Home
INSTALLATION MANUAL INSTALLATIONSANLEITUNG
Contents
1. Po Cal N CAUTION Leave a space of 100 mm or more between the inlet port and the ceiling Fasten the unit securely with Special nuts A and B 3 3B Installation the unit Wall mounted type Floor standing concealed type A WARNING Install the air conditioner in a location which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries If the job is done with the panel frame only there is a risk that the unit will come loose Please take care 3 3B 1 UNIT INSTALLATION EXAMPLE Wall mounted type Floor standing concealed type Connect the locally purchased duct 1 Inlet side Connect the duct to the locally purchased inlet flange Connect the flange to the body with the locally purchased tapping screws Wind the inlet flange connecting to the duct with the aluminum tape etc to avoid the air leakage CAUTION When the duct is connected to inlet side remove contained filter and surely attach locally purchased filter at inlet opening 2 Outlet side Connect the duct with adjusting inside of outlet flange Wind the outlet flange connecting to the duct with the aluminum tape etc to avoid the air leakage Insulate the duct
2. En 15 6 9 Optional parts cable binding Cable tie Medium Accessories Remote sensor Receiver unit and Auto Louver grille Cable tie Medium Accessories External input and external output Avoid covering the air inlet Power supply with the wiring cable Avoid touching the ceiling with the wiring LLL Ceiling Do not bind the power supply cable and other cables together N CAUTION To protect the cable insulation after opening a knockout hole remove any burrs from the edge of the hole 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Set by either of the methods Each setting method is described 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 3 Automatic address settings Refer to the outdoor unit manual for detailed setting information Set IU AD REF AD SW to 0 N CAUTION Be sure to turn OFF the power before performing the field setting 7 1 Setting the address Manual address setting method If the receiver unit is attached the indoor unit address and the refrigerant circuit address can also be set up through the wireless remote controller CAUTION Use an insulated screwdriver to set the DIP s
3. Custom code setting for indoor unit Set the DIP switch SET 3 SW1 SW2 referring to the Table B Dip switch SET 3 Table B A Factory setting B DiPswihSET3SWi TON DIP switch seT3sw2 ON 7 3 Static pressure mode CAUTION If the applicable static pressure does not match the static pressure mode the static pressure mode may be changed to another mode manually RECOMMENDED RANGE OF EXTERNAL STATIC PRESSURE ARO07 09 12 14 18 OPa to 90Pa AR24 to 50Pa It is necessary to set up a static pressure mode for each usage of static pressure Static pressure can be set at site Relation between set values and static pressure are as the following table FUNCTION SETTING can be performed with the wired or wireless remote controller The remote controller is optional equipment Referto the wired or wireless remote controller manual for detailed setting information Function Number Setting Number Setting Static Pressure 7 4 Switching of drainage function If contained drain pump is not used set the drainage function to Invalid in the drainage function switching If contained drain pump is not use When used under WALL MOUNTED TYPE FLOOR STANDING CONCEALED TYPE When used in natural drainage under CEILING CONCEALED TYPE Installation method Set the DIP switch SET 4 SW1 SW1 refer
4. Duct Field supply Air Intake grille Field supply Outlet side 19 198 25 Inlet side ARO7 09 12 14 AR18 AR24 200 2 400 mm 200 3 600 mm 4 3 3A 2 INSTALL THE FILTERS Install the filters to the unit NS Filter Accessories 7 09 12 14 18 2 filters AR24 3 filters Unit Filter ye n 3 3A 3 DRILLING HOLES FOR BOLTS AND INSTALLING THE BOLTS Using the installation template drill holes for bolts 4 holes Installation template lt gt Drilling position for bolts Air 377mm ARoz o9 12 14 AR18 AR24 a omm oam 3 3A 4 FIX THE UNIT 1 Hang the unit Hanger Hanger bolt Nut A Field supply Washer Accessories Nut B Field supply En 5 Hanger bolt Nut A EZ Hanger Field supply ES Washer LH Accessories Nut B Field supply Unit 120 mi length It might become difficult to open and shut the Cover control box cover when the length exceeds 20 mm 2 Leveling Base horizontal direction leveling on top of the unit Ceiling GOOD PROHIBITED 10 mm or less Level he Air PROHIBITED
5. If the total number of units connected to the breaker exceeds 44 either add a 30mA breaker or use breakers with a greater capacity 6 1 1 Cable specifications Follow the specifications below for the power supply transmission and remote controller cable Recommended cable size mm Power supply 25 Type60245 IEC57 10 50 Hz 198 to 264 V cable or equivalent 2 Cable earth ground Transmission LonWorks 22 AWG LEVEL 4 NEMA 0 33 non polar 2 core twisted pair cable compatible cable d solid core diameter 0 65 mm Cable type Non polar 2 core Remote controller cable 0 33 to 1 25 Sheathed PVC 4 cable 2 wire type Remote controller cable 0 33 Sheathed PVC d cable 3 wire type Use shielded cable in accordance with local rules for remote controller cable Polar 3 core 6 2 Wiring method EXAMPLE Outdoor unit or RB unit 1 3 Transmission Xt 0 l V Z 7 C Ss ghr peer eee Indoor unit Indoor unit Indoor unit m Transmission n n s Remote FOE SET EAE MAMAA control Power supply 2 3 3 2 3 L u OG L u O NES Breaker Breaker Brea
6. Request your dealer or a professional installer to install the unit in accordance with this Manual An improperly installed unit can cause serious accidents such as water leakage electric shock or fire If the unit is installed in disregard of the instructions in the Installation Manual it will void the manufacturer s warranty Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire En 1 If refrigerant leaks while work is being carried out ventilate the area If the refrigerant comes in contact with a flame it produces a toxic gas Installation work must be performed in accordance with national wiring standards by authorized personnel only Except for EMERGENCY never turn off main as well as sub breaker of the indoor units during operation It will cause compressor failure as well as water leakage First stop the indoor unit by operating the control unit converter or external input device and then cut the breaker Make sure to operate through the control unit converter or external input device When the breaker is designed locate it at a place where the users cannot start and stop in the daily work This mark indicates procedures which if improperly performed might possibly result in personal harm to the user or damage to property Z CAUTION Read carefully all security inf
7. 2 1 Precautions for using the R410A refrigerant Z WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leakage make sure that it does not exceed the concentration limit If a refrigerant leakage exceeds the concentration limit it can lead to accidents such as oxygen starvation Do not touch refrigerant that has leaked from the refrigerant pipe connections or other area Touching the refrigerant directly can cause frostbite If a refrigerant leakage occurs during operation immediately vacate the premises and thoroughly ventilate the area If the refrigerant comes in contact with a flame it produces a toxic gas 2 2 Special tool for R410A Z WARNING To install a unit that uses the R410A refrigerant use dedicated tools and piping materials that have been manufactured specifically for R410A use Because the pressure of the R410A refrigerant is approximately 1 6 times higher than the R22 failure to use dedicated piping material or improper installation can cause rupture or injury Furthermore it can cause serious accidents such as water leakage electric shock or fire Tool name Contents of change Name and Shape Application Pressure is huge and cannot be
8. E P Grille 3 Leave the space required to service the air conditioner b 4 A place from where the air can be distributed evenly throughout the room by the unit Inlet air 150 150 5 Install the unit where connection to the outdoor unit or RB unit is easy or more Strong and 7 7 1 more 6 Install the unit where the connection pipe can be easily installed Strong and 1 durable floor 74 150 durable floor 400 mm 20mm 20mm 7 Install the unit where the drain pipe can be easily installed or more or more or more or more 7 pip y 8 Install the unit where noise and vibrations are not amplified 9 Take servicing etc into consideration and leave the spaces Also install the unit Right side where the filter can be removed PIPE side Dia QO are Grill 3 2A Installation dimensions Ceiling concealed TET NG Provide a service access for inspection purposes 3 Do not place any wiring or illumination in the service space as they will impede service 150 mm Inlet air 150 mm Installation Dimensions 2 Strong and 7 7 Tor more Strong and durable ceilin Strongand aec dies g g 150mm durable floor 490 mm 20mm 20mm 2 or more or more or more or more Indoor unit n m T Right 3 3A Installation the unit Ceiling concea
9. 12 6 5 External input and external output Optional parts Controller PCB OFF ON SW3 sw4 511 sw2 itch Q do Mz Dry contact terminal a CNA04 CNAO2 E Output terminal ral CNB01 Apply voltage terminal CNAO3 01 1 External input Indoor unit can be Operation Stop Emergency stop or Forced stop by using indoor unit PCB CNAO1 or CNAO2 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04 A twisted pair cable 22 AWG should be used Maximum length of cable is 150 m Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Input select Use either one of these types of terminal according to the application Both types of terminals cannot be used simultaneously e Apply voltage terminal CNA01 CNA03 When a power supply must be provided at the input device you want to connect use the Apply voltage terminal 1 CNAO3 DC power supply PCB 12 to 24V Load resistance i Input device 1 Input
10. 8 13 2 12 70 1 2 0 to 0 5 16 6 15 88 5 8 19 7 19 05 3 4 24 0 When using conventional R22 flare tools to flare R410A pipes the dimension A should be approximately 0 5 mm more than indicated in the table for flaring with R410A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A It is recommended that a R410A flaring tool is used Width across flats Pipe outside diameter Width across flats of mm in Flare nut mm re 6 35 1 4 17 N 9 52 3 8 22 12 70 1 2 26 2 15 88 5 8 29 19 05 3 4 36 4 3 2 Bending pipes If pipes are shaped by hand be careful not to collapse them Do not bend the pipes in an angle more than 90 When pipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than 3 times N CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection N CAUTION Be sure to install the pipe against the port on the indoor unit correctly If the centering is improper the flare nut cannot tighten smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe Hold the t
11. Auto louver grille Optional parts Connection method Connection terminals Controller PCB Enee peas m Auto louver grille terminal CN12 mim Remove the existing connector and replace it with the remote sensor connector ensure that the correct connector is used The original connector should be insulated to ensure that it does not come into contact with other electrical circuitry Use conduit hole when external output cable is used N CAUTION To protect the cable insulation after opening a knockout hole remove any burrs from the edge of the hole Setting for room temperature correction When a remote sensor is connected set the function setting of indo
12. D Drain hose Hose band Fasten the Hose band at the position where horizontal against earth ground The Hose band must be positioned at the right side of the Drain hose as the figure 2 Be sure to connect Drain pipe with adhesive polyvinyl chloride so that there is no leakage Applying area of adhesive Joint pipe Field supply Drain pipe VP25 Field supply 4 mm or less CAUTION Do not connect to the Drain hole with adhesive Using adhesive may cause damage and water leaks 3 After installing the Drain hose D check if the drainage is smooth N CAUTION To prevent excessive force on Drain hose 1 avoid bends or twists To bend or twist may cause water leaks 4 After checking for drainage attach the Drain hose insulation B 3 to insulate following the instructions as in the figures To avoid space with Drain hose D and Hose band press firmly the Drain hose insulation B Ensure there is i no space i E Drain hose insulation B 7 Accessories STEP1 STEP3 Butt the insulation against the unit Unit Slit STEP 1 Press firmly Press firmly K D Press firmly STEP 2 Slit Press firmly Press firmly Roll the in wwa sulation over the joint STEP 3 FINISH Check that there is no gap between the unit and the drain hose insulation When drain pump is used Ceil
13. control box En 8 1 Ceiling concealed type Gap of 1 5 to 2m GOOD Downward gradient 4 4 2 5 to 5 0 mm E Eyi Supporter 100 mm or more L iz V VP25 O D 32 mm Locall d ocally arranged pipe onmens 2 PROHIBITED Zz Rise Z Air bleeding Observe the following procedures to construct centralized drain pipe fittings A ES 1 j VP30 or more Downward gradien 2 38 1 100 2 Wall mounted type Floor standing concealed type GOOD Downward gradient 2 5 to 5 0 mm 100mm 25 0 0 32 mm or more or more Locally arranged pipe PROHIBITED Air bleeding Trap Observe the following procedures to construct centralized drain pipe fittings M VP30 or more O D 38 mm or more Downward gradient 1 100 or more En 9 5 2 Install the drain pipe 1 Be sure to use supplied Drain hose D and Hose band 2 Hose band Accessories D Drain hose Accessories Drain Hard PVC side hole Hose band 4 mm or less
14. for wiring Otherwise a short circuit could result Use the included connection cables and power cables or ones specified by the manufacturer Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoor unit or RB unit Erroneous wiring may cause burning of the electric parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire Always fasten the outside covering of the connection cable with the cable clamp If the insulator is chafed electric discharge may occur Install an earth leakage breaker In addition install the earth leakage breaker so that the entire AC main power supply is cut off at the same time Otherwise electric shock or fire could result Always connect the earth ground cable Improper earthing grounding work can cause electric shocks Install the remote controller cables so as not to be direct touched with your hand Perform wiring work in accordance with st
15. of the control box GOOD Gap of 1 5 to 2 1 772227 2 Y Supporter Locally arranged pipe 1 M V VP25 O D 1 Max 300mm 32 mm or more 700 mm or less Horizontal 2 upward gradient PROHIBITED Air bleeding Rise 7 Me YZ Zz FZ Trap LL Ils 2 2 Observe the following procedures to construct centralized drain pipe fittings VP30 or more O D 38 mm or more Downward gradient 1 100 more 7 4 Le 700 mm or less A 5 1B When drain pump is not used Natural drainage N CAUTION Set 7 4 Switching of drainage function Drain pump cannot be used if it is installed in wall mounted type floor standing concealed type If the drain pump is not used please replace with the drain cap Ceiling concealed type Wall mounted type Floor standing concealed type Use general hard polyvinyl chloride pipe VP25 outside diameter 32 mm Do not perform a rise trap and air bleeding Provide a downward gradient 1 100 or more Provide supporters when long pipes are installed Usean insulation material as needed to prevent the pipes from freezing Install the pipes in a way that allows for the removal of the
16. on the interior surface Otherwise the expansion valve or capillary tube may become blocked with contaminants Improper pipe selection will degrade performance As an air conditioner using R410A incurs pressure higher than when using conventional R22 refrigerant it is necessary to choose adequate materials 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units or RB unit respectively onto the pipe and perform the flare processing with a flare tool Use the special R410A flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes Check if L is flared uniformly and is not cracked or scratched xm Thicknesses of copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are available on the market Thicknesses of Annealed Copper Pipes R410A Pipe outside diameter mm in Thickness mm 6 35 1 4 0 80 9 52 3 8 0 80 12 70 1 2 0 80 15 88 5 8 1 00 19 05 3 4 1 20 4 2 Pipe req
17. the screw heads may be damaged and prevent the screws from being properly tightened 4 Do not tighten the terminal screws too much otherwise the screws may break 5 See the table for the terminal screw tightening torques 6 Please do not fix 2 power supply cables with 1 screw Strip 25 mm Loop e Screw with special washer Screw with Gable special washer Cable end Loop lt I Cable end pet zi zz Loop af Terminal block T Cable N WARNING When using solid core cables do not use the ring terminal If you use the solid core cables with the ring terminal the ring terminal s pressure bonding may malfunction and cause the cables to abnormally heat up B For strand wiring 1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening tor
18. to avoid the dew condensation N CAUTION Check that duct work does not exceed the range of external static pressure of equipment Make sure to insulate ducts to avoid the dew condensation Make sure to insulate between ducts and walls if metal ducts are used Please explain handling and washing methods of locally purchased materials to the customer To prevent people from touching the parts inside the unit be sure to install grilles on the inlet and outlet ports The grilles must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installation screws to prevent water from leaking around the port AR07 09 12 14 18 Model Set the static pressure outside the unit to 90 Pa or less the allowable range is between 0 and 90 Pa AR24 Model Set the static pressure outside the unit to 50 Pa or less the allowable range is between 0 and 50 Pa Remove the screws and then remove cover and fan guard Install the cover with the screws as shown in the illustration below Model Screw AR07 09 12 14 9 AR18 11 AR24 13 screw Cover Fan guard 3 3B 2 INSTALL THE FILTER Install the filters Accessories to the unit Filter AR07 09 12 14 18 2 filters AR24 3 filters Unit Filter N 4 3 3B 3 FIX TH
19. 9 5 E 15 15 amp CNAO2 1 o IE z s o ices uu ek i mM E t CNAO2 B 1 0 B Device for DC Current NOTE When connected to multiple indoor units directly it will cause breakdown Operation behavior Edge f e Input signal type Pulse The input signal type can be selected It is switched by DIP switch on the indoor unit PCB DIP switch Set 2 SW2 Input signal type OFF Factory setting Edge The width of pulse ON Pulse must be longer than 200msec e When function setting is Operation Stop mode In the case of Edge input Connector Input signal Command OFF ON Operation Ch1 of 1 or CNA02 ON OFF Stop In the case of Pulse input Connector Input signal Command Ch1 OFF ON Operation CNAO1 or 2 Ch2 OFF ON Stop The last command has priority The indoor units within the same remote controller group operates in the same mode e When function setting is Emergency stop mode In the case of Edge input Connector Input signal Command OFF ON Emergency stop Ch1 of CNAO1 or CNAO2 ON OFF Normal In the case of Pulse input Connector Input signal Command Ch1 OFF ON Emergency stop CNAO1 or CNA02 Ch2 OFF ON Normal All indoor units of same refrigera
20. D 83 DIP switch SW SW SW SW 1 2 3 4 Table C DIP switch SET 4 SW3 Cooling temperature setting range OFF Factory setting Standard 18 to 30 C ON Extension 18 to 32 C NOTE Please do not make a standard setup and an extension setup intermingled in remote controller group 7 7 Function setting FUNCTION SETTING can be performed with the wired or wireless remote controller The remote controller is optional equipment Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 Refer to 7 1 Setting the address for indoor unit address and refrigerant circuit ad dress settings Turn the power of the indoor unit ON before starting the setting Turning on the power to the indoor units initializes EEV so make sure the piping air tight test and vacuuming have been conducted before turning on the power Also check again to make sure no wiring mistakes were made before turning on the power Function details Function Function Setting number Default Details 00 Default Adjust the filter cleaning interval Filter indicator notification If the notification is too interval 11 01 Longer early change to setting 01 If the notification is too late change to 02 Shorter setting 02 00 Enable O A T Disable Enable or disable the filter in
21. E UNIT 1 Fixing method of the unit To prevent overturning fix the unit to the floor or the wall To avoid the vibration of the unit insert the spacer between the unit and the floor or the wall and fix it 2 Leveling Base horizontal direction leveling on top of the unit 0 lt 2 IN GOOD 10 mm or less PROHIBITED N CAUTION Fasten the unit securely with Special nuts A and B En 6 4 PIPE INSTALLATION N CAUTION Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R410A models Also when storing the piping securely seal the openings by pinching taping etc While welding the pipes be sure to blow dry nitrogen gas through them 4 1 Selecting the pipe material N CAUTION Do not use existing pipes from another refrigeration system or refrigerant Use pipes that have clean external and internal sides without any contamination which may cause trouble during use such as sulfur oxide dust cutting waste oil or water It is necessary to use seamless copper pipes Material Phosphor deoxidized seamless copper pipes It is desirable that the amount of residual oil is less than 40 mg 10 m Do not use copper pipes that have a collapsed deformed or discolored portion especially
22. _AMIRSTAGE ARXD07GALH ARXDO9GALH ARXD12GALH ARXD14GALH ARXD18GALH ARXD24GALH R410A REFRIGERANT This Air Conditioner contains and operates with refrigerant R410A THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED BY QUALIFIED PERSONNEL egulations id or service of this product FUJITSU GENERAL LIMITED A CAUTION Refer to Figura su nd Ten movan and local legislation regulations co instal e operation manuals before INSTALLATION MANUAL INDOOR UNIT Duct type For authorized service personnel only INSTALLATIONSANLEITUNG INNENGERAT Kanaltyp Nur fur autorisiertes Fachpersonal MANUEL D INSTALLATION APPAREIL INTERIEUR type conduit Pour le personnel agr uniquement MANUAL DE INSTALACION UNIDAD INTERIOR Tipo conducto Unicamente para personal de servicio autorizado MANUALE DI INSTALLAZIONE UNITA INTERNA tipo a condotto A uso esclusivo del personale tecnico autorizzato EFXEIPIAIO ETKATAZTAZHZ EXOTEPIKH MONAAA T rroc aywyo M vo EEOUDIOSOTNHEVO TEXVIK MANUAL DE INSTALA O UNIDADE INTERIOR Tipo de tubagem Apenas para t cnicos autorizados KILAVUZU ic UNITE Kanal tipi Yaln zca yetkili servis pe
23. accordance with relevant local and national regulations Specifications for local wiring power cord and branch wiring are in compliance with local code Max wire length Set a length so that the voltage drop is less than 2 Increase the wire diameter when the wire length is long Refer to the table for the breaker specifications of each installation condition Perform the power crossover wiring within the range of the same refrigerant system When the crossover wiring is done make a connection for indoor units to satisfy conditions A and B below A Current breaker requirements Model MCA MFA ARXD07GALH 0 38 A ARXDO9GALH 0 42A ARXD12GALH 0 46A 20A ARXD14GALH 0 74 A ARXD18GALH 0 66A ARXD24GALH 0 94 A MCA Minimum Circuit Ampacity MFA Main Fuse Ampacity When the power crossover wiring is done make it so that the total of the MCA of the connected RB units and indoor units does not exceed the 15 A For RB unit MCA refer to the RB unit installation manual If the capacity of connected RB units and indoor units exceeds the upper limit either add breakers or use a breaker with a greater capacity B Earth leakage breaker requirements Maximum connectable indoor units or Breaker capacity indoor units RB units 30 mA 0 1 sec or less 44 or less 100 mA 0 1 sec or less 45 to 128 Heat pump type indoor units Heat recovery type indoor units and RB units
24. andards so that the air conditioner can be operated safely and positively Connect the connection cable firmly to the terminal board Imperfect installation may cause a fire If the supply cable is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard N CAUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller terminals as this will damage the product Never bundle the power supply cable and transmission cable remote controller cable together Separate these cable by 50 mm or more Bundling these cables together will cause miss operation or breakdown When handling PCB static electricity charged in the body may cause malfunction of the PCB Follow the cautions below Establish an earth ground for the indoor and outdoor units and peripheral devices Cut power breaker off Touch metal part of the indoor unit for more than 10 seconds to discharge static electricity charged in the body Do not touch terminals of parts and patterns implemented on PCB En 10 6 1 Electrical requirement Voltage rating 230 V Operating range 198 to 264 V Select the power cable type and size in
25. d the range of external static pressure of equipment Make sure to insulate ducts to avoid the dew condensation Make sure to insulate between ducts and walls if metal ducts are used Please explain handling and washing methods of locally purchased materials to the customer To prevent people from touching the parts inside the unit be sure to install grilles on the inlet and outlet ports The grilles must be designed in such a way that cannot be removed without tools Flange Field supply Aluminum tape Tapping screw for flange connection M4 x 10mm Field supply z u Insulation material Field supply Aluminum tape Flange Field supply Air Duct Intake grille Field supply Field supply Bottom Inlet Side Outlet When connecting the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installation screws to prevent water from leaking around the port AR07 09 12 14 18 Model Set the static pressure outside the unit to 90 Pa or less the allowable range is between 0 and 90 Pa AR24 Model Set the static pressure outside the unit to 50 Pa or less the allowable range is between 0 and 50 Pa Replace the cover as follows Remove the screws and then remove cover and fan guard Install the cover with the screws as shown in the illustration below Model Screw AR07 09 12 14 9 AR18 11 AR24 13
26. device 2 Input device 3 connected unit 1 Make the power supply DC12 to 24V Select a power supply capacity with an ample surplus for the connected load Do not impress a voltage exceeding 24V across pins 1 2 and 1 3 a The allowable current is DC 5mA to 10mA Recommended DC5mA Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor units with a connected unit be sure to make a branch outside the indoor unit using a pull box etc as shown on below example En 13 DC power supply 4 12to24V Oo 2 gt Indoor unit Load i i resistance i i ee ded i Input device 2 Indoor unit connected unit Indoor unit e Dry contact terminal CNA02 CNA04 When a power supply is unnecessary at the input device you want to connect use the Dry contact terminal 2 CNAO4 connected unit c Select very low current use contacts usable at DC12V DC1mA or less d The wiring is different from Apply voltage terminals Be sufficiently careful when wiring When connected to Dry contact terminals of multiple indoor units with a connected unit insulate each indoor unit with relay etc as shown on below example x 5 5 CNA02 9 gt scit E III 1
27. dicator Filter indicator 3 action 13 Display Setting 02 is for use with a central only on remote controller 02 central remote controller Cool air 00 Default Adjust the cool air trigger tempera ture To lower the trigger tempera orm 30 01 Adjust 1 ture use setting 01 To raise the 02 Adjust 2 trigger temperature use setting 02 00 Default Adjust the heat air trigger tempera ture lower the trigger temperature Heat air 01 Adjust 1 by 6 degrees C use setting 01 To temperature 31 lower the trigger temperature by 4 trigger 02 Adjust 2 degrees C use setting 02 To raise the trigger temperature use setting 03 Adjust 3 03 Enable or disable automatic system 00 Enable restart after a power outage Auto restart is an emergency func tion such as for power failure etc Auto restart 40 Do not start and stop the indoor unit by this function in normal operation Be sure to operate by the control 01 Disable unit converter or external input device 00 Superlow Restrain the cold airflow with making Cool Air 43 Follow the the airflow lower when starting heat Prevention tting on ing operation To correspond to the 01 seung ventilation set to 01 the remote controller 00 Start Stop Allow an external controller to start or stop the system or to perform an emergency stop If an emergency stop is p
28. e ERROR CODES please refer to the Manual of IR Receiver Unit or Wired Remote Controller
29. erformed External 46 01 Emergency from an external controller all control stop refrigerant systems will be disabled f forced stop is set indoor unit stops by the input to the external Forced input terminals and Start Stop by a 02 stop remote controller is restricted d Al Change the target for reporting Error report 47 Display only errors Errors can either be reported target on central in all locations or only on the central 01 remote remote controller controller Follow the When set to 01 the fan stops when Fan setting 00 setting on the thermostat is OFF in cooling when cooling 49 the remote operation Connection of the wired thermostat controller remote controller 2 wire type OFF or 3 wire type and switching its 01 Stop thermistor are necessary 8 TEST RUN 8 1 Test run using Outdoor unit Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to be used for the test run 8 2 Test run using Remote Controller Refer to the Installation Manual for the remote controller to perform the test run using the wireless remote controller When the air conditioner is being test run the OPERATION and TIMER indicators flash slowly at the same time En 18 9 CHECK LIST 10 ERROR CODES Pay special attention to the check items below when installing the indoor unit s After installation is complete be sure to check the following check items again CHECK ITEMS If n
30. es large one on each end of the insulation Make sure that the cable ties overlap the heat insulation pipe Coupler heat insulation Accessories Cover this portion with heat insulation cable tie Large Heat insulation Accessories CAUTION After checking for gas leaks refer to the Installation Manual of the outdoor unit perform this section Install heat insulation around both the large gas and small liquid pipes Failure to do so may cause water leaks 5 INSTALLING DRAIN PIPES Z WARNING Do not insert the drain piping into the sewer where sulfurous gas occurs Heat exchange erosion may occur Insulate the parts properly so that water will not drip from the connection parts Check for proper drainage after the construction by using the visible portion of transparent drain port and the drain piping final outlet on the body N CAUTION Do not apply adhesive agent on the drain port of the body Use the attached drain hose and connect the drain piping 5 1A When drain pump is used Use general hard polyvinyl chloride pipe VP25 outside diameter 32 mm Do not perform a rise trap and air bleeding Provide a downward gradient 1 100 or more Provide supporters when long pipes are installed Usean insulation material as needed to prevent the pipes from freezing Install the pipes in a way that allows for the removal
31. es or art objects It can degrade the quality of the preserved or stored objects 300 mm or more 100 mm more Do not install where there is the danger of combustible gas leakage 400 mm or Do not install the unit near a source of heat steam or flammable gas more Install the unit where drainage does not cause any trouble S rvice space Install the indoor unit power supply cable transmission cable and remote controller prevent TV reception interferenes or radio noise rors The purpose ofthisisio Even if they are installed more than 1 m apart you could still receive noise under Floor standing concealed type some signal conditions If children under 10 years old may approach the unit take preventive measures so that The wall mounted type floor standing concealed type requires a tem they cannot reach the unit perature correction setting Perform this in 7 FIELD SETTING Decide the mounting position with the customer as follows dmm 10mm or less or less Right side 1 Install the indoor unit on a place having a sufficient strength so that it withstands PIPE side against the weight of the indoor unit Left side 2 The inlet and outlet ports should not be obstructed the air should be able to blow all j 2 over the room
32. ication error Network communication error Peripheral unit communication error Indoor unit address setting error Connection unit number error in wired remote controller system ndoor unit power supply abnormal ndoor uni error ndoor uni communication circuit wired remote controller error ndoor unit room temp thermistor error ndoor unit heat ex temp thermistor error ndoor unit fan motor 1 error ndoor unit coil expansion valve error ndoor unit water drain abnormal Outdoor unit miscellaneous error RB unit error Display mode 0 55 ON 0 5s OFF 0 15 ON 0 15 OFF Number of flashing Wired Remote Controller Display UTY RNKY UTY RNKG UTY RNKYT 3 wire type Error code SU MO TU WE l FR URY RNRY UTY RNRG 2 wire type Mode Touch the Next Page or previous page to switch to other indoor unit information Y Error Information Pee us m A Error icon Fri 10 00AM Status Page 1 3 Set Ter Fan Air Flow Direction pE Eror Code 1445 JI status f menu J Monitor t Touch the Status Touch the Error Information Error Code 14 15 Y 2 digit numbers are corresponding to the error code in the preceding table For more information refer to the installation manual of the remote controller For details on marking th
33. ing concealed type only Do not cover the JL panel window When drain pump is not used Natural drainage Do not cover the control box cover Note Check for drainage Pour about 1 liter of water from the position shown in the diagram or from the airflow outlet to the dew tray Check for any abnormalities such as strange noises and whether the drain pump functions normally Au N CAUTION Make sure the drain water is properly drained 6 ELECTRICAL WIRING N WARNING Electrical work must be performed in accordance with this Manual by a person certified under the national or regional regulations Be sure to use a dedicated circuit for the unit An insufficient power supply circuit or improperly performed electrical work can cause serious accidents such as electric shock or fire Before starting work check that power is not being supplied to the all units For wiring use the prescribed type of cables connect them securely making sure that there are no external forces of the cables applied to the terminal connections Improperly connected or secured cables can cause serious accidents such as overheating the terminals electric shock or fire Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Install sleeves into any holes made in the walls
34. ker ms A LIN LIN LIN Power supply Remote controller Remote controller Remote controller Master Slave En 11 1 When connecting to the Heat Recovery System refer to the installation manual of the RB unit 2 Earth Ground the remote controller if it has a earth ground cable 3 When connecting the 2 wire type remote controller Y3 is not used Crossover wiring of power supply Indoor unit Indoor unit Indoor unit Power supply Power supply Power supply L Mg L N O o o Pull box E a Breaker Pull box 1 N Power supply Earth Ground the remote controller if it has an earth ground wire Connect the earth ground wire of the remote controller to the earth ground terminal of transmission Before attaching the cable to terminal block 6 3 1 Power supply cable Adjust the length of power supply cable to avoid excessive tension with referring figure below 20 mm Earth Ground cable L 30 mm A For solid core wiring 1 To connect the electrical terminal follow the below diagram and connect after looping it around the end of the cable 2 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 3 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise
35. led side side type D 2 N WARNING Install the air conditioner in a location which can withstand a load of at least 5 times the i weight of the main unit and which will not amplify sound or vibration If the installation 150 mm 400 mm location is not strong enough the indoor unit may fall and cause injuries or more or more If the job is done with the panel frame only there is a risk that the unit will come loose Please take care En 3 3 3A 1 UNIT INSTALLATION EXAMPLE CEILING CONCEALED TYPE Connect the locally purchased duct 1 Inlet side Connect the duct to the locally purchased inlet flange Connect the flange to the body with the locally purchased tapping screws Wind the inlet flange connecting to the duct with the aluminum tape etc to avoid the air leakage CAUTION When the duct is connected to inlet side remove contained filter and surely attach locally purchased filter at inlet opening 2 Outlet side Connect the duct with adjusting inside of outlet flange Wind the outlet flange connecting to the duct with the aluminum tape etc to avoid the air leakage Insulate the duct to avoid the dew condensation Side Inlet Side Outlet Insulation material Field supply Aluminum tape Flange Field supply Duct Intake grille Field supply Field supply Side Inlet Side Outlet Duct CAUTION Check that duct work does not excee
36. location Correct initial installation location is important because it is difficult to move unit after it is installed 240 mm or more Service access Ceiling 2500 mm or more When no ceiling N CAUTION Do not install the unit in the following areas Area with high salt content such as at the seaside Floor It will deteriorate metal parts causing the parts to fail or the unit to leak water 2 Area filled with mineral oil or containing a large amount of splashed oil or steam Adjust the wind direction in the room depending on the shape of blow out opening such as a kitchen Service access It will deteriorate plastic parts causing the parts to fail or the unit to leak water i Area that generates substances that adversely affect the equipment such as sulfuric 1 7 gas chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline Control If gas leaks and settles around the unit it can cause a fire Z d box Unit Area where animals may urinate on the unit or ammonia may be generated Do not use the unit for special purposes such as storing food raising animals growing plants or preserving precision devic
37. measured with a Cable tie Medium For transmission and remote controller conventional R22 gauge To prevent erroneous mixing cable binding of other refrigerants the diameter of each port has been 3 Gauge manifold changed It is recommended to use a gauge manifold with a high pressure display range 0 1 to 5 3 MPa and a low pressure H display range 0 1 to 3 8 MPa Cable tie Large For fixing the coupler heat insulation To increase pressure resistance the hose material and base Charging hose size were changed A conventional R22 vacuum pump can be used by installing a vacuum pump adapter Vacuum pump Be sure that the pump oil does not backflow into the system Filter Small Use one capable for vacuum suction of 100 7 kPa 5 Torr 755 mmHg Gas leakage detector Special gas leakage detector for HFC refrigerant RA10A ARO7 09 12 14 24 2 3 Accessories EE Filter Big NWARNING For installation purposes be sure to use the parts supplied by the manufacturer or other prescribed parts The use of non prescribed parts can cause serious accidents such as the unit to fall water leakage electric shock or fire The following installation parts are furnished Use them as required Drain hose For installing drain pipe VP25 O D 32 1 0 25 Keep the Installation Manual a safe place and do not discard any other accessories until the installation work has been com
38. nt 6 2 Wiring method 6 3 Unit wiring 6 4 Connection of wiring 12 6 5 External input and external output Optional 13 6 6 Remote sensor Optional parts 6 7 IR receiver unit Optional parts 6 8 Auto louver grille Optional parts 6 9 Optional parts cable binding 7 FIELD SETTING 7 1 Setting the address 7 2 Custom code setting 7 3 Static pressure mode 7 4 Switching of drainage function 7 5 Switching of airflow direction louver function 7 6 Switching the upper limit of cooling temperature Tr Function SaN iere reet pre p d epe Crete 8 TESTRUN 8 1 Test run using Outdoor unit PCB 8 2 Test run using Remote Controller eene 18 pM rr AN ci E 19 10 ERROR CODE T 19 1 SAFETY PRECAUTIONS Be sure to read this Manual thoroughly before installation The warnings and precautions indicated in this Manual contain important information pertaining to your safety Be sure to observe them Hand this Manual together with the Operating Manual to the customer Request the customer to keep them on hand for future use such as for relocating or repairing the unit This mark indicates procedures which if improperly performed NWARNING might lead to the death or serious injury of the user
39. nt system stops when Emergency stop operates e When function setting is Forced stop mode In the case of Edge input Connector Input signal Command OFF ON Forced stop Ch1 of CNA01 or CNAO2 ON OFF Normal In the case of Pulse input Connector Input signal Command Ch1 OFF ON Forced stop CNAO1 or 2 Ch2 OFF ON Normal When the forced stop is triggered indoor unit stops and Operation Stop operation by a remote controller is restricted When forced stop function is used with forming a remote controller group connect the same equipment to each indoor unit within the group Selection method of functions Operation Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit e Forced thermostat off function Edge input only Connector Input signal Command OFF ON Thermostat off Ch3 of CNA03 or CNA04 ON OFF Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed Output voltage Hi DC12V 2V Lo OV Permissible current 50mA Output select e When indicator etc are connected directly Operation indicator Error indicator Indoor unit Fan status indicator connec
40. or unit as indicated below Wiring arrangement Function Number 30 Controller PCB Clamp Set the Setting Number to 00 Default Function Number 31 z Set the Setting Number to 02 d N Refer to 7 7 Function setting for details about Function Number and Setting Number Eman aaa E pog gt 6 7 IR receiver unit Optional parts x For the installation method please refer to the INSTALLATION MANUAL of IR receiver IE A unit U r3 Connection method E V H e Connection terminals Ll Controller PCB g l H rg CE i JL g EE H B IR receiver c I Solo unit terminal N CAUTION To protect the cable insulation after opening a knockout hole remove any burrs from the edge of the hole
41. ormation before use or install the air conditioner Do not attempt to install the air conditioner or a part of the air conditioner by yourself This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation place The installation must be carried out in compliance with regulations in force in the place of installation and the installation instructions of the manufacturer This unit is part of a set constituting an air conditioner It must not be installed alone or with non authorized by the manufacturer Always use a separate power supply line protected by a circuit breaker operating on all wires with a distance between contact of 3mm for this unit The unit must be correctly grounded and the supply line must be equipped with a differential breaker in order to protect the persons The units are not explosion proof and therefore should not be installed in explosive atmosphere Never touch electrical components immediately after the power supply has been turned off Electric shock may occur After turning off the power always wait 5 minutes before touching electrical components This unit contains no user serviceable parts Always consult authorized service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT
42. orque wrench at its grip keeping it at a right angle with the pipe in order to tighten the flare nut correctly Connect the piping so that the control box cover can easily be removed for servicing when necessary En 7 In order to prevent water from leaking into the control box make sure that the piping is well insulated When the flare nut is tightened properly by your hand hold the body side coupling with a separate spanner then tighten with a torque wrench See the table below for the flare nut tightening torques Tighten with 2 wrenches Holding wrench Torque wrench Flare nut Indoor unit pipe Body side Connection pipe Flare nut mm in 6 35 1 4 dia 9 52 3 8 dia 12 70 1 2 dia 15 88 5 8 dia 19 05 3 4 dia Tightening torque N m kgf cm 16 to 18 160 to 180 32 to 42 320 to 420 49 to 61 490 to 610 63 to 75 630 to 750 90 to 110 900 to 1 100 4 4 Installing heat insulation Install the heat insulation material after performing a refrigerant leak check see the In stallation Manual for the outdoor unit for details 4 4 1 COUPLER HEAT INSULATION Insulate by the coupler heat insulation Accessories around the gas pipe and liquid pipe of indoor side After installing the coupler heat insulation wrap both end with vinyl tape so that there is no gap After affixing the coupler heat insulation secure it with 2 cable ti
43. ot performed correctly cd Has the indoor unit been installed Vibration noise indoor unit correctly may drop Has there been a check for gas leaks No cooling No heating refrigerant pipes Has heat insulation work been Water leakage completed drain easily from the indoor Water leakage Is the voltage of the power source the same as that indicated on the label on the indoor unit Are the wires and pipes all connected completely Is the indoor unit earthed grounded 15 the connection cable the specified thickness Are the inlets and outlets free of any obstacles Does start and stop air conditioner operation by remote controller or external No operation device After installation is completed has the No operation heat or burn damage No operation heat or burn damage Short circuit No operation heat or burn damage No cooling No heating proper operation and handling been explained to the user En 19 If you use a wired type remote controller error codes will appear on the remote control ler display If you use a wireless remote controller the lamp on the photodetector unit will output error codes by way of blinking patterns See the lamp blinking patterns and error codes in the table below Error indications Wired Remote OPERATION TIMER lamp FILTER lamp Controller Error lamp green orange red code Error contents Remote controller commun
44. pleted Do not discard any accessories needed for installation until the installation work has been completed Name and Shape Application Hose band For installing drain hose Operating Manual Drain hose insulation B Insulates the drain hose This book For positioning the indoor unit Model No Application Installation Manual Installation template iR TGceiverunit UTB WC For the wireless remote controller UTY XSZX Room temperature sensor External output wire 9379529013 For output port For control input port Washer For installing indoor unit External input wire D 9368779016 Apply voltage terminal External input wire F 9368779023 For control input port Dry contact terminal External input wire B 9368778002 For forced thermostat Apply voltage terminal External input wire E 9368778019 se hber For indoor side pipe joint Large pipe port Dry contact terminal 1 1 Auto louver grille UTD G S W For Auto louver grille Coupler heat insulation Large i Coupler heat insulation Small For indoor side pipe joint Small pipe En 2 3 INSTALLATION WORK 300 mm or more 20 mm or more SERM 20 Z WARNING A E Select installation locations that can properly support the weight of the indoor Install 4 the units securely so that they do not topple or fall 3 1 Selecting an installation
45. ques 7 Please do not fix 2 power supply cables with 1 screw Ring terminal EN 7 gt eS Screw with spe Screw with Cable es cial washer special washer Ring terminal Ring z m terminal ef en block 71 Cable 6 4 Connection of wiring 1 Remove the cover 2 Connect the connection cable N CAUTION When switching the DIP switch SW1 be sure to turn off the power supply to the indoor unit Otherwise the PC board of the indoor unit may be damaged Z WARNING Use ring terminals and tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly cause heavy damage inside the unit Tightening torque M4 screw 1 2 to 1 8 Power supply L N GND 12 to 18 kgf cm 6 3 2 Transmission and Remote controller cable Transmission cable 25 mm Shielded cable no film L _ 40mm Remote controller cable For 3 wire type For 2 wire type 20 mm 20 mm X Y Connect remote controller and transmission cables as shown in Fig A Fig A GOOD PROHIBITED Different diameter Connect to 1 side A WARNING Tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly cause heavy damage inside the unit Terminal number Tightening torque M3 screw Transmission X1 X2 Remo
46. ring to the Table C X10 MED DIP switch SET 4 Table C Drainage function Valid Factory setting DIP switch OFF SET4SW1 ON Drainage function Invalid 7 5 Switching of airflow direction louver function When auto louver grille Optional parts is attached set the airflow direction louver func tion Valid The airflow direction louver of auto louver grille can be operated by the remote controller while the airflow direction louver function is valid Installation method Set the DIP switch SET 4 SW2 SW2 referring to the Table D m L 3 DIP switch SET 4 Table D Airflow direction louver function Invalid Factory setting ON Airflow direction louver function Valid DIP switch OFF SET 4 Sw2 o 20 Pa 30 Pa 40 Pa 26 50 Pa A 60 70 Pa 50 Pa 50 Pa 09 90 50 Pa Setting static pressure becomes 50 if AR24 is set to 06 through 09 En 17 7 6 Switching the upper limit of cooling temperature This setting can be raised the upper limit of the cooling temperature setting range This setting can be used when connecting to the following controllers Wired remote controller 2 wire type Central remote controller Touch panel controller System controller Service tool Web monitoring tool DIP switch setting Set the DIP switch SET 4 SW3 referring to the Table C IU AD REF AD REF A
47. rsoneli i in PART NO 9374342273 02 INSTALLATION MANUAL PART NO 9374342273 02 VRF system indoor unit Duct type Contents 1e SAEETYPREGAUTIONS d estt esee e 1 2 ABOUT THE UNIT 2 1 Precautions for using the R410A refrigeran 2 2 Special tool for RA10A 2 3 Accessories 2 4 Optional parts 9 INSTALLATION WORK nascita thx eret bti aep dato 3 3 1 Selecting an installation location eene 3 3 2A Installation dimensions Ceiling concealed 3 3 2B Installation dimensions Wall mounted type Floor standing concealed type 3 3 3A Installation the unit Ceiling concealed 3 3 3B Installation the unit Wall mounted type Floor standing concealed type 5 4 PIPE INSTALLATION 4 1 Selecting the pipe material 4 2 Pipe requirement 4 3 Flare connection Pipe connection 4 4 Installing heatinsulation 5 8 5 1 When drain pump is used 5 1B When drain pump is not used Natural drainage na 5 2 althe Grain pp anaa ELECTRICAL WIRING inito 6 1 Electrical requireme
48. te controller Y1 Y2 Y3 0 5 to 0 6 Nm 5 to 6 kgf cm CAUTION To peel the film from the lead cable use a dedicated tool that will not damage the conductor cable When installing a screw on the terminal block do not cut the cable by overtightening the screw On the other hand an undertightened screw can cause faulty contact which will lead to a communication failure Remote controller cable Y1 Red Y2 White Y3 Black i X1 X2 Transmission cable GND L N Power supply cable Cable clamp For 2 wire type For 3 wire type Y1 Non poler Y1 Red Connect the remote yv9 nNon pol Y2 Whi poler White controllereable Y3 Do not connect 1 Y3 Black DIP switch 5 m SW1 et the DIP switch 2WIRE SW1 Factory setting 1 If you connect the remote controller cable to the terminal Y3 2 wire type remote controller does not work Cable tie Medium Accessories Avoid covering the air inlet with the wiring cable Ceiling Do not bind the power supply cable and other cables together En
49. ted unit e When connecting with unit equipped with a power supply Connected device 1 Connected device 2 Connected device 3 connected unit Relay Field supply Operation behavior Connector Output voltage Status External output1 0v Stop Pins d DC 12V Operation External output2 ov Normal CNBO1 Pins 1 3 ib DC 12V Error External output3 ov Indoor unit fan stop EU DC 12V Indoor unit fan operation 3 Connection methods Wire modification Remove insulation from wire attached to wire kit connector Remove insulation from field supplied cable Use crimp type insulated butt connector to join field cable and wire kit wire Connect the wire with connecting wire with solder IMPORTANT Be sure to insulate the connection between the wires Option parts Field supply External input output wire ae Solder and insulate the connected parts Connection terminals and wiring arrangement In following figure all the possible connectors are connected for description In actual installation you cannot connect all the connectors at once Controller PCB X N CAUTION To protect the cable insulation after opening a knockout hole remove any burrs from the edge of
50. the hole En 14 Wiring arrangement 6 6 Remote sensor Optional parts Controller PCB comp Connection method Connection terminals Controller PCB ll Li A Remote sensor terminal CN8 m ro m eoi mim Wiring arrangement S 7 Controller PCB Use 7 pins for receiver unit cabe S Atfirst connect the receiver unit cable to the controller PCB Attach the core that comes between controller PCB and the clamp Use conduit hole when external output cable is used N CAUTION To protect the cable insulation after opening a knockout hole remove any burrs from the edge of the hole 6 8
51. troller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD SW in sequence from 0 Seting Setting range Type of switch Setting example 0 Remote controller address If 4 indoor units are connected Indoor unit Indoor unit Indoor unit Indoor unit RC AD SW RC AD SW RC AD SW RC AD SW 0 1 2 3 HH H H N controller o 7 7 Address 0 1 2 3 4 5 6 7 Rcapsw s o af ef oT Address 9 10 nf 12 t3 314 15 ii 2 wire type Rotary switch RC AD SW Factory setting 0 Since the remote controller address settings are automatically configured you do not need to configure them If configuring manually it is necessary to configure both the indoor unit and the remote controller For details please refer to the remote controller manual En 16 7 2 Custom code setting Selecting the custom code prevents the indoor unit mix up Up to 4 codes can be set Perform the setting for both the indoor unit and the remote controller Code change Confusion A B unit Em 7 T Remote Due 1 controller A B D
52. uirement N CAUTION Refer to the Installation Manual of the outdoor unit for description of the length of connecting pipe or for difference of its elevation Use pipe with water resistant heat insulation N CAUTION Install heat insulation around both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80 96 use heat insulation that is 20 mm or thicker If heat insulation is used that is not as thick as specified condensation may form on the surface of the insulation In addition use heat insulation with heat conductivity of 0 045 W m K or less at 20 C 4 3 Flare connection Pipe connection N WARNING Tighten the flare nuts with a torque wrench using the specified tightening method Otherwise the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame Ej eA Dimension mm ipe outside diameter P nd FlaretoolforR410A Dimension B 54 mm clutch type 6 35 1 4 9 1 9 52 3
53. witches Rotary switch Example 0 907 YP Rotary switch Example 0 9694 E REF AD REF AD lo xr Road Setting range 907 Setting Indoor unit address to 63 example v 969 2 IU AD x 1 90 7 ae Setting 0 to 99 example v 63 99 REF AD 10 REF AD 1 1 Indoor unit address Rotary switch IU AD x 1 Factory setting 0 Rotary switch IU AD x 10 Factory setting 0 When connecting multiple indoor units to 1 refrigerant system set the address at IU AD SW as shown in the Table A 2 Refrigerant circuit address Rotary switch REF AD x 1 Factory setting 0 Rotary switch REF AD x 10 Factory setting 0 In the case of multiple refrigerant systems set REF AD SW as shown in the Table A for each refrigerant system Set to the same refrigerant circuit address as the outdoor unit If working in an environment where the wireless remote controller can be used the addresses can also be set using the remote controller If setting the addresses using the wireless remote controller set the indoor unit address and refrigerant circuit address to 00 For information on setting using the wireless remote controller Table A Rotary Rotary Address Switch Setting Switch Setting Refrigerant circuit xx N Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure 3 Remote con
Download Pdf Manuals
Related Search
Related Contents
Mapefloor PU 410 Mapefloor PU 410 Maintenance Moteurs frein FFB Algemeen Page 1 1.製品概要 本機はデジタル入力(3id)とアナログ Télécharger le fichier ram d`am octobre 2014 SoftBank 200SH 取扱説明書 2Wire Uniplex Business Software for ULTRIS on RISC SPD 32.83.01 Owner's Manual Mode d`emploi: Deutsch, English, Francais Copyright © All rights reserved.
Failed to retrieve file