1. 8 Installing the Step Down 8 Installing ima Ac 8 Wiring the Step Down 9 Connecting Load Equipment ise 10 Turning On the Step Down 10 Using the Step Down Transformer usa 11 Chapter 4 5 4 2 20 2 0 11 Produc CCI eie a ATTORE 12 TABLE OF CONTENTS CHAPTER 1 SAFETY AND GENERAL INFORMATION Save These Instructions This Safety section contains important instructions that must be followed during installation and maintenance of APC equipment Conventions Used in this Manual The following symbols are used throughout this manual Carefully read all information boxes and abide by the instructions The WARNING sign denotes a serious hazard It calls attention to a procedure practice condition or the like which if not correctly performed or adhered to could result in injury to personnel The CAUTION sign denotes a hazard It calls attention to an operating procedure practice or the like which if not correctly performed or adhered to could result in damage to or destruction of all or part of the product The NOTE sign denotes important information It calls attention to a procedure practice condition or the like w
2. Rear View Component Identification che Nite Bec 060000000000000006000000 000000000000000000 e AP9621 5 2 SYTF2J SURT005 SURT006 Figure 5 OOO WEB NS O oe 2 gt 9900 OOQ O 90009 Fr OOOO 55999 000000 0000 990 SS 51 22 Figure 6 SUTF3 SYTF3 SYTF3J CHAPTER 3 INSTALLATION Cleats Two cleats one on each side of the Step Down Transformer engage with the rack mounting rails to secure in the equipment rack Mounting Flanges O Two mounting flanges Figure 2 and 4 secure the Step Down Transformer in the rack Front Bezel A bezel covers the front of the Step Down Transformer The bezel is removed during the installation for the SUTF3 SYTF2 SYTF2J SYTF3 and SYTF3J models Fans Two fans on the front of the Step Down transformer circulate airflow and cool the unit The redundant fan will not operate unless the internal temperature of the unit becomes 100 F or failure of the main cooling fan SUTF3 SYTF2 SYTF2J SYTF3 SYTF3J SURT005 SURTOO6 Figure 7 Input Wiring Provides access to wiring terminal blocks for hard wiring the input see Figure 6 Provided with an input cord for use in many applications see Figure 7 Input Circuit Breaker The input circuit breaker protects the product and load equipment from extreme overloads
3. infusion pumps and any other device designated as critical by the U S F D A Hospital grade wiring devices and reduced leakage currents that meet medical safety standards may be ordered as options on many APC UPS systems APC does not claim that units with these modifications are certified or listed as such by APC or any other organization therefore these units do not meet the requirements for use in direct patient care Limited Warranty American Power Conversion APC warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase except in India where the period is one year for battery module s Its obligation under this warranty is limited to repairing or replacing at its own sole option any such defective products To obtain service under warranty you must obtain a returned material authorization RMA number from customer support Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase This warranty does not apply to equipment that has been damaged by accident negligence or misapplication or has been altered or modified in any way This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase EXCEPT AS PROVIDED HEREIN AMERICAN POWER CONVERSION MAKES NO WARRANTIES EXPRESSED OR IMPLIED
4. INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FORA PARTICULAR PURPOSE Some states do not permit limitation or exclusion of implied warranties therefore the aforesaid limitation s or exclusion s may not apply to the purchaser EXCEPT AS PROVIDED ABOVE IN NO EVENT WILL APC BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE Specifically APC is not liable for any costs such as lost profits or revenue loss of equipment loss of use of equipment loss of software loss of data costs of substitutes claims by third parties or otherwise This warranty gives you specific legal rights and you may have other rights that vary from state to state Copyright and Trademark Information Entire contents copyright 2003 by American Power Conversion Corporation All rights reserved Reproduction in whole or in part without permission is prohibited Symmetra Smart UPS Smart UPS NetShelter InfraStruXure and PowerChute are registered trademarks of American Power Conversion Corporation All other trademarks are the property of their respective owners CHAPTER 1 SAFETY AND GENERAL INFORMATION CHAPTER 3 INSTALLATION About Your Step Down Transformer VAC and accessories Figure 1 Step Down Transformer stand alone device Table 1 System Configurations and Model Numbers Complete Availab
5. Power Distribution Unit PDU Power distribution receptacles for connecting load equipment CHAPTER 3 INSTALLATION Unpacking The Step Down Transformer is packaged in a robust shipping carton Carefully remove the package contents The packaging is recyclable save it for reuse or dispose of it properly Inspection Inspect the equipment upon receipt APC has designed robust packaging for your product However accidents and damage may occur during shipment Notify the carrier and dealer if there is damage or missing equipment Contents Check the packaging contents The shipping package contains the Step Down Transformer mounting rails and mounting hardware Your package may contain a Bezel Kit If the bezel is not already installed snap it on to the UPS as instructed below Installing the Step Down Transformer This section provides information on the steps required to install and connect the Step Down Transformer Installing in a Four Post Rack Follow the instructions contained in the Addendum SU Rack Mount Rails 2U 5U sheet 990 7034G to mount the rails in your NetShelter or 19 in 46 5 cm rack It is recommended that the Step Down Transformer is installed directly above the UPS in the rack 1 Install the mounting rails using the instructions contained in the Rail Kit 2 Slide the Step Down Transformer frame into the rack The Step Down Transformer is heavy Three people must suppor
6. reduce the risk of fire connect only to a circuit provided with 30 amp maximum branch circuit overcurrent protection in accordance with the National Electrical Code ANSI NFPA Regulatory Agency Approvals Regulatory Agency Symbols 6 LISTED 42C2 E95463 LR63938 CHAPTER 1 SAFETY AND GENERAL INFORMATION Life Support Policy As a general policy American Power Conversion APC does not recommend the use of any of its products in life support applications where failure or malfunction of the APC product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness APC does not recommend the use of any of its products in direct patient care APC will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to APC that a the risks of injury or damage have been minimized b the customer assumes all such risks and c the liability of American Power Conversion is adequately protected under the circumstances Examples of devices considered to be life support devices are neonatal oxygen analyzers nerve stimulators whether used for anesthesia pain relief or other purposes autotransfusion devices blood pumps defibrillators arrhythmia detectors and alarms pacemakers hemodialysis systems peritoneal dialysis systems neonatal ventilator incubators ventilators for both adults and infants anesthesia ventilators
7. APC Step Down Transformer Models AP9621 SURTOO5 SURTO06 SUTF3 SYTF2 SYTF2J SYTF3 and SYTF3J User s Manual English www apc com 990 7820D July 2003 TABLE OF CONTENTS APC Contact Numbers and Support Visit the APC Web site for contact numbers and support at http www apc com support Chapter 1 Safety and General 1 Save These Instructions iii aida 1 Conventions Used in this Manual stc nta tina r n 1 Ae e E o 1 De energizing Safety MM 2 ie ee 2 Regulatory Agency Approvals inician A rede arrives U KK UE 2 hs een 3 LINEA AP o O O a A ee 3 Copyright and Trademark 3 Chapter 2 Basics arnold 5 About Your Step Down Transformer 2 000000 1 5 Produc OVON ON 6 Front View Component 7 Rear View Component 7 Chapter 3 Instalado Nissan 7 Bla e ee A PU E o o a 8 INS DECH ON ops tee ibas dieta oratoria 8 relais
8. e redundant fan will turn on 10 CHAPTER 3 INSTALLATION Using the Step Down Transformer Connect the Step Down Transformer to a UPS for continuous power during a utility power failure The transformer has an efficiency of 90 This requires 5500 VA for a 5000 VA load 5000 VA for a 4500 VA load and 3900 VA for a 3500 VA load Be careful not to overload your branch circuit or UPS For the AP9621 SYTF2 and SURTOO5 models to output the full 5000 VA the input must be hardwired to a 5500 VA source Operating the Step Down Transformer below its specified input voltage range may cause it to overload and shut down to prevent it from over heating When connecting directly to a branch circuit ensure that the line voltage is within specification When connecting to a UPS ensure that the line voltage into the UPS 15 within specification before transferring to bypass Operating the Step Down Transformer above its input voltage range may cause equipment damage 11 CHAPTER 4 SPECIFICATIONS Product Specifications Electrical Specifications AP9621 SUTF3 5 2 SYTF2J 5 SURTOOG SYTF3 SURTOOS Nominal Input Voltage VAC 208 Input Voltage Range VAC 185 to 230 180 to 220 Maximum Input Current amps Line cord Installation L6 30 22 Hardwire Installation 26 Line Frequency Hz 50 or 60 Efficiency 90 to 95 Maximum Output Power VA Line cord Installation L6 30 4500 3500 Hardwire Installa
9. hich is essential to highlight Handling Safety Be careful Do not lift heavy loads without assistance 32 55 kg 70 120 Ib This equipment is intended for installation in a temperature controlled indoor area free of conductive contaminants Refer to Specifications at the APC web site www apc com support for the actual temperature range CHAPTER 1 SAFETY AND GENERAL INFORMATION De energizing Safety To de energize this equipment toggle the rear input circuit breaker to the OFF position and then disconnect the equipment from the AC power outlet Electrical Safety e The protective earth conductor carries the leakage current from the load devices computer equipment Therefore the size of the conductor must be at least as large as the wire required by IEC 950 An insulated grounding conductor that is identical in size insulation material and thickness to the grounded and ungrounded branch circuit supply conductors except that it is green with or without a yellow stripe is to be installed as part of the branch The grounding conductor described above 15 to be grounded to earth at the service equipment or if supplied by a separately derived system at the supply transformer or motor generator set The attachment plug receptacles near the unit or subsystem are all to be of a grounding type and the grounding conductors serving these receptacles are to be connected to earth ground at the service equipment To
10. l block Each terminal is labeled The Step Down Transformer requires a 208 VAC single phase input from a power source with a minimum branch breaker rating of 30 amps Inspect the connections Attach the new access panel provided in the literature kit CHAPTER 3 INSTALLATION Connecting Load Equipment Plug all load equipment into PDU O receptacles m O o e For AP9621 SYTF2 SYTF2J SURTOO5 and SURTOOG AR echt models the receptacles are divided into 4 groups each group is protected by a 15 amp circuit breaker A colored label identifies each circuit and its circuit breaker e For SUTF3 SYTF3 and SYTF3J models the output is divided into 4 groups Each group is protected by a 20 amp circuit breaker that contains one 1 receptacle e When connecting the equipment distribute the loads evenly on the four output circuits Turning On the Step Down Transformer v PPP ob 0000000000000000000000 000000000000000000 1 Turn on the Step Down Transformer by switching the rear panel input circuit breaker to the ON position For AP9621 SYTF2 SYTF2J SURTOO5 and SURTOOG models a colored label identifies each circuit and its circuit breaker 2 Turnon all connected equipment Depending on your required output power one of the fans may not be turning because the internal temperature of the Step Down Transformer is less than 100 F If 100 F is reached th
11. le Nominal Nominal Frequency System Power VA Input Output Hz End Item Voltage Voltage VAC SKU VAC North 27 2 1 4500 5000 and SURTOO5 208V O Y G SYTF3 4500 208 120 60 SUTF3 SYTF2J SURTOOG i SYTF3J 50 or 60 Power cord connected units have an available power of 4500 VA with a L6 30 plug Units with an available power of 5000 VA must be hardwired due to input current Ensure that the pin number for T slot receptacles is correct This Step Down Transformer is designed for use with a UPS that provides a higher output voltage 200 or 208 It converts the output to a lower voltage 100 or 120 VAC a common voltage level used by many computers The Step Down Transformer may also be used as a Power Distribution Input 3 foot cord with L6 30P or hardwired Output 2 15 amp circuits with 4 5 20R T slots and 2 15 amp circuits with 2 5 20R T slots or hardwired Input 2 foot cord with L6 30P Output 4 20 amp circuits with 4 L5 20R Input 3 foot cord with L6 30P Output 2 15 amp circuits with 4 5 20R T slots and 2 15 amp circuits with 2 5 20R T slots Input 2 foot cord with L6 30P Output 4 20 amp circuits with 4 L5 20R CHAPTER 3 INSTALLATION Product Overview Front View Component Identification Figure 2 AP9621 Figure 3 5 2 SYTF2J SYTF3 5 Figure 4 SURT005 SURT006
12. t the unit 3 To secure the Step Down Transformer frame in the rack screw the four decorative screws through the holes in the ears of the UPS and into the screw clips 4 Ifthe bezel has not already been attached align the tabs on the sides of the bezel with the slots on the front of the Step Down Transformer and gently snap it into place Install the bezel with the rear fins facing down Figure 9 SUTF3 S SYTF3 SYTF3J Wiring the Step Down Transformer ER i ae a ue rw Pu NEMA L6 30 Ko EN A AAN al AA CHOC O00006000000000000000000 000000000000000000 CDC E Beck 6 y ON OA A 00000000000000000000000 O000000000000000000 2 CHAPTER 3 INSTALLATION For cord connected installations plug the input power cord into the outlet For hardwired installations Verify that all branch circuit mains are de energized and locked out before installing cables or making connections Wiring by a licensed electrician is required Check national and local codes before wiring Use 10 gauge 6 wire Make sure the input circuit breaker is OFF a Remove the input wiring access panel Disconnect the power cord from terminal block Connect the new wires Q to the termina
13. tion 5000 3500 For continuous operation below Vin 205 VAC the output load must be reduced to limit the maximum input current to the amount specified in the table above Continuous operation above the maximum specified input current may cause the unit to overheat and shutdown Please contact APC for additional information Not available on SUTF3 and SYTF3 models 12 CHAPTER 4 SPECIFICATIONS Other Specifications Dimensions H x W x D 3 5 in x 19 in x 26 in with bezel Overall 8 9 cm x 48 3 cm x 66 cm Weight Net 95 Ibs 43kg Shipping 110 Ibs 50 kg Temperature Operating 0 to 40 C Storage 25 to 65 C Humidity relative Operating and storage 5 to 95 Elevation Operating 0 to 3 000 m 0 to 10 000 ft Storage 0 to 15 000 m 0 to 50 000 ft Agency Approvals UL 1778 AP9621 SUTF3 SYTF2 SYTF2J SYTF3 SYTF3J SURT005 and SURTOOG models CSA 66 AP9621 SUTF3 SYTF2 and SYTF3 models 13