F-3100 SERIES In-line Electromagnetic Flow Meter
Contents
1. F 3100 SERIES In line Electromagnetic Flow Meter Installation amp Basic Operation Guide 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 0670 7 16958 www onicon com sales onicon com 01 13 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 2 SAFETY INFORMATION This meter was calibrated at the factory before shipment To ensure correct use of the meter please read this manual thoroughly Regarding this Manual This manual should be passed on to the end user Before use read this manual thoroughly to comprehend its contents The contents of this manual may be changed without prior notice All rights reserved No part of this manual may be reproduced in any form without ONICON s written permission o ONICON makes no warranty of any kind with regard to this material including but not limited to implied warranties of merchantability and suitability for a particular purpose All reasonable effort has been made to ensure the accuracy of the contents of this manual However if any errors are found please inform ONICON ONICON assumes no responsibilities for this product except as stated in the warranty If the customer or any third party is harmed by the use of this product ONICON assumes no responsibility for any such harm owing to any defects in the product which were
2. direction of flow in the piping system and orient the meter accordingly mm FLOW DIRECTION E IMPORTANT NOTE Flow direction is indicated by polarity symbols and flow totals are accumulated separately based on direction The polarity of the flow indication may be reversed by reversing the polarity of the Ka coefficient 3 1 3 Remote Mounted Transmitter Find an easily accessible location where wire connections can be made and meter readings can be taken from floor level Mount the transmitter on a vibration free surface Avoid locations that contain electric motors or other strong sources of electrical interference IMPORTANT NOTE The F 3100 remote mounted transmitter option is provided without a pre amplifier As a result the maximum distance it can be located away from the sensor body is limited to 65ft A remote transmitter option with a pre amplifier is available with the F 3200 advanced transmitter With this model the remote transmitter may be located up to 1640ft away from the sensor body Contact ONICON if you need to locate the remote transmitter more than 65ft from the sensor body 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 13 3 1 4 Minimum Straight Run Requirements The straight run requirements presented below represent the minimum requirements for accurate flow measurement For optimum performance
3. or attached to Buyer s purchase order form Buyer s acceptance of delivery of ONICON S products constitutes its acceptance of these Conditions of Sale DELIVERY AND TITLE All product shipments are F O B shipping point and title passes to the Buyer at the time ONICON delivers the merchandise to the carrier Risk of loss or damage to the product passes to the Buyer at the time ONICON delivers the product to the carrier The Buyer immediately upon receipt should inspect all shipments and should there be any evidence of damage or loss in transit Buyer must file claims or tracers upon carrier ONICON will assist in tracing shipments upon reguest LIMITED WARRANTY ONICON warrants that for a period of two 2 years following the date of original shipment of an ONICON product i the product will conform to ONICON s standard written specifications applicable to such product in effect on the date of Buyer s order or as modified by ONICON s quotation or Buyer s purchase order accepted by ONICON ii the product will be free from defects in workmanship and iii that ONICON has title to the product prior to shipment to the Buyer provided however that the warranties provided herein shall be void and may not apply in the event Buyer misuses or damages a product including but not limited to any use by the Buyer of a product for an application other than one of a type approved by ONICON ONICON S sole liability and Buyer s sole remedy for any breach of t
4. provide as much additional straight run as possible IMPORTANT NOTE For proper operation install the flow meter in a straight run of pipe free of bends tees valves transitions and obstructions for a distance of at least 3 diameters upstream and 2 diameters downstream Recommended Installation Avoid these installations Place flow meter at least 3 pipe diameters upstream and 2 pipe diameters downstream from bends and obstrutions 3 DIA 2 DIA Avoid downward flow which can lead to partially filled pipes lt O N lt O 69 The electrodes should be located in the horizontal axis 3 o clock and 9 o clock in order to prevent sediment from settling on them Electrode Location 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 14 3 2 MECHANICAL INSTALLATION IMPORTANT NOTE F 3100 transmitters and sensor bodies are two parts of one uniquely calibrated system and must be installed together Mixing components from other systems will result in significant calibration errors 3 2 1 Standard Transmitter Dimensions Net weight 1 6 lbs 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 15 3 2 2 Sensor Dimensions amp Weights Ansi Class 150 Flanged Sens
5. 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 18 3 2 3 Installation Drawings for Conductive Pipe Note 2 INSTALLATION IN STEEL CONDUCTIVE PIPE Let 2 Note 1 Using a 21 0 159 drill bit drill a 2 deep hole in edge of each mating flange Tap each hole using a 10 32 tap Secure the ring connectors provided and grounding wires to the flange using the green grounding screws provided Alternate method Weld 10 32 studs not provided to the flange faces and attach ring connectors with 10 32 nuts not provided Note 2 Provide a ground connection at the input power terminals inside the transmitter enclosure Note 3 Provide a guality earth ground connection to the meter From best to worst grounding options include 1 Earth grounding rod driven into the soil 2 Earth wire connected directly to the building electrical service panel 3 Earth wire connection inside an electrical outlet mear the meter CAUTION The earth connections must be made as shown Failure to do so will result in erratic operation of the meter 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 19 INSTALLATION IN CONDUCTIVE PIPE Note 1 Note 1 Using a 21 0 159 drill bit drill a 4 deep hole in edge of each mating flange Tap each hole using a 10 32 tap Secure t
6. Also refer to the START UP AND COMMISSIONING GUIDE located on the preceeding pages REPORTED PROBLEM POSSIBLE SOLUTIONS No signal Verify correct wiring to control system See wiring diagram Check display for alarm messages Verify that the pipe is full Verify that the sensor body and transmitter are both connected to earth ground Reading is too high or low Verify correct wiring to control system see wiring diagram Confirm that the output signals are consistent frequency vs analog etc Confirm that the control system is programmed for correct flow range or scale factor Analog signal seems high or Check for ground loop or offset voltage low and does not correspond Verify that the sensor body and transmitter are both connected to earth ground to frequency output Disconnect analog signal input from control system and measure analog outputs directly from the flow meter Re connect signal input to control system and measure the analog signals again Any difference between these readings indicates a potential ground loop or offset voltage Please contact ONICON for further assistance Control system displays Verify that all of the wires from the flow meter are connected to the display module or Btu flow rate but no flow rate is meter indicated on the local The freguency output wire green must be connected for any ONICON display or Btu meter display module or Btu meter 1500 North Belcher Roa
7. Remote Mount Cable Wiring Instructions enyn 31 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 5 TABLE OF CONTENTS CONTINUED 4 0 F 3100 START UP AND COMMISSIONING eee erre 32 4 1 Display And Keypad OUperatton rererananarereraaaanmnrena 33 4 2 Helpful Hints For Start Up And Commissioning YY 34 tart Un A Wd C onn sain le eran dae n 34 4 4 Start Up And Commissioning Workaheet AA 35 45 Tronblesnoonino GWide see ES TORR ANEA 35 4 6 Alarm Interpretation And Standard 1 018 HY HYAY Y nn Y Ao 36 APPENDIX A 1 FIELD REMOTE MOUNTING THE TRANSMITTER oo YHA HY A Y Ayy 38 A2 CONDITIONS RE EE 41 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 6 SECTION 1 0 INTRODUCTION 1 1 PURPOSE OF THIS GUIDE The purpose of this guide is to provide installation and commissioning procedures and basic operating instructions for the F 3100 In line Electromagnetic Flow Meter 1 2 PRINCIPLE OF OPERATION The operating principles of ONICON F 3100 In line Electromagnetic Flow Meters are based on Faraday s Law of Electromagnetic Induction Faraday s Law states that a voltage will be induced in a conductor water or other conductive liquid when it passes through a magnetic field generated by the meter and the induced
8. in applicable guotations by ONICON or Buyer s purchase orders accepted by ONICON shall constitute the entire agreement between ONICON and Buyer pertaining to any resulting contract They can be modified only in writing 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 41
9. not predictable or for any indirect damages Safety Precautions The following general safety precautions must be observed during all phases of installation operation service and repair of this product Failure to comply with these precautions or with specific WARNINGS given elsewhere in this manual violates safety standards of design manufacture and intended use of the product ONICON Incorporated assumes no liability for the customer s failure to comply with these reguirements If this product is used in a manner not specified in this manual the protection provided by this product may be impaired The following symbols are used in this manual WARNING Messages identified as Warning contain information regarding the personal safety of individuals involved in the installation operation or service of this product CAUTION Messages identified as Caution contain information regarding potential damage to the product or other ancillary products IMPORTANT NOTE Messages identified as Important Note contain information critical to the proper operation of the product 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 3 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 4 TABLE OF CONTENTS INTRODUCTION snes
10. rate from measured analog signals Current Output GPM measured current in mA 4 Full Scale Analog Flow Rate 16 Scaled Output Each contact closure unit volume identified as Scale Factor measure and record time interval between contact closures Compare various output signals to Compare the flow rates calculated in STEP 7 to the flow rate indicated by the display and the each other and to the flow rate control system Refer to troubleshooting guide when readings are inconsistent displayed and to the control system 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 34 4 4 START UP AND COMMISSIONING WORKSHEET Please read all installation instructions carefully prior to proceeding with these steps Use the following worksheet for checking off the commissioning steps and recording measured values STEP TESTIMEASUREMENT S N SIN SN SIN Meter location 7 serial S N if ordered 0 70000 sew fU 6 Comectpower o The following steps reguire flow in the pipe Flow signal readings should be taken while holding the flow rate constant if possible Otherwise take the various output readings as guickly as possible Analog or binary outputs 4 20 mA signal mA mA mA mA scaled output interval Flow rates meter display control system 4 5 TROUBLESHOOTING GUIDE NOTE
11. tat eee 7 Tel Purpose Or This E 0 E E E a E E O 7 L2 Principle Or Operation ups gs pisa spas DESSE an 7 7 Typical Flow Meter 13 8 0 44 00060 0444 Standard Features And Spechcations 1 4 Additional Hardware That May Be Reouired AAA 9 1 5 LST Groundin RINGS sanita ii GU CU 9 dis Gake o une ER FN AR HF HF OFER RR SE RF DH 10 1 6 Working Environment a 10 1 7 Warranty And Serial Number ANNER 10 20 CH GC 11 2 1 Checking That You Have Received Everything eeesssserssssrrrersssrrrrress 11 3 90 A FN aa fa 12 OMe ess HE FFF LAR Pio ISEC ESA FFF as RUE GELADO FF 12 LLL General 0 E EER 13 3 2 Flow 13 Glo Remote Mount EE tee 13 3 1 4 Minimum Straight Run Reouirements Ynyr 14 32 Mechanical e WE 15 3 2 1 Standard Transmitter Dimensions sessssessessssserreesssserereessseeeees 15 3 2 2 Sensor Body Dimensions amp Weigebte A 16 3 2 3 Installation Drawing For Conductive Pipe eessseessseereessseseees 19 3 2 4 Installation Drawing For Non Conductive Pipe 21 3 2 5 Installation Drawing For Threaded Connections 22 3 20 eu O eegen 23 See ee Te te eu EE 25 o Remote Mount Tan nu seenen eegene Eege 26 so aa a o 27 S328 REQUITEMEN UG cuia eE E E 27 3 3 2 Power And Output Signal Wiring 1811011018 27 Soo Barn A 30 3 3 4
12. 765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 27 Step 1 Loosen screws to lift cover Step 2 Lift cover to expose electrical connections Armee Tt Tat Mdn 00 Don Step 3 Make SIGNAL connections as shown Step 4 Open cover to expose POWER Connections Pull straight out on connectors to remove them SIGNAL CONNECTIONS POWER CONNECTIONS 4 20 mA Output Pulse Out 2 Pulse Out 1 Remove retaining screw to Power connections Pin 9 Pos Pin 18 Pos Pin 16 Pos expose connector are under this cover Pin 10 Neg Pin 19 Neg Pin 17 Neg Shown with High Voltage BIS 4 DES ac E ELECTT A o 3 O OW i IE WEB RR a Pulse Output 1 Pulse Output 2 16 outl 18 out2 Opto coupled open collector pulse outputs Maximum voltage 40VDC Maximum current 100mA Maximum saturation voltage collector emitter 100mA 3 VDC 17 out1 19 out2 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 28 POWER CONNECTIONS CONTINUED Step 5 Pull straight out on the connector to remove it Low voltage High voltage version version Step 6 Wire the connector as shown based on input type Earth connection must be made 15 45 Var 10 04 Vide 90 265VAC Step 7 Use the right hand strain reli
13. F 3100 In line Electromagnetic Flow Meters ordered with the remote transmitter mounting option will be shipped in one carton that contains the flow sensor body the transmitter with mounting hardware and the necessary cable to connect the two together Remove each and inspect it for physical damage IMPORTANT NOTE F 3100 transmitters and sensor bodies are two parts of one uniquely calibrated system and must be installed together Mixing components from other systems will result in significant calibration errors Grounding Rings Grounding rings are optional accessories that may be required for proper installation Grounding rings may be shipped in a separate carton Remove each and inspect it for physical damage SECTION 3 0 INSTALLATION The F 3100 In line Electromagnetic Flow Meter should be installed by experienced plumbers electricians and others with related knowledge and experience in the heating cooling and fluid metering fields ONICON will be happy to assist with technical recommendations and to provide guidance by telephone and or email On site field engineering installation and service are also available at an additional cost The installer should use good trade practices and must adhere to all state and local building or other applicable codes 3 1 SITE SELECTION Careful attention during the site selection process will help the installers with the initial installation reduce start up problems and make future m
14. F to 140 F The electrical power should be relatively clean free of high frequency noise large voltage transients and protected from power surges and brown outs 1 7 WARRANTY amp SERIAL NUMBER Warranty ONICON s complete warranty is included in Appendix A of this manual as part of the Conditions of Sale ONICON provides a two year warranty Serial Number The F 3100 has 2 separate serial numbers The transmitter serial number is located on the identification plate located on the electronics enclosure The sensor serial number is located on the identification plate located on the sensor body 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 10 SECTION 2 0 UNPACKING The F 3100 is generally shipped in one package unless optional hardware or equipment is ordered Notify the freight carrier all products are shipped insured and ONICON s Customer Service Department if any items are damaged in transit 2 1 CHECKING THAT YOU HAVE RECEIVED EVERYTHING e Standard Documentation Enclosed with each F 3100 is a comprehensive documentation package that includes the following items Certificate of Calibration The F 3100 Installation and Operation Guide Please notify ONICON if any of these items are missing ONIG OAN E INCORPORATED F 3100 SERIES In line Electromagnetic Flow Meter Installation amp Basic Operation
15. Guide FLOW METER PEL i CERTIFICATE OF CALIBRATION CALIBRATION amp CONFIGURATION DATA for F 3000 SERIES MAGNETIC FLOW METERS METER DATA CALIBRATION of PRIMARY FLOW ELEMENT Meter Tag CT WH Ka factor 1 0951 Model F 3103 111 Medium Water Serial Number 220177 Component S N s 04N1420 38M6901 Primary Calibration Date 4 12 2011 Meter Size 3 Max Operating Pressure 225 psi This meter was manufactured for ONICON Incorporated Max Operating Temperature 212 F The original manufacturer certifies that this flow meter was Connections ANSI 150 Class Flanges calibrated against standards that are traceable to IT Italy Peripheral device serial number 220177 5 ay FACTORY PROGRAMMED OUTPUT SIGNALS Performed at ONICON Factory can be reprogrammed in the field Analog Flow Range 4 20 mA 0 to 230 Gal Min Full Scale Freguency Output 200 00 Hz Scaled Pulse Output 1 pulse 100 Gallons Programmed By GL Date 5 25 2011 1500 N Belcher Road Clearwater Florida 33765 Tel 727 447 6140 Fax 727 442 5699 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 11 Integral Mount Transmitter F 3100 In line Electromagnetic Flow Meters with integrally mounted transmitters are shipped fully assembled Remove the meter from the shipping carton and inspect it for physical damage Remote Mount Transmitter
16. ON F 3100 SERIES FLOW METERS Thee Te 4 p 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 32 4 1 DISPLAY AND USER INTERFACE The F 3100 standard transmitter is equipped with a 2 line by 16 character LCD with 0 2 high characters Three pushbutton switches located inside the transmitter enclosure are used to change the displayed data and program the meter functions Momentarily press the UP top button to view alarm Leg Te F De d BEE Fee dl E messages d AA TA E E mappa Momentarily press the RIGHT middle button to advance y to the next menu page The ENTER bottom button is used in programming Flow Rate Partial Positive Flow Total Flow Direction Indicator Flow Rate Percentage of Full Scale Engineering Units Partial Positive Flow Total Total Negative Flow Total Total Positive Flow Total Partial Negative Flow Total Positive Flow Total Flow Rate Negative flow Total Flow Velocity When selected this page will cause the menu pages Flow Rate d Partial Negative Flow Total to scroll automatically 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 33 4 2 HELPFUL HINTS FOR START UP AND COMMISSIONING A step by step procedure and companion worksheet ar
17. Voltage 10 63 VDC 15 45 VAC 45 66 Hz 300 mA maximum High Voltage Mains 90 265 VAC 45 66 Hz 35 mA maximum IMPORTANT NOTE This option is not field selectable Contact the factory if you need to change the input voltage rating CAUTION WARNING This product must be connected to earth ground for proper operation Failure to do so will result in erratic operation and an increased risk of injury WARNING All mains voltage connections must be made through pre drilled conduit strain relief opening located at the bottom of the enclosure Failure to do so will result in an increased risk of injury 3 3 2 Power and Output Signal Wiring Instructions Factory Default Output Configurations ONICON pre programs the analog and pulse outputs based on application specific data provided at the time the meter is ordered The table below shows how the pulse outputs are configured based on whether the application has bi directional flow and if the meter will be connected to an ONICON peripheral device such as an ONICON Btu meter or display module In all applications the analog 4 20 mA output is available at terminals 9 and 10 Application Pulse Output 1 Pulse Output 2 Terminals 16 amp 17 Terminals 18 amp 19 Scaled Pulse Bi directional Scaled Output This output will be configured for frequency if the flow meter is provided with a peripheral device 1500 North Belcher Road Clearwater FL 33
18. ailure to do so will result in erratic operation of the meter 3 2 5 Installation Drawing for Threaded Connections THREADED PROCESSED CONNECTION flow direction E CGC 3 DIA AU 2 DIA MINIMUM UPSTREAM MINIMUM STRAIGHT PIPE RUN DOWNSTREAM STRAIGHT PIPE RUN CAUTION The earth connections must be made as shown Failure to do so will result in erratic operation of the meter 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 22 3 2 6 Installation Instructions WARNING Installation of this product should only be attempted by qualified tradespersons and must comply with all local state and federal building codes 1 Thoroughly clean all flange surfaces removing all traces of any old gasket material or any adhesive residue 2 Inspect all flange surfaces for warping pitting or other surface imperfections that may prevent a good seal 3 Use new bolts nuts and hardened washers ONICON recommends the use of B7 nuts bolts and washers Prior to installation lubricate the bolt threads nuts washer faces and the underside of the bolt head with lubricant Fel Pro G5A or eguivalent This lubricant is necessary to ensure uniform stress distribution on the sealing surface Use care not to get any lubricant on the liner or gasket material 4 Genter the new gasket
19. aintenance easier For example do not install the flow meter where it will be difficult for personnel to perform periodic maintenance When selecting a site for mounting consider the criteria under Section 1 6 WORKING ENVIRONMENT as well as the following IMPORTANT NOTE Proper site selection is critical to the performance of this flow meter The flow meter must be properly located within the piping system in order to ensure an accurate flow measurement 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 12 3 1 1 General Guidelines When properly installed the flow meter will only measure flow associated with that portion of the piping system for which the flow measurement is being made Choose the location with the longest straight unobstructed run of pipe keeping in mind that in some applications it may be possible to locate the meter in either the supply or return pipe 3 1 2 Flow Direction F 3100 flow meters are inherently bi directional and changes in flow direction are indicated by a change in polarity of the sensing signal In order for the meter to display the correct polarity it is necessary to orient the meter relative to flow direction during the installation process The sign of the flow rate is positive when the flow direction is from to as printed on the tag plate as shown below Prior to installation determine the
20. ct The following general suggestions are provided to assist the installer in choosing the proper gasket material In all cases the responsibility of selecting the appropriate material rests with the installer Gaskets are used to create a seal between the flow meter liner surface and the surface of the mating flange The proper choice of gasket material will allow for a leak free connection at the time of installation and maintain that seal over time How well the gasket works depends on a number of factors Each of these should be considered when choosing a gasket material e Is it chemically compatible with the fluid e Will it withstand the expected minimum and maximum operating temperatures e Does it provide enough resiliency and creep resistance to maintain loading over time e Will it deform enough to create a seal by filling imperfections in the sealing surfaces e Is it thick enough to take up variations in flatness of the surface In many cases a simple 1 8 red rubber gasket with a Shore A hardness Durometer of 60 80 will suffice Your local gasket supplier should be able to guide you in selecting the best material for your application 1 6 WORKING ENVIRONMENT The F 3100 was designed for installation and use in typical industrial environments that are free of corrosive liquids and fumes direct liquid exposure direct sunlight temperature extremes and vibrations The operating ambient air temperature range is 4
21. d Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 35 4 6 ALARM INTERPRETATION AND STATUS LED s ALARMS LL Alarm Indicators Symbol When activated this symbol indicates flow in excess of the set point Range 0 125 of full scale m When activated this symbol indicates flow below the set point Range 0 125 of full scale Open coil connection e Signal error e When activated indicates empty pipe Calibration running Transmitter in simulated output mode O Pulse output saturated change pulse rate or duration Nig me es LAT SRI 4 TT TT TE Status LED Continuously ON Initialization of firmware Flashing LED 1 second rate Normal operation Flashing LED lt 1 second rate Alarm condition 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 36 APPENDIX A 1 FIELD REMOTE MOUNTING THE TRANSMITTER A 2 CONDITIONS OF SALE 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 37 Field Remote Mounting the Transmitter Wiring Instructions Section 1 Removing the Transmitter Before attempting to remote mount the transmitter disconnect power at the source Step 1 Open cover Slide cover off to the right if desired S
22. e located on the next two pages Please read all installation instructions and these helpful hints carefully before proceeding with installation start up and commissioning 1 ONICON flow meters are individually calibrated for a particular application Be sure to verify the pipe size and location 2 The electronic sensing system will not work in air The pipe must be full for proper operation 3 When measuring analog output signals remember that currents mA must be measured in series while voltages are measured in parallel If the 4 20 mA signal is already connected to a control system you must break the connection and measure the signal in series 4 When measuring freguency outputs in hertz take your multimeter out of autorange mode and manually set range for a voltage level above 15 VDG This will prevent false readings when signal is not present 5 Never connect power to analog or frequency output signal wires ONICON F 3100 Flow Meters are not loop powered devices 4 3 START UP AND COMMISSIONING Please read the entire procedure carefully before proceeding Wiring instructions are located on pages 21 24 of this manual A worksheet for checking off the following steps and recording measured values is located on the next page Confirm flow meter location and Is the meter located in the correct location as reguired by the plans adequate straight pipe run to achieve Compare actual straight pipe upstream and downstream
23. ef for installing the power cable or power conduit EI 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 29 3 3 3 Earth Connection F 3100 Electromagnetic Flow Meters are designed to detect microvolt signal levels at the electrodes located in the flow meter body These signals are generated as conductive fluids flow through the magnetic field generated by the meter If enough random electrical noise is present at the electrodes it can interfere with the flow measurement Care must be taken during installation to minimize the effects of electrical noise on the flow meter The most effective way to minimize the effects of electrical noise is to make sure that the pipe fluid flow meter body and flow meter transmitter are all connected to the same earth ground This accomplishes two important goals First it ensures that the pipe fluid flow meter body and electronics are all at the same electrical potential and second it ensures that this electrical potential is the same as earth ground In order to be certain that the meter is properly connected to earth the flow meter body earth connections at the flanges or on the neck of wafer meters and the transmitter earth connection should be run directly to a Known earth connection The length of this earth cable should be as short as practically possible preferably l
24. es Step 8 Re install the cover 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 39 Section 3 Wiring the Transmitter Step 1 Remove the retaining nut and black plastic plug from the center strain relief on the enclosure and feed the nut over the end of the Step 2 Attach the green connectors to the end of the cable Numbers on each wire correspond to the numbers on the cable Then feed the connectors cable through the strain ze relief mM Step 3 Step 4 Re install the connectors and tighten the strain relief Re install the power cable and connector Remove the o ring from the remote mount bracket and place it into the gland on the bottom of the enclosure as shown Step 5 Step 6 Attach the mounting Close and fasten bracket using the the cover screws and lock washers supplied in the kit IMPORTANT NOTE Transmitter programming must be changed to complete the remote mount installation 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 40 12 CONDITIONS OF SALE ACCEPTANCE The following Conditions of Sale apply to all sales of ONICON s products These provisions shall apply even if ONICON fails to object to provisions appearing on incorporated by referenced in
25. he foregoing warranty is for ONICON to repair or replace at ONICON s option any defective product that is returned to ONICON during the warranty period EXCEPT AS MAY BE SPECIFICALLY AGREED BY ONICON IN WRITING IN RELATION TO EACH SALE NO OTHER WARRANTIES SHALL APPLY WHETHER EXPRESSED IMPLIED OR STATUTORY AND THERE SHALL BE NO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE REMEDIES ONICON s OBLIGATION UNDER THE FOREGOING WARRANTIES IS LIMITED SOLELY TO REPAIR OR REPLACEMENT AT ONICON s OPTION OF DEFECTIVE OR NONCONFORMING PRODUCTS ONICON SHALL NOT BE LIABLE FOR CONSEOUENTIAL INDIRECT PUNITIVE INCIDENTAL OR SPECIAL DAMAGES WHETHER FOUND ON CONTRACT TORT OR ANY OTHER THEORY OF LAW No products shall be returned to ONICON without its prior consent and transportation and insurance costs shall be prepaid Any repair or replacement of ONICON s products under the foregoing warranty will be at no charge to the Buyer provided such repair is done at the ONICON factory or authorized service center ONICON products that are repaired or replaced under this warranty will be returned to Buyer via the same method of shipment use to return the product to ONICON Repair or replacement of ONICON products is conditioned upon ONICON s acknowledgement of any alleged defect or nonconformance during the warranty period and issuance of a Return Authorization number All product returns must reference the Return Authorization number on the
26. he ring connectors provided and grounding wires to the flange using the green grounding screws provided Alternate method Weld 10 32 studs not provided to the flange faces and attach ring connectors with 10 32 nuts not provided Note 2 For meters provided with a grounding electrode connect grounding wire to terminal on the meter neck as shown Note 3 Provide a ground connection at the input power terminals inside the transmitter enclosure Note 4 From best to worst grounding options include 1 Earth grounding rod driven into the soil 2 Earth wire connected directly to the building electrical service panel 3 Earth wire connection inside an electrical outlet mear the meter CAUTION The earth connections must be made as shown Failure to do so will result in erratic operation of the meter 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 20 3 2 4 Installation Drawing for Non Conductive Pipe INSTALLATION IN NON CONDUCTIVE PIPE EXPLODED VIEW LILIA GASKET 4PL 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 21 On e WAFER INSTALLATION IN NON CONDUCTIVE PIPE GASKET IT GROUNDING RING A GASKET FF ot et NU Flow Direction CAUTION The earth connections must be made as shown F
27. in a flow laboratory against standards that are directly traceable to government standards A certificate of calibration accompanies every meter ACCURACY 0 4 of reading from 3 3 to 33 ft sec 0 8 of reading from 1 to 3 3 ft sec 0 0075 ft s at flows less than 1 ft s PROGRAMMING Factory programmed for specific application MEMORY Nonvolatile memory retains all program parameters and totalized values in the event of power loss DISPLAY Alphanumeric LCD displays total flow flow rate flow direction amp alarm conditions OUTPUT SIGNALS Isolated 4 20 mA analog output for flow rate Two programmable open collector pulse outputs configurable for freguency pulse or directional flow TEMPERATURE RANGE Liguid temperature range Polypropylene liner 329 to 1409F Ebonite liner 23 to 1759F PTFE liner 4 to 212 F 266 F with remote electronics Ambient temperature range 14 to 1229F MAINTENANCE Periodically inspect the power supply cables cable glands and the enclosure for signs of damage Inspect installation and mounting hardware for loose connections MECHANICAL Electronics Enclosure Standard Nylon NEMA 4 Optional Remote mount transmitter version maximum distance from the sensor is 65ft Outer Body Material Standard Carbon Steel Painted Optional 316 Stainless Steel Flow Tube Internal 304 Stainless Steel Connection Type Standard ANSI 150 Class Flange Optional ANSI 300 Class Flange Opt
28. ional Wafer Optional Threaded Process Connection ELECTRICAL This eguipment is intended for INSTALLATION CATEGORY OVERVOLTAGE CATEGORY H applications Input Power Factory Selectable Standard 90 to 265 VAC 45 to 66 Hz and 35 mA maximum Optional 10 to 63 VDC 15 to 45 VAC 45 to 66 Hz and 300 mA maximum Overcurrent Protective Device Ratings Supply mains overcurrent protective devices with the following ratings e 120 VAC 50 60 Hz 15 A e 230 VAC 50 Hz 6 A Wiring Flow signals Use 18 22 AWG shielded cable Standard input power Use a three wire service with one wire a protective earth ground The installation must comply with all local state and federal building codes Optional input power Use PVC jacketed copper cable with a wire gauge suitable for the length of run and required maximum current carrying capacity The installation must comply with all local state and federal building codes PRESSURE AND CONDUCTIVITY Maximum Operating Pressure Exclusive of flange rating Ebonite 1000PSI Polypropylene 230PSI PTFE 580PSI Minimum Fluid Conductivity 5 microsiemens centimeter Note Specifications are subject to change without notice 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 8 1 5 ADDITIONAL HARDWARE THAT MAY BE REQUIRED 1 5 1 Grounding Rings Grounding rings may be reguired whenever
29. meters are installed in non metallic or lined pipes Grounding rings placed before and after the meter eliminates electrical noise that will interfere with the proper operation of the meter ONICON provides grounding rings as an optional accessory Grounding ring dimensional information and part numbers are listed below For proper operation grounding rings are reguired before and after the meter 5 8 Jee i gt Grounding Ring Dimensions amp ONICON Part Numbers Size it 2 5 8 4 9 16 ang 15212 15213 4 15214 15215 15216 15217 2 5 8 4 9 16 1 15 16 6 8 3 10 11 16 Jang us 8 11 fi2 15m6 Iran un 15218 9 1 2 13 3 8 15219 1 13 3 8 15220 15221 15222 15223 6 15224 15225 5 H H H 99 99 99 99 99 99 99 99 99 99 1 28 1 4 31 1 8 2 7 8 34 3 4 3 1 2 15226 36 Jon 41 14 4 15227 42 ur as 52 2 4 1 2 15228 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 9 1 1 9 A 10 12 14 16 16 20 24 30 36 42 1 5 2 Gaskets Gaskets are required for sensor bodies with ebonite and polypropylene liners and are strongly recommended for meters with PTFE liners Gasket dimensions must comply with ASME B16 5 flange standards ONICON is not a gasket manufacturer and does not supply gaskets for this produ
30. of the meter location to desired results recommended distances identified in this manual Confirm that the control system input point is properly configured for the analog range or scale factor identified on the calibration certificate Confirm connection to correct Confirm that the flow meter serial number matches the ONICON display or Btu meter ONICON display or Btu meter if serial number when ordered together ordered Prior to connecting the power verify that the wiring is correct as shown in this manual and or the additional wiring diagram provided with ONICON display or Btu meter If in doubt contact ONICON for assistance before proceeding further Verify that the input voltage available Low voltage 10 63 VDC or 15 45 VAC 45 66 Hz 300 mA maximum to power the meter is appropriate for the meter version Check label inside High voltage 90 265 VAC 45 66 Hz 35 mA maximum transmitter enclosure LV Low voltage HV High voltage 6 Connect power Wait approximately 45 seconds after power on before proceeding further The following steps require flow in the pipe Flow signal readings should be taken while holding the flow rate constant if possible Otherwise take the various output readings as quickly as possible Measure and record analog or binary Refer to flow meter wiring diagram for the various outputs available based on your particular outputs flow meter model Use the following formulas to calculate flow
31. on the liner surface Do not allow the gasket to protrude into the flow stream 5 Use the torque specifications shown below to determine the recommended final bolt torgue reguirements 6 Using a torque wrench tighten the bolts in at least three stages 30 60 amp 100 using a repeating pattern seguence shown in the diagrams below ANSI Class 150 Flange Bolt Tightening Seguence Liner material 12 bolt 16 bolt 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 23 ANSI Class 150 Flange Bolt Tightening Sequence 24 bolt 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 24 3 2 7 Torque Specifications Tighten uniformly in a diagonal sequence as per the table below Contact ONICON for torque specifications for meters with a nominal diameter larger than 24 inches Torque Specifications in ft lb Operating Pressure 19 eR Ol N AN OJo ps PTFE ER 32 aoo 51 67 CO so Bo o 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 25 3 2 8 Remote Mount Transmitter Remote mount transmitters are provided with a single L b
32. or Overall Dimension SE EEE gt E i J Shown with 4 bolt pattern Sensor Size Nominal Diameter 1 12 1 5 2 28 4 5 e 8 10 12 Weightinlos 66 97 11 15 4 215 264 32 0 35 2 55 75 138 159 Sensor Size po Sensor size 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 16 Wafer Style Sensor Overall Dimensions Es Sensor Size Es nio 1 pape e fae ele fs e e iw um 1 16 2 20 aaa 276 sss 425 aes 567 677 787 1067 12 08 140 1717 1921 je ll lol fofo so 70a 060 ats 1554 awen 26 55 40 aa 75 oa mn won a ss so 7 06 Threaded Version Polypropylene Stainless Steel eight 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 17 Recommended method for lifting all sensors with eyebolts The eyebolts are designed to hold only the weight of the meter WARNING Eyebolts are provided to assist in the safe installation of meters with a nominal diameter greater than 6 inches The eyebolts are onl TL to hold the weight of the meter Do not attempt to place an additional load on the eyebolts during installation 1500 North Belcher Road Clearwater FL 33765 Tel 727
33. outside of the shipping carton and on any paperwork referencing the return PRICES AND PAYMENT TERMS The prices set forth in the most recent guote or acknowledgement as applicable supersede all previous prices or guotations All guotations are subject to change or withdrawal without notice except as may be specifically noted on the face of the guotation The prices shown do not include sales excise or government charges payable by ONICON to Federal State or local authority Any such tax or charge now or hereafter imposed upon the sale or shipment of the products under this contract will be added to the purchase price Buyer agrees to reimburse ONICON for such tax or charge or provide ONICON with an acceptable exemption certificate Payment of invoices will be due 30 days from the date of shipment of the products contained therein In the event that payment of an invoice is not received by the invoice due date ONICON will assess a late fee not to exceed 1 590 per month or 18 per year or the maximum allowableby law whichever is lower CANCELLATION Buyer may cancel its order or any part of it by sending written notice of cancellation to ONICON and paying a reasonable cancellation fee as determined by ONICON The reasonable cancellation fee will reflect among other factors the expenses already incurred and commitments made by ONICON sales and administrative costs and profit as determined by ONICON If Buyer received a reduced price based on the guan
34. racket with two 14 mounting holes The bracket is secured to the transmitter by means of 8 large bolt with a knurled knob for a head To mount the bracket first separate it from the transmitter housing and attach it to the wall or other vertical surface Cable from the sensor body is attached to the transmitter using the center strain relief Cable is supplied already attached to the sensor body Mounting Bracket Cable wires are D labeled with numbers which correspond to connection terminals on the transmitter CAUTION DO NOT drill holes in the transmitter Use only the openings that are provided DO NOT cut the remote cable Goil excess cable at one end Ss am 1 Install sensor Del cable here 0 0 25 Diameter 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 26 3 3 ELECTRICAL INSTALLATION 3 3 1 Input Power Requirements F 3000 Electromagnetic Flow Meters equipped with standard transmitters are available with two different options for input power This is not a user selectable function and must be configured at the factory Special care is required to ensure that the F 3100 is properly connected to earth through an earth wire This connection is required to prevent random electrical noise from interfering with the operation of the meter See section 3 3 3 for details Low
35. t 25 feet in length The table below lists earth connections from best to worst IMPORTANT NOTE Non metallic pipes are more a Weare to electrical noise Grounding rings installed upstream and downstream of the flow meter body to reduce the electrical noise present in the pipe may be reguired for proper operation CAUTION Do not use bolts that hold pressure to make earth connections Using flange bolts may result in poor electrical connections due to the presence of paint and or lubricants Use the dedicated flange earth connections or the dedicated earth connection on the neck of wafer style meters arth wire connected directly tothe building local sorvico panel 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 30 3 3 4 Remote Mount Cable Wiring Instructions Caution Do not cut the remote mount cable The wires are not color coded Cable wires are labeled with numbers which correspond to connection terminals on the transmitter Install remote cable through the center strain relief as shown Connect the coil and electrode wires to the appropriate terminals according to the numbered tags on each wire 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 31 SECTION 4 0 METER START UP amp COMMISSIONING FOR ONIC
36. tep 2 Open compartment to expose power connection Step 3 Remove power connector from its socket Remove wires from the connector and set aside Step 4 Remove electrode and coil connectors from their sockets Step 5 Step 6 Step 7 Remove electrode and coil wires Remove mounting screws from Carefully separate the electronics from connectors and set aside the bottom of the enclosure enclosure from the sensor body Screws do not need to be fully As the two come apart feed the removed sensor wires through the opening in the bottom of the enclosure 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 38 Section 2 Installing the Remote Mount Junction Box Step 1 Remove the cover and circuit board from the remote mount junction box Step 3 Re install the cir cuit board Step 5 Install the remote mount cable through the strain relief supplied with the junction box Step 7 Cables should be connected as shown Remote transmitter cable Step 2 Feed the cales through the holes in the bottom of the junction box and mount it in place Install the remote mount cable to the numbered terminal block positions Step 4 Attach the cables to the terminal blocks as shown Note Each wire is labeled with a number that corresponds to a terminal location Sensor cabl
37. tity of products ordered but has not purchased the applicable guantity at the time of cancellation Buyer will pay the price it would have paid had ONICON s sale price been based on the guantity actually purchased CHANGES If Buyer makes any changes in its drawings designs or specifications applicable in any contract with ONICON that cause an increase or decrease in the cost of performance of the contract or if such changes result in rework or obsolescence an eguitable adjustment shall be made to the contract Such changes are subject to ONICON S prior written consent EXCUSABLE DELAY ONICON shall under no circumstance be responsible for failure to fill any order or orders when due to fires floods riots strikes freight embargoes or transportation delays shortage of labor inability to secure fuel material supplies or power at current price or on account of shortages thereof acts of God or of the public enemy any existing or future laws or acts of the Federal or State Government including specifically but not exclusively and orders rules or regulations issued by any official or agency of any such government affecting the conduct of ONICON s business with which ONICON in its judgment and discretion deems it advisable to comply as a legal or patriotic duty or due to any cause beyond ONICON Ss reasonable control PATENTS ONICON shall defend all suits or proceedings brought against Buyer or its customers arising from claimed infringemen
38. ts of any patent trademark service mark or copyright for any product furnished by ONICON and shall indemnify it against all costs fees and damages on the condition Buyer promptly notifies ONICON in writing and provides information and assistance to enable ONICON to conduct the defense provided that ONICON shall have no such obligation in case of infringement resulting from ONICON s conformance to special requirements of Buyer If ONICON is not able to settle any such suit or proceeding on acceptable terms ONICON may at its option reguire return of the infringing product and refund the purchase price to Buyer less a reasonable allowance for depreciation or use FAIR LABOR STANDARDS ACT ONICON represents that all products delivered under this contract are furnished in accordance with the applicable provisions of the Fair Labor Standards Act as amended APPLICABLE LAW This document and any resulting contract shall be governed by and construed in accordance with the laws of the State of Florida The courts of the State of Florida and the federal courts located in Florida shall have jurisdiction and venue with respect to litigation to this contract In the event of litigation the prevailing party shall be entitled to recover attorney s fees and costs from the non prevailing party including appellate attorney s fees MODIFICATIONS These Conditions of Sale along with the prices guantities delivery schedules and other provisions and instructions
39. voltage will be directly proportional to the velocity of the conductor By placing electrodes on opposite sides of the flow tube it is possible to accurately measure the induced voltage and determine the corresponding velocity of the flowing liquid WARNING Only qualified service personnel should attempt to install or service this product Serious injury may result from the improper installation or use of this product 1 3 TYPICAL FLOW METER INSTALLATION ONICON S F 3100 Series In line Magnetic Flow Meters are suitable for volumetric flow measurement of electrically conductive liquids in a wide variety of applications including bi directional applications CS INSTALLATION IN STEEL CONDUCTIVE PIPE II II Flow direction lt DD gt 1500 North Belcher Road Clearwater FL 33765 Tel 727 447 6140 Fax 727 442 5699 sales onicon com F 3100 Flow Meter Manual 01 13 0670 7 Page 7 1 4 STANDARD FEATURES AND SPECIFICATIONS A built in user interface amp display A single 4 20 mA output for flow rate Two programmable open collector pulse outputs Outputs may be programmed to provide an indication of flow direction a scaled pulse for totalizing flow a high resolution frequency output to drive peripheral devices an indication of an alarm condition Empty pipe detector Internal self diagnostic functions amp fault alarms CALIBRATION Flow meters are wet calibrated
Download Pdf Manuals
Related Search
Related Contents
Notice utilisateur - Airélec - Assistance technique DOCUMENT DE RÉFÉRENCE 2007/2008 User`s Guide - CNET Content Solutions Les programmes de 1980 decl-00074-ft_vet anios_decl Optimus 742 Stereo System User Manual NVR-TAB8 S2 (8GB) TABLET ANDROID 8” (20,32cm Dell Wyse P45 HP Photosmart C3100 All-in Sony VGN-N100 Kitchen Entertainment Center User Manual Copyright © All rights reserved.