1. 2 INSTALLATION SITE PREARRANGEMENT At the mounting installation phase be sure all safety precautions have been considered Always consider how important it is the correct positioning of gas detectors to get the optimum response Be careful never to install gas detectors close to air intakes or fans causing strong air currents Be sure the detectors are attached to a firm base to prevent vibration that can damage them producing unreliable results Although the electronics comply with the electromagnetic compatibility rules it is advised to keep the detectors at a distance from any radio frequency senders such as radio links or similar Please be also sure that detectors are placed in a convenient location for future maintenance and calibration requirements All of the gas lighter than air tend to spread upwards so the detector should be placed at 30 cm from the ceiling in order to maximise the effectiveness of the detection LPG as well as Butane Gasoline vapours and all of the gases heavier than air tend to spread downwards so the detector should be placed at 30 cm from the floor There are some substances that when present in the atmosphere being analysed can considerably change the response of the sensor and even damage it irremediably in particular silicones silicon halides tetraethyl lead hydrogen sulphide carbon tetrachloride trichlorethylene Whenever their presence is presumed it is recommended to check the detector
2. s sensitivity at short time intervals and always after an alarm intervention with sample gas bottles Detectors are factory calibrated for the specific gas required by the customers Future modification of the preset calibration can be carried out in our Laboratory only it being a procedure requiring specific procedures and equipments ALLARM LEVELS JUMPERS PROGRAMMING Custom 10 15 25 m On A E Om 10 15 30 10 20 30 o mM A Om T 10 25 35 3 INSTALLATION 3 1 CORRECT POSITIONING MODE The detector is always to be mounted with the sensing element placed downward For no reasons at all the enclosure can be drilled Wall mount the detectors by employing the existing holes For EEx d versions to be mounted in classified hazardous areas we advise to use explosion proof cable glands to seal the cables inlets 3 2 DETECTOR CIRCUIT LAYOUT 1 Vcc 12 24V 2 Rs485 A 3 Rs485 B 4 Gnd 5 Vcc 12 24V 6 4 20mA OUT Ta 5 4 20mA lolo Negative output mode DEFAULT Detector circuit layout Main plugin terminal board for connections Thresholds setting point DIP SWITCH Jp41 i9 Jp3 sso 3 P Le 4 20mA mode eje ee ofo ol a Dn Positive output DO ele Analog amplifier J11 Plug in connettor board for display or r
3. H 200 D 110 mm Eexn L 106 H 180 D 62 mm Orientamento Installazione verticale con sensore rivolto verso il basso Per versione EEx d CESIO1ATEXO053 In conformit alle normative EN50014 1997 A1 A2 EN50018 2000 Certificazione ATEX LBT 7629 2 PREDISPOSIZIONE D INSTALLAZIONE Durante le operazioni di montaggio installazione gli impianti devono essere messi in sicurezza Ricordiamo anche come in fase di installazione sia opportuno tenere in considerazione alcune norme generali in quanto un posizionamento non corretto pu pregiudicare il funzionamento ottimale del rivelatore Si raccomanda di non installare rivelatori gas nelle vicinanze di prese d aria e o ventilatori che provocano forti correnti d aria rivelatori non devono essere altres posti in zone nelle quali siano presenti vibrazioni e sebbene immuni da disturbi a radiofrequenze consigliabile non installarle in prossimit di emettitori radio ponti radio o apparecchiature simili Altra buona norma quella di installare il rivelatore in zone facilmente accessibili per le operazioni di test e calibrazione DEL SITO Tutti i gas pi leggeri dell aria disperdendosi nell ambiente occuperanno la parte alta dell ambiente ed il rivelatore deve quindi essere posizionato a 30 cm dal soffitto per ottenere un efficace intervento gas pi pesanti dell aria GPL Butano Vapori benzina al contrario disperdendosi stazioneranno nella parte bassa dell a
4. MUST BE IN OFF POSITION JUST FOR ENRICHEMENT OXYGEN GAS DETECTOR VERSION JUST FOR DEPLETION OXYGEN DETECTOR VERSION ON Position 4 20 mA transmission output proportional to the detector range 0 100925 OFF Position 10 20 mA current loop output to operate with fire control panels usiging a current voltage conversion the operative thresholds are the 1st and 2nd DS1043 028B 6 LBT 7629 3 3 STAND ALONE OR 4 20 MA OUTPUT CONNECTION Please check the carton box comprises all of the components Wiring between the detector and the control panel should be carried out with shielded cables Wires cross section depends on the distance between the control panel and the detector e for a distance up to m 100 we advice a 3 core wire with cross section area of 0 75 mm e for a distance between m 100 and 200 we recommend 3 x 1 0 mm e for a distance between m 200 and 300 we recommend 3 x 1 5 mm Should any junctions be necessary on the wires please make sure there is no interruption on the shield Please remember that the shield is to be connected to the ground from the control panel side only Also remember never to connect the shield to the connectors Ensure the wire connections either clutching or crimping type are duly carried out with terminals that do not oxidise or loosen Better of all would be to solder them The SMART3 gas detectors are designed to be connected to any c
5. e per distanze comprese fra 100 e 200 mt si usino cavi con sezione di 1 0 mm e per distanze comprese fra 200 e 300 mt si usino cavi con sezione di 1 5 mm Nel caso vi siano giunzioni nel cavo di collegamento assicurarsi che vi sia continuit anche sulla schermatura dei cavi Ricordarsi che la schermatura deve essere collegata a terra unicamente dal lato unit di controllo o gruppo di alimentazione mentre non dovr mai essere collegata sui rilevatori Assicurarsi che la realizzazione di giunzioni sui cavi di alimentazione mediante dispositivi di serraggio o a crimpare sia eseguito a regola d arte con capicorda e o morsetti che nel tempo non si ossidino o allentino E sempre preferibile eseguire giunzioni saldate Il rilevatore SMART3 pu essere collegato a centrali di sicurezza di qualsiasi tipo Le prestazioni migliori si ottengono con una centrale di tipo analogico 4 20 mA con indicazione proporzionale della concentrazione di gas in ambiente SCHEMA COLLEGAMENTO per 4 20 mA Nello schema seguente viene riportato il tipico collegamento di un rilevatore SMART3 ad una centrale Urmet Domus N B NEL CASODI CENTRALI CON INGRESSO 4 20 MA POSSIBILE COLLEGARE 1 SOLO RILEVATORE A CIASCUN INGRESSO COLLEGAMENTO RILEVATORI UTILIZZANDO L USCITA 4 20 mA CON CENTRALI ANALOGICHE 4 20mA MORSETTIERA MORSETTIERA RILEVATORE CENTRALE 1 Vcc 12 24V 4 GND 2 Rs485 A 5 Vcc 12 24V 3 Rs485 B 6 4 20mA OUT 4 COLLAUDO E USO 4 1 ACCE
6. E PREVENTIVA Tutti i RIVELATORI DI GAS ad uso industriale secondo la direttiva CEI 31 35 CAP IV devono essere controllati ogni tre sei mesi risultati delle prove effettuate dovranno essere registrate su di un apposito quaderno da esibire alle autorit competenti e seguito di un eventuale verifica Nel caso in cui siano presenti inquinanti nell ambiente in grado di alterare le caratteristiche originali dei sensori le operazioni di manutenzione dovranno essere effettuate con maggior frequenza 5 2 MANUTENZIONE CORRETTIVA Per anomalie riscontrabili durante il test funzionale rivedere la fase di collaudo al capitolo 4 Se durante la manutenzione preventiva il rilevatore non rileva il gas per cui tarato inviare il prodotto al fornitore dello stesso che a sua volta provveder ad inviarlo al costruttore E possibile ricalibrare il rilevatore utilizzando il dispositivo di acquisizione dei parametri da richiedere al fornitore CAL GAS 5 3 ISTRUZIONI PER LA DISMISSIONE Togliere alimentazione al rilevatore scablare la morsettiera e rimuovere il contenitore dalla tubatura metallica e dai relativi sistemi di bloccaggio 6 SEGNALAZIONI DI ALLARME E DI GUASTO Per l utilizzo in stand alone del rivelatore SMART3 necessario disporre della scheda 3 rel SKBR3N Su questa scheda si possono verificare gli stati di allarme e di guasto tramite gli appositi led 7 IDENTIFICAZIONE RIVELATORI RIVELATORI EEx n RIVELATORI EExd LB
7. Ex nA enclosure SMART3 DU 4 20mA DS1043 028B 1 2 EXPLOSIVE GAS TECHNICAL CHARACTERISTICS NET PEL NEMOTO PELLISTOR ATEX certificate ATEX CESI 01ATEX013U or CESI 01ATEX066U Measurement range 0 100 LEL Resolution Out analog 0 1 mA Power supply 12 24 Vdc 20 15 Consumption at 12Vdc 140 mA medium 180 mA max Microprocessor 10 bit Flickering LED 4 20 mA default or 0 10 20mA Sensing element Sensor head Control unit Visual indications Proportional output Relay outputs with status indicating LED optional 3 relays with tension free changeover contacts 24V 1A Zero drift compensation variable average on the values sampled 1024 points 5 full scale or 10 readout 5 minutes lt 1 minutes lt 30 sec T50 lt 60 sec T90 5 Full scale or 10 readout Auto zero routine Digital filte Resolution Precision Warm up time Stabilization time Response time Repeatability Storage temperature 25 60 C Operating temperature 10 55 C Relative humidity 20 90 Rh 40 C Operative pressure 80 110 KPa Air velocity lt 6 mS Weight Eex d 700 gr EEx nA 400 gr Watch dog Internal for the microprocessor status control Dimension EExd L 105 H 200 D 110 mm Eexn L 106 H 180 D 62 mm Orientation The detector must be mounted sensor head downward ATEX certificate CESI01ATEX053 for EEx d version In compliance with EN50014 1997 A1 A2 EN50018 2000 LBT 7629
8. FAULT e Uscita positiva J11 Connettore per scheda display o rel Connettore di misura per controllo parte analogica Circuito rivelatore Morsettiera di collegamento estraibile DIP SWITCH per selezionare le soglie Scheda amplificatore analogica Pees El Comnessione elemento sensibile ed di indicazione di stato 3 2 1 SCHEMA TOPOGRAFICO SCHEDA 3 REL OPZIONALE Consultare il manuale fornito con la stessa 3 2 2 PROGRAMMAZIONE DEL RIVELATORE Il rilevatore viene calibrato per il gas specificato al momento dell acquisto Successivamente possibile ricalibrare lo strumento utilizzando l apposito strumento come specificato al punto 5 2 Il rilevatore viene configurato per avere di default una uscita proporzionale 4 20mA E possibile ottenere uscite a 0 10 20mA corrispondenti a e OmA condizione di normale funzionamento o guasto e 10mA superamento prima soglia di allarme e 20mA superamento seconda soglia di allarme Configurando diversamente i dip switch presenti sulla scheda base si possono modificare le soglie di allarme Anche disponendo della scheda opzionale a 3 rel possibile modificare le soglie di intervento dei rel come indicato nella tabella seguente PROGRAMMAZIONE JUMPERS PER SOGLIE DI ALLARME RILEVATORE D ON 10 15 25 BEEE Custom 123456 or M O Z 10 15 30 Co al O gt 2 N
9. LT status signalling output current would be forced to 23mA and to reset the normal working conditions it would be necessary power the unit off and on The flashing red LED on the motherboard indicates the detector s working condition as detailed in the following table Flash rate seconds Meaning 5 MAINTENANCE 5 1 PREVENTIVE MAINTENANCE ROUTINES All GAS DETECTORS are to undergo a working test every three to six months according to the EN 60079 10 Test results are to be recorded into a suitable book to be shown to the Authority in case of inspection In environments where polluting elements might alter the original sensor performances periodical testing should be carried out at shorter time intervals 5 2 CORRECTIVE MAINTENANCE ROUTINES For any anomaly found during the working test please check the tests performances as described on chapter 4 If during the preventive maintenance performances the detector does not react to the gas it has been calibrated for please return the instrument to your supplier that on his turn will return it to the manufacturer for repair It is possible to recalibrate the detector by employing the parameter acquisition device available on request 5 3 DISASSEMBLY INSTRUCTIONS Power the unit off disconnect the wires on the terminals and dismount the housing from any blocking systems 6 ALARM AND FAULT INDICATIONS To employ SMARTS as stand alone detectors it is necessary to use the 3 relay
10. NSIONE AI momento in cui il circuito viene alimentato si accende ad intermittenza lenta il led rosso sulla scheda base L uscita in corrente 1 5MA circa Trascorsi 2 minuti circa il led rosso lampeggia con una frequenza pari allo stato in cui si trova il rilevatore vedere Tabella al punto 4 3 e l uscita in corrente si porta a 4 0mA Terminata la fase di preriscaldamento il rilevatore in grado di funzionare correttamente Sono comunque necessarie 2 ore circa affinch il rilevatore raggiunga le prestazioni ottimali 4 2 COLLAUDO Verificare la risposta del rivelatore utilizzando una miscela idonea oppure con vapori di alcool 4 3 USO Il rivelatore funziona automaticamente e autonomamente pertanto non richiesto alcun contributo da parte del suo utilizzatore In caso di malfunzionamento il rilevatore forza l uscita a 1 8mA circa Se la concentrazione di gas misurata supera il 100 LIE il LED sul circuito stampato si accende come per la segnalazione del fault l uscita viene forzata a 23 MA e per ripristinare il corretto funzionamento DS1043 028B del rivelatore si dovr togliere e ridare alimentazione ll LED rosso lampeggiante posto sulla scheda base del circuito indica lo stato in cui il rilevatore si trova come illustrato nella tabella sottostante Frequenza lampeggio in secondi 1 ON 1 OFF 1 ON 1 OFF 0 1 ON 1 OFF 2x0 1 ON 1 OFF 3x0 1 ON 1 OFF ON ON Guasto W D 5 MANUTENZIONE 5 1 MANUTENZION
11. Om N 10 20 30 o M A Om OLE o Mo o M oc 10 25 35 oM o Mo o Mi VALORI IN RIFERITI AL FONDO SCALA DIP SWITCH PER IMPOSTARE LE SOGLIE DI ALLARME SONO N 3 4 5 6 IL DIP SWITCH N 1 NON UTILIZZATO E DEVE ESSERE IN POS OFF SOLO PER RILEVATORI DI ARRICCHIMENTO DI OSSIGENO SOLO PER RILEVATORI DI DEFICENZA DI OSSIGENO DS1043 028B 8 DT 15 25 40 23 25 27 345 6 15 30 45 Non usata DEI 5 19 18 17 C 19 17 15 IL DIP SWITCH N 2 SELEZIONA LA MODALIT ON DELL USCITA IN CORRENTE ul 5 Posizionare ON uscita analogica proporzionale in corrente 4 20 mA corrispondente allo 0 100 del fondo scala del rilevatore Posizionare OFF uscita Doppia Soglia 10 20 mA per centrali a variazione di assorbimento le soglie operative sono la 1 e la 2 LBT 7629 3 3 COLLEGAMENTO MODALIT STAND ALONE OPPURE USCITA 4 20 MA Verificare che nella confezione ci siano tutte le parti componenti Per il collegamento del sensore con l unit di elaborazione e alimentazione si raccomanda l uso di cavo schermato La sezione del cavo da utilizzare dipende dalla distanza del rilevatore dalla centrale e per distanze inferiori a 100 mt si usino cavi con sezione di 0 75 mm
12. T 7629 Codice 1043 701 1043 703 1043 704 1043 705 Codice 1043 721 1043 722 1043 723 1043 724 1043 725 1043 726 1043 728 1043 729 1043 730 1043 731 ENGLISH INDEX TINTA TNA 5 t dco oom mE 5 1 2 Explosive das FOC TUNG AC AA INS EN ETE CO EE E o rmm 5 2 INSTALLATION SIME Liz iicuxdigee EEEE 6 SINS TALLA TION ti 6 SA So ies egos AAA O E yq RE iene untranamnenateensesinmteee senses 6 Se Detector creuit IA OUD erstes once 6 SM MOL Tela card layout OPIO is iaia 6 3 22 Detector prodr Aia o 6 33 Standalone or4A 20 MA ouiput Connection anice aaa 7 4 TES ANS ANDO WORKING OFERATION ai e alia 7 il PON Lc 7 VC PROF RO ORSI IRE 7 A PRE en 7 B MAINVABUE nr 7 51 Preventive DIAMANTI aiar 7 52 GOMECIVe Mananc TOUS TEN ETE TET 7 bi ISAS Sei conica S 7 0 ALARM AND FAULTINDICATNON enna 7 1 INTRODUCTION 1 1 DESCRIPTION SMART3 gas detectors are used in atmospheres where the principal constituent is air to detect the presence of combustible substances with concentrations expressed as a LEL Lower Explosion Limit The professional industrial type catalytic sensor PELLISTOR employed for the detection of flammable compounds offers a great precision and selectivity with most of the explosive gases thus avoiding false alarms The management
13. Urme Mod DOMUS 1043 DS 1043 028B LBT 7629 MANUALE D INSTALLAZIONE ED USO DEI RIVELATORI GAS SERIE SMART3 PER GAS INFIAMMABILI USER MANUAL FOR SMART3 SERIE EXPLOSIVE GAS DETECTORS ITALIANO INDICE 1 INTRODUZIONE eran 2 lui DESCI o e o a e PO eee 2 1 2 Caratteristiche tecniche per gas esplosivi ascii A aiar 2 2 PREDISPOSIZIONE DEL SITO D INSTALLAZIONE nia 3 INSTALLATION E nn 3 SA Modalita peril coretta an tarare rene 3 3 2 SCHEMA ODOT ANCO sra 3 3 2 1 Schema topografico scheda 3 rele Opzionale cirie siriani 3 3 2 2 Pr grammazione del WC israele ire 3 3 3 Collegamento modalit stand alone oppure uscita 4 20 MA 4 ES RAP ii 4 di SC aio 4 A 4 A O A o A A soe 4 MANUTENZIONE as 4 o Manutenzione Pre raro aan 4 de Manutenzione CORE STEIN i ana anio eis 4 5 3 Istruzioni per la dismissione COEGNALAZIONI DIFACLARME E DIGUAS TO bei 4 MIPENVFPCAZIONERVELSPOR Ioia 4 1 INTRODUZIONE 1 1 DESCRIZIONE Rilevatori di gas della serie SMART3 vengono impiegati per rilevare in una atmosfera costituita principalmente da aria la presenza di sostanze combustibili in concentrazioni esprimibili in LIE Limite Inferiore di Esplosivit Il sensore industriale PELLISTORE utilizzato nelle versioni per miscele esplosive conferisce una precisione ed una selettivit ottimale con la maggior parte dei gas esplosivi evita
14. card SKBR3N The LEDs mounted on the relay card allow an easy check of alarm and fault status LBT 7629 DS 1043 028B FILIALI 20151 MILANO Via Gallarate 218 Tel 02 380 111 75 Fax 02 380 111 80 00043 CIAMPINO ROMA Via L Einaudi 17 19A Tel 06 791 07 30 Fax 06 791 48 97 80013 CASALNUOVO NAPOLI Via Nazionale delle Puglie 3 Tel 081 193 661 20 Fax 081 193 661 04 30030 VIGONOVO VENEZIA Via del Lavoro 71 Tel 049 738 63 00 r a Fax 049 738 63 11 http www urmetdomus com e mail info 9 urmetdomus it LBT 7629 STABILIMENTO URMET DOMUS S p A 10154 TORINO ITALY VIA BOLOGNA 188 C Telef 011 24 00 000 RIC AUT Fax 011 24 00 300 323 Call Center 011 23 39 801 MT1015U
15. elay board gt d D Sensing Measure connettor for element connection checking of analog circuit part Status led indication 3 2 1 3 RELAY CARD LAYOUT OPTIONAL Please refer to the technical instruction supplied along with the card 3 2 2 DETECTOR PROGRAMMING Detectors are factory calibrated for the specific gas required by the customers Future modification of the preset calibration can be carried out by employing the instrument described on paragraph 5 2 The default configuration provides a 4 20mA proportional output It is also possible to have outputs set at 0 10 20mA corresponding to e OmA correct working condition or Fault e 10mA 1st alarm threshold attainment e 20mA 2nd alarm threshold attainment By modifying the dipswitches configuration on the motherboard different alarm thresholds might be obtained It is also possible to modify the relay intervention when using the 3 relay card as per the following table 15 25 40 15 30 45 25 35 50 20 40 60 23 25 27 1 Not used 19 18 17 19 17 19 96 VALUES REFERRED TO THE DETECTOR S RANGE THE DIP SWITCH No 2 SELECTS QN THE CURRENT OUTPUT MODE ONLY DIP SWITCHES No 3 4 5 6 ARE TO BE USED TO SET ALARM LEVELS P THE SWITCH No 1 IS NOT USED AND
16. mbiente ed il rivelatore deve quindi essere posizionato a 30 cm dal pavimento Vi sono alcune sostanze che se presenti nella atmosfera da analizzare possono alterare considerevolmente la risposta del sensore fino a danneggiarlo irrimediabilmente es siliconi silicati alogeni tetraetile di piombo acido solfidrico tetracloruro di carbonio tricloroetilene trielina Allorch si presuma la presenza di queste sostanze si consiglia di verificare frequentemente e sempre dopo ogni intervento degli allarmi la sensibilit del rilevatore con gas di taratura Il rilevatore viene calibrato in fabbrica specificamente per la sostanza richiesta dal cliente Non possibile successivamente modificare la taratura dello stesso se non da parte del costruttore in quanto trattasi di una procedura che richiede procedure ed attrezzature particolari 3 INSTALLAZIONE 3 1 MODALIT PER IL CORRETTO MONTAGGIO Il rivelatore deve sempre essere installato con l elemento sensibile testa di rivelazione rivolta verso il basso Il contenitore del rivelatore per nessuna ragione deve essere forato per il fissaggio utilizzare i fori gi esistenti Per la versione EEx d da installare in aree classificate esplosive si raccomanda l utilizzo di pressacavi antideflagranti per sigillare l entrata dei cavi 3 2 SCHEMA TOPOGRAFICO CIRCUITO 1 4Vcc 12 24V 2 Rs485 A 3 Rs485 B 4 Gnd 5 4 Vcc 12 24V 6 4 20mA OUT 123 4 20mA ase Uscita negativa 2919 DE
17. me presenti Il rivelatore S MARTS viene commercializzato e nel contenitore antideflagrante EEx d certificato ATEX SMART3 AD e nel contenitore EEx nA SMART3 DU DS1043 028B 1 2 CARATTERISTICHE TECNICHE PER GAS ESPLOSIVI PELLISTORE NEMOTO serie NET PEL Certificata ATEX CESI 01ATEX013U o CESI 01ATEX066U 0 100 LIE Out analog 0 1 mA 12 24 Vdc 20 15 140 mA medio 180 mA massimo Microprocessor 10 bit Led ad intermittenza 4 20 mA default o 0 10 20mA Elemento sensibile Testa sensore Campo di misura Risoluzione Alimentazione Assorbimento a 12Vcc Unita di controllo Segnalazioni luminose Uscita proporzionale Uscite a rel con led di indicazione stato opzionale N 3 rel contatti in scambio liberi da tensione 24V 1A Compensazione delle derive di zero Procedura di autozero Filtro digitale medie mobili sui valori acquisiti Risoluzione 1024 punti Precisione 5 F S oppure 10 della lettura Tempo preriscaldamento 5 minuti Tempo stabilizzazione lt 1 minuto Tempo di risposta Ripetibilit lt 30 sec T50 lt 60 sec T90 5 del F S oppure 10 della lettura Temperatura di stoccaggio 25 60 C Temperatura operativa 10 55 C Umidit relativa 20 90 Rh 40 C Pressione di esercizio 80 110 KPa Velocit dell aria lt 6 mS Peso Eex d 700 gr EEx nA 400 gr Watch dog Interno per il controllo del microprocessore Dimensioni EExd L 105
18. ndo al massimo falsi allarmi Il microprocessore presente sulla scheda elettronica del rivelatore oltre al normale funzionamento provvisto dei seguenti algoritmi software Autodiagnosi del sistema che verifica costantemente il corretto funzionamento dell hardware sensore compreso Durante tale fase il LED rosso lampeggia molto lentamente Inseguitore di Zero per il mantenimento del parametro del sensore prescindendo da possibili derive dovute a variazioni termiche o fisiche del sensore stesso Filtro digitale che consente di correggere fenomeni transitori che potrebbero causare una instabilit del sistema o errori di lettura con conseguenti falsi allarmi Ciclo d isteresi viene applicato alle uscite digitali associate alle soglie d allarme e consente l eliminazione delle continue commutazioni nell intorno dei punti di soglia Watch dog per il controllo del microprocessore In caso di intervento la corrente di uscita viene forzata a OmA il led rosso di segnalazione resta acceso Se sul rilevatore installata la scheda 3 rel il rel di Fault si attiva Il Rivelatore fornisce una uscita proporzionale in corrente 4 20 mA corrispondente allo 0 96 del LIE Limite Inferiore d Esplosivit Opzional disponibile e una scheda dotata di 3 rel SKBR3N con contatti puliti liberi da tensione Un rel associato all uscita di Fault e watch dog mentre gli altri due possono essere associati a due delle tre soglie di allar
19. ontrol unit accepting a 4 20 mA input signal better when panels have an LC display for the proportional readout of the concentration 4 20 mA CONNECTION DIAGRAM The following drawing shows the connection of a SMART3 detector to a Urmet Domus control panel N B CONTROL PANELS ACCEPTING A 4 20MA INPUT SIGNALS ALLOW THE CONNECTION OF ONLY ONE DETECTOR PER INPUT 4 20 mA CONNECTION TO ANALOG CONTROL UNIT CONTROL UNIT S TERMINAL BOARD GAS DETECTOR TERMINALS IDENTIFICATION 1 Vcc 12 24V 2 Rs485 A 3 Rs485 B 4 GND 5 4 Vcc 12 24V 6 4 20mA OUT 4 TESTING AND WORKING OPERATIONS 4 1 POWER ON When the detector is powered on the red LED on the motherboard starts blinking at slow intermittence Output current is nearly 1 5mA After two minutes the red LED intermittence frequency is equivalent to its status see table on paragraph 4 3 and the output current is 4 0mA Once the warm up is over the detector starts working correctly and does not need any further operation although the optimal performances will be reached after two hours 4 2 TESTING Testing should be carried out by using appropriate gas mixture or alcohol vapour DS1043 028B 4 3 USE The detector works autonomously and automatically Once duly connected no further operations are required In case of malfunction the current is forced to 1 8mA Should the measured gas concentration exceed 100 the red LED on the motherboard lights up as for the FAU
20. software incorporates algorithms designed to correct the effects of transients which may cause unstable operation or incorrect readings with associated false alarms The main software algorithms are Self diagnostic procedure to control the detector main operational parts both hardware and sensing element During this phase the red LED blinks very slowly Zero point tracking to maintain the zero parameter of the sensor apart from possible drifts due to thermal or physical variations of the sensor Digital filter employed in the digital analysis of the analogue values sampled it allows correcting phenomena that might cause system s instability or wrong readouts thus provoking false alarms Hysteresis cycle applied to the outputs to eliminate continuous O C switching close to the preset alarm thresholds Watch dog for the microprocessor control In case of intervention the output current drops down to OmA The red LED stops blinking and remains on If the 3 relay card is plugged in Fault relay will activate The detector offers a proportional output current corresponding to 0 LEL Lower Explosion Limit Available optional e Athree relay card SKBR3N with tension free changeover contacts One relay is associated to Fault and Watch dog The remaining two are to be associated to two out of the three preset thresholds SMARTS detectors are available e in Explosion proof EExd ATEX certified enclosure SMART3 AD e in E