1. IF NEEDED EGS I amp S 01 NOTICE Typical steam boiler without connections available below the water line is not recommended due to insufficient water temperature especially during warmer months when the space heating system is not operational Boiler water temperature at the bottom of a steam boiler can be 50 F lower than the boiler s water temperature limit setting during such periods FILL BOILER SYSTEM 1 On new boiler installations do not purge the boiler or space heating system through the water heater During any boiler or space heating system flushing cleaning or purging the water heater should be isolated to avoid possible attack on the carbon steel coil by chemical additives 2 Purge air from boiler water heater piping 3 Check system for leaks Repair as necessary AN DANGER Positively assure all electrical connections are unpowered before attempting installation or service of electrical components or connections of the water heater or building Lock out all electrical boxes with padlock once power is turned off WARNING When installed the water heater must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 and or the CSA C22 1 Electric Code Failure to properly wire electrical connections to the water heater may result in serious physical harm Electrical power may be from more than
2. pan depth must be suitable for draining and collecting water and have a minimum length and width of at least four 4 inches measured from the jacket of the water heater The drain pan as described above can be purchased from your plumbing professional The drain pan must be piped to an adequate drain The piping must be at least 34 in diameter and pitched for proper drainage Clearance from Combustible Materials Rear Table 2 Combustible Material Clearances Recommended Service Clearances Non Piping Front Rear T amp P Relief Side Aquastat Valve Side CAUTION Do not drop water heater Do not bump water heater jacket against floor Appliance Location 1 Boiler Location Locate the Single wall Indirect as close to the boiler as practical 2 Fixture Locations For fastest delivery of hot water place the Single wall Indirect close to points of use EGS I amp S 01 Additional Recommended Components 1 Shut off Valves Allows isolation of water heater from domestic water system and or boiler system during service 2 Unions Allows water heater movement during service if adequate clearance cannot be provided 3 Thermal Expansion Tank If the water heater is installed in a closed water supply system such as one having a back flow preventer in the cold water line provide thermal expansion control Contact the water supplier or local plumbing inspector for additional information A WAR
3. the event of excessive potable water temperatures Install the combination temperature and pressure relief valve into the opening provided and marked for this purpose on the water heater Some models may already be equipped or supplied with a temperature and pressure relief valve Verify that the combination temperature and pressure relief valve complies with local codes If the temperature and pressure relief valve does not comply with local codes replace it with one that does EGS I amp S 01 NOTICE If the boiler takes longer to heat up from a cold start than the water availability as noted above hot water shortage may occur Hot water availability is based off drawing 80 of the heated tank volume at 4 gallons per minute flow rate The maximum heat transfer through the coil heat input of the water heater at 240 F boiler water supply temperature and 210 F potable water temperature is 94 100 Btu hr for residential models and 180 300 Btu hr for commercial models Potable water temperature is limited to below 210 F and nominal water containing capacity is below 120 gallons for all single wall indirect models Accordingly per Part HLW 101 2 Section IV of the ASME Boiler and Pressure Vessel Code all Lochinvar Single wall Indirect products are exempted from compliance with the code GENERAL INFORMATION FEATURES This water heater contains the following features HEAT EXCHANGER The heat exchanger coi
4. unions are recommended for future service convenience The use of an air separator and vent is recommended to eliminate air in the system Pipe and fittings between the boiler and Single wall Indirect must be 94 diameter or larger VACUUM BREAKER COLD WATER HOT WATER OUTLET SUPPLY TEMPERATURE AND PRESSURE 7 RELIEF VALVE FROM BOILER SUPPLY Z k AR VENT CIRCULATOR AR SEPARATOR PEE a VALVE Cl DK COLD WATER SUPPLY EXPANSION TANK EXPANSION TANK IF NEEDED Z TO SPACE HEATING ZONE S SUPPLY KE BOILER SPACE HEATING ZONE VALVE e r R A ai gt S BOILER RETURN DRAIN VALVE r SINGLE WALL INDIRECT RETURN la FROM SPACE HEATING ZONE S Figure 1 Water Boiler Piping with Zone Valves 2 For a space heating system that utilizes CIRCULATORS refer to Figure 2 The Single wall Indirect connection labeled FROM BOILER SUPPLY should be piped to the boiler supply piping Mount the circulator making sure the flow arrow points toward the water heater The use of shut off valves and unions are recommended for future service convenience The use of an air separator and vent is recommended to eliminate air in the system Pipe and fittings between the boiler and Single wall Indirect must be 34 diameter or larger VACUUM BREAKER COLD WATER HOT WATER OUTLET SUPPLY TEMPERATURE AND PRESSU
5. water heater if any external part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system that was under water This water heater is suitable for installation on combustible flooring DO NOT install this water heater on carpeting DO NOT operate this water heater without first being certain it is filled with water Flammable items pressurized containers or any other potential fire hazardous articles must never be placed on or adjacent to the heater Containers of flammable gases should not be stored or used in the same room with this water heater Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time generally two weeks or more Hydrogen gas is extremely flammable To prevent the possibility of injury under these conditions we recommend that the water faucet be opened for several minutes at the kitchen sink before you use any electrical appliance that is connected to the hot water system If hydrogen is present there will be unusual sounds such as air escaping through the pipes as hot water begins to flow Do not smoke or have open flame near the faucet at the time it is open NOTICE 116 C Insulation blankets are not required for this water heater This water heater meets or exceeds the ASHRAE IES 90 1b standards with respect to insulation and standby loss requirem
6. EGS I amp S 01 INSTALLATION amp SERVICE MANUAL SINGLE WALL INDIRECT WATER HEATER AN WARNING To avoid damage or injury there must be no materials stored against the indirect water heater and proper care shall be taken to avoid unnecessary contact especially by children with the indirect water heater Do not store or use gasoline or other flammable liquids in the vicinity of this water heater or any other appliance For your family s comfort safety and convenience we recommend this water heater be installed and serviced by a plumbing professional TABLE OF CONTENTS IMPORTANT INFORMATION vsssscsssssssssssssssessnsseeess 1 GENERAL INFORMATION ovcsssssssssssssessssssseessssssnssnes 3 PRE INSTALLA TION ssisssscsssesessnuncoossssssuccseasesessiececsse 4 WATER CONNECTIONS ovscsssssssssssosssssssssssosssssssssssooss 6 ELECTRICAL CONNECTIONS ovssesssssssssssssessssnssssees 8 OPERATING INSTRUCTIONS eessssssssssssssssssssssssseeens 8 MAINTENANCE sisssassssscsassesiacssonesnisdotsnscnisscnsotivisonse 10 TROUBLESHOOTING GUIDE ssessssssssssssessssssssssees 12 IMPORTANT INFORMATION The equipment must be installed in accordance with those installation regulations required in the area where the installation is to be made These regulations must be carefully followed in all cases Authorities having jurisdiction shall be consulted before installations are made All wiring on water heaters installed in the USA must be i
7. NING Do not plug the inlet and outlet tappings of tankless heater left installed in the boiler MOVE THE WATER HEATER TO A PERMANENT POSITION BY SLIDING OR WALKING WATER CONNECTIONS 2M WARNING FAILURE TO INSTALL AND MAINTAIN A NEW LISTED TEMPERATURE AND PRESSURE RELIEF VALVE WILL RELEASE THE MANUFACTURER FROM ANY CLAIM WHICH MIGHT RESULT FROM EXCESSIVE TEMPERATURE AND PRESSURES Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time HYDROGEN GAS IS EXTREMELY FLAMMABLE To prevent the possibility of injury under these conditions we recommend the hot water faucet be opened for several minutes at the kitchen sink before you use any electrical appliance that is connected to the hot water system If hydrogen is present there will be an unusual sound such as air escaping through the pipes as hot water begins to flow Do not smoke or have open flame near the faucet at the time it is open Keep clear of the temperature and pressure relief valve discharge line outlet The discharge may be hot enough to cause scald injury The water is under pressure and may splash A CAUTION If sweat fittings are to be used DO NOT apply heat to the nipples on top of the water heater Sweat the tubing to the adapter before fitting the adapter to the water connections It is imperative that heat is not applied to the nipples containing a plastic liner WARNING Te
8. NTIL THE LEAKAGE IS CORRECTED Liquefied petroleum gas propane gas is heavier than air and will remain at floor level if there is a leak Basements crawl spaces closets and areas below ground level will serve as pockets for accumulation of leaking gas This water heater is supplied with an adjustable thermostat to control water temperature Hot water temperatures required for automatic dishwasher and laundry use can cause scald burns resulting in serious personal injury and or death The temperature at which injury occurs varies with the person s age and the time of exposure The slower response time of disabled persons increases the hazards to them NEVER allow small children to use a hot water tap or to draw their own bath water NEVER leave a child or disabled person unattended in a bathtub or shower EGS I amp S 01 WARNING Installation is not complete unless a pressure and temperature relief valve is installed into the side of the water heater See the Water Connections section of this manual for details This water heater contains very hot water under high pressure Do not unscrew any pipe fittings or attempt to disconnect any components of this water heater without positively assuring the water is cool and has no pressure Always wear protective clothing and equipment when installing starting up or servicing this water heater to prevent scald injuries Do not rely on the pressure and temperature gauges to determine th
9. RE f RELIEF VALVE FROM BOILER SUPPLY kml AR VENT CIRCULATOR AIR SEPARATOR REDUCING VALVE HIKES Bd coLD WATER SUPPLY SPACE HEATING EXPANSION TANK CIRCULATOR RETURN pt 5 D 9 BOILER RETURN DRAIN VALVE m SINGLE WALL INDIRECT Figure 2 Water Boiler Piping with Circulators EXPANSION TANK IF NEEDED Homs TO SPACE e HEATING ZONE S SUPPLY BOILER FROM SPACE HEATING ZONE S CONNECT STEAM BOILER SUPPLY PIPING Figure 3 represents a typical steam boiler connection diagram Refer to the boiler installation manual or contact the boiler manufacturer for an appropriate piping diagram The use of a union shut off valves and a drain valve is recommended for future service convenience The use of an in line Y style strainer is required to prevent accumulation of sludge in the water heater s coil VACUUM BREAKER COLD WATER SUPPLY MINIMUM LOW Va WATER LINE 1 MINIMUM PIPING TO CIRCULATOR HOT WATER OUTLET TEMPERATURE AND PRESSURE T Y ATRAINER RELIEF VALVE BOILER SUPPLY It kt HJ HH i WATER x DN TEMPERATURE LIMIT CIRCULATOR MOUNTED CLOSE TO FLOOR IH I E BOILER RETURN 6 bot gt SINGLE WALL DK INDIRECT BOILER DRAIN VALVE Figure 3 Typical Steam Boiler Connections connections available below the water line EXPANSION TANK
10. acity above 220 000 Btu hr will not increase the rating of the water heater Ratings are based on 180 F boiler water 2 Circulator Sizing Refer to Table below for the corresponding pressure drop through the coil for the given model Calculate the pressure drop of all straight pipe and fittings on the supply and return of the water heater at the selected flow rate Add the piping fitting pressure drop to the pressure drop through the water heater coil Select a circulator that will provide an appropriate flow rate at the combined pressure drop Table 1 Water Heater Performance Model Hot Water Coil Heat Pressure Drop Availability Transfer at 12 GPM Minutes Area Sq Ft Feet of Head EGS030 PEGsos0 9 0 m2 1m3 SYSTEM ZONE CONTROL The Single wall Indirect water heater must be installed as a zone separate from the space heating system The domestic hot water zone s piping and circulator must be sized for a minimum flow rate with all zones in use and a maximum flow rate with only the water heater in use For this reason the preferred method of zone control is with circulators 1 Circulators With space heating zones using circulators the Single wall Indirect should be added as an additional zone with a circulator 2 Zone Valves Select a valve with a low pressure drop to assure adequate flow through the water heater 3 Hybrid The space heating zone can be zoned using zone valves
11. al expansion of water in a closed water supply system or it may be due to a faulty relief valve Thermal expansion is the normal response of water when it is heated Ina closed system thermal expansion will cause the system pressure to build until the relief valve actuation pressure is equaled Then the relief valve will open allowing some water to escape slightly lowering the pressure Contact your water supplier or local plumbing inspector on how to control this situation ABOVE ALL DO NOT PLUG THE TEMPERATURE AND PRESSURE RELIEF VALVE THIS IS NOT A SOLUTION AND CAN CREATE A HAZARDOUS SITUATION 3 Anode Inspection and Replacement This water heater is equipped with multiple sacrificial anodes Anodes protect the glass lined tank from corrosion by sacrificing themselves through electrolysis When the anode material is consumed there is no more protection and corrosion of the tank accelerates Inspection of the anode every year allows you to identify a spent anode and replace Replace the anode when its diameter is 3 8 of an inch or every other year which ever is first Aggressive very hot and softened water causes rapid consumption of the anode requiring frequent inspections Anodes are available from your distributor or from the manufacturer listed on the rating plate To inspect or replace an anode The anodes on this water heater are easily accessible from the top of the heater making replacement simple and quick Turn t
12. and the Single wall Indirect zoned with a circulator DOMESTIC HOT WATER PRIORITY Two options are available Priority and Non Priority 1 Priority Demand for space heating is interrupted or postponed until the domestic hot water demand is satisfied This option provides maximum delivery of domestic hot water Priority is recommended when a Boiler net output is 100 000 Btu per hour or less or b When boiler output required to satisfy domestic hot water demand is at least 50 of the boiler output required to satisfy space heating demand or c When an interruption in space heating can be tolerated during a long domestic hot water draw EGS I amp S 01 2 Non Priority Boiler output is divided between space heating and domestic hot water heating Delivery of domestic hot water can be reduced during simultaneous space and domestic hot water heating operations depending on such factors as boiler output boiler over sizing number of space heating zones calling for heat and the ratio of domestic hot water load to space heating load COMPONENT LOCATION AN CAUTION This water heater must be located in an area where leakage of the tank water line connections or the temperature and pressure relief valve will not result in damage to the area adjacent to the water heater or to lower floors of the structure When such locations cannot be avoided a suitable drain pan must be installed under the water heater The drain
13. ation Setting the water heater temperature at 120 F will reduce the risk of scalds Some states require settings to specific lower temperatures WARNING Install a discharge line so that water discharged from the temperature and pressure relief valve will exit within six 6 inches above or any distance below the structural floor and cannot contact any live electrical part The discharge line is to be installed to allow for complete drainage of both the temperature and pressure relief valve and the discharge line The discharge opening must not be subjected to blockage or freezing DO NOT thread plug or cap the discharge line It is recommended that a minimum clearance of four 4 inches be provided on the side of the water heater for servicing and maintenance of the combination temperature and pressure relief valve Do not place a valve between the combination temperature and pressure relief valve and the tank SACRIFICIAL ANODES Three sacrificial anode rods have been installed in the tank head to extend tank life The anode rods should be inspected annually to determine the amount of sacrificial decay and replaced when necessary to prolong tank life Water conditions in your area will influence the time interval for inspection and replacement of the anode rod The use of a water softener may increase the speed of anode consumption More frequent inspection of the anode is needed when using softened or phosphate treated water C
14. e temperature and pressure of the water heater This water heater contains components that become very hot Do not touch any components unless they are cool Improper installation adjustments alteration service or maintenance can cause property damage personal injury or loss of life Failure to follow all instructions in the proper order can cause personal injury or death Read and understand all instructions including all those contained in component manufacturer s manuals which are provided with the appliance before installing starting up operating maintaining or servicing this appliance Keep this manual and literature in legible condition and posted near the appliance for reference by owner and service technician This water heater requires regular maintenance and service to operate safely Follow the instructions contained in this manual Installation maintenance and service must be performed only by an experienced skilled and knowledgeable installer or service agency CAUTION The maximum boiler water supply temperature to the indirect heat exchanger must not exceed 240 F WARNING It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating properly when the installation is complete DO NOT operate the water heater with jumpered or absent controls or safety devices DO NOT tamper with or alter the water heater and or controls DO NOT operate the
15. ents TEMPERATURE AND PRESSURE RELIEF VALVE WARNING Keep clear of the combination temperature and pressure relief valve discharge line outlet The discharge may be hot enough to cause scald injury The water is under pressure and may splash For protection against excessive temperatures and pressure install temperature and pressure protective equipment required by local codes but not less than a combination temperature and pressure relief valve certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials as meeting the requirements of the Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems ANSI Z21 22 and the Standard CAN1 4 4 Temperature Pressure Temperature and Pressure Relief Valves and Vacuum Relief Valves The combination temperature and pressure relief valve must be marked with a maximum set pressure not to exceed the maximum working pressure of the water heater The combination temperature and pressure relief valve must also have an hourly rated temperature steam BTU discharge capacity not less than the hourly rating of the water heater The supplied combination temperature and pressure relief valve when properly installed and unrestricted will discharge the maximum input produced by a 240 F 116 C boiler supply temperature A lower boiler supply temperature will reduce the input required to be discharged in
16. h a 160 F maximum setting set at the factory to 120 F About 1 1 2 seconds 155 F About 1 second Table 4 Scald Relationships closed contacts close returning boiler control to space heating WARNING SCALDING This water heater can deliver scalding temperature water at any faucet in the system Be careful whenever using hot water to avoid scalding injury By setting the aquastat on this water heater to obtain an increased water temperature you may create the potential for scald injury To protect against injury you should install an ASSE approved mixing valve a device to limit the temperature of water to protect against scald injury via mixing hot and cold water supply in the water system This valve will reduce point of discharge temperature in branch supply lines Such valves are available from the manufacturer of this water heater or a local plumbing supplier Please consult with a plumbing professional A DANGER a BURN Water temperatures over 125 F can cause severe burns instantly or death from scalds Children disabled and elderly are at highest risk of being scalded See Temperature Adjustment section of this manual before setting thermostat at water heater Feel water before bathing or showering Temperature limiting valves are available consult local plumbing supplier Figure 5 Scald Warning 2 For the most energy efficient operation adjust the a
17. he water heater electricity off for the zone containing the Single wall Indirect Flow water until the discharge is cool or allow enough time for the potable water to cool naturally Connect a hose to the drain valve Locate the hose s discharge in an area where any remaining hot water will not cause any damage or injury b Open the drain valve to flush any sediment out of the bottom to the heater c Shut off the cold water supply Make sure all hot water fixtures and circulating pumps are turned off d Wait for water flow from the hose to stop Remove the anode using a socket of the appropriate size Do not use an impact wrench e Inspect and replace the anode as required Use pipe tape or sealant when reinstalling the anode f Close the drain valve Open a hot water fixture to allow air to escape Open the cold water supply to the heater and allow the tank to fill g Check your anode and drain valve for leaks h Turn the water heater electricity on for the zone containing the Single wall Indirect Sediment Annual but harsh water quality may dictate more frequent service Depending on water conditions a varying amount of sediment may collect in the tank Levels requiring service are indicated by a small temperature difference in the supply and return lines See also Scale below Repeated flushing usually clears such material As a preventive measure water should be drawn from the tank at the drain valve
18. l has 1 NPT female fittings These water heaters with single wall heat exchangers meets the Uniform Plumbing Code for installation in all potable water systems provided that e The boiler water including additives is practically non toxic having toxicity rating of class of 1 as listed in Clinical Toxicology of Commercial Products e The boiler water pressure is limited to maximum 30 psig by approved relief valve e The heat transfer medium is potable water or contains only substances that are recognized as safe by the U S Food and Drug Administration FDA e The pressure of the heat transfer medium is maintained less than the normal minimum operating pressure of the potable water system e The equipment is permanently labeled to indicate that only additives recognized as safe by the FDA shall be used in the heat transfer medium EGS I amp S 01 ADJUSTABLE AQUASTAT The temperature may be adjusted from 80 F to 160 F The aquastat thermostat was adjusted to 120 F before the heater was shipped from the factory It is recommended that lower temperatures be used to avoid the risk of scalding Refer to the Warnings and the section on SCALDING under Operating Instructions It is further recommended in all cases that the water temperature be set for the lowest temperature that satisfies your hot water needs This will also provide the most energy efficient operation of the water heater and minimizes scale form
19. lectrical Connections Aquastat setting too low Adjust aquastat to higher setting See Operating Instruction Undersized boiler with no Rewire for priority priority to domestic hot water Peak use of hot water is greater Determine peak usage and compare to tank capacity than tank storage capacity Faulty tank aquastat Replace aquastat Reduce demand or consider larger tank Faulty aquastat Replace aquastat Boiler high limit set too low Increase boiler high limit setting 2 06 Printed in USA
20. mperature and pressure relief valve discharge piping must be piped near the floor to eliminate potential of severe burns Do not pipe in any area where freezing could occur Do not install any shut off valves plugs or caps to the temperature and pressure relief valve or piping INSTRUCTIONS FOR POTABLE CONNECTIONS BEFORE PROCEEDING WITH THE INSTALLATION CLOSE THE MAIN WATER SUPPLY VALVE After shutting off the main water supply open a faucet to relieve the water line pressure to prevent any water from leaking out of the pipes while making the water connections to the water heater After the pressure has been relieved close the faucet The COLD water inlet and HOT water outlet are identified on the top of the water heater Make the proper plumbing connections between the water heater and the plumbing system to the house Install a shut off valve in the cold water supply line If this water heater is installed in a closed water supply system such as one having a back flow preventer in the cold water supply provisions must be made to control thermal expansion DO NOT operate this water heater in a closed system without provisions for controlling thermal expansion Warranties do not cover damages from thermal expansions such as pressure bulges and or deformities A properly sized expansion tank will alleviate most problems Your water supplier or local plumbing inspector should be contacted on how to control this situation After in
21. n accordance with the National Electrical Code and or local regulations or in Canada installed in accordance with the Canadian Electrical Code and or local regulations The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning product life DANGER Indicates an imminently hazardous situation which if not avoided will result in death serious injury or substantial property damage AN WARNING Indicates a potentially hazardous situation which if not avoided may result in moderate or minor injury or property damage A CAUTION Indicates a potentially hazardous situation which if not avoided could result in death serious injury or substantial property damage NOTICE Indicates special instructions on installation operation or maintenance which are important but not related to personal injury hazards DANGER DO NOT store or use gasoline or other flammable combustible or corrosive vapors and or liquids in the vicinity of this or any other appliance IF YOU SMELL GAS Q DO NOT try to light any appliance Q DO NOT touch any electric switch do not use any telephone in your building Q Immediately call your gas supplier from a telephone in another building Follow the gas supplier s instructions Q If you cannot reach your gas supplier call the fire department DO NOT OPERATE THE APPLIANCE U
22. o materials stored against the water heater and proper care must be taken to avoid unnecessary contact especially by children with the water heater UNDER NO CIRCUMSTANCES SHAL FLAMMABLE MATERIALS SUCH AS GASOLINE OR PAINT THINNER BE USED OR STORED IN THE VICINITY OF THE WATER HEATER OR IN ANY LOCATION FROM WHICH FUMES COULD REACH THE WATER HEATER Installation or service of this water heater requires ability equivalent to that of a licensed tradesman in the field involved Plumbing and electrical work are required OPERATING INSTRUCTIONS SYSTEM START UP Follow boiler installation instructions to place boiler in operation SEQUENCE OF OPERATIONS 1 Aquastat senses stored water temperature drops below desired setting a Domestic hot water priority only Normally closed contacts open to interrupt space heating EGS I amp S 01 2 Aquastat satisfied Table 4 details the approximate relationship of water a Aquastat contacts open turning off domestic hot temperature and time with regard to scald injury and may water circulator and de energizing relay be used as a guide in determining the safest water b Normally open contacts open stopping boiler temperature for your applications operation c Domestic hot water priority only Normally APPROXIMATE TIME TEMPERATURE RELATIONSHIPS IN SCALDS WATER TEMPERATURE ADJUSTMENT 1 The aquastat controls the maximum water temperature in the tank The differential is a fixed 5 F wit
23. one source Make sure all power is off before attempting any electrical work ELECTRICAL CONNECTIONS Install electric wiring in accordance with National Electric Code or the Canadian Electrical Code and local regulations See the boiler s installation manual for wiring diagrams The Single wall Indirect is supplied with an aquastat temperature control This aquastat must be installed in the aquastat well location of the water heater Refer to Figure 4 Remove the cover and loosen the clamping screws Insert the aquastat capillary bulb to the well bottom as shown and screw the aquastat clamp securely in the well groove The aquastat acts as a thermostat for zone control and should be wired accordingly Refer to the boiler or zone control manufacturer s instructions if any additional wiring is required The control is factory set at 120 F and care should be made to not rotate this dial while wiring the control Once electrical connections are complete secure the aquastat cover back in place AT NO TIME SHOULD WATER HEATER OPERATION TAKE PLACE WITHOUT THE COVER ON THE CONTROL TEMPERATURE DIAL BACK OF AQUASTAT teh i 9 o INSERT BULB AS SHOWN WIRE TERMINALS W L crap screws CROSS SECTIONAL VIEW Figure 4 Aquastat Control AN WARNING Water heaters are heat producing appliances To avoid damage or injury there must be n
24. ontact the plumbing professional who installed the water heater or the manufacturer listed on the rating plate for anode replacement information PRE INSTALLATION INSPECT SHIPMENT carefully for any signs of damage If damage is noted do not install the product Contact the shipper or manufacturer listed on rating plate All equipment is carefully manufactured inspected and packed Our responsibility ceases upon delivery of the packaged heater to the carrier in good condition NOTE Any claims for damage or shortage in shipment must be filed immediately against the carrier by the consignee IMPORTANT DECISIONS REQUIRED BEFORE INSTALLATION SIZING 1 Boiler DOE Heating Capacity The Single wall Indirect water heater will provide the rated performance only if used in conjunction with a boiler with a DOE heating capacity Boiler Output minimum of 220 000 Btu hr If the boiler has less capacity the output of the tank will be reduced To determine the approximate reduction in output from the tank use the following formula New Rating maximum first hour rating x Actual Boiler Output Capacity Minimum Boiler Output Capacity For example what would the 140 F first hour rating be if model EGS050 was installed with a boiler having a DOE heating capacity of 180 000 BTU hr Answer New Rating 297 gal hr x 180 000 BTU h 220 000 BTU hr 297 gal hr x 0 818 243 gal hr NOTICE Increasing the boiler DOE heating cap
25. quastat for the minimum water temperature necessary to meet domestic hot water needs Refer to Figure 6 Use a small flat screwdriver to rotate the temperature dial through the hole directly below the temperature indication window The temperature setting is aligned with the notch in this window IT IS NOT NECESSARY TO REMOVE THE COVER TO ADJUST THE TEMPERATURE SETTING THE AQUASTAT COVER SHOULD NEVER BE REMOVED WITHOUT ELECTRICITY BEING FIRST DISCONNECTED TEMPERATURE INDICATION WINDOW ADJUSTING SCREW Figure 6 Aquastat Control EGS I amp S 01 3 After the water heater completes a heat up cycle check the water temperature at a faucet Allow enough water to flow to ensure that the water temperature reflects the tank temperature Adjust the water heater s temperature setting as necessary a Adjusting to a lower temperature setting will not immediately affect water temperature Draw sufficient water or allow the water heater to sit until a heat up cycle is initiated Repeat step 3 b Adjusting to a higher temperature may not immediately affect water temperature If a heat up cycle begins return to step 3 If a heat up cycle does not begin draw sufficient water or allow the water heater to sit until a heat up cycle is initiated Repeat step 3 MAINTENANCE The Single wall Indirect is intended to provide a service life of many years Components that require service however may be subject to failure Failure to u
26. se the correct procedures or parts in these circumstances may make the water heater unsafe The owner should arrange to have the following inspections and simple maintenance procedure performed by qualified service personnel at the frequencies suggested 1 Boiler and Domestic Water Piping Annual Check all piping for signs of leakage at joints unions and shut off valves Repair as needed 2 Temperature Pressure Relief Valve Annual The temperature pressure relief valve should be checked to ensure that it is in operating condition To check the relief valve lift the lever at the end of the valve several times The valve should seat properly and operate freely If water does not flow remove and inspect for obstructions or corrosion Replace with a new valve of the recommended size as necessary Do not attempt to repair the valve as this could result in improper operation and a tank explosion In areas with poor water conditions it may be necessary to inspect the temperature relief valve more often than once a year 10 CAUTION Before manually operating the valve make sure that a drain line has been attached to the valve to direct the discharge to an open drain Failure to take this precaution could mean contact with extremely hot water discharging from the valve during this checking operation If the temperature pressure relief valve on the heater discharges periodically or continuously it may be due to therm
27. stallation of the water lines open the main water supply valve and fill the water heater While the water heater is filling open several hot water faucets to allow air to escape from the water system When steady streams of water flow through the faucets close them and check all water connections for possible leaks EGS I amp S 01 4 NEVER OPERATE THE WATER HEATER WITHOUT FIRST BEING CERTAIN THAT IT IS FILLED WITH WATER INSTRUCTIONS FOR BOILER CONNECTIONS The Single wall Indirect connection labeled To Boiler Return should be piped to the boiler return piping as close to the boiler as possible and especially after any flow control or check valves in the space heating return piping The use of a union and a shut off valve is recommended The use of a flow control or check valve is required to prevent back flow through the water heater during operation of the space heating system Pipe and fittings between the boiler and Single wall Indirect should be 94 diameter or larger CAUTION Maximum boiler water supply temperature to the indirect heat exchanger must not exceed 240 F 116 C CONNECT WATER BOILER SUPPLY PIPING 1 For a space heating system that utilizes ZONE VALVES refer to Figure 1 The Single wall Indirect connection labeled FROM BOILER SUPPLY should be piped to the boiler supply piping Mount the circulator making sure the flow arrow points toward the water heater The use of Shut off valves and
28. until it runs clear Scale Annual Hard water may cause scale to build up on the outside of the heat exchanger coil A water softener will prevent this problem See also Sediment above Symptoms would be reduced recovery capacity or reduced temperature differential between boiler supply and return lines Repeated flushing should resolve the problem 11 EGS I amp S 01 EGS I amp S 01 TROUBLE SHOOTING GUIDE PROBLEM CAUSE SOLUTION No hot water at faucet Water at faucet too hot Insufficient hot water Boiler cycles more per day in summer Boiler does not operate Refer to boiler installation instructions Check main service switch Check fused disconnect Circulator does not operate Check power supply Replace as necessary Improper aquastat setting calibration Turn tank aquastat to appropriate or setting Zone valve does not open if used Check power supply Replace as necessary Electrical problem relay wiring etc Check fuse and replace Check circuit breaker andreset if applicable Check power supply Scale build up If boiler circulator and tank are operating satisfactorily coil may have scale coating See Maintenance Clogged cold water filter or Clean or replace filter or strainer boiler supply strainer if used Aquastat set too high Lower aquastat setting See Operating Instructions Improper system plumbing Compare to plumbing in Water Connections Improper system wiring Compare to wiring in E
Download Pdf Manuals
Related Search
Related Contents
POSIMAG® - PMIS3 / PMIS4 Sensori di posizione Manuel – Août 2012 Version Française manuel d`utilisation convertisseur de mesure Philips BTB7150 User Guide Manual University of Manchester - The Translation Research Summer School User Manual Electric - Smart Seating Solutions Samsung BD-E5500 Kasutusjuhend Copyright © All rights reserved.