Home

Dehumidifier Service and Parts Manual

image

Contents

1. EU e MODEL D40A 5 FID 20 e MODEL D50A 21 e MODEL D65A 22 6 REPLACEMENT PARTS LIST MODEL D30A ab DESCRIPTION PARTNO REMARK 130411 BASE ASSEMBLY SELD SINGLE 3041A10028C 130910 CABINET ASSEMBLY SINGLE 3091A20015D 131110 CASE ASSEMBLY SINGLE 3111A10016F 330870 DRAIN PAN ASSEMBLY 3087A10011B 148380 TANK ASSEMBLY BUCKET 4839A10001D 152302 FILTER MECH AIR 5230A20026A 162615 SENSOR
2. EVAPORATOR ASSEMBLY EVAPORATOR ASSEMBLY LOW PRESSURE SIDE LOW PRESSURE SIDE CONDENSER ASSEMBLY CONDENSER ASSEMBLY HIGH PRESSURE SIDE HIGH PRESSURE SIDE COMPOUND GAUGE COMPOUND GAUGE I i MANIFOLD GAUGE E A gt amp B eG B I CAPILLARY CAPILLARY TUBE TUBE SEE INSETS BELOW SEE INSETS BELOW J COMPRESSOR COMPRESSOR 2 U SS ee VACUUM PUMP CHARGING CYLINDER EXTERNAL LI Figure 27A Pulling Vacuum Figure 27B Charging 15 4 IROUBLESHOOTING GUIDE Problem Dehumidifier does not start Dehumidifier does not dry Possible Causes Remedy Make sure the dehumidifier s plug is pushed completely into the outlet The dehumidifier is unplugged Check the house fuse circuit breaker box and replace the fuse or reset the breaker The fuse is blown circuit breaker is tripped Water has reached its preset level Empty the bucket and replace properly Make sure the slots on both sides of the bucket are positioned correctly Bucket is not in the proper position and light is on Check if wiring loose or fails Replace wiring The control may not be set high Turn the Humidity Control knob to a the air as it should
3. This button controls the humidity in the room e Press button to raise the humidity setting Press gt button to lower the humidity setting The humidity setting can be set to a permanent On setting or to a specific humidity setting between 3596 and 7096 in 596 increments e On setting Dehumidifier runs continuously regardless of humidity condition 3596 7096 setting Dehumidifier runs on and off according to surrounding humidity conditions SE Auto Restart Once power is restored after a power outage the unit returns to its previous operation setting after a 2 minute delay The fan runs immediately when the power is restored 1 5 HOW TO OPERATE DEHUMIDIFIER 1 5 1 HOW DOES THE DEHUMIDIFIER WORK Condenser Moist humid air is drawn over a cold refrigerated Motor Evaporator dehumidifying coil Moisture in the air condenses on this Fan coil and drains into a bucket or through the bucket into a hose and drain Dry clean air is drawn over the condenser where it is actually heated several degrees and discharged out the front grille into the room See Figure 3 B t is normal for the surrounding air to become slightly warmer as the dehumidifier operates This warming effect further reduces the relative humidity of the surrounding air Figure 3 1 5 2 LOCATION FOR THE DEHUMIDIFIER connection Allow at least 12 inches of space on all sides of the unit for good air circulation
4. EE m gt lt x 1 os 5 oo c 225 a2 Oa B TT Eu 5 285 S c D no 5 5 58 5 8 e BETIE 5 8 Qs NN LSE el ux 528 E Dok zo o b E BSH a gt lt 5 52 Set S sae 5 8 t ox m y O lt OQ 52 Q4 5 5 Q gt s lt ac 89 C tc G o 5 D lt 5H Exc O 52 z z Z ees 5 Qs O23 lt 4s 5 9 84 9 On O 0 2S r 2 s LO 55 5 5 558 5 D a a tc O 3c Q o 9ST 23 S L gt 209090 A gt Sow Ws ss A o 30 lt lt g 5 SHOE m c 55 0 gt t z2 o oom z om 2 105285 ao 5 Se c odor co D odes oz 2 c c 2iL gt C IL cz gt gt lt gt gt ZQ A 95 N ot g h soa t O D 09 yx ootorgsoo Sg ENED cs T wd X N o9 o o Oo cr o9 zs 9 0 3 9 o e IN lt O lt 5 O lt r N E r lt E c oO e c0 a oO a A 11 Figure 17 Figure 18 Figure 19 Figure 20 X 4 EYE YEA Y
5. Dehumidifier Service and Parts Manual 115Volts D30A D40A D50A D65A D30A D40A D50A D65A 03 03 CONTENTS 1 PREFACE OSAP ET VAP RE CAUTIONS Stato 3 1 2 FEATURES AND DIMENSIONS ut aos ed 3 ala amukuna Sua 8 SIONS ste 3 13 SPECIFICATIONS una g 4 I GONE Tes orn dM s M mM 5 1 5 HOW TO OPERATE DEHUMIDIFIER coda 6 1 5 1 HOW DOES THE DEHUMIDIFIER WORK RE adi d ap PUR 6 1 5 2 LOCATION FOR THE DEHUMIDIFIER anasu 6 15 3 MICRO SWITCH streets du 6 1 54 RUT CIDEFROST Sauna 6 5 5 HUMIDITY CONTROLLER st 7 un nam m ae 7 2 CIRCUIT DIAGRAM ore 8 3 DISASSEMBLY INSTRUCTIONS S MECHANICAL PARTS i Su a 10 3 1 1 BUCKET AND AIR FILTER 10 3 1 2 FRONT CASE ANDCOPCOVER daten aqu da 10 3 1 3 CABINET AND CONTROL nd ici ar obtenido arra on dui dA d 10 akan a ca Uma ds NS SU 11 SO POWER CORD ASSEMBLY caren at
6. Shaded pole motor 65W 1A Thermal cutoff 266 F 130 C SWITCH ASSEMBLY MICRO 15A 250VAC OUTSIDE 30 40 PINTS DIMENSIONS 385 x 530 x 340 15 3 46 20 14 46 x 13 6 16 W x H x D mm in 50 60 PINTS 385 x 600 x 340 15 3 446 x 23 19 16 x 16 6 6 NET WEIGHT kg lbs 22 7 50 0 17 2 37 8 21 2 46 8 21 6 47 6 x NOTE Specifications are subject to minor change without notice for further improvement 1 4 CONTROL Continuous 4Hr On Off High 2Hr On Off Low TIMER a Fan Speed e This controls the speed of the airflow e High Fan speed is set to high Low Fan speed is set to low When Fan Speed button is pressed the fan speed mode is changed Timer e Press this button to select type of operation e Select continuous for uninterrupted operation e Select either 2 or 4 Hr On Off for cycled operation The unit will operate for 2 or 4 hours and then shut off completely for 2 or 4 hours The cycle repeats until you change the setting When Timer button is pressed the Timer indicator lights shift as follows Continuous gt 2 Hr On Off gt 4 Hr On Off gt Continuous HUMIDITY CONTROL Figure 2 Bucket Full Indicator This light glows when the water bucket is full and needs to be emptied Power Operation starts when this button is pressed and stops when the button is pressed again Humidity Control
7. ASSEMBLY 6877A30013H 249950 CONTROL BOX ASSEMBLY 4995A10074F 264110 POWER CORD ASSEMBLY 6411A20001Y 266011 SWITCH ASSEMBLY MICRO 6600A30003C 268712 PWB PCB ASSEMBLY DISPLAY 6871A20279A 268714 PWB PCB ASSEMBLY MAIN 6871A20162K 346811 MOTOR ASSEMBLY SINGLE 4681A20040E 35211A TUBE ASSEMBLY SUCTION SINGLE 5211A20812A 352113 TUBE DISCHARGE 5210A21843A 354210 EVAPORATOR ASSEMBLY 5421A20131A 336600 HOUSING ASSEMBLY 3660A10003A 550140 ISOLATOR COMP 5040AR4195A 552111 TUBE ASSEMBLY CAPILLARY 5211A20814A 554030 CONDENSER ASSEMBLY 5403A20110A 554160 RE COMPRESSOR SET 2521C A8626 359012 FAN TURBO 5900A20032A 567502 O L P 6750C 0009E 349600 MOUNT MOTOR 4960A20009A 667482 P T C ASSEMBLY 6748C 0003D 135500 COVER TOP 3550A20162A 436500 HANDLE 3650A20003A 144410 CASTER ASSEMBLY ROLLER 4441A30001B 238310 ESCUTCHEON 3831A20051C 235512 COVER ASSEMBLY DISPLAY 3551A10024A 349480 ORIFICE 4948A10023A 336610 HOUSING ASSEMBLY SINGLE 3661A10019A 558511 DRIER ASSEMBLY 5851A30001A 23 MODEL D40A DESCRIPTION S REMARK 130411 BASE ASSEMBLY WELD SINGLE 3041A10028A 130910 CABINET ASSEMBLY SINGLE 3091A20015B 131100 CASE ASSEMBLY SINGLE 3111A10016B 330870 DRAIN PAN ASSEMBLY 3087A10011A 148380 TANK ASSEMBLY BUCKET 4839A10001D 152302 FILTER MECH AIR 5230A20026A 162615 SENSOR ASSEMBLY 6877A30013H WOCZZ
8. See Figure 4 The dehumidifier must be operated in an enclosed area to be most effective E Close all doors windows and other outside openings to the room Place the dehumidifier in a location that does not restrict air flow into the rear coil or out the front grille The operation of dehumidifier in a basement will have little or no effect in drying an adjacent enclosed storage area such as a closet unless there is adequate circulation of air in and out of the area Figure 4 1 5 3 MICRO SWITCH The micro switch assembly which is located on the drain pan of inside unit automatically shuts off the dehumidifier when the bucket is full note the Auto Shut Off lights to indicate bucket must be emptied The bucket replaces in its place the unit again turns itself on 1 5 4 AUTO DEFROST When frost builds up on the cooling coils the unit will automatically cycle off until the frost disappears The fan continues to run NOTE The unit is designed to be operated at temperature above 65 F 18 C in normal condition If the dehumidifier is operated in low temperature conditions the temperature and humidity conditions of room are low some frost can be formed in its evaporator coil and the unit will be operated ON OFF repeatedly In this case please check on your room temperature condition and stop the unit 1 5 5 HUNIDITY CONTROLLER The humidity control can be set On or 35 70 RH Relative Humidity for normal operation
9. 074H 264110 POWER CORD ASSEMBLY 6411A20001Z 266011 SWITCH ASSEMBLY MICRO 6600A30003C 268712 PWB PCB ASSEMBLY DISPLAY 6871A20279A 268714 PWB PCB ASSEMBLY MAIN 6871A20162K 346811 MOTOR ASSEMBLY SINGLE 4681A20040E 35211A TUBE ASSEMBLY SUCTION SINGLE 5211A20875A 352113 TUBE ASSEMBLY DISCHARGE SINGLE 5211A20934A 354210 EVAPORATOR ASSEMBLY 5421A20133A 336600 HOUSING ASSEMBLY 3660A10003A 550140 BUSHING 4830A30005A 552111 TUBE ASSEMBLY CAPILLARY 5211A20933A 554030 CONDENSER ASSEMBLY 5403A20114B 554160 COMPRESSOR SET 2520UCDA003 359012 FAN TURBO 5900A20032A 567502 O L P 6750U L058A 349600 MOUNT MOTOR 4960A20009A 135500 COVER TOP ASSEMBLY 3551A20096A 436500 HANDLE 3650A20003A 144410 CASTER ASSEMBLY ROLLER 4441A30001B 238310 ESCUTCHEON 3831A20051C 235512 COVER ASSEMBLY DISPLAY 3551A10024A 349480 ORIFICE 4948A10023A 336610 HOUSING ASSEMBLY SINGLE 3661A10019A 25 MODEL D65A DESCRIPTION PART NO REMARK 130411 BASE ASSEMBLY WELD SINGLE 3041A10028B 130910 CABINET ASSEMBLY SINGLE 3091A20015F 131110 CASE ASSEMBLY SINGLE 3111A10016C 330870 DRAIN PAN ASSEMBLY 3087A10011C 148380 TANK ASSEMBLY BUCKET 4839A10001E 152302 FILTER MECH AIR 5230A20026A 162615 SENSOR ASSEMBLY 6877A30013H WOCZZ CAPACITOR 6120AR2359V 249950 CONTROL BOX ASSEMBLY 4995A10074D 264110 POWER CORD ASSEMBLY 6411A20001Z 266011 SW
10. CAPACITOR 0CZZA20003D 249950 CONTROL BOX ASSEMBLY 4995A10074G 264110 POWER CORD ASSEMBLY 6411A20001Y 266011 SWITCH ASSEMBLY MICRO 6600A30003C 268712 PWB PCB ASSEMBLY DISPLAY 6871A20279A 268714 PWB PCB ASSEMBLY MAIN 6871A20162L 346811 MOTOR ASSEMBLY SINGLE 4681A20040E 35211A TUBE ASSEMBLY SUCTION SINGLE 5211A20781A 352113 TUBE ASSEMBLY DISCHARGE SINGLE 5211A20780A 354210 EVAPORATOR ASSEMBLY 5421A20131A 336600 HOUSING ASSEMBLY 3660A10003A 550140 BUSHING 4830A30005A 552111 TUBE ASSEMBLY CAPILLARY 5211A20789A 554030 CONDENSER ASSEMBLY 5403A20114A 554160 COMPRESSOR SET 5416A90009A 359012 FAN TURBO 5900A20032A 567502 O L P ASSEMBLY 6751A20001F 349600 MOUNT MOTOR 4960A20009A 135500 COVER TOP 3550A20162A 436500 HANDLE 3650A20003A 144410 CASTER ASSEMBLY ROLLER 4441A30001B 238310 ESCUTCHEON 3831A20051C 235512 COVER ASSEMBLY DISPLAY 3551A10024A 349480 ORIFICE 4948A10023A 336610 HOUSING ASSEMBLY SINGLE 3661A10019A 24 MODEL D50A DESCRIPTION PART NO REMARK 130411 BASE ASSEMBLY WELD SINGLE 3041A10028B 130910 CABINET ASSEMBLY SINGLE 3091A20015F 131110 CASE ASSEMBLY SINGLE 3111A10016C 330870 DRAIN PAN ASSEMBLY 3087A10011C 148380 TANK ASSEMBLY BUCKET 4839A10001E 152302 FILTER MECH AIR 5230A20026A 162615 SENSOR ASSEMBLY 6877A30013H WOCZZ CAPACITOR OCZZA20001R 249950 CONTROL BOX ASSEMBLY 4995A10
11. CE PARTS MODEL D40A D50A D65A MAIN PCB 5 5 amp lt DISPLAY P C B BUCKET SW HUMIDITY SENSOR THERMISTOR WIRING DIAGRAM 3854A20247F LOCATION DESCRIPTION PART NO QTY RE NO D40A D50A D65A PER SET MARKS 1 POWER CORD ASSEMBLY 6411A20001Y 6411A20001Z 1 2 MOTOR ASSEMBLY SINGLE 4681A20040E 1 5 3 CAPACITOR OCZZA20003D OCZZA20001R 6120AR2359V 1 S 4 COMPRESSOR ROTARY SET 5416A90009A 2520UCDA003 2520UCDA004 1 S 5 O LP ASSEMBLY 6751A20001F 6750U LO58A 6750U LO48A 1 S 6 PWB PCB ASSEMBLY DISPLAY 6871A20279A 1 5 7 SENSOR ASSEMBLY 6877A30013H 1 5 8 SWITCH ASSEMBLY MICRO 6600A30003C 1 5 9 PWB PCB ASSEMBLY MAIN 6871A20162L 6871A20162K 1 s x S SERVICE PARTS A ALTERNATE PARTS N NOT SERVICE PARTS 3 DISASSEMBLY INSTRUCTIONS 3 1 MECHANICAL PARTS 3 1 1 BUCKET AND AIR FILTER 1 Disconnect the power supply 2 Press the power button off 3 Remove the bucket See Figure 7 4 Pressing the hooks pull out the air filter See Figure 8 3 1 2 FRONT CASE AND TOP COVER 1 Remove 4 screws which fasten the front case 2 Pull the front case at the lower side to the front and push front case upward See Figure 9 3 Remove 2 screws that secure the top cover and cabinet 4 Separate the top cover See Figure 10 3 1 3 CABIN
12. ET AND CONTROL BOX Upper Remove the bucket air filter and top cover according to the procedure above 2 Remove a screws which fasten the control box upper and pull out the control box upper See Figure 11 3 Disconnect housing PWB PCB ASSEMBLY DISPLAY from control box lower and remove front case completely 4 Remove 7 screws on all sides of the cabinet 5 Lift up the cabinet a little from the base pan and separate it by pulling out backward See Figure 12 Figure 7 L 77 V7 ZZ S lt NZZZ 7 Figure 11 Figure 12 10 Figure 13 Figure 14 Figure 15 Figure 16 I Q r3 ANGE 65 64 D NON s J 6 4 3 GG ESTY JS S V g As AIN ASL NETS IRR V TIILI f 8 Dim S DE NI 7 u VZN x EN II i j 4 UT JN A Pe LER INST 7 AT a amp WOLTER lt Q frp 5 e 2 gt E io 2 a Vu ee 9 ee o mo T 9 O89 o 0222 gt S aes MT viS a o Ze c E 32 r o o o uo m 5
13. ITCH ASSEMBLY MICRO 6600A30003C 268712 PWB PCB ASSEMBLY DISPLAY 6871A20279A 268714 PWB PCB ASSEMBLY MAIN 6871A20162E 346811 MOTOR ASSEMBLY SINGLE 4681A20040E 35211A TUBE ASSEMBLY SUCTION SINGLE 5211A20869A 352113 TUBE ASSEMBLY DISCHARGE SINGLE 5211A20931A 354210 EVAPORATOR ASSEMBLY 5421A10033A 336600 HOUSING ASSEMBLY 3660A10003A 550140 BUSHING 4830A30005A 552111 TUBE ASSEMBLY CAPILLARY 5211A20930A 554030 CONDENSER ASSEMBLY 5403A20114B 554160 COMPRESSOR SET 2520UCDA004 359012 FAN TURBO 5900A20032A 567502 O L P 6750U L048A 349600 MOUNT MOTOR 4960A20009A 135500 COVER TOP ASSEMBLY 3551A20096A 436500 HANDLE 3650A20003A 144410 CASTER ASSEMBLY ROLLER 4441A30001B 238310 ESCUTCHEON 3831A20051C 235512 COVER ASSEMBLY DISPLAY 3551A10024A 349480 ORIFICE 4948A10023A 336610 HOUSING ASSEMBLY SINGLE 3661A10019A 26 Use Factory Certified Parts FRIEDRICH AIR CONDITIONING CO Visit our web site at www friedrich com Post Office Box 1540 4200 N Pan Am Expressway San Antonio Texas 78295 1540 210 357 4400 FAX 210 357 4480 P NO 3828A20090N Printed in the U S A D30A D40A D50 65A 03 03
14. Ineffective dehumidifying Noise enough higher number Room temperature is too low Moisture removal is best at higher room temperatures Lower room temperatures will reduce the moisture removal rate This unit is designed to be operated at temperatures above 65 F 18 C Airflow is restricted Make sure there are no curtains blinds or furniture blocking the front or back of the dehumidifier Doors and windows may Check that all doors windows and not be closed tightly other openings are securely closed Clothes dryer may be blowing Install the dehumidifier away from moisture laden air into the room the dryer The dryer should be vented to the outside Check for gas leakage at heat Repair gas leak exchange and connecting tube Clean the air filter Check if the air filter is clogged with dust Set and use the dehumidifier at a sturdy flat and level place Check if the unit is securely positioned 16 CONDITION REMEDY 1 Dehumidifier does not start Both compressor and fan motor do not operate No power Poor plug contact at outlet Check power supply at outlet Correct if none Install plug properly or replace it Bucket is full If Auto Shut Off lights empty the bucket and replace properly Humidity control is at Off position Turn the humidity control switch toward Max Wire disconnect or loose Connect wire Refer to wiring dia
15. M 1 When replacing the refrigeration cycle be sure to discharge the refrigerant system by using a refrigerant recovery system After discharging the unit completely remove the desired component and unbrace the pinch off tubes Solder service valves into the pinch off tube ports leaving the valves open Solder the pinch off tubes with service valves After doing the above procedures the valve must be closed and left in place on the system for any subsequent procedures 6 Evacuate as follows 1 Connect the vacuum pump as illustrated in Figure 27A 2 Start the vacuum pump slowly open manifold valves A and B with two full turns counterclockwise and leave the valves closed The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold and entire system Xu If high vacuum equipment is used just crack valves A and B for a few minutes then open slowly with the two full turns counterclockwise This will keep oil from foaming and being drawn into the vacuum pump 3 Operate the vacuum pump for 20 to 30 minutes until 600 microns of vacuum are obtained Close valves A and B and observe vacuum gauge for a few minutes A rise in pressure would indicate a possible leak or moisture remaining in the system With valves A and B closed stop the vacuum pump 4 Remove the hose from the vacuum pump and place it on the charging cylinder See Figure 27B Open valve C Dis
16. N 7752 lt Zes 4 2 LIN 2m D ASSEMBLY DISPLAY from PWB PCB ASSEMBLY MAIN 3 1 3 2 Remove 5 screws that secure the PWB PCB DISPLAY to cover display MOTOR assembly upward after unhooking 2 hooks on the unhooking 3 hooks on the housing See Figure 19 3 Turn the nut clockwise and full out the fan by hands housing See Figure 18 2 Remove a screw that secures housing and orifice to heat exchanger and drain pan and lift housing and separate the orifice from housing after carefully See Figure 19 4 Unfasten 2 screws that secure the motor ASSEMBLY 1 Remove 4 screws that fasten the housing assembly 3 2 7 HOUSING ASSEMBLY FAN AND 3 2 6 CONTROL PANEL 1 Disconnect housing of PWB See Figure 20 5 Separate the motor 12 3 2 8 DRAIN PAN 1 Remove the housing assembly according to the procedure above 2 Unfasten 2 screws that secure the drain pan to base pan 3 Pull the drain pan backward then take it up from the base pan See Figure 21 3 3 REFRIGERATING CYCLE 3 3 1 CONDENSER EVAPORATOR AND CAPILLARY TUBE Remove the insulation on the H E assembly 2 Pierce the pinch off tube to discharge the refrigerant using a FREON recovery system 3 After discharging the refrigerant completely remove 2 screws between the housing assembly and H E See Figure 22 4 Lift the H E an
17. See Figure 5 If you need drier air press the Humidity Control button If you need moister air press the Humidity Control button Press the Power button to stop the unit manually 1 5 6 DRIER D30A Dryer is used to prevent capillary blockage from moisture in the refrigerant system and H E condenser and evaporator Also dryer is used to remove corrosion of the components NOTE When dryer is replaced proper injection to capillary is needed On opening the dryer it should be welded instantly The oxidization of dryer inside and all tubes inside after welding can be prevented Auto Restart v HUMIDITY CONTROL a Figure 5 Figure 6 Dryer 2 CIRCUIT DIAGRAM MODEL D30A MAIN PCB DISPLAY P C B BUCKET THERMISTOR FUSE 250V T3 15A SW HUMIDITY o WIRING DIAGRAM 3854A20247E LOCATION DESCRIPTION PART NO QTY RE NO D30A PER SET MARKS 1 POWER CORD ASSEMBLY 6411A20001Y 1 2 MOTOR ASSEMBLY SINGLE 4681A20040E 1 S 3 P T C ASSEMBLY 6748C 0003D 1 S 4 RE COMPRESSOR SET 2521C A8626 1 S 5 6750C 0009E 1 S 6 PWB PCB ASSEMBLY DISPLAY 6871A20279B 1 S 7 SENSOR ASSEMBLY 6877A30013H 1 S 8 SWITCH ASSEMBLY MICRO 6600A30003C 1 S 9 PWB PCB ASSEMBLY MAIN 6871A20162K 1 S S SERVICE PARTS A ALTERNATE PARTS N NOT SERVI
18. charge the line at the manifold connection 5 The system is now ready for final charging 7 Recharge as follows 1 Refrigeration cycle systems are charged from the High side If the total charge cannot be put in the High side the balance will be put in the suction line through the access valve which you installed as the system was opened 2 Connect the charging cylinder as shown in Figure 27B With valve C open discharge the hose at the manifold connection 3 Open valve A and allow the proper charge to enter the system Valve B is still closed 4 If more charge is required the high side will not take it Close valve A 5 With the unit running open valve B and add the balance of the charge a Do not add the liquid refrigerant to the Low side b Watch the Low side gauge allow pressure to rise to 30 Ibs c Turn off valve B and allow pressure to drop d Repeat steps B and C until the balance of the charge is in the system 6 When satisfied the unit is operating correctly use the pinch off tool with the unit still running and clamp on to the pinch off tube Using a tube cutter cut the pinch off tube about 2 inches from the pinch off tool Use sil fos solder and solder pinch off tube closed Turn off the unit allow it to set for a while and then test the leakage of the pinch off connection NOTE THE REFRIGERANT R134a IS USED SOME MODELS CHECK THE SPECIFICATION LABEL ON THE CABINET When dischargin
19. d open the H E around 45 degree counterclockwise carefully 5 Unbrace each of interconnecting tubes of the evaporator and condenser carefully Remove the H E assembly from the orifice See Figure 23 Unbrace the capillary tube at the connections of each condenser and evaporator See Figure 24 8 Remove 4 screws between condenser and evaporator See Figure 24 N 3 3 2 P T C OR OVERLOAD PROTECTOR O L P FOR RECIPROCATING COMPRESSOR D30A 1 Discharge the refrigerant by using a refrigerant Recovery System 2 After purging the unit completely unbrace the suction and discharge tubes at the compressor connections 3 Remove a screw or a nut which fastens the terminal cover 4 Disconnect the lead wire from the overload protector or P T C assembly Remove the overload protector O L P or P T C assembly See Figure 25 3 3 3 ROTARY COMPRESSOR 1 Discharge the refrigerant by using a refrigerant Recovery System 2 After purging the unit completely unbrace the suction and discharge tubes at the compressor connections 3 Remove the nuts and washers which fasten the compressor See Figure 26 4 Remove the compressor See Figure 26 AC TANGA WAALS CALA A 2222 LLY 27 Ly VY c ACA pe 7 AC Figure 24 Using Recipro Compressor model Figure 25 Figure 26 13 3 4 HOW TO REPLACE THE REFRIGERATION SYSTE
20. externally mounted Replace if open If the compressor temperature is high remove O L P cool and retest 3 Does not defrost control Defrost control is defective Check defrost control replace it 4 Insufficient dehumidification Low relative humidity Turn dehumidifier off Poor air circulation Move dehumidifier to obtain free and unobstructed air circulation H E clogged with dust and dirt Clean evaporator and or condenser assembly Air filter is dirty Clean it Motor is not operating Check Motor repair or replace it CONDITION REMEDY 5 Noisy operating Fan If cracked out of balance or partially missing replace it Some material plunged and rattle Remove it Tube hits frame Adjust tubing routine carefully Fan blade hits frame Check Motor Mount If loose tighten it Internal compressor noise Replace compressor Loose set screws Worn bearings of Motor Assembly Tighten them If knocking sounds continue when running or loose replace the motor If the motor hums or noise appears to be internal while running replace motor assembly 6 Water drips The bucket is not installed properly The bucket should be properly positioned on the hangers of the drain pan Connection may be loose Check connection and repair Leak in bucket Replace bucket Water drips when bucket removed for emptyi
21. g refrigerant R134a purging instrument should be used only for R134a without mixing that of refrigerant R22 When checking the leakage of refrigerant R134a leakage test tool should be used only for R134a The pump for discharging should be high efficiency Final discharging value must be managed below 0 5 Torr Maximum water should be less than quantity 150mg in the cycle all tubes and H E assembly system If water quantity is over 150mg it causes acid or corrosion in the cycle system and the capillary tube to be clogged by water and harmful materials The model charged the refrigerant R134a should be used dryer to prevent water from overflowing 14 Equipment needed Vacuum pump charging cylinder manifold gauge brazing equipment pinch off tool capable of making a vapor proof seal leak detector tubing cutter hand tools to remove components service valve
22. gram for terminal identification Repair or replace loose terminal Capacitor Discharge capacitor before testing Test capacitor Replace if not within 10 of manufacturer s rating Replace if shorted open or damaged 2 Motor runs but compressor does not run Voltage 115V 10 It must be between 103 5V and 126 5V If not within limits call an electrician Wiring Check the wire connections If loose repair or replace the terminal If the wires are disconnected refer to wiring diagram for identification and replace the wires Check the wire connections If not according to the wiring diagram correct the connections Rotary switch Check for continuity refer to the wiring diagram for terminal identification Replace the switch if the circuit is open Defrost control The Defrost Control senses frost build up on the evaporator coil and automatically shuts off the compressor The fan continues to run drawing air across the coil and melting the frost When the coil is defrosted the compressor automatically restarts and dehumidifying resumes Capacitor Discharge capacitor before servicing Check the capacitor Replace if not within 10 of manufacturer s rating Replace if shorted open or damaged Compressor Check the compressor for open circuit or ground If open or grounded replace the compressor Overload protector O L P Check the compressor O L P if
23. ng Before removing bucket the unit should be turned off Bucket overflows Check micro switch and float 7 Compressor cycles on overload protector O L P High or low line voltage 115V 10 Check line voltage It must be between 103 5V and 126 5V volts If intermittent provide new supply Poor air circulation Move dehumidifier for free and unobstructed air flow Heat Exchange clogged with dust or dirt Clean dust or dirt on the Heat Exchange Motor If not running determine the cause Replace if required Bad P T C assembly if assembled Check P T C Repair Short circuit or ground in electrical circuit Check electrical circuit Repair Unit pressures not equalized Allow 2 or 3 minutes for pressure to equalize before starting compressor Capacitor Test the capacitor Wiring Check the terminals If loose repair or replace Refrigeration system Check the system for a restriction Stuck compressor Check compressor replace compressor Overload protector O L P 18 Check O L P if externally mounted Replace if open If the compressor temperature is high remove the O L P cool and retest 5 EXPLODED VIEW INTRODUCTION MODEL D30A 75 554160 G6 1550140
24. ore servicing or replacing any electrical or non electrical component Do not cut off the grounding prong or alter the plug in any manner at any circumstances 1 2 FEATURES AND DIMENSIONS 1 2 1 FEATURES Quiet operation High efficiency Adjustable humidistat Automatic defrost Automatic shut off Bucket full indicator light Easy roll casters Removable amp large capacity bucket Washable air filter Two speed fan Drain hose connection 1 2 2 DIMENSIONS mm in 385 15346 340 13646 _ 385 15 3 16 34013616 D30A D40A Model D50A D65A Model Figure 1 1 3 SPECIFICATIONS MODELS D30A D40A D50A D65A ITEMS CAPACITY Pints 24hrs 30 40 50 65 POWER SUPPLY Phase V Hz 10 115V 60Hz REFRIGERANT R134a R22 REFRIGERANT CHARGE oz g 5 47 155 5 64 160 7 23 205 7 76 220 OPEN 30 2 F 1 40 550 32 9 F 0 5 0 5 30 2 1 0 5 THERMISTOR CLOSE 50 0 F 10 0 5 53 6 F 12 0 5 50 0 10 0 5 COMPRESSOR MODEL NO LX86HAQG 2S7B126A QA084CBB QA114CBF TYPE P6R8MC WORKING TME 0 3 13 se P T C TIME RETURN TIME 65 sec ASSEMBLY AMPERE 10A MAXIMUM VOLTAGE 200V OVERLOAD PROTECTOR FOR COMPRESSOR PROTECTOR INTERNAL PROTECTOR FUSE FOR MOTOR CAPACITOR 2 40uF 200VAC 30uF 270VAC 270VAC MOTOR ASSEMBLY SINGLE
25. tele asishka Su upra du i RU 11 3 2 2 SENSOR ASSEMBLY etsy tat ala au a Museu un 11 3 2 3 PWB PCB ASSEMBLY MAIN ito iE e database ba d 11 BD d CAPACITOR Sas ama aa eet Lt scc a CQ RN aed 11 325 MICRO SWITCH ASSEMBLY 11 3 2 6 CONTROL hed atthe aa 19 3 2 7 HOUSING ASSEMBLY FAN AND MOTOR 12 3 2 8 DRAIN 18 SS REFRIGERATING CYCLE Ath 18 3 3 1 CONDENSER EVAPORATOR AND CAPILLARY 13 3 3 2 P T C OR OVERLOAD PROTECTOR O L P FOR RECIPROCATING COMPRESSOR 13 3 3 3 ROTARY COMPRESSORS u a 13 3 4 HOW REPLACE REFRIGERATION SYSTEM iu d RR Rt DP abd 14 4 TROUBLESHOOTING QGUIDE 1 16 5 EXPLODED VIEW INTRODUCTION 19 6 REPLACEMENT PARTS LIST rompe ti taii rends 23 1 PREFACE This Service Manual provides various service information containing the mechanical and electrical parts etc This dehumidifier was manufactured and assembled under the strict quality control system The refrigerant is charged at the factory Be sure to read the safety precaution prior to servicing the unit 1 1 SAFETY PRECAUTIONS Disconnect power supply bef

Download Pdf Manuals

image

Related Search

Related Contents

CONDITIONS GÉNÉRALES DU CONTRAT D  FNPPSF FEDERATION NATIONALE DES PECHEURS  パブリックコメントの回答  RC-20 Owner`s Manual  Switches administrados Ethernet Stratix 5700 Manual del usuario  Scuba Series 720P  Manhattan 172554  AUTOMATIC LEVEL C300, C310, C320, C330    L`école enfin expliquée aux parents (et aux autres)  

Copyright © All rights reserved.
Failed to retrieve file