Home
Installation and operating instructions thermostatic
Contents
1. Note Water Regulations shower hose connections requires the showerhead be constrained by a fixed or sliding attachment so that it can only discharge water at a point not less than 25mm above the spill over level of the relevant bath shower tray or other fixed appliance The use of the supplied soap dish will in most cases meet this requirement but if the showerhead can be placed within a bath basin or shower tray then a double check valve or similar must be fitted in the supply pipework to prevent back flow Pressure relief safety device A pressure relief device PRD is designed into the shower unit which complies with European standards The PRD provides a level of appliance protection should an excessive build up of pressure occur within the shower Do not operate the shower with a damaged or kinked shower hose or a blocked showerhead which can cause the PRD to operate When commissioning the showerhead must be removed from the flexible hose Failure to follow this procedure may also cause the PRD to operate Make sure the shower is positioned over a bath or shower tray because if the PRD operates then water will eject from the bottom of the unit Should this happen turn off the electricity and water supplies to the shower at the isolating switch and stopvalve Contact Customer Service for advice on replacing the PRD FITTING THE SHOWER TO THE WALL Note The control knobs are an integral part of t
2. the shower hose Note The Start Stop button will not be connected the only way to exit the commissioning mode is to remove power to the PCB e Allow the system to run until the water flows freely without bubbles in it Turn the Temperature control knob slowly from number 1 to the temperature lock out setting and back again a few times to release any trapped air e Stop the shower using the isolating switch e Remove the cover connect the PCB ribbon cable fiig 20 refit the cover and secure using all of the retaining screws Adjusting the Maximum temperature stop The temperature control valve has an adjustable maximum temperature stop mechanism that is supplied factory set for 47 C To select a lower or higher maximum temperature stop setting remove the locking screw from the mechanism and rotate the mechanism to the preferred setting point to align with the screw fixing point Insert the locking screw through the temperature setting label and lock in place fig 18 DIP SWITCH SETTINGS A four way DIP switch block is mounted on the control PCB that allows the user to configure the shower to perform different functions fig 19 Dip Switch No DIP switch 1 On DIP switch 1 Off DIP switch 2 Off DIP switch 3 Off DIP switch 2 Off DIP switch 3 On DIP switch 2 On DIP switch 3 Off DIP switch 2 On DIP switch 3 On DIP switch 4 Operation Enabled Audible Feedback On Factory setting Audible
3. connectors as full engagement cannot be guaranteed DO NOT use excessive force when making these connections Make sure the backplate is square on the wall and tighten the retaining screws which hold it to the wall Turn on the water supply and check for leaks in the pipework connection to the shower Note At this stage no water can flow through the unit Important Using a suitable sealant always seal around the incoming pipework to prevent water entering the wall Important Under No circumstances must the Inlet be rotated 90 and the pipe fitted directly The shower has not been designed for this method of connection See below WARNING The outlet of the shower acts as a vent and must not be connected to anything other than the hose and showerhead supplied A Bottom Entry B Top Entry C Rear Entry ELECTRICAL CONNECTIONS Switch off the electricity supply at the mains Fig 12 shows a schematic wiring diagram The cable entry points are shown in fig 1 The cable can be surface clipped hidden or via 20 mm conduit Note Conduit entry can only be from rear Route the cable into the shower unit and connect to the terminal block fiig 13 as follows Earth cable to terminal marked D Neutral cable to terminal marked N Live cable to terminal marked L Important Fully tighten the terminal block screws and make sure that no cable insulation is trapped under the screws Loose con
4. installation Please keep it for future reference The shower installation must be carried out by a suitably qualified person and in the sequence of this instruction book Care taken during the installation will provide a long trouble free life from your shower SPECIFICATIONS Electrical Nominal power rating at 240V 8 5kW 40 MCE rating Nominal power rating at 230V 7 8kW 40 rating Pump motor rating 120 Watt single phase Water Inlet connection 15 mm diameter Outlet connection 2 BSP male thread Entry Points Water bottom back and top Cable bottom back and top Materials Backplate cover controls showerhead ABS Sprayplate Acetal Elements Minerally insulated corrosion resistant metal sheathing Dimensions Height 300 mm Width 316 Depth 90 mm Standards and Approvals Splashproof rating IPX4 Complies with the requirements of current British and European safety standards for household and similar electrical appliances Complies with requirements of the British Electrotechnical Approvals Board BEAB Meets with Compliance with European Community Directives CE ADVICE TO USERS Important When first installed the unit will be empty It is essential the unit should contain water before the elements are switched on It is vital that the commissioning procedure is followed Failure to carry out this operation will result i
5. the installation DO NOT solder fittings near the shower unit as heat can travel along pipework and damage components Compression fittings Must be used to connect to the inlet of the shower Note An additional stopvalve complying with Water Regulations Must be fitted in the water supply to the shower as an independent means of isolating the water in order to carry out maintenance or servicing Important Before completing the connection of the water supply to the inlet of the shower flush out the pipework to remove all swarf and system debris This can be achieved by connecting a hose to the pipework and turning on the water supply long enough to clear the debris to waste Procedure Turn off the water supply isolating stopvalve Connect the mains water supply to the Inlet of the shower via 15mm copper stainless steel or plastic pipe using a 15mm x 15mm compression fitting see fig 10 for advice on Rear Entry fitting Centre of Soldered Elbow Centre of Water Inlet Note If installing a feed pipe from the back the use of a soldered Elbow connector is recommended It should be positioned approximately 105mm from the inlet connector centre The centre of the inlet valve to the wall surface is 21mm The Inlet fitting is designed to rotate through 180 to allow for either Top or Bottom Rear entry fitting fig 11 Note The inlet fitting is designed to enter a compression fitting only DO NOT use push fit
6. 1 Low flow condition 7 Low flow LED comes Low flow condition Shower will not start until water in the unit has on when shower is running Shower switches off has caused temperature sensor in the shower to operate cooled and LED goes off If problem persists 1 Check showerhead is not blocked 2 Check shower hose is not restricted 3 Check filter is not blocked 4 Check water supply to shower is adequate Flow switch has failed 8 Low flow LED flashes continuously when start stop bar pressed Shower will not start Replace flow switch assembly 9 Low flow and shutdown LED s alternately flashing when power turned on to unit Shower will not start Start Stop switch failed Replace cover assembly 10 1 Outlet thermistor failed 10 Low flow and shutdown LED S flashing simultaneously when start stop bar pressed Shower will not start 10 1 1 Replace thermistor 11 Low flow and shutdown LED S permanently on when power is turned on Shower will not start 11 1 Power pcb faulty 11 1 1 Replace power pcb Note Identify cause of operation before fitting new PRD unit When fitting a new PRD follow the commissioning procedure It is advised all electrical maintenance repairs to the shower should be carried out by a suitably qualified person In the unlikely event of unit failure other than detailed in the fault finding page please contact Customer Service for advice T150Z pum
7. 5 TAGE TINGE 23410804 T150Z pumped thermostatic electric shower SPARE PARTS Ref Description Part No Solenoid outlet elbow assembly not shown P23410803 Heater can wire set NOt 83313440 Triac and wires NOt P19520903 Thermister NOt 22012030 WG PRONE COVER 7073708 17 1507 Pumped Front cover assembly 523410600 includes PCB and start stop switch FAULT FINDING Important Switch off the electricity at the mains supply and remove the circuit fuse before attempting any fault finding inside the unit Problem Symptom Cause Action Cure 1 Shower inoperable no 1 1 Interrupted power 1 1 1 water flow supply 1 2 Unit malfunction 1 2 1 1 2 2 1 3 Thermal cut out 1 3 1 operated gt Water too hot 2 1 Temperature control set incorrectly 2 2 Unit malfunction 2 2 1 Water too cool cold 3 1 Temperature control 3 1 1 set incorrectly 3 2 Maximum 3 2 1 temperature stop set incorrectly 3 3 Unit malfunction 3 3 1 4 Water will not stop 4 1 Control ribbon cable flowing from unit is not connected to unless switched off at PCB isolating switch 5 Pressure relief device
8. 5 1 Blocked 5 1 1 has operated water showerhead ejected from PRD 5 2 Twisted blocked 5 2 1 tube flexible shower hose 5 3 Showerhead not 5 3 1 removed while commissioning Blown fuse or circuit breaker Check supply Renew or reset fuse or circuit breaker If it fails again consult a qualified electrician Power cut Check other appliances and if necessary contact local Electricity Supply Co Have unit checked Ring Customer Service The thermal cut out safety device has operated Have the unit checked by a suitably qualified service engineer or contact Customer Service Alter the temperature control Have the unit checked by a suitably qualified service engineer or contact Customer Service Alter the temperature control Alter the Maximum temperature stop Have the unit checked by a suitably qualified service engineer or contact Customer Service Remove cover and connect ribbon cable Clean sprayplate and then fit a new PRD Check for free passage through hose Replace hose if necessary and then fit new PRD Fit new PRD Commission unit with showerhead removed FAULT FINDING Problem Symptom Cause Action Cure 6 Low flow LED permanently on when start stop bar pressed Shower will not start 6 1 1 Insufficient water flow available 1 Check showerhead is not blocked 2 Check shower hose is not restricted 3 Check filter is not blocked 4 Check water supply to shower is adequate 6
9. Feedback Off Timed Shutdown 5 Mins Timed Shutdown 10 Mins Timed Shutdown 20 Mins Factory setting Timed Shutdown 30 Mins Switch Position ON 1 2 1 VE om 8 2 1 om 2 REPLACING THE COVER Attached to the display PCB inside the cover is a 10 way ribbon cable The ribbon cable connector must be plugged into the socket located at the right of the power PCB situated inside the unit fig 20 Note The cable connector can be fitted to the socket only one way The ribbon cable has a coloured edge which is at the bottom when correctly fitted to the socket Note The ribbon cable is preformed to fold flat when the cover is fitted Important Before finally fitting the cover the following steps must be taken a Check all plumbing connections are watertight b Check terminal block screws are fully tightened c Make sure pipe and cable entering the unit do not prevent the cover locating correctly to the backplate Offer the cover to the unit Guide into position so that the knob spindle locates correctly minor adjustment may be necessary to align the knob and spindle Should any difficulty arise re check the points above While applying slight pressure to the cover secure in position with the retaining screws Turn the electric supply back on at the isolating switch
10. TRITON T150Z thermostatic pumped electric shower TRITON IMPORTANT Erk Under NO circumstances must this shower be connected directly to a mains water supply It is designed for GRAVITY FED COLD WATER systems ONLY Failure to comply may invalidate product warranty Installation and operating instructions INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER 2180759C April 2009 CONTENTS PAGE Important safety information 1 MEMO CUI S T A 2 2 PACS 2 inona EREA 3 4 Electrical reguremeN E 5 6 7 ANG SNOWED 8 Fitting the shower to the wall 9 COMMECIIONS essa 10 11 12 Shower drain pumps not supplied sciccscucsseveasasrianrpiarasmnaswrenrerene 13 14 COMMITS 15 16 PEE DID SWIC gt 17 Replacing 18 Operating the shower Operating 19 21 Instructions for installers and service engineers 22 23 24 25 26 G arantec CEC To check the product suitability for commercial and multiple installations please contact Triton s specificatio
11. The Power indicator will light No water will flow now until the Start Stop button is pressed However it is recommended that the water and electric supplies to the shower are turned off while the riser rail kit is being installed The flexible hose can be left attached to the shower outlet Make sure the supplied sealing washer is fitted OPERATING THE SHOWER When the electricity supply to the shower is switched on at the isolating switch the power on indicator will light Start Stop To start the shower Press the start stop button and water will flow After a few seconds a flow of heated water will be available fig 21 To stop the shower manually The shower can be stopped by pressing the start stop button When pressed the phased shutdown will begin and water will cease to flow after a few seconds fig 21 To stop the shower timed Shutdown Shutdown times can be set at 5 10 20 factory setting or 30 minutes When the indicator WARNING illuminates it indicates there is 1 minute before the timed shutdown will turn the shower off This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the applia
12. ain full advantage of the power provided by the shower use the shortest cable route possible from the consumer unit to the shower It is also necessary to satisfy the disconnection time and thermal constraints which means that for any given combination of current demand voltage drop and cable size there is a maximum permissible circuit length The shower circuit should be separated from other circuits by at least twice the diameter of the cable or conduit The current rating will be reduced if the cabling is bunched with others surrounded by thermal loft or wall insulation or placed in areas where the ambient temperature is above 30 C Under these conditions derating factors apply and it is necessary to select a larger cable size Table A Circuit Protection unit cartridge rating MCB fuse 7 OkW 7 SkW Table B Twin and earth PVC insulated cable Current carrying capacity Clipped direct or buried a Installed in an In conduit non insulated insulated wall trunking wall 6 mm2 6 6 32A 38A 46A 10 mm2 10 mm2 10 mm2 43A 52A 63A 16 mm2 16 mm2 16 mm2 57A 69A 85A Note Cable selection is dependent on derating factors 9 2 In the majority of installations the cable will unavoidably be placed in one or more of the above conditions This being so it is strongly recommended to use a minimum of 10mm cabling throughout the shower installation 9 3 In any event it is essential th
13. at individual site conditions are assessed by a competent electrician in order to determine the correct cable size and permissible circuit length WATER REQUIREMENTS The installation must be in accordance with Water Regulations Bylaws Supply Source Minimum Head Maximum static pressure Maximum inlet temperature Minimum inlet temperature WARNING Under no circumstances must this shower be connected directly to the mains water supply To ensure activation of the heating elements the shower must be connected to a cold water supply which is Gravity Fed Only from a static cold water storage cistern with a minimum capacity of 114 litres 25 gallons There must be a maximum head of water of 10 metres and a minimum head of 8 cm as measured between the bottom of the cistern and the top of the shower unit There must be no other cold water draw offs between the cistern and the unit and the pipe must not supply water to any other tap or fitting at a lower level Note The supply pipe from the cistern should be on the opposite side to the float operated valve to prevent air being drawn into the pipe when the cistern is filling If it is intended to operate the shower in hard water areas above 200 ppm temporary hardness a scale inhibitor should be fitted Fig 5 shows a typical system layout DO NOT use jointing compounds on any pipe fittings for the installation Pe Diagrammatic view not to scale Mi
14. ater supply to the shower The inlet filter is situated inside the water inlet fitting fig 24 To gain access to the filter remove the cover and right hand trim plate Unscrew the cap on the water inlet fitting Inspect the O ring for damage when the filter is removed Do not over tighten the filter cap on reassembly When cleaning the filter DO NOT use a sharp object as it will cause damage It is preferable to use an old toothbrush or similar SPARE PARTS Ref Description Part No 1 Top and bottom pipe entry 83313430 2 Thermalsafety cUtOUt 22012020 3 Power printed circuit 7073709 4 Can and element P19520700 Ds Fow switch 519521007 6 Temperature Control 519520805 7 block and S23410901 8 Solenoid 23410801 9 23411001 10 Pressure relief device 82800450 11 Shower outlet reservoir suniswnrrenassouatevenieonsaximnannrxiass P23410802 12 Access trimplate s 7053949 13 Heater inlet valve assembly S19520806 14 Motor and pump P15211002 1
15. comply with BS 7671 Requirements for electrical installations IEE wiring regulations building regulations or any particular regulations as specified by the local Electrical Supply Company This appliance MUST be earthed In accordance with The Plugs and Sockets etc Safety Regulations 1994 this appliance is intended to be permanently connected to the fixed wiring of the electrical mains system Make sure all electrical connections are tight to prevent overheating Fuses do not give personal protection against electric shock 30mA residual current device RCD MUST be installed in all UK electric and pumped shower circuits This may be part of the consumer unit or a separate unit Switch off immediately at isolating switch if water ceases to flow during use Other electrical equipment i e extractor fans pumps must not be connected to the circuits within the unit Switch off at isolating switch when not in use This is a safety procedure recommended with all electrical appliances As with all electrical appliances it is recommended to have the shower and installation checked at least every two years by a competent electrician to ensure there is no deterioration due to age and usage INTRODUCTION This book contains all the necessary fitting and operating instructions for your electric shower Take time to read this book thoroughly and familiarise yourself with all instructions before commencing
16. cuits This may be part of the consumer unit or a separate unit Shepperton Park TRI N Triton Road Nuneaton Warwickshire CV11 4NR MODEL 230 240V ru IPX4 MAX PRESSURE MIN PRESSURE RATED PRESSURE MODEL No 00000000 SERIAL No 00000000 38 Schematic of installation circuit Pull cord isolating switch Shower can be part of uni unit Consumer Fuse MCB unit ve supply 80A or 100A L S SH main switch RCD Incoming 6 1 6 2 8 1 8 2 9 1 A 45 amp double pole isolating switch with a minimum contact gap of 3 mm in both poles must be incorporated in the circuit It must have a mechanical indicator showing when the switch is in the OFF position and the wiring must be connected to the switch without the use of a plug or socket outlet The switch must be accessible and clearly identifiable but out of reach of a person using a fixed bath or shower except for the cord of a cord operated switch and should be placed so that it is not possible to touch the switch body while standing in a bath or shower cubicle It should be readily accessible to switch off after using the shower Where shower cubicles are located in any rooms other than bathrooms all socket outlets in those rooms must be protected by a 30mA RCD The current carrying capacity of the cable must be at least that of the shower circuit protection see Table B To obt
17. des 4 25306 25310 A4 2 AKW Archimedes 4F 25301 25305 A4F Technical Helpline 01905 823 299 E mail sales akw medicare co uk For AKW Pump information please visit www akw medicare co uk CONTOUR SHOWERS PRIMO XTRA 5 1 Pump Only PRIMO XTRA O5PPOTA With UPS 3 22 gully to suit a shower tray PRIMO XTRA O5PPO01B With USG1 WH gully to suit a wet floor former PRIMO XTRA 5 1 With CSG1 gully for screed floors Technical Helpline 01606 592 586 E mail sales contour showers co uk For Contour Showers Pump information please visit www contour showers co uk NICHOLLS and CLARKE Ltd 1 P6821619 Phlexiflow Twinned pump waste system bottom exit tray kit 2 P6821620 Phlexiflow Twinned pump waste system top exit tray kit 3 P6821620 Phlexiflow Twinned pump waste system wet floor kit Technical Helpline 0208 586 4600 E mail Tony wright jones nichollsandclarke com For Pump information please visit www nichollsandclarke com WHALE PUMPS 1 SDPO44T Tray kit 2 SDPOS4T Wet Floor Kit Technical Helpline 0845 0694 253 E mail info whalepumps com For Whale Pump warranty information please visit www whalepumps com No endorsements are offered by Triton Showers regarding any third party products listed within this fitting book COMMISSIONING The first operation of the shower is intended to flush out any remaining unit debris and to make Turn bleed sure the heater unit co
18. ff a signal is sent to the transformer and after a preset time delay stops the supply of DC voltage to the pump Please refer to the relevant Pump manufacturers installation instructions for full details of operation WARNING The pump is a non gravity installation It is advised that where the property is left unattended for an extended period of time that the water supply to the shower is shut off CONNECTING THE CONTROL WIRE The showers internal Pump Control Wire electrical connector is shown in fig 14 Note Numbers 1 and 2 only cover connecting the outgoing wire within the shower Please refer to the relevant Pump manufacturers installation instructions for Pump connection and relevant IEE regulations that must be met 1 Connect the Control Wire from the pump to the shower via the terminal block situated at the bottom of the showers PCB 2 The Control Wire MUST be routed behind B and out through D The wire MUST NOT be routed near to A Warning DO NOT route the Control wire near to A the Pump Motor A Pump Motor B PCB C Solenoid Valve D Trimplate Pump wire terminal block DANGER Rotating Parts Control wire to connect the shower to the pump transformer module Pumps are not supplied with any products manufactured by Triton Showers see page 14 for compatible pumps COMPATIBLE SHOWER DRAIN PUMPS The following Pumps are compatible with the shower AKW Medicare 1 AKW Archime
19. he cover DO NOT attempt to remove them Unscrew the two top and bottom two retaining screws fig 7 and lift the cover from the backplate Entry positions for the mains water and electric cable are from the top bottom or from the back Note Deviations from the designated entry points will invalidate product approvals If bottom entry has been chosen fit the appropriate cut out in the top of the backplate fig 8 If top entry has been chosen fit the appropriate cut out in the bottom of the cover fig 9 After choosing the site for the shower use the Installation Template supplied to mark the four fixing holes the position of which are shown in fig 7 Drill and plug to suit the fixing screws supplied The wall plugs provided are suitable for most brick walls use an appropriate masonry drill but if the wall is plasterboard or a soft building block you must use suitable wall plugs and an appropriate drill bit Screw the top two fixing screw into position leaving the base of the screw head protruding 6mm out from the wall Hook the backplate over the top of the two screw and fit the other fixing screws into position DO NOT fully tighten the screws at this stage as the fixing holes are elongated to allow for out of square adjustment after the plumbing connections have been completed PLUMBING CONNECTIONS Plumbing to be carried out before wiring DO NOT use jointing compounds on any pipe fittings for
20. ice Spares Department Payment should be made by credit debit card excluding American Express or Diners Card Payment can also be made by pre payment of a pro forma invoice by cheque or money order TRITON STANDARD GUARANTEE Triton guarantee this product against all mechanical and electrical defects arising from faulty workmanship or materials for a period of two years for domestic use only from the date of purchase provided that it has been installed by a competent person in full accordance with the fitting instructions Any part found to be defective during this guarantee period we undertake to repair or replace at our option without charge so long as it has been properly maintained and operated in accordance with the operating instructions and has not been subject to misuse or damage This product must not be taken apart modified or repaired except by a person authorised by Triton This guarantee applies only to products installed within the United Kingdom and does not apply to products used commercially This guarantee does not affect your statutory rights What is not covered 1 Breakdown due to a use other than domestic use by you or your resident family b wilful act or neglect c any malfunction resulting from the incorrect use or quality of electricity gas or water or incorrect setting of controls d faulty installation Repair costs for damage caused by foreign objects or substances Total loss of the prod
21. installation fault a charge will be made A charge will also be issued if nobody is at home when the service engineer calls or adequate parking permit is not available If the product is no longer covered by the guarantee an up front fixed fee will be charged before the site visit Should proof of purchase not be available on an in quarantee call or should the service engineer find that the product is no longer under guarantee the engineer will charge the same fixed price and the customer will be expected to pay the engineer before he leaves If payment is not made on the day an administration charge will be added to the fixed charge If a debt is outstanding from a previous visit or from any other Triton purchase Triton reserves the right to withhold service until the debt has been settled Triton takes the health safety and wellbeing of its employees very seriously and expects customers to treat all staff members with respect Should any employee feel threatened or receive abuse either verbally or physically Triton reserves the right to withhold service and will support the employee with a legal prosecution Replacement Parts Policy Availability It is the policy of the manufacturer to maintain parts availability for the duration of production and a period of five years thereafter in accordance with industry standards Spare parts are available via our website www tritonshowers co uk or by telephoning Triton Customer Serv
22. isable to contact the local electricity supply company 1 1 The electrical rating of the shower is shown on the rating label Fig 3 within the unit 2 Before making any sort of electrical connection within the installation make sure that no terminal is live If in any doubt switch off the whole installation at the mains supply and remove the correct fuse 3 shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring main spur socket outlet lighting circuit or cooker circuit 3 1 The electrical supply must be adequate for the loading of the unit and existing circuits 4 Check your consumer unit main fuse box has a main switch rating of 80A or above and that it has a spare fuse way which will take the fuse or Miniature Circuit Breaker MCB necessary for the shower Fig 4 4 1 If your consumer unit has a rating below 80A or if there is no spare fuse way then the installation will not be straightforward and may require a new consumer unit serving the house or just the shower 4 2 You will need to contact the local electricity company They will check the supply and carry out what is necessary 5 For close circuit protection DO NOT use rewireable fuse Instead use a suitably rated Miniature Circuit Breaker MCB or cartridge fuse see Table A 5 1 30mA residual current device RCD must be installed in all UK electric and pumped shower cir
23. n advisory service before installation Telephone 0844 980 0730 Facsimile 0844 980 0744 E mail technical tritonshowers co uk 1 2 1 3 1 4 1 5 1 6 1 8 1 9 2 2 2 3 PLEASE READ THIS IMPORTANT SAFETY INFORMATION Products manufactured by Triton are safe and without risk provided they are installed used and maintained in good working order in accordance with our instructions and recommendations WARNING DO NOT operate shower if frozen or suspected of being frozen It must thaw out before using DO NOT operate the unit if the showerhead or spray hose becomes damaged DO NOT restrict flow out of shower by placing showerhead in direct contact with your body DO NOT operate the shower if water ceases to flow during use or if water has entered inside the unit because of an incorrectly fitted cover GENERAL Isolate the electrical and water supplies before removing the cover Read all of these instructions and retain them for later use DO NOT take risks with plumbing or electrical equipment Isolate electrical and water supplies before proceeding with the installation The unit must be mounted onto the finished wall surface on top of the tiles Do not tile up to unit after fixing to wall Contact Customer Service see back page if any of the following occur If it is intended to operate the shower at pressures above the maximum or below the minimum stated If the unit shows a distinct cha
24. n damage to the unit and will invalidate the guarantee The following points will help you understand how the shower operates a The electric heating elements operate at a constant rate at your chosen power setting It is the rate of the water passing through the heater can which determines the water temperature The slower the flow the hotter the water becomes the faster the flow the cooler the water b During winter the mains water supply will be cooler than in the summer so the flow rate will vary between seasons at any one temperature setting At different times of the year you may have to adjust the position of the temperature control to maintain your desired temperature setting c The stabiliser valve minimises variations in shower temperature during mains water pressure changes If changes in shower temperature are experienced during normal use it will most likely be caused by the water pressure falling near to or below the minimum level The drop in pressure may be due to water being drawn off at other points in the house whilst the shower is in use If pressure drops appreciably below the minimum the heating elements will automatically cut out If ever the water becomes too hot and you cannot obtain cooler water first check that the sprayplate in the showerhead has not become blocked DO NOT place items such as soap or shampoo bottles on top of the unit Liquid could seep through the joint between the cove
25. nce Hotter low flow shutdown Temperature control knob mk 4 6 N 7 9 temperature Cooler To adjust the shower temperature The water temperature is altered by changing the amount of Hot water from the heater can that is mixed with Cold water from the inlet This is done by moving the temperature control knob fig 22 Adjusting the temperature control will alter the flow of water through the unit After obtaining your preferred showering temperature the number setting can be remembered and left as the preferred setting To decrease the shower temperature Turn the temperature control anti clockwise this will increase the flow of water through the shower and is indicated by lower numbers and make the water cooler To increase the shower temperature Turn the temperature control clockwise this will decrease the flow of water through the shower and is indicated by higher numbers and make the water hotter When the start stop button is pressed water will continue to flow in order to remove heated water inside the unit see phased shutdown process P21 Water will cease to flow after a few seconds After phased shutdown the unit must be isolated via the 45amp isolating switch Note It is advisable to be certain that the showering temperature is satisfactory by testing with your hand before stepping under the showerhead There will always be a time delay of a fe
26. nections can result in cable overheating Note The supply cable earth conductor must be sleeved The outer sheath of the supply cable must be stripped back to the minimum Terminal block Earth post Start stop switch Cover PCB Solenoid 10 way ribbon cable Thermal cut out PCB live PCB neutral The supply cable must be secured either by routing through conduit or in trunking or by embedding in the wall in accordance with IEE regulations The use of connections within the unit or other points in the shower circuit to supply power to unspecified equipment other than that listed on page18 will invalidate the guarantee 1 2 3 4 5 6 7 8 9 DO NOT switch on the electricity supply until the cover has been fitted Note The elements on UK models are to 240V specification and will give a lower kW rating if the voltage supply is below 240V WARNING After any servicing of the water supply always flush out the pipework to remove any debris In these circumstances the unit should only be re started by following the commissioning procedure on page 15 16 relay relay Power 5 25kW 1 3 25kW Outlet thermistor Low flow switch Pump motor Terminal block SHOWER DRAIN PUMPS Principals of operation When the shower is turned on an internal sensor sends a signal to the transformer to supply DC voltage to the pump When the shower is turned o
27. nge in performance If the shower is frozen If it is intended to operate the shower in areas of hard water above 200 ppm temporary hardness a scale inhibitor may have to be fitted For advice on the Triton Scale Inhibitor contact Triton Customer Service The showerhead must be cleaned regularly with descalent to remove scale and debris otherwise restrictions to the flow on the outlet of the unit will result in higher temperatures and could also cause the Pressure Relief Device in the unit to operate This product is not suitable for mounting into steam rooms or steam cubicles PLUMBING The plumbing installation must comply with Water Regulations Building Regulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS 6700 The supply pipe must be flushed to clear debris before connecting to the shower unit DO NOT solder pipes or fittings within 2 4 2 5 2 6 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 10 300mm of the shower unit as heat can transfer along the pipework and damage components DO NOT fit any form of outlet flow control as the outlet acts as a vent for the heater can DO NOT use excessive force when making connections to the flexible hose or showerhead finger tight is sufficient All plumbing connections must be completed before making the electrical connections ELECTRICAL The installation must
28. nimum capacity L water 114 litres 25 gallons cistern Mains electric Stop Isolating supply via double valve valve pole switch _ Double pole isolating switch Separate permanently connected supply from consumer unit WARNING The shower must not be positioned where it will be subjected to freezing conditions a ee 7 Mains cold water supply either top bottom or back entry Shower unit can be mounted either side of riser rail Height of sprayhead and shower to suit user s requirement i Height of shower should bea minimum of 1 metre from base Diagrammatic view not to scale IMPORTANT The unit must be mounted on a flat surface which covers the full width and length of the backplate It is important that the wall surface is flat otherwise difficulty may be encountered when fitting the cover and subsequent operation of the unit may be impaired SITING OF THE SHOWER For ease of servicing the unit must always be mounted on the surface of tiled walls Never tile up to the unit Refer to Fig 6 for correct siting of shower Position the unit where it will not be in direct contact with water from the showerhead Position the shower unit vertically Allow enough room between the ceiling and the shower to access the cover top screws
29. ntains water before the we 3 elements are switched on turns out e Make sure that the electricity supply to the unit and isolating switch has been turned off then remove the front cover and disconnect the PCB cable Also remove the right hand trimplate e Turn the water supply to the unit on and turn the bleed screw fig 15 approximately 3 turns out Make sure that an absorbent cloth is in place to catch any purged water Let the water flow approximately 30 60 seconds is advised until a steady stream of water with no bubbles in it flows from the bleed screw Once this has been achieved re tighten the bleed screw e Refit the right hand trimplate and the cover fig 16 17 DO NOT connect the PCB cable at this time This will allow the unit to operate in commissioning mode This allows the pump to operate but does not engage the heater can circuits This is to allow the system to flush and fill with water and purge any remaining air e Secure the cover with a couple of the retaining screws The following operation must be carried out with the flexible hose screwed to the outlet but without the showerhead attached Make sure the outlet of the flexible hose is directed to waste Turn the Temperature control to number 1 then re enable the power the isolator switch Turn on the isolator switch The pump will operate and water will flow from
30. ped thermostatic electric shower T150Z pumped thermostatic electric shower T150Z pumped thermostatic electric shower Service Policy In the event of a product fault or complaint occurring the following procedure should be followed 1 Telephone Customer Service on 0844 980 0750 having available your details including post code the model number and power rating of the product together with the date of purchase Based on information given over the telephone a Triton Customer Service Advisor will attempt to diagnose the fault and confirm whether a site visit from a qualified service engineer is required All products attended to by a Triton service engineer must be installed in full accordance with the Triton installation guide applicable to the product Every product pack contains an installation guide however they can also be bought via our Customer Service Spares Department Our engineer will require local parking and if a permit is required this must be available to the engineer on arrival at the call It is essential that you or an appointed representative who must be over 18 years of age is present for the duration of the service engineer s visit If the product is in guarantee you must produce proof of purchase Where a call under the terms of guarantee has been booked and the failure is not product related i e scaling and furring incorrect water pressure pressure relief device operation or electrical plumbing
31. r and backplate and possibly damage the sealing rubber This product is rated at 30 minutes on 30 minutes off MAIN COMPONENTS J E h a Dr _ 17 6 Inside unit fig 1 1 gt SY cable pipe entry Wall screw fixings Cover screw fixings Thermal safety cut out Power printed circuit board Can and element assembly Flow switch assembly J Temperature Control Terminal block Earth connection Solenoid valve Water inlet Pressure relief device PRD NI JI 90 fetal wl Shower outlet Filter Pump motor Pump Trimplate Bottom cable pipe entry T150Z pumped thermostatic electric shower MAIN COMPONENTS continued Inside Cover fig 2 20 Stop start switch Inside 21 Control printed circuit board Inside 22 Front cover T150Z pumped Other items Screw fixing kit Instructions guarantee etc TRITON 1502 ELECTRICAL REQUIREMENTS WARNING THIS APPLIANCE MUST BE EARTHED The installation supply cable and circuit protection must conform with BS 7671 IEE wiring regulations and be sufficient for the amperage required The following notes are for guidance only 1 The shower must only be connected to a 230 240V ac supply If you are installing a shower with a kilowatt rating above 9kW it is adv
32. the shower Timed Shutdown a indicator temperature Temperature Protection During normal operation if the flow of water through the unit is restricted power to the elements will be reduced to maintain the shower temperature When the flow of water through the unit returns to normal power to the elements will be automatically restored to the setting at the time of interruption NOTE The Timed Shutdown Indicator will only operate if the unit reaches of the predetermined shut down Safety cut out The unit is fitted with an over temperature safety device In the event of abnormal operation which could cause unsafe temperatures within the unit times of 5 10 20 factory setting or the device will disconnect the heating elements 30 minutes To set the unit to one of and remove power from the electronics making these times see page 17 the shower unit inoperable It will require a visit from a qualified engineer to identify the nature of the fault and replace the safety device INSTRUCTIONS FOR INSTALLERS AND SERVICE ENGINEERS ONLY WARNING ENSURE THE FILTER IS RE INSERTED INTO THE INLET BODY AFTER CLEANING DO NOT OVERTIGHTEN CAP RS B amp CLEANING THE FILTER It is recommended that the filter is periodically cleaned in order to maintain the performance of the shower It is essential that this operation is carried out by a competent person Switch off the electricity and w
33. uct due to non availability of parts Compensation for loss of use of the product or consequential loss of any kind Call out charges where no fault has been found with the appliance The cost of repair or replacement of pressure relief devices showerheads hoses riser rails and or wall brackets isolating switches electrical cable fuses and or circuit breakers or any other accessories installed at the same time The cost of routine maintenance adjustments overhaul modifications or loss or damage arising therefrom including the cost of repairing damage breakdown malfunction caused by corrosion furring pipe scaling limescale system debris or frost Customer Service F 0844 980 0750 Trade Installer Hotline Z 0844 980 0730 Fax 0844 980 0744 Triton Showers Triton Road Nuneaton Warwickshire CV11 4NR www tritonshowers co uk Triton is a division of Norcros Group Holdings Limited E mail serviceenquiries tritonshowers co uk Extended Warranty AVAILABLE NOW Call 0844 980 0740 for more details TRITON reserve the right to change product specification without prior notice amp TRITON SHOWERS 2009
34. w seconds between selecting a flow rate and the water reaching the stable temperature for that flow rate OPERATING FUNCTIONS fig 23 Power on indicator green When the electricity supply to the shower is Power On indicator switched on at the isolating switch the power indicator will light up Low flow indicator red Low Flow indicator low fl If a low flow condition occurs the unit will turn a off the water flow immediately It will be necessary to wait until water in the unit has reduced to a comfortable temperature at which point the LED will extinguish Pressing the start button will then restart the unit Timed Shutdown indicator yellow The operation of this LED denotes that a Timed shutdown has been programmed into the unit Temperature When the indicator illuminates it indicates there control knob is 1 minute before the timed shutdown setting 5 The indicator will then flash for 5 seconds prior to the shower switching off an audible beep will also commence if it has been set to do so see commissioning section for information on how to program the unit Phased shutdown In use every time the Start Stop button is pressed power is switched off to the elements Water will continue to flow for a few seconds flushing out any remaining hot water This makes sure the next immediate user will not X receive a slug of hot water if standing under the showerhead when starting
Download Pdf Manuals
Related Search
Related Contents
Mise en page 1 Manuel d`utilisation Mise en page 1 Midland Radio 75-785 Two SDS_FDS Ortho® Home Defense® Max™ No-Pest ZD500 Series™ Guía del usuario - Zebra Technologies Corporation TITRE : Aptitude et vision : profession, sport, déficient visuel, travail Samsung L77 Bruksanvisning Copyright © All rights reserved.
Failed to retrieve file