1. This parameter sets the maximum temperature thermometric allowed for the gas at the evaporator outlet If the MOP situation is reached with particularly high or normal superheat values for example if the unit is started with particularly high temperatures of the fluid being cooled the risk exists that the unrestricted and extended action of the MOP routine will lead to a refrigerant suction temperature that is excessive for the correct operation of the compressor for this reason a limit has been introduced for the maximum suction temperature This parameter limits the action of the MOP protection routine so that when the value is reached the corrective action of the protection routine is stopped completely until the temperature of the refrigerant returns below the set value The value set depends on the refrigeration unit and its design and is indeed a rated value for the unit no recommendations are possible 1 3 Alarms enable delay COMM These parameters enable certain alarms some of which can be delayed by a time in seconds while others are always immediate Opened EEV effective only when the optional battery is used This enables the function that checks the complete closing of the expansion valve following the shutdown of the unit if the valve is not closed the user must take action to reset the system A delay cannot be assigned when the alarm is enabled it is always immediate and can only be reset using the Goahead proced
2. high evaporation temperature reached N B A value of 0 zero seconds completely disables the protection routine HiTcond Protection HiTcond limit High condensing pressure threshold indicated as C saturated temperature This parameter defines the high condensing pressure protection activation threshold above this value integral control starts using a set constant with the aim of returning and maintaining the saturated condensing temperature below the set value This should be used exclusively after laboratory tests and only on systems without capacity modulation this is in fact preferable to the HiTcond routine to avoid shutdowns due to high pressure If the compressor is shutdown due to the activation of the thermal overload protector the high condensing pressure situation needs to be resolved this may be due to an excessively low threshold HiTcond and or a value that is incompatible with the operating conditions HiTcond Protection Integral time This parameter is the integration constant for the high condensing pressure protection HiTcond The recommended value is 3 seconds and can be increased to approx 10 seconds if the action is too intense excessive closing of the valve as a response to high pressure and decreased to 2 seconds if the action is too bland excessively high condensing temperature reached N B A value of 0 zero seconds completely disables the protection routine Suction temperature high limit
3. unit is started until the activation of the MOP protection routine From when the unit starts until this time elapses the MOP protection routine is deactivated so as to allow smooth unit start up with an evaporation pressure that is greater than the MOP threshold value The recommended value is 60 seconds however the changeability of the starting dynamics of the different units means that the time must be optimised in the set time the evaporation pressure must fall below the value set for the MOP Limit or else the MOP routine will be activated MOP Protection MOP limit High suction pressure threshold MAXIMUM OPERATING PRESSURE indicated as C saturated temperature This parameter defines the high pressure protection activation threshold above this value integral control starts using a set constant with the aim of returning and maintaining the saturated suction temperature below the set value The value set depends on the refrigeration unit and its design and is indeed a rated value for the unit no recommendations are possible Cod 030220205 rel 1 0 30 03 06 16 EVD200 parameter guide MOP Protection Integral time This parameter is the integration constant for the high pressure protection MOP The recommended value is 2 seconds and can be increased to approx 10 seconds if the action is too intense excessive closing of the valve as a response to high pressure and decreased to 1 second if the action is too bland excessively
4. Guida parametri EVD 200 Manuale d uso User manual LEGGI E CONSERVA QUESTE ISTRUZIONI 4 READ AND SAVE THESE INSTRUCTIONS CAREL Technology amp Evolution Contents 1 1 12 1 3 EVD200 parameter guide iii nen 15 Driver configuration seene sensan anaa aaa a eet deed 15 ROPA O 15 Alarms enable delay COMM 17 EVD200 parameter guide 1 EVD200 parameter guide The following recommended settings are purely indicative and should be checked according to the design characteristics and the refrigeration unit used 1 1 Driver configuration Drivers connected Enter the number of drivers in the pLAN Battery present Indicate whether the battery module is installed 1 2 Parameter configuration e Manufact CH the parameters on this screen are used when the driver is operating in chiller mode e ManufactHP the parameters on this screen are used when the driver is operating in heat pump mode e Manufact DF the parameters on this screen are used when the driver is operating in defrost mode e Manufact COMM the parameters on this screen are used in all modes and relate to the driver the expansion valve and the refrigerant circuit This category includes parameters such as the type of refrigerant the type of probes used the alarms the characteristics of the expansion valve etc EEV Type Select the type of expansion valve connected Selecting the CUSTOM option allows th
5. e configuration parameters described below to be set manually Refrigerant This parameter sets the type of refrigerant used on the unit this setting is required to calculate the saturated temperatures based on the DEW POINT EEV position This parameter enables the EVDriver control function AUTO setting or can be used to manually open the valve MANUAL setting In this case two further values are visible the required opening of the valve and the absolute position of the valve in terms of control steps Circuit EVV Ratio COMM The percentage of compressor cooling capacity to valve capacity is the ratio between the maximum cooling capacity of the circuit where the EVDriver is installed and the maximum capacity of the expansion valve 100 opening in the same operating conditions The conditions used to calculate the capacity do not need to be the rated values however the calculation conditions Te Tc must be identical for the valve and the compressor and should be as near as possible if not equal to the effective normal operating conditions of the unit The recommended initial value is 60 unless there are considerable differences between the capacity of the valve and the system SHeat Stp This indicates the superheat control set point The recommended value is 6 C Values below 3 C are not recommended Dead zone The dead zone is the semi interval of temperature around the superheat set point inside which no control
6. h a threshold of 2 C If the threshold is lower the time must also be decreased to 0 5 C N B A value of 0 zero seconds completely disables the protection routine LOP protection LOP limit Low suction pressure threshold LOWEST OPERATING PRESSURE indicated as C saturated temperature This parameter defines the activation threshold for the low pressure protection below this value integral control starts using a set constant with the aim of returning and maintaining the temperature above the set value The recommended value is from 5 C to 10 C below the typical minimum saturated evaporation temperature of the installation Example for chillers with a rated evaporation temperature of 3 C and a minimum admissible evaporation temperature of 1 C set the LOP Limit to 6 C The low superheat protection LOW SHeat PROTECTION always has priority over the low suction pressure protection LOP PROTECTION LOP protection Integral time This parameter is the integration constant for the low pressure protection LOP The recommended value is 2 seconds and can be increased to approx 10 seconds if the action is too intense excessive opening of the valve as a response to low pressure and increased to 1 second if the action is too bland excessively low evaporation temperature reached N B A value of 0 zero seconds completely disables the protection routine MOP Protection Startup delay This is the waiting time from when the
7. is performed recommended value 0 C Increase to 1 C in the event of system instability however only after having attempted to resolve the problem with the other control constants described below Values above 2 C are not recommended Prop Int Diff factor The proportional integration and derivative constants are the main EVDriver control parameters These define the PID superheat control function see classic PID control theory for a more detailed description of their meanings Recommended values Proportional gain factor Standard or reference values CAREL E2V 3 Sporlan 30 3193 steps 20 Alco EX5 EX6 7 Sporlan 50 250 6386 steps 30 Alco EX7 15 Danfoss ETS 50 20 Alco EX8 20 Danfoss ETS 100 30 Sporlan 20 1596 steps 15 Danfoss ETS 250 400 35 Cod 030220205 rel 1 0 30 03 06 15 EVD200 parameter guide The recommended range is given by the formula step max LA Kp 20 100 Lee Max step maximum expansion valve control steps QCIRC capacity of the refrigerant circuit in kW at the defined operating conditions QEEV capacity of the expansion valve in KW in the same conditions for this value refer to the documents on the valve If there are many operating conditions that are significantly different cooling capacity Te Tc use an average Kp based on the values those calculated using the formula or deriving from the tests carried out in the different conditions whilst generally favouring l
8. ower values and reducing the integral times of the protectors LOW SH MOP Compressors with continuous control inverter or stepless screw if the control dynamics are especially fast increase the values of the proportional constant so as to allow the valve to respond to the cooling capacity faster The values entered may be increased up to 300 depending on the situation Integral time The values used in the various applications range from 10 to 100 seconds depending on the dynamics of the evaporator used The recommended values are Plates 25 Finned coil and tube bundle 30 to 45 Values above 80 seconds are only recommended for utilities featuring evaporators with a high average refrigerant duration such as the majority of centralised utilities display cabinets for supermarkets Differential time The recommended value is 1 5 seconds and this generally does not need to be changed Low SHeat protection Low limit Low superheat threshold below this value an integral control function is activated in addition to the PID integration action with programmable constant The recommended value is 2 C with superheat set point greater than 4 C If the set point is lower the low superheat threshold must also be reduced with a difference between the two of at least 2 C Low SHeat protection Integral time This parameter is the integration constant for the low superheat protection The recommended value is 1 0 seconds wit
9. ure in the Manufacturer menu of the EVDriver configuration Control alarms If setting a value of 10 seconds the alarm situation must remain in place for more than 10 seconds before the alarm is activated and displayed If the alarm situation ceases before the set delay time the timer is set to zero A time of 0 zero seconds corresponds to disabling the alarm and opening the alarm relay if enabled for this alarm Low SHeat This sets the delay time for the activation of the low superheat alarm High TSuct This sets the delay time for the activation of the high suction temperature alarm LOP This sets the delay time for the activation of the low suction pressure alarm MOP This sets the delay time for the activation of the high suction pressure alarm CAREL reserves the right to make modifications or changes to its products without prior notice Cod 030220205 rel 1 0 30 03 06 17 90 0 0 OL 18H SOZOZZOE0 POD