Contents

1. oo0oo0ooo o L Io o o o o o o o o o o o B DIA FLOW CONTROL VALVE AND CROSS OVER PIPING oc oc wi wi O O T2 z PLAN z z 5 E zZ LL ee a o FACE OF ADIA z INLET PIPING COL INLET INLET PIPING SHOWN WITH C D TYP MULTI CELL 7 DASHED LINES IS BY OTHERS ke 4 zZ e ENDWALL G ELEVATION BASE OF TOWER COLUMNS Ly Tower GPM Dimensions Model per cell A B c D E F G 1011 380 2140 10 8 4 0 8 0 8 11 11 8 12 574 1021 580 3220 10 8 6 0 12 0 8 11 11 8 12 572 1031 580 3220 10 8 6 0 12 0 10 1 12 10 12 574 1041 790 3240 10 8 8 0 16 0 11 254 13 11 12 57 1041 3241 4300 16 123 8 0 16 0 11 5 13 11 2 12 87 NOTE 1 Use this bulletin for preliminary layouts only Obtain current 4 Marley piping terminates at face of a cast iron flat face flange drawings from your Marley sales representative 2 Pumping head contributed by the tower is static lift shown on page 5 Actual pumping head will vary according to tower circulating GPM Total pumping head will be furnished at time of proposal 3 If your application requires a bypass system recommended location is through
2. 9 I HAH B DIA FLOW CONTROL VALVE AND CROSS OVER PIPING D a WN L N y i O Ii w Hl eet a os ae i J EN I z PLAN WL J T o E z d e 2 Z M q i FACE OF ADIA INLET PIPING D TYP MULTL CELL DASHED LINES SEN OTHERS 4 z esi ENDWALL ELEVATION G BASE OF TOWER COLUMNS 4 Tower GPM Dimensions Model Per Cell A B c D E F G 1211 1050 5750 16 124 8 0 16 0 13 2 16 6 4 15 6 1221 1050 5750 16 125 8 0 16 0 14 2 17 6 15 6 1231 1320 7200 16 12 10 0 20 0 14 2 17 6 15 6 1241 1500 7050 16 123 12 0 24 0 14 2 17 6 15 6 1241 7051 8650 20 16 12 0 24 0 14 5 17 6 15 8 1251 1500 7050 1a 125 12 0 24 0 16 234 19 6 15 6 1251 7051 8650 20 16 12 0 24 0 16 5 19 6 15 8 1261 1850 7050 16 125 14 0 28 0 16 234 19 6 15 6 1261 7051 10100 20 16 14 0 28 0 16 5 19 6 15 8 NOTE 1 Use this bulletin for preliminary layouts only Obtain current 4 Marley piping terminates at face of a cast iron flat face flange drawings from your Marley sales representative which conforms to class 125 lb ASME B 16 1 specifications 2 Pumping head contributed by the tower is static lift shown 5 Supports on tower for crossover piping are are part of the tower on page 9 Actual pumping head will vary according to tower design Do not support the riser s dead lo
3. deel l LAL COL COL COL E 5 A BAYS 4 0 L 5 ___ TOP OF FAN CYLINDER ce B TOP OF FAN DECK ee eae ENDWALL i ELEVATION BASE OF TOWER COLUMNS oy Tower GPM Width Length Height A B c Maximum Static Model Per Cell Ww L H Motor hp Lift 1211 1050 5750 31521 16 0 14 51 4 6 0 144 60 14 5 1221 1050 5750 33 2 16 0 14 5 4 7 0 168 75 14 5 1231 1320 7200 33 2 20 0 14 5y 5 7 0 168 75 14 5 1241 1500 8650 33 2 24 0 14 54 6 7 0 168 75 14 5 1251 1500 8650 37 2 24 0 14 54 6 7 0 2164 100 14 5 1261 1850 10100 37 2 28 0 14 5 7 7 0 216 100 14 5 NOTE 1 Last number of model indicates number of cells Change as 3 Height shown is from base of tower columns to fan deck Wood appropriate for your selection Primary engineering data is per basin if used elevates tower 61 4 If concrete basin is used cell subtract 1 6 for height above top of basin curb 2 Fan hp is usually less than shown here Marley Sigma 1200 Cooling Tower Engineering Data Piping
4. Operating Cooling Towers During Freezing Weather Normally two speed motors are provided in 1800 900 RPM single winding configuration which is the least expen sive two speed option They are also available in other combi nations including the more expensive double winding Variable Speed Control Frequency modulation devices work well on induced draft propeller fan cooling towers such as the Sigma However their design must include the capability to lock out any critical fan speeds and the very low fan speed ranges Marley VFD drive systems are designed to combine abso lute temperature control with ideal energy management The cooling tower user selects a cold water temperature and the drive system will vary the fan speed to maintain that tem perature Precise temperature control is accomplished with far less stress to the mechanical equipment components The improved energy management provides fast payback Indeed many utilities offer generous rebates for users having installed VFD drives 12 Marley Sigma 1000 1200 Cooling Tower Engineering Data Environmental Enclosures Occasionally cooling towers are located inside architectural enclosures for aesthetic reasons Although Sigma towers adapt well to enclosures a poorly designed enclosure can impair proper operation An effective design includes gener ous air inlet paths with the tower s fan cylinder discharge at or above the top of the enclosure See Marley Tec
5. and we strongly recommend that you require it of all bidders Portable ladders and other make do access means are inappro priate for equipment of this size and complexity E This basic specification assumes that the tower will be erected over a concrete basin at grade level If the tower is to be installed on an elevated supporting platform the plywood cold water collection basin indicated on page 17 should be included in the specifications E Please be clear in your specifications and inquiry documents regarding the full scope of work expected That will help assure that your bid comparisons will be made on as equal a basis as possible and will help to avoid any misunder standings during the execution and implementation of the contract Marley Sigma 1000 1200 Cooling Tower Specifications Options 22 Specification Value Control Options Control System Add the following paragraph in the Mechanical Equipment section Each cell of the cooling tower shall be equipped with a UL listed control system in a NEMA 3R or 4X outdoor enclosure capable of controlling single speed or two speed motors as required and designed specifi cally for cooling tower applications The panel shall include a main fused disconnect with an external operating handle lockable in the off position for safety Across the line magnetic start ers or solid state soft start starters as required shall be controlled with a thermos
6. 1041 26 5 4 16 0 29020 27200 Use this bulletin for preliminary layouts only Do not use for construction Obtain current drawings from your Marley sales representative Concrete basin design and construction are by other contractors or purchaser Operating weight is total wet operating weight of tower only excluding water in concrete basin Maintain at least 2 0 of clear space at endwall faces for construction purposes Air inlet faces must have unobstructed air supply Consult your Marley sales representative for recommendations if nearby obstructions may interfere 4 Minimum basin depth is 1 6 Maximum basin depth is 5 6 Extended interior columns for deep basins are available as an option Perimeter columns remain at 1 6 below top of basin curb 5 All anchor bolts complete with nut and washer must be furnished by others Bolts must be diameter with 2 all thread projection 6 Other contractors or purchaser must design construct and furnish sump and overflow to suit requirements Marley Sigma 1200 Cooling Tower Engineering Data Schematic oc O C DIA FAN lt 3 fo H T 5 PLAN 3 gt
7. Marley Sigma 1000 1200 Cooling Tower Engineering Data amp Specifications i COOLING TECHNOLOGIES Marley Sigma 1000 1200 Cooling Tower Table of Contents Engineering Data 1000 Schematic 4 1000 Piping 5 1000 Support 6 1200 Schematic 8 1200 Piping 9 1200 Support 10 Energy Management 12 Environmental 13 Specifications Base Base 14 Thermal Performance 15 Construction 16 Fan Deck and Fan Cylinder 17 Mechanical Equipment 18 Fill Louvers and Drift Eliminators 19 Hot Water Distribution System 20 Casing 20 Access 20 Cold Water Collection Basin 21 Scope of Work 21 Specifications Options Control Options Control System 22 Basin Heater 23 Fan Motor Variable Speed Drive 23 Marley Premium VFD System 24 Vibration Limit Switch 25 Convenience and Safety Options Stairway 26 Plenum Walkway 26 Ladder Extension 26 Ladder Safety Cage 26 Oil Level Sight Glass 27 Miscellaneous Options Wood Cold Water Basin 27 Redwood Components 27 Hot Water Basin Covers 27 Air Inlet Screens 27 Low Noise Tower 28 Watertight Partitions Between Cells 29 Fire Safety Options 29 Marley Sigma 1000 1200 Cooling Tower M ime 1000 1200 towers are field erected general purpose crossflow wood cooling towers designed to serve normal air conditioning and refrigeration systems as well as medium sized industrial loads They evolve from the crossflow concept of towers pioneered by Marley in 1938 and incorporate over 65
8. noise concerns are limited to nighttime when ambient noise levels are lower and neighbors are trying to sleep You can usually resolve these situations by using two speed motors in either 1800 900 or 1800 1200 RPM configura tion and operating the fans at reduced speed without cycling after hours The natural nighttime reduction in wet bulb tem perature makes this a very feasible solution in most areas of the world but the need to avoid cycling may cause the cold water temperature to vary significantly e Variable speed drives automatically minimize the tower s noise level during periods of reduced load and or reduced ambient without sacrificing the system s ability to maintain a constant cold water temperature This is a relatively inexpensive solution and can pay for itself quickly in reduced energy costs e Where noise is a concern at all times for example near a hos pital the best solution is to oversize the tower so it can operate continuously at reduced 1200 or 900 RPM motor speed even at the highest design wet bulb temperature Typical sound reduc tions are 7 dBA at 2 3 fan speed or 10 dBA at 1 2 fan speed but larger reductions are often possible e Extreme cases may require inlet and discharge sound attenu ator sections however the static pressure loss imposed by attenuators may necessitate an increase in tower size This is the least desirable approach because of the significant cost impact and because of th
9. 1231 33 6 4 5 20 0 49100 46560 1241 33 6 4 6 24 0 59020 56470 1251 37 634 6 24 0 61200 58530 1261 37 634 7 28 0 70900 68240 NOTE 1 Use this bulletin for preliminary layouts only Do not use for construction Obtain current drawings from your Marley sales representative Concrete basin design and construction are by other contractors or purchaser 2 Operating weight is total wet operating weight of tower only excluding water in concrete basin 3 Maintain at least 2 0 of clear space at endwall faces for construction purposes Air inlet faces must have an unobstructed air supply Consult your Marley sales representative for recommendations if nearby obstructions may interfere 4 Minimum basin depth is 1 6 Maximum basin depth is 5 6 Extended interior columns for deep basins are available as an option Perimeter columns remain at 1 6 below top of basin curb 5 All anchor bolts complete with nut and washer must be furnished by others Bolts must be diameter with 2 all thread projection 6 Other contractors or purchaser must design construct and furnish sump and overflow to suit requirements Cooling towers are usually selected to produce a specific cold water temperature at the higher summertime wet bulb temperatures During the remainder of the year the cooling tower is capable of producing much colder water Unless your system will benefit from the coldest possible water
10. bypass to maintain the set point emperature of the cold water The drive design shall be operated as a stand alone system without the need for a BMS sys tem Operator controls shall be mounted on the front of the enclosure and shall consist of start and stop control bypass VFD selector switch Auto Manual selec tor switch manual speed control and solid state temperature controller An emergency bypass selector switch inter nal to the panel allowing the fluid cooler an motor to be run at full speed shall be furnished To prevent heating problems in the fluid cooler fan motor and to assure proper gear box lubrication the VFD sys em shall de energize the motor once 25 motor speed is reached and cool ing is no longer required The VFD shall include de icing logic with auto canceling and adjustable time Speed in De Ice mode shall not exceed 50 motor speed The fluid cooler manufacturer shall supply VFD start up assistance Tower vibration testing throughout the speed range is required to identify and lockout any natural frequency vibration levels which may exceed CTI guidelines Vibration Limit Switch E Unless specified otherwise a Metrix switch will be provided A double pole Add the following paragraph in the double throw model is also available If Mechanical Equipment section A purchased in conjunction with the Control single pole double throw vibration limit System it is also factory wired The switch in a NEMA 4
11. can render the limits of customary construction standards inadequate for cooling tower design The importance of shear plates is discussed at length in Marley Difference Item S 3 Ask your Marley representative for a copy See notes on page 27 regarding the use and availability of red wood Specification of minimum member sizes assures that all offerings will conform to an industrial level of construction Multicell towers must have plenum partitions between cells Otherwise air will be induced downward through an inoperative fan bypassing the fill entirely Without these partitions part load or off season operation of the tower would be completely unsat isfactory Marley Sigma 1000 1200 Cooling Tower Specifications Base Specification Value 4 0 Fan Deck and Fan Cylinder 4 1 The fan deck shall act as a working The indicated design values for framing and decking not only give platform for maintenance personnel you assurance that the tower can withstand long term operation It shall be fabricated of no less than in a hostile environment but that it will accept many years of 1 thick 7 ply exterior grade treated inspection and maintenance traffic by your operating personnel Douglas Fir plywood and shall be designed for a uniform live load of Fiberglass reinforced polyester fan cylinders provide the close tip 60 psf or a concentrated load of 600 clearances and smooth airflow contour necessary for good fan pounds perfo
12. endwalls and shall include a lift out door in each transverse parti tion to give free access through the tower The top of the tower shall be equipped with a sturdy 42 high wood guardrail system top rails intermediate rails and toeboards conforming to OSHA standards Posts shall be 4 x4 on no greater than 8 0 centers Guardrails shall be 2 x4 Single 2 x4 top rail will be acceptable up to 6 0 span Above 6 0 span an additional 2 x4 cap strip shall be included ML E Gravity flow distribution basins are a feature of crossflow type towers These basins are out where they can be easily inspect ed even maintained while the tower is in operation Spray systems of counterflow towers sandwiched between the top of the fill and the drift eliminators are extremely awkward to access and maintain Marley flow control valves remain serviceable for the life of the tower and provide a continuing means of flow regulation between hot water basins and between cells of multicell towers as well Towers without valves do not provide this valuable oper ating flexibility s CEE 2 Trrrd pss d va J A bs aha w E E The access doors on other towers may be unreasonably small Specifying the size of the door will cause those bidders to take exception alerting you to a potential maintenance headache Good maintenance practice requires periodic access to the top o
13. equipped with guardrails Ladder Extension Add the following paragraph in the Access and Safety section Provide a ladder extension for connection to the base of the ladder attached to the tower casing This extension shall be long enough to rise from the roof grade level to the base of the tower Anchorage and lateral bracing of the ladder extension shall be by others Ladder Safety Cage Add the following to the end of this paragraph A heavy gauge galvanized steel safety cage shall surround the ladder extending from a point approxi mately 7 0 above the base of the ladder to the top of the guardrail sur rounding the fan deck E Although they are not neces sary for routine operation and maintenance stairways do provide a safe and comfort able means of access to the top of the tower that is often overlooked in the initial cool ing tower purchase They are designed in straight run or double back configurations to accommodate your site requirements Ei This option permits freedom of movement for inspection or main tenance within the tower without the need for wading boots or tower drainage It also helps prevent maintenance personnel from damaging submerged accessories in the cold water basin such as screens probes basin heaters etc E Many towers are installed such that the base of the tower is 2 0 or more above the roof or grade level This makes it difficult to get up to the base of the attach
14. joints and all fasteners shall be in accordance with CTI STD 119 Basic design criteria shall be 30 psf wind load and 5 g seismic load All wood components shall be treated after fabrication with chromated cop per arsenate CCA by the full cell process to a chemical retention of 0 4 lbs ft Structural columns and diagonals shall be 4 x4 Framing girts may be 2 x4 except for those supporting the hot water basins and fill Those girts shall be 2 x6 minimum located both sides of the support columns Multicell towers shall include treated Douglas Fir plywood partitions between cells in the plenum area Partitions shall extend the full height of the tower from the base of fill to the underneath side of the fan deck Column lines shall be on no greater than 4 0 longitudinal centers and the base of all perimeter columns shall be firmly anchored to galvanized steel base plates Framing joints shall be made with 1 2 diameter or larger series 300 stainless steel machine bolts nuts and washers EThe limiting water quality values indicated are those which are acceptable for the normal materials of construction specified If water of more aggressive quality is anticipated please change hardware material requirement to 300 Series stainless steel as indicated below and following Cooling Technology Institute standards take into account the hot humid environment in which a cooling tower normally operates This environment
15. of 25 or less Para 8 1 e Fan cylinders of fire retardant FRP having a flame spread rating of 25 or less Para 4 2 e thick fireproof fiber reinforced cement overlay over the fan deck and will provide FRC overlaid distribution basin covers Para 4 1 e 34 thick plywood partitions both sides of the column line between cells to achieve a fire rating of at least 30 minutes Para 3 5 and this page SP COOLING TECHNOLOGIES 7401 WEST 129 STREET OVERLAND PARK KANSAS 66213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008 SPX Cooling Technologies Inc Printed in USA SIG TS 08A
16. which means that you the owner will have to pay for the additional basin wiring starters piping etc eThe reimbursement of a portion of the total contract price equal to the percentage deficiency in performance Under no circumstances should you allow the manufacturer to re pitch the fans to increase motor brake horsepower above that shown in the proposal That creates additional operating costs that will continue for the life of the tower and imposes no pen alty on the manufacturer 95 90 85 80 Hi 5 F RANGE 75 lt gt 10 F RANGE A 15 F RANGE COLD WATER TEMP F 60 55 50 55 60 65 70 75 80 WET BULB TEMP F Typical cooling tower performance curve Marley Sigma 1000 1200 Cooling Tower Specifications Base Specifications Specification Value Construction The tower shall be capable of with standing water having a pH of 6 5 to 8 0 a chloride content NaCl up to 750 ppm a sulfate content S04 up to 1200 ppm a sodium bicarbonate con tent NaHCO3 up to 200 ppm a cal cium content CaCO3 up to 800 ppm silica SiO2 up to 150 ppm and design hot water temperatures up to 120 F The circulating water will contain no oil grease fatty acids or organic sol vents The structural framework of the tower shall be Douglas Fir designed in accor dance with CTI STD 114 Nylon shear plates shall be utilized to transmit loads at critical
17. years of design advancements that our customers have found valuable Sigma cooling towers represent the current state of the art in this cooling tower category This publication not only relates the language to use in describing an appropriate Sigma cooling tower but also defines why certain items and features are important enough to specify with the intention of insisting upon compliance by all bidders The left hand column of pages 15 through 29 provides appropriate text for the various specification paragraphs whereas the right hand column comments on the meaning of the subject matter and explains its value Pages 15 through 22 indicate those paragraphs which will result in the purchase of a cooling tower which will not only accomplish the specified thermal performance but which will include normal operation and maintenance enhancing accessories and features It will also incorporate those standard materials which testing and experience has proven to provide best results in normal operating conditions Pages 23 through 29 provide some paragraphs intended to add those features components and materials that will customize the tower to meet the user s requirements Space does not permit definition and explanation of all of the possible options that can be applied to the Sigma SPX Cooling Technologies realizes that you the purchaser must be happy with the tower s characteristics and we are prepared t
18. 1200 Cooling Tower Specifications Options 23 Specifications Specification Value Basin Heater Add the following paragraph in the Cold Water Basin section Provide a system of electric immersion heat ers and controls for each cell of the tower to prevent freezing of water in the collection basin during periods of shutdown The system shall consist of one or more stainless steel elec tric immersion heaters installed in a galvanized steel heat shield provided in the floor of the basin A NEMA 4 enclosure shall house a magnetic contactor to energize heaters a trans former to provide 24 volt control circuit power and a solid state circuit board for temperature and low water cutoff A control probe shall be located in the basin to monitor water level and tem perature The system shall be capable of maintaining 40 F water temperature at an ambient air temperature of _ F Wiring of the heaters and controls shall be the responsibility of the purchaser Fan Motor Variable Speed Drive Marley All Weather ACH550 System Add the following paragraph in the Mechanical Equipment section when VFD is used with customers Building Management System A complete UL listed Variable Speed Drive system in a NEMA 1 indoor NEMA 12 indoor or NEMA 3R outdoor enclosure shall be provided The VFD shall use PWM technology with IGBT switching and integrated bypass design VFD out put switching shall not cause mechanical issues with gearbo
19. ad or operating load circulating GPM Total pumping head will be furnished at time from the tower Do not brace the riser s seismic or thrust loads of proposal against the tower 3 If your application requires a bypass system recommended location is through tower endwall into plenum area Review of the system by SPX Cooling Technologies engineering is required Marley Sigma 1200 Cooling Tower Engineering Data Support OVERALL LENGTH OF BASIN 4 7 1 2 C Bays 4 0 L 4 7 12 x EACH ADDITIONAL CELL L 11 5 8 S ANCHOR BOLT COL ANCHOR BOLT J Ya lo AIR INLET FACE PERN lt M a in ol H o Ob ZO lt M ee te H z 2 co oc i E B O Oo w T W LW Ons Q Q E O 28 O E a i so J HJ 3z S z 2 5 ADDITIONAL SUMP a DAA i WHEN REQUIRED a 5 O ejar 3 eg Ng ee ae a gt oo ZO lt M 7 Et SLT eae ERTE AIR INLET FACE PLAN Tower Dimensions Operating Weight Ib Model w A B c L Single Cell Each Cell Add 1211 areo 8 6 PAO 4 16 0 61250 55900 1221 33 10 9 6 8 10 4 16 0 65530 60660 1231 33 10 9 6 8 10 5 20 0 77960 73110 1241 33 10 9 6 8 10 6 24 0 93790 88940 1251 377 10 11 6 10 10 6 24 0 101020 95740 1261 a7 10 11 6 10 10 7 28 0 116260 111000 NOTE 1 Use this bulletin for preliminary layouts only Al
20. e accessibility and maintainabil ity of all operating components The spacious interior provides easy access to fill drift eliminators all basin accessories and is one of two primary accessways to the fan Geareducer and other mechanical components At the fan deck level the hot water distribution basins are easily inspected and cleaned while the tower is operating if you wish The mechanical equipment can also be readily accessed from this level Except for the cold water basin no counterflow tower component requiring routine maintenance is as easily accessed The confined areas that typify counterflow designs can make difficult work for maintenance personnel Marley Sigma 1000 1200 Cooling Tower Specifications Base Specifications Specification Value Thermal Performance The tower shall be capable of cooling GPM of water from ___ F to F at a design entering air wet bulb temperature of F The cool ing tower manufacturer shall guarantee that the tower supplied will meet the specified performance conditions when the tower is installed according to plans The purchaser will arrange for an on site thermal performance test to be conducted in the presence of the manufacturer and owner and under the supervision of a qualified disinter ested third party in accordance with CTI Cooling Technology Institute ATC 105 standards during the first full year of operation If the tower fails to per form withi
21. e obstruction to normal maintenance procedures Your Marley representative can help you meet your sound requirements Marley Sigma 1000 1200 Cooling Tower Specifications Options 29 Specifications Specification Value Watertight Partitions Between Cells Replace the last sentence in this paragraph with the following Partitions shall be 3 4 x 5 ply factory fabricated grooved and splined treated Douglas Fir plywood sheets installed and sealed watertight to permit inde pendent cell operation Fire Safety Options E In addition to the normal partition function of preventing air bypass page 17 this option allows you to use each partitioned cell of your tower independently This is valuable where a single multicell tower is serving several separate systems or where winter operation may require less than full tower capability E Occasionally critical processes or local codes may require you to install a fire protection sprinkler system on a wood tower or pay higher insurance premiums or both Our first recommendation in such a case would be for you to consider using a Sigma Steel cooling tower as listed in the Factory Mutual Approval Guide Another alternative that could be acceptable to your insurance carrier and which you may wish to evaluate would be to make your Sigma tower as fire resistant as possible This can be done by any or all of the following measures e FRP casing having a flame spread rating
22. ed ladder The ladder extension alleviates this problem Marley ladder extensions are available in standard 5 0 and 11 0 lengths and will be field cut to fit E To meet OSHA guidelines towers whose fan decks are 20 0 or more above roof or grade and which are equipped with lad ders are required to have safety cages sur rounding the ladders Marley Sigma 1000 1200 Cooling Tower Specifications Options 27 Specifications Specification Value Oil Level Sight Glass Replace paragraph 5 4 with the fol lowing A galvanized oil gauge and drain line shall extend from the gear reducer to the vicinity of the motor and shall be equipped with a bronze bodied oil level sight glass Miscellaneous Options Wood Cold Water Basin Replace paragraph 10 1 with the fol lowing Include a cold water collection basin constructed of pressure treated Douglas Fir plywood Basin floor shall be 3 4 thick 5 ply supported by 6 deep joists on 2 0 centers Basin sides shall be 1 thick 7 ply The basin floor shall lock into a dado groove in the sides to form a watertight seal A depressed side outlet sump of either FRP or hot dip galvanized steel having a 1 4 thick faceplate drilled for a stan dard class 125 ASME flange connec tion will be included An appropriately sized 4 diameter or larger galvanized standpipe overflow shall be provided The standpipe shall be removable for flush out cleaning of the bas
23. f the tower to inspect the distribution basins as well as the struc tural integrity of the fan deck fan cylinder and fan especially the fan blade securing hardware And there are no induced draft cool ing tower designs that are immune to this need Marley Sigma 1000 1200 Cooling Tower Specifications Base 5 Specification Value io Each endwall of the tower shall be equipped with a 20 wide aluminum vertical ladder through bolted to the endwall structure Ladder shall rise from the cold water basin level to the top of the fan deck guardrail and shall be designed and installed in confor mance with OSHA standards Cold Water Collection Basin The cold water collection basin shall be of poured in place concrete provided under scope of work done by others The concrete basin design shall be based upon certified loads and dimen sions provided by the cooling tower manufacturer Scope of Work The cooling tower manufacturer shall be responsible for the design fabrica tion and delivery of materials to the project site and for the erection of the tower over supports provided by others Unless otherwise specified all external piping pumps controls and electrical wiring will be outside the cooling tower manufacturer s scope of work For the comfort and safety of your operat ing personnel the Sigma tower includes a ladder and guardrail of the quality and design indicated
24. fy the RPM to be 1800 900 1500 750 in 50 Hertz regions The driveshaft turns at the motor speed and is therefore most sensitive to operational imbalance Stainless steel manufacture assures that the driveshaft will not become unbalanced as a result of corrosion The extended oil line to an external dip stick provides a conve nient means of checking the level of oil in the Geareducer As indicated on page 27 a sight glass is also available in lieu of the dip stick Fans of the size used on large cooling towers are applied at speeds and horsepowers that generate considerable torque and structural tubular steel resists this torque very effectively The Marley torque tube assures that all of the mechan ical equipment remains aligned and that the rotating fan is prop erly positioned within the fan cylinder Hot dip galvanizing after fabrication assures that all steel surfaces will be heavily coated with zinc for long term protection against corrosion Even in aggressive water conditions the heavy construction of the unitized support normally precludes the need for stainless steel The value of a 5 year mechanical equipment warranty speaks for itself Except for the motor all of the mechanical equipment on a Marley tower is made by SPX Cooling Technologies Cooling tower vendors who purchase commercial fans gear boxes driveshafts etc may require that you deal directly with those commercial suppliers for warranty sat
25. hnical Report H 004 External Influences on Cooling Tower Perfor mance for design recommendations It may also be advisable to increase your design wet bulb temperature by 1 F to compensate for potential recirculation initiated by the enclosure You ll benefit from discussing your project with your Marley sales representative Sound Control A Sigma tower operating in an unobstructed environment will meet all but the most restrictive noise limitations and will react favorably to natural attenuation Where the tower will operate within an enclosure the enclosure itself will usually have a damping effect on sound Distance will also reduce sound by about 5 dBA each time the distance is doubled Where noise at a critical point is likely to exceed an acceptable limit you have several options listed below in ascending order of cost impact Noise concerns are often limited to nighttime when ambi ent noise levels are lower and neighbors are trying to sleep You can usually resolve these situations by using two speed motors in either 1800 900 or 1800 1200 RPM configuration and operating the fans at reduced speed without cycling after hours This relatively inexpensive solution pays for itself quickly in reduced energy costs Where the problem can exist at all times Such as near a hospital the best solution is to oversize the tower so it can operate continuously at reduced 1200 or 900 RPM motor speed Typical sound red
26. housing shall be requirement for manual reset assures that installed on the mechanical equipment the tower will be visited to determine the support for wiring into the owner s cause of excess vibration control panel The purpose of this switch will be to interrupt power to the motor in the event of excessive vibra tion It shall be adjustable for sensitiv ity and shall require manual reset Marley Sigma 1000 1200 Cooling Tower Specifications Options 26 Specification Value Convenience and Safety Options Stairway Replace paragraph 9 3 with the fol lowing A 30 wide column supported 45 stairway with 8 rise and run of treated Douglas Fir shall be provided at the tower endwall rising from grade roof to the fan deck elevation Stair columns shall be 4x4 Guardrails shall be 2 x4 The upper guardrail shall have an eased edge for the protection of operating personnel Stairway founda tion shall be by others designed in accordance with drawings provided by the cooling tower manufacturer The stairway shall conform to OSHA stan dards Plenum Walkway Add the following to the end of this paragraph Provide a 30 wide walkway extending from one endwall access door to the other through the length of the tower Walkway shall be constructed of treated Douglas Fir and the top of the walkway shall be above the cold water basin overflow level If the cold water basin is deeper than 4 0 the walkway shall be
27. how anchor bolt locations Obtain current drawings from your Marley sales representative before designing supports 2 Other contractors or purchaser must design and erect 5 supporting steel 3 If steel beams are used they must include dia holes to accept anchor bolts provided If concrete beams or pilasters are used dia anchor bolts embedded in the concrete must be provided by others construction purposes Air inlet faces must have unobstructed air supply Consult your Marley sales representative if nearby obstructions may interfere Operating weight is wet weight of tower and wood basin including 6 of water in the collection basin This is the recommended operating water level for all models NOTE 1 Marley Sigma 1000 Cooling Tower Engineering Data Concrete Basin A BAYS 4 0 B PER CELL 6 MIN 6 6 6 MIN 6 MIN 4 COL COL AIR INLET FACE A A N pmi pem j i W z Q a Q 2 Ww Ww PLAN amp Z d S z a i rT _ 6 MIN ies m 1 6 1 O RECOMMENDED OPERATING WATER LEVEL gt 17 6 m 1 0 RECOMMENDED w OPERATING WATER LEVEL FLAT BASIN SECTION DEEP BASIN SECTION Tower Dimensions Operating Weigt b Model Ww A B Single Cell Each Cell Add 1011 21 10 2 8 0 15120 13500 1021 21 10 3 12 0 20160 18400 1031 24 2 3 12 0 21240 19500
28. in A float operated mechanical makeup valve shall also be included installed adja cent to the endwall access door Redwood Components Hot Water Basin Covers Add the following paragraph in the Hot Water Distribution System section The distribution basins shall include treated Douglas Fir plywood covers at least 3 4 thick These covers shall be designed to withstand 60 psf live load and shall be easily removable for maintenance Air Inlet Screens Add the following paragraph to the Fill Louvers and Drift Eliminators Section The air inlet faces of the tower shall be covered by 1 mesh hot dip galvanized welded wire screens Screens shall be mounted in galvanized steel U edging and shall be removable Hi The oil level sight glass is a convenience item that is preferred by many users The same purpose is of course served by either the dip stick or the sight glass E Marley basins are used to permit the installation of towers on elevated platforms or foundations The cross section drawing on page 4 shows the relationship of the optional basin sump and overflow to a typical steel beam support platform E Most of the wood components in the tower are available of pres sure treated redwood However redwood lacks the strength of Douglas Fir which may require structural modifications of the tower Please discuss the available redwood options with your Marley sales representative E These covers are desig
29. ion levels which may exceed CTI guide lines Marley Premium VFD System Add the following paragraph in the Mechanical Equipment section when VFD is used as a stand alone system A complete UL listed Variable Speed Drive system in a NEMA 12 indoor or NEMA 3R outdoor enclosure shall be provided The VFD shall use PWM technology with IGBT switching and integrated bypass design VFD output switching shall not cause mechanical issues with gearbox teeth or drive shafts The VFD shall catch a fan spinning in the reverse direction without tripping The panel shall include a main disconnect with short circuit protection and external operating handle lockable in the off posi tion for safety The system shall include a solid state PI temperature controller to adjust frequency output of the drive in response to the tower fluid tempera ture The temperature of the fluid and Marley Sigma 1000 1200 Cooling Tower Specifications Options i Specification Value set point shall be displayed on the door of the control panel The bypass shall include a complete magnetic bypass circuit with capability to isolate the VFD when in the bypass mode Transfer to he bypass mode shall be automatic in he event of VFD failure or for specific rip conditions allowing safe transfer of utility voltage to the motor Automatic bypass with an earth ground condition is not allowed The bypass contactor shall be cycled on and off while operat ing in
30. isfaction Marley Sigma 1000 1200 Cooling Tower Specifications Base Specification Value Fill Louvers and Drift Eliminators Fill shall be film type 15 mil thick E Louvers integral with the fill thermoformed PVC with louvers keep the flowing water within formed as part of each fill sheet Fill the confines of the fill The sep shall be suspended from stainless arate external louvers used by steel structural tubing supported from others permit water to escape a the upper tower structure and shall the fill and form ice or produce be elevated above the floor of the cold an unsightly situation adjacent water basin to facilitate cleaning Air to the tower If you plan to use inlet faces of the tower shall be free of your tower in the wintertime water splash out particularly for free cooling w integral louvers will put your Drift eliminators shall be PVC triple operating concerns to rest pass and shall limit drift losses to no more than 0 010 of the design GPM Vertical blade type eliminators as flow rate well as misdirected cellular types cause much of the fan power to be wasted in turn ing the horizontal flow of air vertical for its exit through the fan cylinder This power is of course not available for contribution to thermal performance Drift rate varies with design water loading and air rate as well as drift eliminator depth and number of directional changes The indicated rate of 0 010 or
31. iveshaft equipped with neo prene flexible coupling elements A galvanized oil gauge and drain line shall extend from the gear reducer to the vicinity of the motor and shall be equipped with a dip stick for oil level measurement The complete mechanical equipment assembly for each cell shall be sup ported by a rigid unitized support that resists misalignment between the motor and the gear reducer Support shall be heavy wall tubular steel to which heavy plate platforms for the motor and gear reducer have been welded and the assembly shall be hot dip galvanized after fabrication The support assembly shall also provide an inlet connection for incoming hot water and shall serve as a crossover pipe to deliver water to both sides of the tower The mechanical equipment assembly shall be warranted for no less than five 5 years This warranty shall cover the fan s speed reducers driveshafts and couplings and the unitized supports E Standard fan drives of other manufacturers may use V belts Considering the size of fans involved and the horsepowers applied this is not good design practice Geareducer drive is far more reliable and trouble free and is currently offered as an option by at least two other cooling tower manufacturers Unless otherwise specified motor speed will be 1800 RPM in 60 Hertz areas and 1500 RPM in 50 Hertz areas If you prefer the operating flexibility of two speed operation please speci
32. l dimensions show anchor bolt locations Obtain current drawings from your Marley sales representative before designing supports 2 Note carefully anchor bolt location relative to beam orientation See plan above 3 Other contractors or purchaser must design and erect supporting steel 4 If steel beams are used they must include dia holes to accept anchor bolts provided If concrete beams or pilasters are used dia anchor bolts embedded in the concrete must be provided by others 5 Maintain no less than 2 0 of clear space at Endwall Faces for construction purposes Air Inlet Faces must have unobstructed air supply Consult your Marley sales representative if nearby obstructions may interfere Operating weight is wet weight of tower and wood basin including 6 of water in the collection basin This is the recommended operating water level for all models Marley Sigma 1200 Cooling Tower Engineering Data Concrete Basin PLAN A BAYS 4 0 B PER CELL AIR INLET FACE J x N a z Ww z Q Q a W z ie z a O o z a ENDWALL FACE 1 O RECOMMENDED PERATING WATER LEVEL Loo a heel 1 0 RECOMMENDED OPERATING WATER LEVEL FLAT BASIN SECTION DEEP BASIN SECTION Tower Dimensions Operating Weight Ib Model w A B Single Cell Each Cell Add 1211 31 6 4 16 0 39040 35910 1221 33 6 4 16 0 41960 39420
33. less is easily achievable without pre mium cost If a lower rate is required please discuss with your Marley sales representative Drift Eliminator Louver Section Section Fill Section Marley Sigma 1000 1200 Cooling Tower Specifications Base 20 Specifications Specification Value Hot Water Distribution System The mechanical equipment support crossover pipe shall deliver water to two open hot water basins per cell at the fan deck elevation Water shall exit these basins to the fill by gravity through metering orifice type polypro pylene nozzles situated in the basin floor Nozzles shall be easily removable and replaceable Heavy duty industrial grade flow control valves shall be provided at the inlet to each basin These valves shall permit both flow balancing and maintenance shut off to selected cells or portions of cells Valves shall have machined cast iron bodies with stain less steel operating stems and heavy duty locking handles Casing Tower endwalls shall be cased with ribbed FRP panels lapped and sealed to prevent leakage Tower corners shall be finished with FRP corner rolls Access Single cell towers shall include a 33 wide by 61 high molded FRP access door in one endwall casing for access to the interior of the tower Casing access door shall be hinged and equipped with a latch operable from both inside and outside the tower Multicell towers shall have an access door in both
34. n the limits of test tolerance then the cooling tower manufacturer will install additional cells and or make such corrections as are agreeable to the owner and shall pay for the cost of a retest If the tower still fails to per form as specified then the manufac turer shall make such reimbursements as are appropriate and agreeable to the owner to compensate for the perfor mance deficiency E Your reason for purchasing a cooling tower is to obtain a con tinuing flow of cooled water as defined in the first paragraph at left If the tower that you purchase is incapable of performing as specified then you will not have received full value for your money Bear in mind that the size and cost of a cooling tower var ies directly with its true thermal capability This paragraph is intended to protect you against either intentional or inadvertent under sizing of the tower by the manufacturer Judging the level of performance of a cooling tower on critical processes is never easy and the potential risk of a non performing cooling tower usually causes the requirement for a mandatory acceptance test to be very desirable Your contract with the successful bidder should establish the acceptable remedies for missed performance which might include eThe addition of one or more cells of tower as necessary to bring the cooling tower to the specified level of performance This is usually limited to the scope of work as defined in the specs
35. ned to keep leaves and debris out of the circulating water system They also serve to suppress algae for mation by shielding the incoming hot water from direct sunlight E In wooded or windy areas these screens help to keep leaves or blowing debris out of the cooling tower and circulating water system Marley Sigma 1000 1200 Cooling Tower Specifications Options 28 Specifications Specification Value Low Noise Tower Add the following at the end of this paragraph The cooling tower shall be quiet operating and shall produce an overall level of sound no higher than____ dBA at the critical location indicated on the Plans E Sound produced by a Sigma Steel tower operating in an unob structed environment will meet all but the most restrictive noise limitations and will react favorably to natural attenuation Where the tower has been sized to operate within an enclosure the enclosure itself will have a damping effect on sound Sound also declines with distance by about 5 or 6 dBA each time the distance doubles Where noise at a critical point is likely to exceed an acceptable limit you have several options listed below in ascending order of cost impact eWhere only a slight reduction in noise will satisfy and the source of concern is in a particular direction merely turning the tower may be the answer Less sound emanates from the cased face of the tower than does from the air intake face e In many cases
36. o provide or provide for any reasonable enhancement that you are willing to define and purchase Your needs will become part of the continuing improvement of this Marley product line Marley Sigma 1000 Cooling Tower Engineering Data Schematic oc wi 5 ke LL C DIA FAN O ke 2 O PLAN 9 Ie O s C gt see ii LDH o o o I i o o o l o IEE IT COL goo COL p 5 A BAYS 4 0 L 5 TOP OF FAN CYLINDER 7 B TOP OF FAN DECK gp on ENDWALL H ELEVATION BASE OF TOWER COLUMNS l Tower GPM Width Length Height A B c Maximum Static Model per cell Ww L H Motor hp Lift 1011 380 2140 21 5 8 0 11 8 2 3 8 84 30 iz 1021 580 3220 21 5 12 0 11 8 2 3 5 96 30 11 7 1031 580 3220 23 9 12 0 11 8 3 3 8 A201 50 Aa 1041 790 4300 26 0 16 0 11 8 4 4 0 144 60 11 7 NOTE 1 Last number of model indicates number of cells Change as appropriate for your selection Primary engineering data is per cell 2 Fan hp is usually less than shown here 3 Height shown is from base of tower columns to fan deck Wood basin if used elevates tower 614 If concrete basin is used subtract 1 6 for height above top of basin curb Marley Sigma 1000 Cooling Tower Engineering Data Piping
37. oved energy management provides fast payback Indeed many utilities offer generous rebates for users having installed VFD drives Marley Sigma 1000 1200 Cooling Tower Specifications Options Specification Value o modulate fan speed maintaining set point temperature The drive s panel dis play shall be able to display the set point emperature and cold fluid temperature on two separate lines The bypass shall include a complete magnetic bypass circuit and with capability to isolate the VFD when in the bypass mode Transfer o the bypass mode shall be manual in he event of VFD failure Once the motor is transferred to the by pass circuit the an motor will run at constant full speed The bypass circuit will not modulate ON and OFF based on fluid temperature The application must be able to handle very cold fluid temperatures while the VFD is in a by pass mode Operator controls shall be mounted on the front of the enclosure and shall consist of start and stop control bypass VFD selection Auto Manual selections manual speed control To prevent heating problems in the fluid cooloer fan motor and to assure proper gear reducer lubrication the VFD system shall de energize the motor once 25 motor speed is reached and cooling is no longer required The fluid cooler manu facturer shall supply VFD start up assis tance Tower vibration testing throughout the speed range is required to identify and lockout any natural frequency vibra t
38. rmance The inert noncorroding nature of FRP assures that these characteristics will persist 4 2 Fan cylinders shall be molded FRP They shall be anchored to the fan deck Even in aggressive water conditions the heavy construction of structure to provide a consistently the fan guard normally precludes the need for stainless steel stable operating shroud for the fan Fan cylinders less than 72 in height shall be equipped with a heavy gauge removable hot dip galvanized steel fan guard for the protection of operating personnel Diagonal and Column Anchorage Diagonal Connector Marley Sigma 1000 1200 Cooling Tower Specifications Base Specifications Specification Value Mechanical Equipment Fan s shall be propellertype incorpo rating heavy duty blades of cast alumi num or high strength inert composite material Blades shall be individually adjustable and replaceable Fan s shall be driven through a rightangle indus trial duty oil lubricated geared speed reducer Speed reducers employing pulleys and belts will not be accepted Motor s shall be ____ hp maximum TEFC 1 15 service factor and specially insulated for cooling tower duty Speed and electrical characteristics shall be 1800 1800 900 RPM single winding phase hertz volts Motor shall be located outside the fan cylinder at the fan deck and shall be connected to the speed reducer by a tubular stainless steel dynamically balanced dr
39. sibility of contaminated discharge air being drawn into building fresh air intake ducts The purchaser should obtain the services of a Licensed professional Engineer or Registered Architect to certify that the location of the cooling tower is in compliance with applicable air pollution fire and clean air codes Marley Sigma 1000 1200 Cooling Tower Specifications Base Specifications Specification Value Base Furnish and install an induced draft crossflow type field erected wood framed PVC fill industrial duty cooling tower of cell s as shown on Plans The limiting overall dimensions of the tower shall be wide ___ __ long and high to the top of the fan cylinder Total operating horse power of all fans shall not exceed hp consisting of ___ motor s Tower shall be similar and equal in all respects to Marley Model hp E Your specification base establishes the type configuration base material and physical limitations of the cooling tower to be quoted During the planning and layout stages of your project you will have focused your attention on a cooling tower selection that fits your space allotment and whose power usage is accept able Limitations on physical size and total operating horsepower avoid the introduction of unforeseen operational and site related influences Specifying the number of cells and the maximum fan hp cell will work to your advantage Crossflow towers are noted for th
40. tatic or solid state tempera ture controller Door mounted selector switches shall be provided to enable automatic or manual control and wired for 120VAC control Control circuit to be wired out to terminal blocks for field connection to a remote vibration switch and for access to extra 120VAC 50VA control power overload trip alarms and remote temperature control devices The temperature controller shall be adjustable for the required cold water temperature If a thermostatic controller is used it shall be mounted on the side of the tower with the tem perature sensing bulb installed in the cold water basin using a suspension mounting bracket If a solid state tem perature controller is used the control ler will be door mounted on the control panel The temperature controller will display two temperatures one for outgoing water and the other for set point Water temperature input shall be obtained using a three wire RTD with dry well in the outlet water piping and wired back to the solid state tempera ture controller in the control panel E If it is your opinion that the control system for the cooling tower should be part of the tower manufacturer s responsibility we are in wholehearted agreement with you Who better to determine the most efficient mode and manner of a tower s operation and to apply a system most compatible with it than the designer and manufacturer of the cooling tower N Marley Sigma 1000
41. tempera ture you should consider controlling cold water temperatures to higher levels You ll also save energy by using such control See Marley Technical Report H 001A Cooling Tower Energy and its Management Always control leaving water temperature by manipulating the quantity of air that the fan moves through the tower Vary ing the quantity of water flow is not normally recommended and can be harmful in freezing weather You can alternately start and stop single speed motors to maintain water tempera tures within an acceptable range However exceeding a total acceleration time of 30 seconds per hour can overheat the mo tor causing the insulation to fail Limiting the number of motor starts on the other hand can produce significant variations in the temperature of the water delivered to the process Increased flexibility can simplify your operating procedures and save you money in the long run both on operation and on maintenance Here are two of the more popular options Marley Sigma 1000 1200 Cooling Tower Engineering Data Energy Management Two Speed Motors Two speed motors improve operating flexibility by increas ing the number of potential operating modes Users in north ern climates will find that the tower can carry winter loads at half speed reducing fan power requirements by 85 during that time Two speed motors also help to control icing during wintertime operation See Marley Technical Report H 003
42. tower endwall into plenum area Review of the system by SPX Cooling Technologies engineering is required which conforms to class 125 lb ASME B 16 1 specifications 5 Supports on tower for crossover piping are part of the tower design Do not support the riser s dead load or operating load from the tower Do not brace the riser s seismic or thrust loads against the tower Marley Sigma 1000 Cooling Tower Engineering Data Support ig OVERALL LENGTH OF BASIN 7 7 12 7 C Bays 4 0 L 4 7 12 ee EACH ADDITIONAL CELL L rl 7 8 ANCHOR 7 8 ANCHOR 7 8 ANCHOR BOLT HOLES AIR INLET FACE BOLT HOLES f BOLT HOLES PEDESE TEEPEE TE UREA RS PEE H 5g T m AS TH OVERFLOW 2d na 7 Ot H zZ N ka b Tia 7 I Z 2 Q E 2 E Ma 3 peg JE z D ADDITIONAL SUMP oa B m WHEN REQUIRED 6 gt O E tt i H ou I As ah O xa FR Eee Sat H 4 2 s 7 m E m A M 7 M 2 a 4 a AIR INLET FACE 11 1 2 PLAN Tower Dimensions Operating Weight b Model Ww A B c L Single Cell Each Cell Add 1011 22 1 4 10 5 3 2 8 0 23620 20500 1021 22 1 4 10 5 3 3 12 0 32140 28980 1031 24 5 4 10 6 5 3 12 0 34440 31020 1041 26 8 4 10 7 6Y2 4 16 0 47620 44000 NOTE 1 Use this bulletin for preliminary layouts only All 4 Maintain no less than 2 0 of clear space at endwall faces for dimensions s
43. uctions are 7 dB at 2 3 fan speed or 10 dB at 1 2 fan speed Extreme cases may require inlet and discharge sound at tenuator sections however the static pressure loss imposed by attenuators may necessitate an increase in tower size This is the least desirable approach because of its significant cost impact and because it obstructs normal maintenance procedures Your Marley sales representative can help you meet your sound requirements 13 System Cleanliness Cooling towers are very effective air washers Atmospheric dust able to pass through the relatively small louver openings will enter the circulating water system Increased concentra tions can intensify system maintenance by clogging screens and strainers and smaller particulates can coat system heat transfer surfaces In areas of low flow velocity such as the cold water basin sedimentary deposits can provide a breed ing ground for bacteria In areas prone to dust and sedimentation you should con sider installing some means for keeping the cold water basin clean Typical devices include side stream filters and a variety of filtration media You should also plan ahead to develop a consistent ef fective program of water treatment A good water treatment program will help to assure long service life while keeping your tower free of potentially harmful biological growths A CAUTION The cooling tower must be located at such distance and direction to avoid the pos
44. x teeth or drive shafts The VFD shall catch a fan spinning in the reverse direction without tripping The panel shall include a main discon nect with short circuit protection and external operating handle lockable in the off position for safety The VFD system shall receive a speed reference signal from the Building Management System monitoring the tower fluid temperature As an option to receiving the speed reference signal from a building manage ment system the drive must have the capability to receive a 4 20 ma tempera ture signal from an RTD transmitter The VFD shall have an internal PI regulator 1 gt EThe basin heater components described at left represent our rec ommendation for a reliable automatic system for the prevention of basin freezing They are shipped separately for installation at the jobsite If aggressive operating conditions are anticipated change galva nized in paragraph 10 2 to Series 300 SS The ambient air temperature that you fill in should be the lowest 1 level of winter temperature prevalent at site Ask for Marley drawing 92 3627 E Marley VFD drive systems are designed to combine absolute temperature control with ideal energy management The cool ing tower user selects a cold water temperature and the drive system will vary the fan speed to maintain that temperature Precise temperature control is accomplished with far less stress to the mechanical equipment components The impr