Home

RECTIFIER PSR06-W USER MANUAL

image

Contents

1. ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSR06 W User Manual Page 22 24 12 Your Notes ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSR06 W User Manual Page 23 24 ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE alwayson Supplier Eltek Valere Deutschland GmbH GB Industrial SchillerstraBe 16 D 32052 Herford T 49 0 5221 1708 210 FAX 49 0 5221 1708 222 Email Info industrial eltekvalere com Internet http www eltekvalere com Copyright ELTEK VALERE DEUTSCHLAND GmbH 2009 All rights reserved
2. Terminal X3 X3 Pin Function 1 Control input for the second voltage line Voz boost charge 2 External On Off 4 Optocoupler common emitter Optocoupler 6 Uo present 15V DC Optocoupler C lo Temperature sensor lead 9 Compensating connection for current dis tribution 2 GND NJ O G1 Do Terminal X3 ET 8 7 6 5 4 5 5 Remote ON OFF Boost charge 2nd voltage line Legend D The connection of Pin 1 to Vo GND enables the second voltage line e g boost charge 2 Connection of the TK sensor by two core cable to pin 7 and pin 9 4 modules are paralleled pin 7 of each individual unit and pin 9 of each individual unit has to be connected 9 At active current sharing mode of paralleled units pin 8 and 9 respectively of each module has to be connected 4 The connection of Pin 2 to Vo GND switches the rectifier externally OFF see the picture above Note The input is potential free with safe electrical decoupling to primary side and with 500Voc to secondary side 5 The relay outputs are potential free with safe electrical decoupling to primary side and with 500Voc to secondary side 9 ATTENTION If you have decoupling diodes in minus at output side the use of sensor leads is not allowed ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSR06 W User
3. B a PSRO6 W 2 ER 2 5 5 5 L min Le eS vu 55 ER ao pa uE 1 ve Dar SE 5 es 1 E lt 55 4 8 fas 0 0 0 0 0 4 E aE 3 oA amp c m 5 5 ae SS A a u T 5 5 5 5 5 2 5 c z e2 5 5 ce e a3 5 z 8 N eo 5 5 E 55 5 of 22 4 Do ne gt A SS 36 3 CT IC ee eee rm a 8 a v D H 3 5 z 5 T 5 5 Ef w 5 a a 5 5 BEE EEE e aft n u u 5 8 E E E 5 D ha aa i u po H e 5 5 5 Ei gt 5 z ae R Ze 8 H 5 Eno o gt ER 3 m 1 n so ur o as w pan 2 E ng Sr u fr E 1 ER us 5 E 5 5 R ER 28 5 5 SS us ga CE L EE 5 a a p 5 m 5 a 5 z 5 5 E S 5 5 en 5 S 1 o 5 bo 5 n 1 ak 5 5 bo u f 5 z ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSR06 W User Manual Page 9 24 5 2 Electrical function description Rectifiers of type PSR consist of the following main parts 1 Input filter suppressing the feedback of high frequency interference produced by the unit into the mains as well as for the attenuation of the interference voltages and voltage transients superim posed on the mains 2 Mains rectifier with switched step up converter operation frequency 100kHz to transform the input voltage in a pre regulated DC voltage of appro
4. ELTEK VALERE always RECTIFIER PSROG W USER MANUAL UM_PSROG W_E_R2 0 W ELTEK VALERE Rectifier always on PSRO6 W User Manual Page 2 24 ATTENTION Read this manual very carefully before installing and commissioning the specified module This manual is a part of the delivered module Familiarity with the contents of this manual is required for installing and operating the specified module The rules for prevention of accidents for the specific country and the general safety rules in accordance with IEC 364 must be observed The function description in this manual corresponds to the date of publishing Technical changes and changes in form and content can be made at any time by the manufacturer without notice There are no obligations to update the manual continually The module is manufactured in accordance with applicable DIN and VDE standards such as VDE 0106 part 100 and VDE 0100 part 410 The CE marking on the module confirms compliance with EU standards 2006 95 EG low volt age and 2004 108 EG electromagnetic compatibility if the installation and operation instructions are followed Supplier Eltek Valere Deutschland GmbH GB Industrial SchillerstraBe 16 D 32052 Herford zZ 49 0 5221 1708 210 FAX 49 0 5221 1708 222 Email Info industrial eltekvalere com Internet http www eltekvalere com Changes and errors excepted Copyright ELTEK VALERE DEUTSCHLAND GmbH
5. Manual Page 17 24 8 Maintenance Due to the implemented components the SMPS unit virtually is maintenance free In case of operation in dusty atmosphere it is regularly advisable to control the dust inside of the unit and if necessary blow it out with com pressed air Deposits of dust can result in reduced cooling and could also result in conductive impurities in combi nation with dew formation or high moisture 9 Fault finding instructions Only skilled and trained technical personnel should carry out all necessary operations at the unit 9 1 Output voltage failure Input voltage present Mains switch on Is the input plug correctly inserted Output terminal polarised or short circuit at the output Parallel operation condition external decoupling diode polarised Monitoring Vo gt responded LED Vo lights up gt gt Corrective action Switch the unit ON OFF and examine the adjustment Vo gt If the unit still does not work even though all checks have been done contact your sales agent or the ELTEK VALERE INDUSTRIAL service department 9 2 Output voltage deviation Does the unit operate in the current limit due to overload Corrective action Reduce the load Adjustment value of Vo correct Corrective action Readjust the output voltage If external sensors lead connection is used is the sensor lead connection open Are the decoupling diodes connected in the output circuit gt gt Cor
6. value 20ADC 2 Adjustment range 50 100 Inominat 10Aoc 50 100 Inominat 8 2Aoc 2 50 100 Inominat 4 5ADC 2 50 100 Inominat Type of battery Lead acid battery 12 cells 24 cells 30 cells 54 cells Efficiency gt 88 289 289 289 Voltage ripple lt 20mVpp lt 20MVpp lt 20mVpp lt 100MVpp Noise voltage according to CCITT lt 1 2mV lt 1 8mV lt 1 8mV Monitoring DC under voltage V lt Threshold value 20 4Vpc Adjustment range 19 2 6 40 8VDc 38 4 bis A8Voc 51 0Voc 48 bis 60VDc 91 8VDc 86 4 bis 108Voc DC over voltage V gt Threshold value 30Voc Adjustment range 26 to 30Voc 60VDc 52 0 6 75VDC 66 0 6 135VDc 119 to 135Voc ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSR06 W User Manual Page 21 24 11 Dimensional Drawings Front View gt i Q Q ur OKO Sur Mur VO p S lemst Var gt Dur Alarm Sr ae 28U oO 0 TA echt Q Q III TITI H D DO le co LI OOO OL 0 LI
7. 2009 All rights reserved ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSR06 W User Manual Page 3 24 Revision history Revision 3 0 Date 2011 01 17 Revision Description of change Writer Date Reworked edition on base of the further manual BHB PSRO6 W D25 CS 1000 HB101 Layout changed several minor text corrections SRE QI New revision status numbering X X introduced values for input Geen 2009 04 08 voltage range changed gt gt wide input range Minor text modifications RTH 2009 04 16 Several minor corrections inserted RTH 2010 03 23 Section 6 and 7 3 as well modified RTH 2011 01 17 ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson User Manual Page 4 24 Contents A SAFETY INSTRUC TIONS eege R A na ana ent Eer 5 B ELECTRONIC WASTE 5 1 GENERAL INFORMATION NENNEN 6 2 TYPE EE 6 3 START UP PROCEDURE ees ile aca Rail 7 4 OPERATION dee ie annee en el eae 7 5 F IERE 8 5 1 CW CUE ET 8 5 2 Electrical Ee Le ea 9 5 2 1 Electrical insulation 5 2 2 le EE 5 2 3 0 5 2 4 Dynamic regulation of output voltage 5 2 5 RFI suppression 5 3 GENENG A NTEN anga Ka GEN Gan Gan NEGO KENE 5 3 1 MAINS voltage IONE OMG geeiert iaai a ni lie eine een EE 5 3 2 Operation monitoring 5 3 3 Output voltage lOW nsssssssssseesee 5 3 4 Output voltage high 5 3 5 Protecti
8. 4 t coefficient of temperature for temperature compensation of charge voltage look also cap 6 2 The monitoring thresholds automatically follow the adjusted nominal values of output voltage The monitoring thresholds for mains step up converter and over heating are not changeable Details about the adjustment ranges of several threshold values see section Technical Data ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSR06 W User Manual Page 13 24 6 External Functions 6 1 Output voltage sensor leads Using sense links for output voltage you are able to compensate voltage losses due to wires and diodes as well The max regulation difference is approx 4 of nominal voltage Interruption on sense links confusing of poles or short circuit can not damage the rectifier At interrupt it can be a voltage increase of max 4 6 2 Temperature compensation of the charging voltage At using of closed batteries we recommend the temperature controlled compensation of charge voltage You have to connect an external active temperature sensor option on signalling connector The coefficient of temperature is normally 4mV K per cell at temperature range of 0 50 C The basic temperature is 20 C The coefficient can be adjusted between 1 to 6mV K per cell The sensor has to be connected using a 2 pole wire 0 25 mm It can be mounted directly on top of battery or on battery poles At
9. _E_R3 0 W ELTEK VALERE Rectifier alwayson PSR06 W User Manual Page 10 24 5 2 3 Output The output line is an IV characteristic acc to DIN 41772 DIN 41773 with factory set decreased charge line 1 at 100 Inom with factory set active current sharing as option The output is continuous short circuit proof constant current controlling 5 2 4 Dynamic regulation of output voltage At load jumps between 10 and 90 Inom 90 and 10 Inom the dynamic voltage difference is max 3 and willbe regulated within max 1 5ms to static levels 5 2 5 RFI suppression Modules of type PSR fulfil the standard VDE 0878 T1 and EN 55011 55022 class B The output ripple is measured psophometric acc to CCITT lt 1 2mV 24V lt 1 8mV 48V and 60V 5 3 Monitoring 5 3 1 Mains voltage monitoring The SMPS is designed for an operation in the specified range see technical data sheet The unit is protected for input voltages up to 270Vac by a varistor at the input side 5 3 2 Operation monitoring Functional monitoring signalling with LED Vout OK criterion output voltage gt 97 of adjusted output voltage without constant current regulation and gt 85 of adjusted output voltage with constant current regulation The signalling threshold of this monitoring automatically follows the adjusted nominal output voltage This signal is included in the collective failure signal of the rectifier Additional there is an optocou
10. big distances gt 2m we recommend a shielded wire with connection of the shield on rectifiers ground 6 3 External switch ON OFF The rectifier can be externally switched off by switching pin 2 of connector terminal X3 to GND according to sec tion 7 3 In this case the switch off does not result in a collective failure signal 6 4 Boost charge mode second voltage line A second voltage line e g boost charge voltage can be enabled at the PSRO6W To enable the second voltage line you have to connect Minus GND to pin 1 of connector terminal X3 see section 7 3 using an external switch The voltage value Vo2 can be adjusted by the user see section 5 4 ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 aes W ELTEK VALERE ectifier alwayson PSRO6 W User Manual Page 14 24 7 Operation elements and connectors 7 1 Front view operation elements Display for voltage and current Bi EB Nur OKO BR Var VO g S LED Displa cour ES wo lt Buttons KE UP DOWN je ala lolala a gt 3 Connection terminal On Off switch 7 2 Indication instruments The unit is equipped with LED instruments 0 999 for current and voltage indication The accuracy corresponds to Class 1 with
11. input output connectors are located at the bottom of the module SNT modules also operates single side grounded or ungrounded at input and output 2 Type Range Type Article code Input voltage range Output Output Designation Vac voltage current PSRO6 Voc A 24 20W 100 006 142 00 120 230 15 10 48 10W 100 006 152 00 120 230 15 10 48 10 60 8 2W 100 006 162 00 120 230 15 10 60 8 2 110 4 5W 100 006 172 00 120 230 15 10 108 4 5 Available options and accessories 1 Temperature sensor lead LM 335 sensor lead in M5 cable shoes with 2m wire article code 880 300 TMP 00 2 Temperature sensor lead LM 335 sensor lead in M5 cable shoes with 4m wire article code 880 300 TMP 01 ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSR06 W User Manual Page 7 24 3 Start up procedure Before connecting to the input voltage it should be checked whether the voltage information on the rating plate corresponds to the available voltage and also that the polarity corresponds to the connection plan of the plug The mains connection is done via terminals below the cabinet The protective conductor should be generally connected protection class 1 leakage current lt 3 5mA The DC output contact has to be connected on terminal X1 The signalling contacts for monitoring sense links and active current are to be connected on terminal X2 X3 Impo
12. ion of 00 1 to 99 9Abc Indication of 00 1 to 999Vbc via potential free contact contact charge 60Vbc 1A via potential free relay contact 1sec time delay contact charge 60Voc 1A for active current sharing voltage value adjustable Temperature compensated 4mV K per cell with external temperature sensor optional temperature adjustable Signal via opto coupler Vo present Lo alternatively Mos Signal via opto coupler Wall cabinet IP 20 Convection cooling 20 C to 45 C 40 C to 85 C IEC 721 part 3 3 Class 3K3 321 381 3C2 352 3M2 lt 1500m according to VDE 0160 issue 5 88 Pt 7 2 2 RAL 7035 front plate approx 5 3kg 280 x 285 x 95mm HxWxD Terminal X1 Terminal X2 X3 Bolt M4 Terminal X1 UM_PSRO6 W_E_R3 0 Rectifier PSRO6 W User Manual Page 20 24 10 2 Type specific data ELTEK VALERE always on Type PSRO6 24 20W 48 10W 60 8 2W 110 4 5W Article code 100 006 142 00 100 006 152 00 100 006 162 00 100 006 172 00 Output Voltage Vo Equalising charge Adjusted value 27 2V0c 1 Adjustment range 23 4 to 28 8VDC 54 5Voc 1 46 6 bis 57 6VDc 68 1Voc 1 58 5 to 72 0VDcC 122 6Voc 1 105 to 130Voc Output voltage Voz Boost charge Adjusted value 28 8Voc 1 Adjustment range 24 to 30VDC 57 66 1 48 to 60Vbc 72 0Vbc 1 60 0 6 129 6Voc 1 108 to 135Voc Output current lo Adjusted
13. lure signal is delayed for approx 1sec The relay contacts between Pin 3 and Pin 5 of X2 are open and between Pin 4 and Pin 5 are closed at error ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSR06 W User Manual Page 12 24 5 4 Output and threshold adjustment The adjustment of output values and monitoring thresholds is very easy All values can be adjusted using the front keys The values are shown on digital displays Enabling the 2nd voltage line via an external circuit is necessary to adjust the boost charge voltage Voz see section 6 4 In normal operation the top display shows the output voltage Vo and Voz and the bottom display shows the out put current lo For any adjustment please follow the following instructions press both keys UP DOWN TV together for a short time the rectifier changes to adjustment mode press the key UP T or DOWN J to change the adjustment parameter see also table on bottom press both keys UP DOWN TV together for a short time the rectifier changes to value change mode press the key UP T or DOWN J to change the adjustment value if you hold the key the value changes quicker e press both keys UP DOWN TY together for a short time the rectifier changes back to the adjustment mode at this moment the changed value will be stored e press both keys UP DOWN TY for approx 3 sec to change back to the operation mode The adjustment m
14. mmetrical Burst test according to EN61000 4 part 4 2kV Surge test according to EN61000 4 part 5 2kV unsymmetrical with safe insulation for Uo lt 60 06 according to VDEO100 part 410 11 83 Section 4 3 2 lt 3 for load steps between 10 90 10 nominal output current transient time t lt 1 ms sustained short circuit proof 1 x nominal output current green LED Vout OK Uo 297 of the adjusted output voltage without current limit or Ua gt 85 of the adjusted output voltage green LED Vout gt Vmin with potential free contact red LED Vout gt UM_PSRO6 W_E_R3 0 Rectifier PSRO6 W User Manual Page 19 24 Constant current operation lo Over temperature Digital instruments Ammeter Voltmeter External functions Signal V lt General fault alarm signal Power measuring Discharge test boost charge Voltage regulation Temperature coefficient External sensor lead connection for output voltage Vo constant current operation lo External ON OFF Design Protection class Cooling Ambient temperature Storage temperature Environmental conditions Max operation altitude Mechanical strength and Shock proof Finish Weight Dimensions Connection terminals AC Input DC Output Signalling Protective conductor connection ELTEK VALERE DEUTSCHLAND 2009 W ELTEK VALERE alwayson yellow LED Iconst red LED bell symbol blinking Indicat
15. ode is for Adjustment of voltage Vox Normal operation adjust voltage using potentiometer Uo to correct value shown at the top display Adjustment of voltage Voz Switch over the unit to Voz line by external switch look chapter 6 for correct connecting of signal connec tor adjust voltage using potentiometer Voz to correct value shown at the top display Adjustment of monitoring threshold V lt Adjust voltage using potentiometer V lt to correct value and measure this value at measurement sockets U lt in front of the unit Adjustment of monitoring threshold V gt Adjust voltage using potentiometer V gt to correct value and measure this value at measurement sockets V gt in front of the unit Adjustment of the current limit Iconst The current limit Iconst is adjusted using the potentiometer Iconst by external load The measured value at the measure bushings V gt and V lt corresponds to V cell for 2 cells Le there is a voltage of 4 8V at the measure bushing for adjusting the V gt to 2 4 V cell The adjustment ranges and the adjustments in the factory should be picked up from the respective technical data sheet Adjustable parameters in adjustment mode Display Parameter Vol Ua1 triple charge voltage Vo2 42 boost charge voltage look also cap 6 4 lo la output current V lt output voltage low threshold look also cap 5 3 3 V gt output voltage high threshold look also cap 5 3
16. on against overheating 5 3 6 SIGNALS Er ee ie nn NG EEN A NGA a nn et unie 5 4 Output and threshold adjustment neuen 6 EXTERNAL RUNCTONS 5555855255 48a en nenn 13 6 1 Output Voltage sensor leads nenne ne 13 6 2 Temperature compensation of the charging voltage 13 6 3 External switch ON OFRF nenne hl 6 4 Boost charge mode second voltage line 7 OPERATION ELEMENTS AND nn 7 1 Front Ee ele 14 72 indication ke Li 14 7 3 Connection tables of input and output terminals sn 8 MAINTENANCE serum en 9 FAULT FINDING INSTRUCTIONS 9 1 0 saranani nana ae Ng aaa a an gaya naen da ai ga E Ng agan gak gan a eh ga d La nag ena ng akaya aaa gen Ng aana AG 9 2 Output voltage d viation ae 17 10 As wat a GARA ee ns 18 10 1 General technical data anna 10 2 Type specific data 11 DIMENSIONAL DRAWINGS FRONT VIEW ENNEN 12 YOUR eaa eaa e a aa an TG anana aga Ba a ae aa en a an aan aa aan 22 ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSRO6 W User Manual Page 5 24 A Safety Instructions Warning Because several components of operating electrical modules are charged by dangerous voltage the improper handling of electrical modules may cause accidents involving electrocution injury or material damages e Operation and maintenance of electrical modules must be performed by qualified skilled personnel such as electrician
17. pler signal Vo O K At operation with internal decoupling diodes the voltage before diodes will be measured ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSR06 W User Manual Page 11 24 5 3 3 Output voltage low Output voltage low monitoring signalling with green LED Vout gt Vmin Criterion output voltage is higher than adjusted level V lt This signal has its own relay contact on signalling connector If the voltage value is O K Pin 6 and Pin 7 of X2 are closed 5 3 4 Output voltage high Output voltage high monitoring signalling with red LED Vout gt Criterion output voltage higher than adjusted level V gt This signal is included in collective failure signal of rectifier If there is an error the LED is switched ON and the recti fier internally switches OFF You have to reset the unit by ON OFF switch 5 3 5 Protection against overheating Protection against overheating signalling with blinking red LED Bell symbol criterion temperature of heat sink gt 90 C This protection reduces the output power if the temperature is on the limit This signal is included in collec tive failure signal If the temperature is normally the output power will be increased automatically 5 3 6 Signals The signals Vo OK Mains OK and Constant Current Mode Iconst are opto coupler signals with a loading of 30 V 5mA The opto couplers switches off at error The collective fai
18. rective action Correct the potential drop by increasing the output voltage of the unit If the unit still does not work even though all checks have been done contact your sales agent or the ELTEK VALERE DEUTSCHLAND service department ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 Rectifier PSRO6 W User Manual Page 18 24 10 Technical Data W ELTEK VALERE alwayson 10 1 General technical data Nominal input voltage range Frequency Nominal input current Power Factor Characteristic curve RFI Conduction related Radiation EMC Cabinet Power cable Control cable Function extra low voltage Dynamic behaviour Short circuit behaviour Function monitoring Mou threshold value floating Monitoring output under voltage U lt Monitoring output over voltage U gt ELTEK VALERE DEUTSCHLAND 2009 120 230Vac 15 10 47 63Hz 2 7A 230VAc 0 99 100 gt Pnom gt 50 0 97 50 gt Prom gt 25 0 95 Prom lt 25 IV characteristic according to DIN 41 772 DIN 41773 according to EN50081 1 according to EN55011 EN55022 limit value class B according to EN 55011 EN55022 limit value class B according to EN50082 2 ESD test according to EN61000 4 part 2 6kV contact 8kV air discharge HF field according to EN61000 4 part 3 10V m 30MHz 1GHz Burst test according to EN61000 4 part 4 2kV Surge test according to EN61000 4 part 5 4kV unsymmetrical 2kV sy
19. reference to the nominal output value of the unit The indication instrument can be converted to the indication of the adjusted theoretical value for the regulation and monitoring via an external circuit of the signal plug ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSRO6 W User Manual Page 15 24 7 3 Connection tables of input and output terminals The following picture shows the terminal area terminal X1 X2 X3 of the rectifier ei a 1 9 Ojo olo a l E 8 B OG T BERERBBEE LT esl Re Al Terminal X1 X1 Pin Function DC Output L DC Output L DC Output L DC Output L PE N Input L1 Input NIDIA Go DO Terminal X2 X2 Pin Function Sensor lead connection Not connected Signal relay general fault alarm NO Signal relay general fault alarm NC Signal relay general fault alarm COM Signal relay U lt COM Signal relay U lt total discharge NO Sensor lead connection m MD 1 A GO ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSR06 W User Manual Page 16 24
20. rtant The rectifier has big capacitors at the output If you connect a switched off module to a battery or other modules which operate in paralleling there is a big capacitor charge current This current may destroy the contacts on out put connectors WARNING After switching off the capacitors hold its voltage for several times Do not touch The rectifier operates with convection cooling The ambient temperature has to be less than 55 C If there is a higher temperature the life time of the modules will be decreased The losses per module are approx 40 to 80W depends on type 4 Operation All operation elements are located on the front panel of the module The function of each element is explained on the following pages See also the front panel drawing on section 7 1 ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 W ELTEK VALERE Rectifier alwayson PSR06 W User Manual Page 8 24 5 Functions 5 1 Circuit diagram KL a j LC Filter T Filter 1 Ausgangssteckverbinder KI XS 3 CTI 910 Han HE KL Dutput plug XL of 2 XI L FIG 1 ZA kadi 8 5 S E es Block Diagram amp
21. s in accordance with EN 50110 1 or IEC 60950 e Install the module only in areas with limited access to unskilled personnel e Before starting work the electrical module must be disconnected from mains Make sure that the module is earthed e Do not touch connector pins as they can be charged with dangerous voltage up to 30 seconds after disconnection e Only spare parts approved by the manufacturer must be used B Electronic Waste Disposal The correct disposal of electronic waste is the responsibility to recycle discarded electronic equipment and is necessary to achieve the chosen level to protect human health and the environment In the case of waste disposal of your discarded equipment we recommend to contact a professional waste management company ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W_E_R3 0 ELTEK VALERE Rectifier alwayson PSR06 W User Manual Page 6 24 1 General Information The primary switched mode rectifier type PSRO6 W named SMPS on the next pages delivers an output power of approx 600W Typical applications are DC power supplies and uninterruptable power supply with battery Rectifiers of type SMPS have good dynamic regulation properties concerning input voltage changes and load varia tions It works with an IV characteristic in accordance with DIN 41772 and it is a complete connectable module in a wall cabinet The operation elements and measurement instruments are located on the front panel the
22. x 380V and to control the waveform of input current sinusoidall An additional function is the limitation of inrush current 3 Transistor bridge to transform the 380Voc in a pulse width modulated AC voltage with an fre quency of 100KHz 4 HF transformer for decoupling of primary and secondary part and to transport the power to sec ondary side Rectifier diodes to make a DC voltage from high frequency AC voltage LC Filter to reduce the voltage ripple on rectifier output Output filter for RFI suppression and to reduce the noise level on DC line Internal power supply for supplying of primary and secondary control units with potential decoup ling 9 Regulation line with decoupling through opto couplers 10 Adjustment panel for adjustment of output parameters signals and measurement instruments OND 5 2 1 Electrical insulation Through the construction of the module also module parts and separate wiring of mains input and DC output the SMPS fulfils the following standards e devices with Uo gt 60Voc protection against shock current because of low voltage with safe electrical de coupling acc to EN 60950 and VDE 0100 e devices with Uo gt 60Vpc safe electrical decoupling to Uo 220 06 acc EN 60950 and VDE 0160 5 2 2 Input A one pole mains switch is used to switch on and off the unit The unit is switched on by a run up stage which limits the switch on current to lt Inom ELTEK VALERE DEUTSCHLAND 2009 UM_PSRO6 W