based devices integrated by Preferred into our Active Directory Is this a supported configuration NOTES Note 1 Access to the IWK corporate network will be granted to equipment configured to be a member of the IWK Active Directory Domain Devices will run the Health Centre s central Anti Virus sol
53. t a time mutually agreeable to the IWK amp the successful vendor before commencement of the evaluation period The IWK reserves the right to waive training on equipment with which it is already familiar Any amp all associated costs are to be detailed in the Cost Proposal The provision of clinical training prior to and immediately following installation is mandatory Specify and list all the clinical in servicing provided in the cost proposal for clinical staff The vendor must provide a detailed clinical implementation and training plan for items 19 1 and 19 2 Two 2 follow up on site training at a mutually agreed upon date is mandatory the vendor is to supply a follow up on site in servicing as described in 19 1 and 19 2 at a time mutually agreeable to the vendor and the Health Centre within a two year period following the go live date Describe all on going training amp education opportunities provided Each vendor shall include and specify all available training material Preference will be given to vendors that are able to supply interactive multi media training application programs E g Video telecommunication presentations multimedia A 50 discount from published rates will apply for any additional training within 2 years of installation Application in service training for all subsequent hardware and or software upgrades or updates installed on the system will be supplied at the time of the update installation at no a
54. the recommended minimum patient weight size and other associated limitations Required Response Please provide details on the type of fluid balance system Gravimetric Required Response Please provide detail on the system sensors and measured parameters Required Response How often are the fluid balance and other measured parameters updated refreshed Required Response Please provide detail on the temperature control and monitoring system Required Response IWK Health Centre CRRT RFP August 25 2014 Final Page 12 of 44 IWK Health Centre Hfx NS Please indicate the blood volume required to prime various treatment sets Required Response Please provide details on pre and post dilution administration of replacement fluid and or the administration of citrate anticoagulant Required Response Human Factors Usability amp Alarm Management Does the system Automatically load patient extracorporeal set or cassette Is it user friendly If so please provide details Required Response Does the system provide on screen Instructions for priming setup through to the initiation of treatment If so please provide details Required Response The machine should manage alarms in such a way that clinicians are provided with information needed to quickly determine the cause of the alarm Please provide details Required Response Does the
55. tions Proponents submitting proposals hereby certify that the Proponent s business is fully compliant with the Personal Information Protection and Electronic Documents Act Canada the Freedom of Information and Protection of Privacy Act and the Personal Information International Disclosure Act Proponents submitting proposals hereby certify that all information necessary to allow the IWK to determine compliance with the Personal Information International Disclosure Act has been provided to the IWK All purchase orders contracts and tender documents RFPs RFQs etc and all items pertaining to them shall be governed and interpreted in accordance with the laws of the province of Nova Scotia Page 41 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS APPENDIX 2 MANUFACTURER DISCLOSURE STATEMENT FOR MEDICAL DEVICE SECURITY MDS2 Manufacturer Disclosure Statement for Medical Device Security MDS Device Category Manufacturer Document ID Document Release Date Software Revision Manufacturer or Representative Contact Information Company Name Telephone MANAGEMENT OF ELECTRONIC PROTECTED HEALTH INFORMATION PHI As defined by HIPAA Security Rule 45 CFR Part 16 4 Yes No N A Note 1 Can this device transmit or maintain electronic ted Health Informati e PHI 2 2 Types of ePHI data elements that can be maint b a Demographic e g name address locati b Medic
56. to be included in the Price Proposal E g tools test circuits jigs extender boards diagnostic amp service software access codes test equipment calibration devices all printed material schematics error codes diagrams Any costs for these including annual license fees shall be included Proprietary tools service manuals diagnostic service software test circuits access codes passwords required to fully service support the equipment must be provided upon product shipment and if necessary included as an option in the pricing proposal The proponent agrees that the Proprietary tools service manuals diagnostic service software test circuits access codes passwords provided with Biomedical Clinical Engineering Factory Service Training may be shared with other employees of the IWK Health Centre IT Training and Education if applicable The vendor must provide technical training for IT personnel if required Page 33 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 20 SITE REQUIREMENTS amp LAYOUT 20 1 Vendor must provide a complete and detailed description of the requirements for the proposed equipment system that may include but not be limited to Shielding Electrical Mechanical HVAC and plumbing Medical gases Structural and access requirements A complete description of environmental conditions required Ceiling wall and floor loading Any special utility and electrical
57. ution and be managed using Microsoft System Centre Vendor Response to Note 1 Note 2 Currently IWK Health Centre is delivering Microsoft updates via an internal update server Vendors must outline the process for applying Microsoft patches and critical updates to the hardware they provide Also include a list of all certified patches and critical updates that your application is currently certified for Any limitations on IWK Health Centre IT Services applying Microsoft patches and critical updates to any relevant client PCs must also be outlined Absence of this information may disqualify your response from further consideration Vendor Response to Note 2 Page 30 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS The vendor should provide details of any wireless communications capability including security and privacy compliance and performance guarantees Access to the WK Corporate wireless network must be using WPA2 with AES encryption Note 3 Vendor Response to Note 3 Page 31 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS 18 TRAINING On site training must be provided for all applicable personnel mandatory On site in servicing must be supplied for all affected clinical Biomedical Engineering amp SPD staff members In servicing shall be scheduled a
58. word change polices that can be Mandatory Authentication applied and any lockout setting that are relevant to your Confidentiality Model sokin The IWK Leverages Microsoft Active Directory as our Primary directory service It is preferred that all new Preferred applications are directly tied into Active Directory to Page 28 of 44 IWK Health Centre CRRT RFP August 25 2014 Final IWK Health Centre Hfx NS simplify account management and ensure that password policies are consistent across all systems What safeguards are in place on your servers and workstations to prevent data loss caused by lost or stolen equipment Items could include encryption of Mandatory data as well as the recommendation to store equipment in physical secure locations To ensure the security of the data that your servers are collecting the IWK would like to locate servers in the IWK Data Centre ensures they are physically secure Preferred under UPS power and in an air conditioned environment Note Storing of the server infrastructure in IWK Data Centre may require your system to function using Layer 3 connectivity Infrastructure Locations Preferred Identify if having your workstation and servers on different subnets introduces concerns with the functionality of your solution Identify the full auditing capabilities of the system Mandatory Auditing of Patient information should have the ability to identify the fo

Download Pdf Manuals

image

Related Search

Related Contents

Owners Manual - Desert Aircraft Australia  VACUUM CLEANER  fiche menuiseries 191009  Samsung MS28F301TAS Manual de Usuario  VOLUME V  Hygro-thermostat USB THS10  Sistemi di prova elettrodinamici MTS Acumen™  GPIO-MM-12 User Manual - Diamond Systems Corporation  Honeywell PLS750C User's Manual  Eglo PIANA  