Home
Bryant SYSTXBBUIZ01 Thermostat User Manual
Contents
1. A04017 Fig 5 Thin Decorative Backplate NN ES r Recessed terminal block in wall 11 2 wide by 2 1 8 high Lo ep E N lt Recessed Mount Ih S m Ser Interlocking Tabs 4 py A03190 LT 000 O Surface Mount lo Backplate to wall IH 5 S al IF Interlocking Tabs 4 A03191 Fig 7 Surface Mount Assembly c Discard or recycle old control NOTE Mercury is a hazardous waste if existing control contains any mercury it MUST be disposed of properly 3 Select Evolution Zone Control mounting plastic recess mount or surface mount and decorative backplate if de sired Route wires through large hole in mounting plastic Level rear plastic against wall for aesthetic value only Evolution Zone Control need not be level to operate properly and mark wall through two mounting holes Drill two 3 16 inch mounting holes in wall where marked Secure mounting plastic to wall using two screws and anchors provided Adjust length and routing of each wire to reach each wire entry on the connector backplate Strip 1 4 inch of insulation from each wire A03188 Fig 8 Large Decorative Backplate A03192 Fig 9 Decorative Backplate Assembly 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 12 13 and 14 A Green Data A B Yellow Data B C White 24VAC Com
2. 2 Make sure all colors match for every terminal 3 Check for 24VAC between the C and D terminal connector of outdoor unit I made a mistake on the start up screens and hit the right side button to get to the run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will appear 3 Scroll down to the INSTALL selection 4 Press the right side button the screen will prompt you to press the right side again to re install the system Control does not see zones 5 through 8 1 Make sure zone module 5 8 has the DIP switches set to the right 2 Recheck wiring to the ABCD connectors Control says I have zones 5 8 but not 1 4 1 Make sure zone module 1 4 has the DIP switches set to the left 2 Recheck wiring to the ABCD connectors Some zones in my zoned system do not provide enough comfort A noticeable difference exists between the actual room temperature and operating set point yet the equipment does not turn on 1 The zone airflow limit may be set too low Perform the Zone Airflow Limit Checkout procedure raise airflow limit setting if possible Some zones provide too much airflow and are noisy 1 The zone airflow limit may be set too high Perform the Zone Airflow Limit Checkout procedure lower airflow limit setting if possible CRITICAL MALFUNCTION SCREEN The following errors will cause a Critical Malfunction screen to pop up Heat and Cool LEDs will a
3. DECORATIVE BACKPLATE Supplied is a thin decorative backplate see Fig 5 to hide any marks screw holes left from the previous thermostat This decorative backplate or beauty ring can be used in either the recess or surface mount installation by snapping it onto back of recessed mount backplate or surface mount backplate before securing to wall See Fig 8 and 9 for a larger decorative backplate P N SYSTXXOLBPO1 5 75 wide X 6 tall which can be ordered separately LI Fig 2 Evolution Zone Control gt A 000 ac d Fig 4 Surface Mount Backplate C Step 3 Installing Evolution Zone Control WARNING ELECTRICAL SHOCK HAZARD A03185 A03186 A03187 Failure to follow this warning could result in personal injury or death Before installing Evolution Zone Control turn off all power to equipment There may be more than one power source to disconnect 1 Turn off all power to equipment 2 If an existing User Interface or control is being replaced a Remove existing control from wall b Disconnect wires from existing control pac aoe
4. lt BACK CONTINUE gt lt BACK CONTINUE gt AIR FILTER MEDIA TYPE HUMIDIFIER INSTALLED U V LIGHTS INSTALLED A03198 Fig 18 Accessories UV Lights whether UV lights are installed on the system select YES or NO then press right side button to continue EG E Section 5 Zoning ZONING ZONING ZONE 1 Ul SEARCHING FOR ZONE 3 RS ZONE EQUIPMENT ZONE 4 RS WORKING UI USER INTERFACE RS REMOTE SENSOR SS SMART SENSOR lt BACK CONTINUE gt Fig 18a Zoning A04084 SEARCHING FOR ZONE EQUIPMENT will appear on the screen to identify the number of zones detected This screen will show Zone 1 Zone 2 etc and indicate all zones having either a remote room sensor or smart sensors associated with them If the system contains smart sensors they must be assigned a zone number before continuing See Smart Sensor Installation Instruc tions on how to assign Smart Sensors to their respective zones When finished press right side button to continue See Fig 18a F Section 6 Equipment Summary EQUIPMENT SUMMARY FURNACE 355MAV0420 SETUP AC 598BNX024 COMPLETE FILTER EAC HUMIDIFIER YES UV LIGHTS YES ZONES 12345678 SAVE ALL SELECTIONS lt NO YES gt lt NO YES gt A04109 Fig 19 Equipment Summary The EQUIPMENT SUMMARY screen will appear after Ac cessories and Zoning have been selected This screen will give a summary of all equipment automatically foun
5. be displayed HUMIDIFY WITH FAN e NO default e YES If YES the humidifier will run with Continuous Fan operation if there is a humidify demand VENTILATOR NOTE Only appears if ventilator is installed CLEAN INTERVAL e 60 to 180 days of actual operation default 90 Interval at which the Clean Ventilator Pre filter notification will turn on UV LIGHTS INSTALLED NO e YES If YES indicates to the system whether UV lights are installed CHANGE INTERVAL 6 to 48 months operation time default 12 months Interval at which the Change UV Lights notification will be displayed Setup SYSTEM MAINTENANCE REMIND OWNER OF ROUTINE MAINTENANCE EVERY This setup is used to adjust the timer interval in which the normal System Maintenance notification is turned on for the homeowner Range OFF 6 to 24 months default 12 months CHECKOUT MENUS The Checkout menu will show the equipment installed in the system A sample checkout menu is shown in Fig 24 CHECKOUT FURNACE HEAT PUMP HEATING HEAT PUMP COOLING HUMIDIFIER ZONING VENTILATOR lt BACK SELECT gt A03204 Fig 24 CHECKOUT MENUS Checkout FURNACE Make sure the furnace is properly installed before continuing LOW HEAT RUNTIME 5 min HIGH HEAT RUNTIME 5 min This menu item allows the furnace to be exercised First a low heat runtime and high heat runtime are selected Range 5 120 min If only the low heat is to b
6. exterior door window or in a closet The remote sensor can be wired to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the OS1 and OSIC connection at the Damper Control Module In either case the Evolution Zone Control will automatically detect the remote room sensor and ignore its internal temperature sensor It is also important to note the humidity sensor cannot be remotely located so do not locate the Evolution Zone Control in an area where humidity sensing may not be accurate NOTE S1 amp S2 connection on UI backplate is now used for Remote Room Sensor NOT for OAT Sensor hookup In addition the Remote Room Sensor is a temperature sensor only having no additional user inputs This sensor is typically connected to the Damper Control Module and used to sense and control temperature in each zone SMART SENSOR Any zone may use a Smart Sensor It provides a temperature display and buttons to adjust the desired temperature in that zone only It also displays outdoor temperature and indoor humidity If a Smart Sensor is used in a zone a Remote Room Sensor may also be used in the same zone The Remote Room Sensor has priority over the Smart Sensor WIRING CONSIDERATIONS Ordinary thermostat wire is recommended Use or larger for normal wiring applica tions Continuous wire lengths over 100 ft should use 20 AWG or larger NOTE ABCD bus wiring only requires a four wire connection however it
7. is good practice to run thermostat cable having more than four wires in the event of a damaged or broken wire during installation Each communicating device in the Evolution Zone System has a four pin connector labeled ABCD It is recommended that the following color code be used when wiring each device A Green Data A B Yellow Data B C White 24VAC Com D Red 24VAC Hot It is not mandatory that the above color code be used but each ABCD connector in the system MUST be wired consistently LOCATING DAMPER CONTROL MODULE All wiring is run back to the Damper Control Module Select a location near the furnace or fan coil where wiring from the User Interface each Remote Room Sensor or Smart Sensor each damper actuator and the equipment itself can come together easily The Damper Control Module is approved for indoor use only and should never be installed with any of its components exposed to the elements The Damper Control Module and zone dampers may be installed in any area where the temperature remains between 4 F to 158 F 20 C to 70 C and there is no condensation The cover must be installed to prevent damage from other sources Do not locate where it will be accessible to children It may be mounted in either vertical or horizontal position Remember that wiring access is likely the most important consid eration CAUTION ELECTRICAL OPERATION HAZARD Failure to follow this caution
8. may result in equipment A damage or improper operation To prevent possible damage to the Damper Control Module DO NOT mount on plenum ductwork or flush against furnace or fan coil MOUNTING EVOLUTION ZONE CONTROL There are two options for mounting the Evolution Zone Control to the wall First become familiar with all plastic assembly pieces shown in Fig 2 through 9 The User Interface will snap together with either the Recess Mount or the Surface Mount backplate RECESS MOUNT This provides the thinnest mounting con figuration See Fig 3 The backplate containing the recessed terminal block can be mounted directly to the wall by cutting a hole 1 2 wide by 2 1 8 high Mark location and cut hole in wall NOTE Always ensure the Evolution Zone Control location is acceptable before cutting any holes in wall SURFACE MOUNT This provides surface mounting configu ration which allows use of a small hole in the wall A surface mount backplate is supplied See Fig 4 Attach backplate as shown in Fig 7 and the assembly will mount directly to the wall requiring only a small hole in the wall allowing a four wire connection to pass through NOTE Once Evolution Zone Control is secured to wall with the backplate assembly snapped together care must be taken not to bend or break the interlocking tabs when removing Gently remove Evolution Zone Control by rocking up down until inter locking tabs release
9. system or the system is transitioned from Off to Cool or Heat modes The blower will run at a medium airflow for one minute Unoccupied Pressing the HOLD button for 3 sec will set the selected zone to unoccupied status All Zones Pressing the zone button for 3 sec will gray out the entire display and put the User Interface into All Zones mode indicated by All Zones in upper left of the display Any changes to set temperature fan or Hold status will occur in all zones when the screen is exited Press the Zone button to exit All Zones mode TROUBLESHOOTING Evolution Zone Control does not power up 1 Recheck wiring to ABCD on all devices 2 Make sure all colors match for every terminal 3 Make sure power is applied to the indoor unit and the amber LED is lit on indoor control circuit board 4 Check for 24VAC between the C and D terminals at Evolution Zone Control terminal connector and Damper Control Module 5 Check fuse on indoor unit s circuit board Display says Indoor Unit Not Found 1 Recheck wiring to ABCD on all devices 2 Make sure all colors match for every terminal 3 Press left side button to try again 4 If display still reads Indoor Unit Not Found disconnect all devices from ABCD and connect User Interface directly to indoor unit Display says Outdoor Unit Not Found and I have a two speed communicating outdoor unit 1 Recheck wiring to ABCD connector on outdoor unit
10. 2 speed heat pump or AC unit a low cool runtime and a high cool runtime are independently selectable to exercise The display will change to show the heat pump or AC operating status Default time Fixed 5 min minimum range 5 120 min Checkout HUMIDIFIER OFF ON The humidifier can be exercised On and Off with this menu option Checkout VENTILATOR SPEED OFF LOW e HIGH The ventilator can be exercised through all of its operating speeds with this menu option Checkout ZONING DUCT ASSESSMENT This is the same Duct Assessment that runs on first start up Measures duct capacity for each zone The Duct Assessment will perform an airflow measurement on each zone and determine the relative size of each zone along with damper leakage This assessment will require approximately 1 minute for each zone in the system NOTE A Duct Assessment will automatically occur every 24 hours at 1 00 p m to check system static and calibrate dampers SENSOR DAMPER CHECK The Sensor Damper Check allows the installer to check each zone damper for operation as well as insure the zone sensor corre sponds to that particular zone When first initiated the Zone 1 damper will fully OPEN and all other zones will CLOSE Using the scroll button the installer can select each zone and verify the damper is fully open while all other dampers remain closed After proper damper operation has been verified the installer can now che
11. 25 4 MINUTES ARE REQUIRED ZONE 4 20 TO COMPLETE PROGRESS ES DAMPER LEAKAGE 10 PRESS START TO BEGIN a lt QUIT START gt lt STOP gt lt QUIT START gt Fig 19a Duct Assessment A04085 QUICK START For first time installers Quick Start will allow a quick start up of the Evolution Zone System before learning all the details of system operation However for the best possible comfort and operation refer to the Evolution Zone Control Owner s Manual A Set Day Time 8 Desired Humidity 1 Flip down the door at the base of the Evolution Zone Control and press the BASIC button 2 Adjust the highlighted HOUR setting using the TIME button Press SCROLL button down to highlight MINUTE Adjust the MINUTE setting using the TIME button Press SCROLL button down to highlight DAY Adjust the current DAY setting using the TIME button Press SCROLL button down to highlight HUMIDITY 8 Press the red HEAT button to select heating humidity DAGA ee NA 9 Adjust desired heating humidity level using either button 10 Press the blue COOL button to select cooling humidity 11 Adjust the desired either button cooling humidity level using 12 To exit press BASIC button or close door 13 If changes are made you will be asked to SAVE CHANGES YES NO B Override Heating Schedule 1 Press the red HEAT button Heating mode is confirmed whe
12. ATIONS WITH EQUIPMENT PLEASE WAIT The User Interface will automatically continue by SEARCHING FOR INDOOR EQUIPMENT followed by SEARCHING FOR OUTDOOR EQUIPMENT See Fig 15 Once the indoor and outdoor equipment has been found the Installer will be asked to select Accessories Proceed to Section 4 Selecting Accessories NOTE If the variable speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected before the initial power up sequence can continue If indoor unit is found but outdoor unit is not found OUTDOOR UNIT NOT IDENTIFIED will appear Proceed to the next section for Outdoor Unit Identification B Section 2 Selecting Outdoor Unit OUTDOOR UNIT NOT IDENTIFIED OUTDOOR UNIT OUTDOOR UNIT SELECT TYPE NONE AC HP ENTER HEAT PUMP SIZE 18000 TO 60000 BTU HEAT PUMP ENTER NUMBER OF SPEEDS 1 or 2 PRESS TO MAKE PRESS TO MAKE PRESS TO MAKE SELECTION SELECTION SELECTION CONTINUE gt lt BACK CONTINUE gt lt BACK CONTINUE gt A03196 Fig 16 Selecting Outdoor Unit If there is no communicating outdoor unit the screen shown in Fig 16 will appear Press either Time or Temp buttons to select AC air conditioner HP heat pump or None no unit installed Press right side button to continue to next screen If either AC or HP has been sel
13. D Red 24VAC Hot NOTE It is not mandatory that the above color code be used but each ABCD connection in the system MUST be wired consis tently A separate ABCD Connector comes inside packaging and should be used when connecting to furnace or fan coil Ensure connector is inserted properly into circuit board See Fig 10 Fig 10 4 Wire ABCD Connector CAUTION ELECTRICAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation Improper wiring of the ABCD connector will cause the Evolution Zone System to operate improperly Check to make sure all wiring is correct before proceeding with installation or turning on power 9 Push any excess wire into the wall Seal hole in wall to prevent any air leaks Leaks can affect operation 10 Attach Evolution Zone Control to the mounting plastic by lining up the plastic guides on the back of the control with the opening on the mounting plastic and push on 11 Perform installation of all other system equipment i e zone sensors dampers humidifier ventilator UV lights etc 12 Turn on power to equipment fr N Zone ___y zove E e o lt Fan Button Button lt Display Screen LCD le gt lt Right Side II IA A A Button Time u lt Heat Button Hold Button Cool Button Temperature Button SCROLL sys
14. FORT is a decreased airflow used to improve humidity control EFFI CIENCY is the airflow used to meet specified ratings MAXI MUM is a fixed airflow speed of 400 CFM ton based on the outdoor unit size DEHUM AIRFLOW e NORMAL default HIGH Normal airflow adjustment used during dehumidifying If duct sweating is an issue selecting HIGH will increase the dehumidi fying airflow speed and reduce the sweating HEATER SIZE e choices dependent upon fan coil model This will show the heater size entered during the start up process This value can be changed to another value limited by the model number of the fan coil If the electric heater is self identifying this value is not shown Setup HEAT PUMP AC COOLING LOCKOUT e NONE default 45 F 50 F s 33 F Outside temperature below which cooling will not be provided ENTERED SIZE e dependent on indoor unit model Size of the outdoor unit entered during the start up process If the outdoor unit is a communicating model this value will not be shown This size can be changed here but is limited to sizes that the indoor unit can handle DEFROST INTERVAL 30 minutes 60 minutes 90 minutes e 120 minutes default Time interval at which defrost cycles can occur on a heat pump ELECT HEAT LOCKOUT LOCKOUT TEMP NONE default e 5 to 55 deg F Outside temperature above which the electric heat will not operate In dual fuel application
15. ICIENCY e COMFORT default e MAXIMUM Selects the airflow of the furnace when cooling COMFORT is a decreased airflow used to improve humidity control EFFI CIENCY is the airflow used to meet specified ratings MAXI MUM is a fixed airflow of 400 CFM ton based on the outdoor unit size DEHUM AIRFLOW NORMAL default HIGH NORMAL airflow adjustment is used during dehumidifying If duct sweating is an issue selecting HIGH will increase the dehumidifying airflow and reduce the sweating LOW HEAT RISE ON OFF default Set this to ON if the system contains a bypass humidifier The ON setting will increase the furnace low heat airflow STAGING e SYSTEM default e LOW HIGH Controls the staging of the furnace SYSTEM setting will allow the Evolution Zone Control to determine furnace staging LOW will only run the low stage of furnace heat HIGH will only run the high stage of furnace heat OFF DELAY e 90 seconds e 120 seconds default e 150 seconds e 180 seconds Amount of time the blower will continue to run after heating has shut off LOCKOUT TEMP NONE default e 5 to 55 deg F Appears on dual fuel systems only furnace with heat pump Outside temperature above which the furnace will NOT run Setup FAN COIL HP AC AIRFLOW EFFICIENCY COMFORT default MAXIMUM Selects the airflow of the fan coil when heating or cooling with a heat pump or cooling with an AC unit COM
16. Installation and Start Up Instructions Evolution Zone Control SYSTXBBUIZO1 Evolution Zone Control SYSTXBBUIZ01 A04031 NOTE Read the entire instruction manual before starting the installation This symbol indicates a change since the last issue TABLE OF CONTENTS SAFETY CONSIDERATIONS uuneesssssnennensennennennenne 1 INTRODUCTION INSTALLATION AND START UP OVERVIEW 1 INSTALLATION cocinada 1 INITIAL POWER UE aE 288 E S E N N 5 QUICK STAR Tsun a 7 INSTALL SERVICE MENUS a OPERATIONAL INFORMATION ccoccoccnccnconcnncnninncancnncanonacnnannos 12 TROUBLESHOOTING mept e E 13 SAFETY CONSIDERATIONS Read and follow manufacturer instructions carefully Follow all local electrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installa tion may damage the Evolution Zone System Recognize safety information This is the safety alert symbol A When you see this symbol on the equipment and in the instruction manual be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death pE Cancels New II UIZO1 0 1 03 04 WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe pra
17. Owner s Manual To enter INSTALL SERVICE menus press and hold the ADVANCED button for at least ten seconds The following menu will appear See Fig 20 NOTE The INSTALL SERVICE menu will automatically exit after 60 minutes of no push button activity EQUIPMENT SUMMARY Shows all equipment recognized by and attached to the system INSTALL Used when adding changing out or uninstalling equipment SETUP Used to view or modify equipment settings CHECKOUT Allows testing of equipment operation SERVICE Used to view operation and fault history of equipment and enter dealer name phone number for display EQUIPMENT SUMMARY MENU EQUIPMENT SUMMARY FURNACE 355MAV0420 AC 598BNX024 FILTER EAC HUMIDIFIER YES UV LIGHTS YES ZONES 1234 lt BACK A04108 Fig 21 EQUIPMENT SUMMARY An example screen is shown in Fig 21 This screen shows indoor unit type and model number outdoor unit type and model number if a 2 speed unit filter type any accessories that are installed and how many zones are recognized INSTALL MENU INSTALL TO ADD UNINSTALL OR RE INSTALL EQUIPMENT PRESS RIGHT SIDE BUTTON lt BACK INSTALL gt A03202 Fig 22 INSTALL This menu item will perform start up process in order to learn all equipment in system Press right side button to initiate the process See Fig 22 SETUP MENU This menu has several layers allowing modification of equipment setti
18. before routing control wiring All wiring must comply with national local and state codes EVOLUTION ZONE CONTROL LOCATION The Evolu tion Zone Control User Interface is the command center for the Evolution Zone System and is typically located in Zone 1 to sense and control temperature in this zone It should be located where it is easily accessible and visible to the adult homeowner or end user For accurate temperature measurement the following guidelines should be followed The Evolution Zone Control and Room Sensors should be mounted Approximately 5 feet 1 5 meters from the floor e Close to or in a frequently used room preferably on an inside partitioning wall e Ona section of wall without pipes or ductwork The Evolution Zone Control and Room Sensors should NOT be mounted e Close to a window on an outside wall or next to a door leading to the outside e Exposed to direct light or heat from a lamp sun fireplace or other temperature radiating objects which could cause a false reading e Close to or in direct airflow from supply registers e In areas with poor air circulation such as behind a door or in an alcove REMOTE ROOM SENSOR OPTION A remote room sensor can be used with the Evolution Zone Control to take the place of the User Interface internal temperature sensor This allows the Evolution Zone Control to be mounted in areas with less than optimal airflow such as near an
19. ck and verify that each remote room sensor corresponds to the proper zone damper in the same zone Start from the top and highlight zone 1 to open damper Temporarily disconnect any other zone remote room sensor at sensor location That zone damper will now OPEN while the Zone 1 damper will close EXAMPLE If the Zone 2 remote room sensor is disconnected the Zone 2 damper will now open as indicated on the User Interface display The word FAIL will also be displayed instead of the actual temperature for Zone 2 Reconnect Zone 2 sensor and try all remaining sensors one at a time in the system Smart Sensors may also be checked see Smart Sensor Installation Instructions for procedure AIRFLOW LIMITS e Low Medium High default e Maximum Because there is no bypass damper the Zone Airflow Limit check will allow the installer to assess the airflow noise generated by the system providing the maximum amount of airflow to each zone Select 9 ZONE then select AIRFLOW LIMIT Low Medium High default or Maximum When Start is pressed right side button the selected zone s damper will fully open all others will close and the indoor unit will provide the maximum airflow for that zone as selected in Setup ZONING Airflow Limits If the airflow noise is objectionable the installer can select a lower airflow noise limit If the noise is not objectionable the installer should leave High selected or even Maximum NOTE S
20. ctices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which may result in enhanced installation reliability or operation INTRODUCTION The Evolution Zone System consists of several intelligent com municating components which includes the Evolution Zone Con trol or User Interface Smart Sensors Damper Control Module variable speed furnace or FE fan coil 2 speed AC or HP which continually communicate with each other via a four wire connec tion called the ABCD bus Commands operating conditions and other data are passed continually between components over the ABCD bus The result is a new level of comfort versatility and simplicity All furnaces or fan coils are variable speed and multi stage for maximum flexibility efficiency and comfort They support con trolled ventilation humidification dehumidification and air qual ity control Either a dual capacity communicating or a standard 24 vac controlled outdoor unit may be used When using conventional outdoor units the variable speed furnace or fan coil provides the 24 volt signals needed to control them Also the Evolution Damper Control Module P N SYSTXBB4ZC01 allows connection of a conventional HRV or ERV without the need for a separate wall control All system components are controlled through the wall mounted Evolution Zone Control which replaces the conventional ther mostat and provides th
21. d 1 1 1 1 I 1 is ce ee ga un BD ul ss D a FL O DEP E A B C D A B ol D 9 GO _ Humidifier HUM NAS Connection 9 Damper com Control 2e a module Sensor e Optional Fig 12 Communicating Indoor Unit w 2 Speed Pu ron Communicating Outdoor Unit A04018 Indoor Zone Control Unit User Interface amp Smart Sensor s ________ Green l Yellow A B C D E EA 1 4 4 1 l l White l I i I i lona roto IO ee l 1 1 l l l I AA A B C D A B 0 1 Spd AC Humidifier 4 Ne of Connection Y gt e 24V Damper e Control vive Y module el gt a el OAT Sensor Fig 13 Connection Diagram for Furnace or FE Fan Coil with 1 Speed AC A04019 Zone Control Variable Speed User Interface amp Fan Coil Smart Sensor s Green r 4 A Yellow AlB CID 1022 22 22 L 1 4 4 4 i l White 1 1 non 1 1 A a Be na a Red a ee ilk a ee sess ST D 1 OR L I allele a s c o 2 alee 1 Spd HP Humidifier HUM A roo ie e Y ta a e Damper A ERE Y o Control NR an ci ee On module y ey e gt gt el OAT Sensor Fig 14 Connection Diagram for FE Fan Coil with 1 Speed HP A04020 isolation relay coil to furnace or fan coil HUM and COM term
22. d or manually selected If a wrong selection was made press left side button BACK selection to go back to that particular screen and make changes When everything is OK press right side button again to continue See Fig 19 The SETUP COMPLETE SAVE ALL SELECTIONS screen will appear after Equipment Summary To Save All Selections press YES right side button Pressing the left side button NO selection will return to the Equipment Summary screen where changes can be performed to any of the equipment selection screens After selecting YES the initial power up sequence of the new Evolution Zone Control is complete The User Interface screen will now display normal operating mode G Section 7 Duct Assessment The following screen will appear after Setup is exited Press right side button to start Duct Assessment Duct Assessment will measure the relative size of the ductwork including damper leakage These measurements are used to control the correct amount of airflow in the zoned system Status messages will appear on the screen to indicate what the system is doing The process will take approximately one minute per zone At the end of the process the display will show the relative size of each zone duct See Fig 19a DUCT ASSESSMENT DUCT ASSESSMENT DUCT ASSESSMENT MEASURE DUCT ASSESSMENT ACTIVE CAPACITY FOR EACH PLEASE WAIT ZONE CAPACITY ZONE OPENING ALL ZONES ZONE1 25 AIRFLOW STABILIZING ZONE 2 20 ZONE 3
23. default 3 This adjusts sensitivity to zone temperature changes 1 most sensitive 9 least sensitive PROGRAMMING e On or Off default On e Periods Per Day 2 or 4 default 4 e Programmable Fan On Off default Off If ON is selected fan can be set to Auto Low Med or High independently in each zone SMART RECOVERY e On or Off default On Applies to programmable operation only Will start recovery 90 minutes prior to schedule change in both heating and cooling mode ENGLISH METRIC DISPLAY F or C default F RESET FACTORY DEFAULTS Program Schedule e Yes No to reset back to Energy Star default Time and Temp schedules User Settings e Yes No to reset the user settings in the Advanced Setup to factory default settings Install Settings e Yes No to reset install settings in Install Service menus to factory default settings Last 10 Faults Yes No to reset last 10 faults under Service Info menu Setup FURNACE Upon a first time start up of the Evolution Zone Control the furnace DIP switch settings will be copied to the furnace setup menu Any changes can then be made from the Evolution Zone Contro AIRFLOW e COMFORT default EFFICIENCY Selects the airflow of the furnace when heating EFFICIENCY is the airflow used to meet specified ratings COMFORT is a decreased airflow used to increase the output air temperature and provide increased comfort AC AIRFLOW EFF
24. e exercised The furnace will execute its ignition start up sequence This sequence will be displayed on the Evolution Zone Control screen After the gas valve and blower motor turn on the screen will automatically change to FURNACE CHECK and show the current operating status of the furnace Checkout FAN COIL ELECTRIC HEAT CHECK ELECTRIC HEAT RUNTIME 5 min Default time 5 min Range 0 120 min If you have a fan coil with electric heaters this menu item will allow the heaters to be exercised 10 With self identifying electric heaters three stages of electric heat are available to be exercised in any combination Non identifying heaters will only provide one stage of heat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout HEAT PUMP HEATING HIGH HEAT RUNTIME 5 min e LOW HEAT RUNTIME 5 min DEFROST NO The heat pump heating mode can be exercised with this menu option With a 2 speed heat pump a low heat runtime and a high heat runtime are independently selectable to exercise A defrost cycle is also selectable Default time Fixed 5 min minimum range 5 120 min Checkout HEAT PUMP COOLING OR AC COOLING HIGH COOL RUNTIME 5 min LOW COOL RUNTIME 5 min The heat pump cooling mode or AC cooling mode can be exercised with this menu option With a
25. e homeowner with a single wall control for all features of the system INSTALLATION AND START UP OVERVIEW This instruction covers installation of the Evolution Zone Control only Physical installation instructions for the indoor and outdoor equipment Damper Control Module and accessories are provided with each unit Setup commissioning operation and troubleshooting of the Evolution Zone System is covered only in this installation instruc tion It is the guide to connecting the system components and commissioning the system once all physical components are installed Special screen prompts and start up capabilities are provided in the Evolution System to simplify and automate the initial commissioning of the system Install Evolution Zone Control according to this instruction Install indoor unit outdoor unit and accessories according to their instructions e Wire complete system according to this instruction e Setup commission and operate system according to this instruction to assure a smooth and trouble free start up INSTALLATION A Step 1 Check Equipment and Job Site INSPECT EQUIPMENT File claim with shipping company prior to installation if shipment is damaged or incomplete B Step 2 Evolution Zone Control Location and Wiring Considerations WARNING ELECTRICAL SHOCK HAZARD A Failure to follow this warning could result in personal injury or possible equipment damage Disconnect Power
26. ected as the outdoor unit type the middle screen will appear See Fig 16 Press either Time or Temp buttons to select appropriate Btu size of outdoor unit then press right side button to continue If a NIM Network Interface Module is applied for non communicating two speed outdoor equipment select 1 or 2 speed compressor operation and press right side button to continue NOTE Range of outdoor unit Btu selection is limited by model number of indoor unit installed The Evolution Zone Control will not allow an outdoor unit size that is not supported by the installed indoor unit NOTE On new system installations the model and serial number will be recognized and displayed On any indoor outdoor board replacements the equipment will be recognized but the exact model serial number will not be displayed C Section 3 Selecting Electric Heater ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 Kw KW NONE 5 10 15 KW PRESS TO MAKE SELECTION lt BACK CONTINUE gt A03197 Fig 17 Selecting Electric Heater If indoor unit is a fan coil and the electric heater is not self identifying ELECTRIC HEATER NOT IDENTIFIED will appear See Fig 17 Press either Time or Temp buttons to select appropriate size of electric heater installed then press right side button to continue NOTE Range of electric heaters available is limited by model number of the fan coil installed The Evolution Zone Control w
27. electing a lower airflow noise limit may decrease the homeowner s comfort in that zone SERVICE MENUS The Service Info menu will only show the equipment installed in the system Below is a sample using a furnace and a heat pump dual fuel A sample service menu is shown in Fig 25 SERVICE INFO FURNACE STATUS HEAT PUMP STATUS ZONING STATUS LAST 10 SYSTEM FAULTS RUN FAULT HISTORY TODAY S DATE MODEL SERIAL NUMBER SERVICE PHONE NUMBER lt BACK SELECT gt A04092 Fig 25 SERVICE INFO MENUS Service FURNACE STATUS The Status screens will show all of the current operating param eters of each installed piece of equipment HEAT STAGE OFF LOW HIGH Displays stage of heat that the furnace is currently delivering AIRFLOW CFM e furnace model dependent Cubic Feet per Minute of air the blower is currently delivering LEAVING AIR TEMP This sensor is NOT required However if LAT sensor is connected to the Damper Control Module the sensor will read leaving air temperature of the furnace COIL TEMP This sensor is NOT required However if HPT sensor is connected to the Damper Control Module the sensor will read temperature at that location i e if placed in return air will read return air temperature INDUCER RPM 90 furnaces only Inducer motor RPM value BLOWER RPM Blower motor RPM value STATIC PRESS e Inches of water Displays static pressure that the furnace is curre
28. en the error code is cleared or disappears furnace heating will resume TWO SPEED OUTDOOR UNIT Code 85 VC voltage at standby Code 86 High capacity compressor lockout USER INTERFACE Temp Sensor Failed NO SENSOR DATA shown in place of actual temp Outdoor Unit communication fault Network Interface Module NIM communication fault Defrost Error defrost signal on for more than 15 minutes The user can press the right side button to dismiss the notice The regular run mode screen will then appear except SYSTEM MALFUNCTION will appear in place of the day time If the error has not disappeared within 24 hours the above display will return If the error code disappears SYSTEM MALFUNCTION will disappear and the day time will reappear 14 15 O 2004 Bryant Heating 8 Cooling Systems 7310 W Morris St Indianapolis IN 46231 16 Printed in U S A iiuizO1 0 1 Catalog No 809 60024
29. ill not allow an electric heater size that is not supported by the installed fan coil D Section 4 Selecting Accessories Once the indoor and outdoor equipment have been found or entered the following screens will appear allowing the Installer to select the AIR FILTER TYPE HUMIDIFIER INSTALLED and UV LIGHTS INSTALLED See Fig 18 Use either Time or Temp buttons to make appropriate selections in the highlighted area on the display screen Press right side button to continue or advance to the next screen AIR FILTER TYPE This accessory screen will appear first The installer will need to enter the type of filter MEDIA EAC or both See Table 1 and make a selection using Time or Temp button then press right side button to continue Table 1 Filter Selection INSTALLED FILTER MENU SELECTION 1 Inch to 4 inch media MEDIA High voltage EAC EAC High voltage EAC 1 to 4 inch media MEDIA EAC HUMIDIFIER INSTALLED This will appear after the Air Filter Type screen Select whether a humidifier is installed on the system YES or NO then press right side button to continue UV LIGHTS INSTALLED This screen will appear to select ACCESSORIES ACCESSORIES HUMIDIFIER INSTALLED YES ACCESSORIES U V LIGHTS INSTALLED YES AIR FILTER TYPE EAC MEDIA MEDIA EAC PRESS TO MAKE PRESS TO MAKE PRESS TO MAKE SELECTION SELECTION SELECTION CONTINUE gt
30. inals will allow the Evolution Zone Control to automatically energize the HUM output during a call for humidification The N O relay contacts will be used to energize the humidifier See fan powered humidifier installation instructions for more details BE WARNING FIRE OR EQUIPMENT HAZARD Failure to follow this warning could result in equipment damage or fire Do not apply 24vac fan powered humidifier with internal power supply direct to indoor unit HUM and COM terminals INITIAL POWER UP NOTE Refer to Functional Overview Fig 11 to become familiar with key function buttons such as System On Off Zone Fan Left Side and Right Side buttons etc These function buttons will be used frequently during setup A Section 1 Power Up Sequence INDOOR UNIT SEARCHING FOR INDOOR EQUIPMENT OUTDOOR UNIT SEARCHING FOR OUTDOOR EQUIPMENT ESTABLISHING COMMUNICATIONS WITH EQUIPMENT PLEASE WAIT WORKING WORKING SOFTWARE VERSION Fig 15 Power Up Sequence This section addresses initial power up or commissioning of a new Evolution Zone Control The User Interface will commu nicate and identify all Evolution components in the system The following is a typical example for a communicating Variable Speed Furnace Fan Coil with a 2 spd Air Conditioner Heat Pump including Dual Fuel The User Interface display will light up and indicate that it is now ESTABLISHING COMMUNIC
31. iring diagram Fig 14 for connecting an FE fan coil with a 1 speed heat pump non communicating outdoor unit When OAT is applied the Evolution system will provide enhanced system features and benefits NOTE For other applications not listed refer to the Network Interface Module NIM Installation Instructions HUMIDIFIER CONNECTION A 24vac bypass or fan powered humidifier may be installed NOTE Do Not Use a traditional humidistat to control humidifier operation If a humidifier is installed let the Evolution Zone Control operate humidifier Bypass Humidifiers A bypass humidifier should be wired directly to the furnace or fan coil HUM and 24vac COM terminals The Evolution Zone Control will automatically energize the HUM output during a call for humidification Fan Powered Humidifiers Most fan powered humidifiers produce internal 24vac in order to energize upon a switch or contact closure For this application a 24vac N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer Applying 24vac Indoor Zone Control Unit 2 Spd AC or HP User Interface amp Smart Sensor s e Green lb A l Yellow A B C D iii B B 4 1 4 1 l l White 1 1 1 1 1 Lo 1 CI Cc l I l l l l l 1 bode 1 ot Re
32. lternately flash at a 1 second rate This appears when system cannot deliver any conditioning at all FAN COIL Code 16 Communication Fault PEE o EEE OUTSIDE 942 FAN AUTO ALERT HVAC SERVICE 1 800 555 1212 CRITICAL MALFUNCTION CALL TECHNICIAN Fig 26 Critical Malfunction Screen A04027 Code 44 Blower Communication Fault Code 41 Blower Motor Fault FURNACE Code 15 Blower Motor Lockout Code 22 Abnormal Flame Proving Signal not dual fuel Code 41 Blower Motor Fault USER INTERFACE No communication with indoor unit SYSTEM MALFUNCTION SCREEN This screen appears when system cannot completely deliver conditioning The following errors will cause a System Malfunc tion Screen to pop up OUTSIDE 94 FAN AUTO 1 HVAC SERVICE 1 800 555 1212 SYSTEM MALFUNCTION CALL TECHNICIAN DISMISS NOTICE gt Fig 27 System Malfunction Screen A04028 FAN COIL Code 37 Heater output sensed ON when not energized FURNACE Code 13 Limit Circuit Lockout Code 14 Ignition Lockout Code 21 Gas Heating Lockout Code 22 Abnormal Flame Proving Signal dual fuel only Code 23 Pressure Switch Did Not Open Code 24 Secondary Voltage Fuse Open Code 33 Limit Circuit Fault AND High Heat Only is active Code 45 Control Circuitry Lockout NOTE For all the above furnace error codes the system will use heat pump heating exclusively if available Wh
33. n it will remain on for a minimum of three minutes If the set point is changed this timer is automatically cancelled allowing the equipment to turn off imme diately when the demand is removed Heat Cool Set points Desired Temperatures A minimum difference of 2 default is enforced between heating and cooling desired temperatures This is done by allowing one setting to push the other to maintain this difference This difference is adjustable via the Install Service menu under Ther mostat Setup Auto Changeover When Auto mode is enabled factory default a change from heat to cool or vice versa will not occur until an opposite mode demand has existed for 30 minutes If the set point is changed the 30 minute requirement is defeated This Auto Changeover time is adjustable via the Install Service menu under Thermostat Setup Range 5 120 min Smart Recovery With Smart Recovery selected factory default transition out of setback begins 1 5 hours before selected recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time It operates in both heating and cooling This only applies to programmable operation Media Filter If MEDIA or MEDIA EAC is installed in the indoor unit the system will perform a static pressure check of the system every 24 hours at 1 00PM to monitor filter accumulation TrueSense Dirty Filter Detection or whenever power is applied to the
34. n the red LED next to the red HEAT button is lit 2 Use the TEMP button to select your desired heating temperature 3 The default time for temporarily overriding the temperature schedule is 2 00 HRS as indicated by the text on the lower left NOTE Override time will not appear if programming has been turned off 4 You can change the temporary override time in 15 minute increments by pressing the TIME button until the desired override time is selected or press the HOLD button anytime to override the schedule indefinitely C Override Cooling Schedule 1 Press the blue COOL button Cooling mode is confirmed when the blue LED next to the COOL button is lit 2 Use the TEMP button to select your desired cooling temperature 3 The default time for temporarily overriding the temperature schedule is 2 00 HRS as indicated by the text on the lower left NOTE Override time will not appear if programming has been turned off 4 You can change the temporary override time in 15 minute increments by pressing the TIME button until the desired override time is selected or press the HOLD button anytime to override the schedule indefinitely PER ae D Quick Program Schedule for All Days This section will give you a quick program schedule for ALL DAYS of the week For more information on how to create customized schedules for every day the entire week or weekend refer to the Owner s Manual 1 Fli
35. ngs No settings will need to be made at equipment i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 23 shows all the information that can be found in the SETUP menu SETUP THERMOSTAT FURNACE HEAT PUMP ZONING ACCESSORIES SYSTEM MAINTENANCE lt BACK SELECT gt A04089 Fig 23 SETUP MENU Setup THERMOSTAT AUTO MODE SETUP Enable Disable Auto Changeover mode default Enable e Auto Changeover Time may be adjusted 5 to 120 minutes default 30 minutes When Auto mode is enabled factory default a change from heat to cool or vice versa will not occur until an opposite mode demand has existed for 30 minutes If the set point is changed the 30 minute timer is deleted HEAT COOL DEADBAND 0 to 6 degrees default 2 A minimum difference of 2 is enforced between heating and cooling desired temperatures This will allow one setting to push the other to maintain this difference eg OFFSETS This option allows calibration or deliberate miscali bration of the temperature and humidity sensors These offsets are added to the actual temperature humidity values defaults 0 e Zone 1 Offset 5 to 5 degrees e Outside Temp Offset 5 to 5 degrees e Humidity Offset 10 to 10 percent CYCLES PER HOUR Maximum cycles per hour 4 default or 6 e Anticipator 1 to 9
36. ntly experiencing LOCKOUT TIMER Seconds If a lockout timer is active this will show the current time value See furnace manual for details on lockout timers Service FAN COIL STATUS ELECTRIC HEAT OFF LOW MED HIGH Displays stages of electric heat that the fan coil is currently delivering AIRFLOW CFM e fan coil model number dependent Cubic Feet per Minute of air the blower is currently delivering LEAVING AIR TEMP This sensor is NOT required However if LAT sensor is connected to the Damper Control Module the sensor will read leaving air temperature of the fan coil COIL TEMP This sensor is NOT required However if HPT sensor is connected to the Damper Control Module the sensor will read temperature at that location i e if placed down stream from evaporator coil and before electric heat will read coil leaving air temperature BLOWER RPM Blower motor RPM value STATIC PRESS Inches of water Displays static pressure that the fan coil is currently experiencing Service HEAT PUMP AC STATUS STAGE HEAT COOL OFF LOW HIGH Displays stage of heating or cooling that the Heat Pump AC is delivering DEFROST NO YES Displays status of defrost mode if heat pump AIRFLOW CFM Indoor unit CFM measurement LEAVING AIR TEMP This sensor is NOT required However if LAT sensor is connected to the Damper Control Module sensor will read leaving air temperature of the indo
37. on in heating cooling and how long the unit has been powered Service TODAY S DATE This menu item allows the installer to enter the current date It is used for time date stamping of system faults This should be entered every time prior to viewing LAST 10 SYSTEM FAULTS section Service MODEL SERIAL NUMBERS e This menu item allows the installer to view the model number and serial number if available of all communicating pieces of equipment in the system Service SERVICE PHONE NUMBER This menu item allows the installer to enter a name and phone number that the homeowner can call for future service of the system This name and phone number will appear to the home owner whenever a service reminder pop up message is displayed i e Change Filter etc To edit e Use Temp button to move cursor left and right Use Time button to select numbers and letters e Use Scroll button to move up and down between NAME and NUMBER OPERATIONAL INFORMATION Zone Selection Press top left ZONE button to select zones Continuous Fan Operation Pressing FAN button will scroll through the following e AUTO No fan operation except during equipment operation LOW Approximately 50 of High Speed operation MED Half way between High and Low speed operation HIGH Highest of either High Heating or High Cooling CFM Five Minute Compressor Timeguard This timer prevents compressor from starting unle
38. or unit COIL TEMP outdoor unit Degrees F Temperature of the outdoor unit coil only available on 2 speed communicating outdoor units BLOWER RPM RPM feedback from indoor motor STATIC PRESS Static pressure of indoor unit Service ZONING STATUS ZONE STATUS This screen will show each zone in the system with the corre sponding damper position POS and CFM being delivered to each zone Damper position range from 0 to 15 O closed 15 open Service LAST 10 SYSTEM FAULTS This screen will show last 10 faults that occurred throughout the system Each fault has the time and date incident recorded Service technician should enter current date in TODAY S DATE menu section BEFORE checking and logging the last 10 system faults Each fault has a two letter acronym preceding the fault name to identify which piece of equipment generated the fault This fault history can be cleared under Thermostat Setup Reset Factory Defaults HP heat pump e AC air conditioner FN furnace FC fan coil e ZO zoning Service RUN FAULT HISTORY The indoor unit and outdoor unit if communicating have the following histories NOTE For Critical Fault Screens see Troubleshooting section in this document Resettable Faults e Fault counters for each piece of equipment that can be reset Cycle Counters Number of heat cool power cycles the unit has performed Run Times e Lifetime hours of operati
39. p down the door at the bottom of the control 2 Press the SCHEDULE button which allows you to create one schedule for the entire home 3 Press either the LEFT or RIGHT side button repeatedly if necessary until ALLDAYS is displayed The WAKE time period will be highlighted 4 Using the TIME button set the start time for this time period 5 Press the red HEAT button Heating temperature will begin flashing 6 Set the heating temperature using the TEMP button 7 Press the blue COOL button Cooling temperature will begin flashing 8 Set the cooling temperature using the TEMP button 9 Set the remaining periods by using the SCROLL button to select DAY EVENING and SLEEP 10 To copy a zone use SCROLL button to select COPY Select YES and copy this zone schedule to other zones using NO or YES 11 Exit the scheduling mode by either closing the door or pressing the SCHEDULE button 12 If changes are made you will be asked to SAVE CHANGES YES NO INSTALL SERVICE MENUS INSTALL SERVICE EQUIPMENT SUMMARY INSTALL SETUP CHECKOUT SERVICE SOFTWARE VERSION 1 SELECT gt lt EXIT A03200 Fig 20 INSTALL SERVICE MENUS The INSTALL SERVICE menus contain a set of vital information This information enables the Installer or Service person to view a summary of what has been installed etc This information is notcovered in the
40. s heat pump will not operate below selected temperature HIGH COOL LATCH NONE default e 80 110 deg F Outside temperature above which only the high speed of a 2 speed outdoor unit will run when cooling Setup ZONING DISABLE ZONING No default e Yes If Yes is selected zoning is disabled and all dampers open The system will run unzoned using the Zone 1 sensor ZONE OFFSETS Zone Temperature Offsets defaults 0 Range 5 to 5 This option allows actual temperature offset for each zone allowing calibration or deliberate mis calibration of each sensor AIRFLOW LIMITS e Low Medium High default Maximum Zone airflow limit which is selectable for each zone Low Medium and High allows a relative noise airflow relationship in a zone i e comfort vs noise Maximum allows unlimited noise airflow i e maximum airflow allowed Setup ACCESSORIES FILTER TYPE MEDIA i e TrueSense e EAC e MEDIA EAC i e TrueSense CLEAN INTERVAL 30 to 180 days of actual blower operation Default 90 Interval at which the Clean Filter notification will turn on Applies to EAC filter selection only HUMIDIFIER INSTALLED NO YES If YES indicates to the system whether a humidifier is installed and enables humidification functions CHANGE PAD INTERVAL 1 to 24 months of humidifier operation default 6 months Interval at which the Change Humidify Pad notification will
41. ss it has been off for at least 5 minutes It can be defeated by simultaneously pressing the Fan and Temp buttons Emergency Heat for heat pump applications To activate Emergency Heat you must press and hold the HEAT button for 3 seconds to activate Keypad Lockout Keypad can be locked by pressing Fan and Zone buttons at the same time for 3 seconds When keys are locked a lock symbol will appear in the upper left corner of screen Follow same procedure to unlock keypad Heat and Cool LED The Heat and Cool LEDs will pulsate during actual equipment operation Equipment Cycle Timer adjustable 4 6 cycles per hour This timer prevents the start of a heating or cooling cycle until 15 or 10 minutes after the last start of the same cycle Its function is to assure that the equipment is not cycled more than the selected times per hour This timer is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan and Temp buttons Ten Minute Staging Timer In multistage heating or cooling this timer prevents any higher stage from turning on until the preceding stage has been on for 10 minutes This timer is defeated if temperature error is greater than 5 F usually due to a large change in desired temperature Three Minute Minimum On Time In normal operation when a stage turns o
42. tem SCHEDULE VACATION Schedule amp Vacation pre On Off Button Program Buttons O O O O I lt Basic amp Advanced PROGRAM Berges Setup Buttons Up Down q Scroll Buttons 2 O O Schedule Vacation 2 Basic Advanced A to program to start end to set time for all other lt Flip Down temperature vacation humidity settings schedule I Door e Scroll up amp down A04038 Fig 11 Functional Overview EQUIPMENT WIRING DIAGRAMS See wiring diagrams Fig 12 13 and 14 for connecting the Evolution Zone Control and Smart Sensors to the Damper Control Module More information regarding Damper Control set up and wiring can be found in Damper Control Module Installation Instructions See wiring diagram Fig 12 which includes a variable speed indoor communicating furnace or FE fan coil with a 2 speed Puron communicating outdoor unit No additional OAT outdoor air temperature sensor is required because the Evolution Zone Control will use the temperature sensor inside the 2 speed unit See wiring diagram Fig 13 for connecting a variable speed indoor communicating furnace or FE fan coil with a 1 speed air condi tioning unit non communicating outdoor An Outdoor Air Tem perature OAT sensor may be installed but is not required at the indoor furnace or fan coil OAT terminals When OAT sensor is applied the Evolution System will provide enhanced system features and benefits See w
Download Pdf Manuals
Related Search
Related Contents
IMPACT User Manual - EcoMetrix Incorporated 1762-UM002 - Rockwell Automation MGC900GB(PDF/775K) MODE D`EMPLOI USER MANUAL Kindle Paperwhite-Benutzerhandbuch 2. Ausgabe 1&1 WebHosting En raison de son poids et afin de faciliter son téléchargement, le TR 92E - TR 111E M09 - action commercialeTER-TSC Copyright © All rights reserved.
Failed to retrieve file