Home

ESOL 1-3KVA Manual test

image

Contents

1. Fault Mode When the UPS has fault The warning red LED is on and the buzzer beeps The UPS will turn to fault mode The UPS cuts off the output and the LCD display fault codes At the moment you can press the mute key to make the buzzer stop beeping temporarily to wait for maintenance You can also press the OFF key to shut down the UPS when confirm that there is no serious fault NOTE As for corresponding information of the fault code please refer to Table 23 Fault Code Standby Mode When UPS is plugged into line and not turn on the UPS will work in standby mode to charge the battery No indicator displays on this mode 45 UPS Turn on and Turn off Start up operation Turn on the UPS in line mode 1 Once mains power is plugged in the UPS will charge the battery at the moment the LCD shows that the output voltage is 0 which means the UPS has no output If it is expected to have the output of bypass you can set the bps ON by LCD setting menu Press and hold the ON key for more than half a second to start the UPS then it will start the inverter Once started the UPS will perform a self test function LED will light and go out circularly and orderly When the self test finishes it will come to line mode the corresponding LED lights the UPS is working in line mode Turn on the UPS by DC without mains power 1 When mains power is disconnected press and hold the ON key
2. To set the minus range in the same way After the minus range is confirmed Long press function setting key gt for more than 2 seconds to exit setting menu Bypass function setting 2 Enter the setting interface Press and_hold the function setting key for more than 2 seconds then come to setting interface short press the scroll key for more than half a second less than 2 seconds to select BPS setting the letters bPS will flash Enter the BPS setting interface Press and hold the function setting key for more than half a second less than 2 seconds at this time the letters bPS will stop flashing The ON or OFF below the bPS will flash Press and hold the scroll key for more than half a second less than 2 seconds to 38 determine whether the BPS function is enabled or disabled Confirm the BPS selecting interface After selecting ON or OFF press and hold the function setting key for more than half a second less than 2 seconds Now the BPS setting function is completed and the ON or OFF below the bPS will light without flashing If you choose OFF then go to step 7 otherwise go ahead to step 5 Set the BPS tolerance range Short press the scroll key or for more than half a second shorter than 2 seconds to select the voltage range in percentage 5 10 15 25 default is 25 then short_ press fun
3. 100 5 130 5 Load transfers to Fault mode after 20 minutes 130 5 150 5 Load transfers to Fault mode after Output Overload 2 minutes Bypass Mode 150 5 200 5 Load transfers to Fault mode after 15 seconds gt 200 5 Load transfers to Fault mode after 140 ms 108 5 150 5 Load transfers to Fault mode after 30 seconds E 150 5 200 5 Load transfers to Fault mode after 300 ms gt 200 5 Load transfers to Fault mode after 20 ms Voltage Waveform Sine wave Harmonic Distortion lt 3 THD on linear load lt 5 THD on non linear load Transfer Time Online mode 0 ms no break High Efficiency mode 10ms maximum due to loss of utility Power Factor 0 9 Load Crest Factor 3to1 67 Table 18 Electrical Output Connections All Models Model Output Connections Output Cables 1K RT IEC C13 10A 6 1EC320 C14 10A 2K RT IEC C13 10A 8 1EC320 C14 10A 3K RT IEC C13 10A 8 1EC320 C14 10A y IEC C19 16A 1 1EC320 C20 10A 1K Tower IEC C13 10A 3 1EC320 C14 10A 2K Tower IEC C13 10A 8 1EC320 C14 10A 3K Tower IEC C13 10A 8 1EC320 C14 10A IEC C19 16A 1 1EC320 C20 10A Table 19 Environmental and Safety All Models 208 230 240 Vac Models EN 61000 2 2 EN 61000 4 2 Level 4 Surge Suppression EN 61000 4 3 Level 3 EN 61000 4 4 Level 4 also on signal ports EN 6100 4 5 Level 4 Criteria
4. Table 5 Parameters inquiring Item Description Graphic Output Display the output voltage and output frequency of the UPS As the following graphic shown the output voltage is 230v amp the output frequency is 50Hz Load Display the numerical value of the active power WATT and apparent power VA of the load For example as the following graphics shown the WATT of the load is 100w VA is 100VA when disconnect load it is a normal phenomenon to show a small numerical value of WATT and VA Temperature Display the temperature of the inverter in the UPS As the following graphics shown the temperature of the inverter is 37 C 35 Input Display the voltage and frequency of the input As the following graphics shown the input voltage is 210v input frequency is 49 8Hz Battery Display the voltage and capacity of the battery As the following graphics shown the battery voltage is 38v the capacity of battery is 100 the capacity of battery is approximately reckoned according to the battery voltage Battery remaining time Display the battery remaining time when under battery mode The number is from 0 to 999 minutes As the following graphics shown there are 686 minutes left for discharging 36 User Settings The UPS has setting functions This user settings can be done under any kind of UPS working mode The setting will ta
5. 25 25 by default 20 30 45 45 by default 65 Table 15 Electrical Input All Models Model Default Input Selectable Input Voltage Range at Voltage Current Voltages 100 Load 230V 200 208 220 230 2 1K AAA 240 200 290 Vac 230V 200 208 220 230 du 2K 37A 240 200 290 Vac 230V 200 208 220 230 rae 3K 13 0A 240 200 290 Vac If rated input voltage selected is 200V the low limit is 180V If rated input voltage selected is 208V the low limit is 190V Under other condition the low limit is 200V The above mentioned voltage is the input voltage window for the UPS with 0 9PF On the contrary the input voltage window can be varied from 110Vac to 290Vac depending on the load percentage of connected equipment Table 16 Electrical Input Connections All Models Model Input Connection Input Cable 1K IEC320 C13 10A 1EC320 C14 10A 2K IEC320 C20 16A 1EC320 C19 16A 3K IEC320 C20 16A 1EC320 C19 16A Table 17 Electrical Output All Models High Voltage Models 200 208 220 230 240V Nominal Outputs voltage configurable or auto sensing 66 1000 2000 3000 VA 0 9 1 8 2 7 kW Frequency 50 or 60 Hz autosensing 108 5 150 5 Load transfers to Fault mode after 30 seconds Output Overload Normal Mode 150 5 200 5 Load transfers to Fault mode after 300 ms gt 200 5 Load transfers to Fault mode after 20 ms
6. Installing Communication Options and Control Terminals To install the communication options and control terminals 1 Install the appropriate connectivity card and or necessary cable s and connect the cables to the appropriate location 2 Route and tie the cable s out of the way 3 Continueto Operation on page 26 28 to start up the UPS Communication Options The UPS has serial communication capabilities through the USB and RS 232 communication ports or through a connectivity card in the available communication bay The UPS supports two serial communication devices according to the following table Independent o Multiplexed 4 Communication Bay USB RS 232 Any connectivity card Available Not in use Any connectivity card Not in use Available O NOTE The communication speed of the RS232 port is fixed at 2400 bps RS 232 and USB Communication Ports To establish communication between the UPS and a computer connect your computer to one of the UPS communication ports using an appropriate communication cable not supplied See Figure 20 21 for the communication port locations When the communication cable is installed power management software can exchange data with the UPS The software polls the UPS for detailed information on the status of 50 the power environment If a power emergency occurs the software initiates the saving of all data and an orderly shutdown of the equipment The cable pins f
7. Figure 20 21 on page 49 for EPO location Figure 24 shows a schematic of the EPO connector contacts Figure 24 EPO Connections You can set the EPO polarity See the EPO Input Polarity setting in User Settings on page 37 NOTE Depending on user configuration the pins must be shorted O or opened to keep the UPS running To restart the UPS reconnect re open the EPO connector pins and turn on the UPS manually Maximum resistance in the shorted loop is 10 ohm NOTE Always test the EPO function before applying your critical load to avoid accidental load loss Load Segments Load segments are sets of receptacles that can be controlled by power management software or through the display providing an orderly shutdown and startup of your equipment For example 54 during a power outage you can keep critical equipment running while you turn off other equipment This feature allows you to save battery power Each UPS has two load segments e Load Segment 1 The power shedding battery voltage of this segment can be set by LCD e Load Segment 2 See Rear Covers on page 71 for load segments for each UPS model wm Max104 SEGMENT1 Max10A O SEGMENT2 O O Figure 25 Load Segments 55 UPSilon2000 Power Management Software 9 Each UPS ships with UPSilon2000 Power Management Software To begin installing UPSilon2000 software see the instructions accompanying the So
8. Not applicable 4 30A 250 Vdc fuses per EBP Se Sealed maintenance free valve regulated lead acid with minimum 3 year yp float service life at 25 C 77 F Monitoring Advanced monitoring for earlier failure detection and warning Recharge Time Internal batteries 3 hours 1 EBP 9 hours 2 EBPs 15 hours 3 EBPs 21 hours to 90 4 EBPs 27 hours Battery Port External six pole Anderson connector on UPS for connection to EBP 70 Rear Covers SEGMENT 1 SEGMENT 2 Figure 30 SEGMENT SEGMENT 2 Figure 31 SEGMENT SEGMENT 2 Figure 32 71 SEGMENT 1 SEGMENT 2 Figure 34 2KVA Tower 72 HESHBSESE DODECI SEGMENT 1 SEGMENT 2 Figure 35 3KVA Tower 8 Troubleshooting The following messages are the information that users would find on UPS when it meets some problems Users can judge if the fault is caused by external factors and know how to deal with it by making full use of the information Fault indicator on indicates that the UPS has detected some faults Buzzer beeps indicates that UPS need to be paid attention to if beeps for a long time it means that there is something wrong with the machine If you need help contact our service department the following messages should be provided for analysis UPS MODEL NO and SERIAL NO Date of fault happened Detailed description of the problem include indicator statements on cover he following table describes typical a
9. flat stable surface with the front of the cabinet facing to you 9 Align the mounting brackets with the screw holes on each side of the UPS and fix with the supplied M4x8 flat head screws see Figure 6 AA Mounting gt Bracket M4X8 Flat Head Screws 2places Figure6 Installing the Mounting Brackets 13 10 If installing optional cabinets repeat Step 8 and 9 for each cabinet 11 Slide the UPS and any other optional cabinets into the rack 12 Secure the front of the UPS to the rack using one M5x12 pan head screws and one M5 cage nuts on each side see Figure 7 Install the bottom screw on each side through the bottom hole of mounting bracket and the bottom hole of the rail Repeat for any optional cabinets M5 Float N hy uns M5X12 Pon Head Screws 2places Figure7 Securing the Front of the Cabinet 13 Continue to the following section Rackmount Wiring Installation Rackmount Wiring Installation This section explains e Installing the UPS including connecting the UPS internal batteries Connecting any Optional EBP S 14 Installing the UPS NOTE Do not make unauthorized changes to the ups otherwise damage may occur to your equipment and void your warranty ED NOTE Do not connect the ups power cord to utility until after installation is completed To install the UPS 1 Remove the front cover of each UPS Press the cover side with LCD display hold the other side and quickly
10. knockout on the top and bottom of the EBP front cover See Figure 13 for the location of the EBP cable knockouts 18 CAUTION A small amount of arcing may occur when connecting an EBP to the UPS This is normal and will not harm personnel Insert the EBP cable into the UPS battery connector quickly and firmly 5 Plug the EBP cable s into the battery connector s as shown in Figure 13 Up to four EBPS may be connected to the UPS Connect black to black Press the connector tightly together to ensure a proper connection To connect a second EBP unclip the EBP connector on the first EBP and pull gently to extend the wiring to the EBP connector on the second EBP Repeat for any additional EBPS 6 Verify that the EBP connections are tight and the adequate bend radius and strain relief exist for each cable A Figure13 Typical EBP Installation 7 Replace the EBP front cover To replace the cover verify that the EBP cables are routed through the EBP cover knockouts cover connects with the cover hook near the left side of the EBP cabinet Repeat for each additional EBP 19 It is the same with the installation of the front cover Refer to UPS installation 8 Verify that all wires connected between the UPS and EBP s are installed behind the front covers and not accessible to users 9 Return to Step 4 to continue the UPS installation Rackmount converted to Tower Installation 1 Rackmount converted to Tower pla
11. 18 TOWER Control Cover 28 Table 1 Indicator Descriptions Indicator Description A On The UPS has an active alarm or fault Red S On The UPS is in Bypass mode 1 The UPS is operating normally on bypass Nene during High Efficiency operation dl On The UPS is in Battery mode Yellow MN Green On The UPS is operating normally NOTE When power on or startup these indicators will turn on and off sequentially NOTE On different operation modes these indicators will indicate differently Refer to Table 7 Table 2 Button function Button Function description Start up combination TOWER Press and hold this key for more than half a second to turn on the UPS RT Press and hold this key for more than half a second to turn on the UPS or to turn off the UPS TOWER Press and hold this key for more than half a Shutdown Rotating second to turn off the UPS combination RT Press and hold this key for more than 2 seconds 29 Hd to circumrotate the LCD Press and hold the key for more than 1 second in Line Battery test Mute mode or economic ECO mode UPS runs self test combination IAH function Press and hold the key for more than 1 second in battery mode UPS runs mute function Scroll or Non function setting mode Press and hold the key for more than half a second less than 2 seconds Indicate the items of the LCD item section orde
12. A EMC CE per IEC EN 62040 2 Certifications Class B 68 Class B EMC Lado 7 Emissions IEC 62040 2 ed2 2005 EN 62040 2 2006 Safety re gt Carte ance IEC 62040 1 1 IEC 60950 1 Agency Markings CECS 0 C to 40 C 32 F to 104 F in Online mode with linear Operating derating for altitude Temperature NOTE Thermal protection switches load to Bypass in case of overheating 20 C to 40 C 4 F to 104 F with batteries Storage Temperature 25 C to 55 C 13 F to 131 F without batteries Transit o er 730 o Temperature 25 C to 55 C 13 F to 131 F Relative Humidity 0 90 noncondensing Operating Altitude Up to 3 000 meters 9 843 ft above sea level Transit Altitude Up to 10 000 meters 32 808 ft above sea level Audible Noise lt 55 dBA at 1 meter typical Leakage Current lt 1 5 mA 69 Table 20 Battery Runtimes in Minutes at 100 Load ALL Models Model Internal Batteries 1 EBP 2EBPs 3 EBPs 4 EBPs 1K 5 22 41 65 87 2K 5 23 44 71 100 3K 3 17 31 52 69 NOTE Battery times are approximate and vary depending on the load configuration and battery charge Table 21 Battery Internal Batteries EBPs Tow r 1000 VA 36 Vdc 3 12V 7 Ah 1K EBP 36 Vdc 2 x 3 12V 7 Ah TA 2000 VA 72 Vdc 6 12V 7 Ah 2K EBP 72 Vdc 2 x 6 12V 7 Ah 9 3000 VA 72 Vdc 6 12V 9Ah 3K EBP 72 Vdc 2 x 6 12V 9 Ah Fuses
13. Output Relay Fault Z 59 Input NTC Fault NTC Input NTC Fault 60 64 64 ey Power Input Fuse Fault O A 74 E De 75
14. U setting function is completed and the numerical value below the OPU will light without flashing Exit from the setting interface Press_and hold function setting key for more than half a second less than 2 seconds exit from the setting interface and return to main interface 40 Battery string number and type setting 4 Enter the setting interface Press and_hold the function setting key for more than 2 seconds then come to setting interface Press and hold the scroll key for more than half a second less than 2 seconds select the function setting choose battery setting interface at the moment the letters bAt will flash Q Enter the battery setting interface Press and hold the function setting key for more than half a second less than 2 seconds then come to setting interface of battery the letters bAt will stop flashing The numerical value below the bAt will flash Press and hold the scroll key for more than half a second less than 2 seconds select the numerical value in accordance with the real connected battery strings Confirm the battery strings setting interface After selecting numerical value press and hold the function setting keyor more than half a second less than 2 seconds Now the battery strings setting is confirmed and the battery type value below will flash set the battery type in the same way Exit from
15. ance This feature can be used for shutting down the load and the UPS by thermal relay for instance in the event of room overtemperature When EPO is activated the UPS shuts down the output and all its power converters immediately The UPS remains on to alarm the fault 52 The EPO circuit is an IEC 60950 safety extra low voltage SELV circuit This circuit must be separated from any hazardous voltage circuits by reinforced insulation CAUTION e The EPO must not be connected to any utility connected circuits Reinforced insulation to the utility is required The EPO switch must have a minimum rating of 24 Vdc and 20 mA and be a dedicated latching type switch not tied into another circuit The EPO signal must remain active for at least 250 ms for proper operation e To ensure the UPS stops supplying power to the load during any mode of operation the input power must be disconnected from the UPS when the emergency power off function is activated NOTE For Europe the emergency switch requirements are detailed in Harmonized document HD 384 48 SI Electrical Installation of the Buildings Part 4 Protection for Safety Chapter 46 Isolation and Switching EPO Connections Wire Function Terminal Wire Size Rating Suggested Wire Size EPO L1 4 0 32 mm2 12 22 AWG 0 82 mm2 18 AWG L2 NOTE Leave the EPO connector installed onto the EPO port of the UPS even if the EPO function is not needed See
16. and cable connection of the UPS and EBPS are the same as RT To install the optional EBP s for a UPS Tower Installation The tower cabinet comes fully assembled and ready to connect CAUTION The cabinet is heavy Removing the cabinet from its carton requires a minimum of two people To install the cabinet 22 1 Place the UPS on a flat stable surface in its final location 2 If installing additional cabinets place them next to the UPS in their final location 3 Continue to the following section Tower Wiring Installation Tower Wiring Installation This section explains e Installing the UPS including connecting the UPS internal batteries e Connecting any optional EBPs Installing the UPS NOTE Do not make unauthorized changes to the UPS otherwise damage may occur to your equipment and void your warranty NOTE Do not connect the UPS power cord to utility until after installation is completed 1 If you are installing power management software connect your computer to one of the communication ports or optional connectivity card see page 51 For the communication ports use an appropriate cable not supplied 2 Ifan emergency power off disconnect switch is required by local codes see Emergency Power off EPO on page 52 to install the EPO switch before powering on the UPS 3 If you are installing EBP s continue to the following section Connecting the EBP s Ot
17. ble Power cord Input and output e RS232 cable If you ordered an optional Extended Battery Module EBP verify that the following additional item is included with the EBP EBP user s guide NOTE Discard the EBP user s guide if you are installing the EBP with a new UPS at the same time Use the UPS user s guide to install both the UPS and the EBP Rackmount Installation The Rackmount cabinet comes with all of the hardware required for installation in a standard EIA or JIS seismic Rackmount configuration with square and round mounting holes The rail assemblies adjust to mount in 19 racks with a distance from front to rear around 70 76 cm 27 to 30 inches deep 10 Checking the Rail Kit Accessories Options Verify that the following rail kit items are included for each cabinet e Left rail assembly Left rail Rear rail 3 M5_8 pan head screws e Right rail assembly Right rail Rear rail 3 M5_8 pan head screws e Rail hardware kit 8 M5 butterfly nuts 2 rear stop brackets 8 M5 umbrella nuts e Mounting bracket kit 2 mounting brackets 8 M4 8 flat head screws Tools Required To assemble the components the following tools may be needed e cross shaped screwdriver 5 and 6 mm wrench or socket Rackmount Setup i CAUTION e The cabinet is heavy Removing the cabinet from its carton requires a minimum of two people e jf installing optional EBP S make sure to install t
18. ction setting key gt for more than half a second shorter than 2 seconds to confirm the selection then to set the minus range To set the minus range in the same way After the minus range is confirmed Long press function setting key gt for more than 2 seconds to exit setting menu Output voltage setting 3 Enter the setting interface Press and hold the function setting key for more than 2 seconds then come to setting interface Press and hold the scroll key for more than half a 39 second less than 2 seconds select the function setting choose output voltage setting interface at the moment the letters OPU will flash Enter the output voltage selecting interface Press and hold the function setting key for more than half a second less than 2 seconds then come to setting interface of output voltage OPU at this time the letters OPU will light for a long time The numerical value below the OPU will flash Press and hold the scroll key for more than half a second less than 2 seconds select the numerical value in accordance with OPU function The provided voltages are 208v 220v 230v 240 you can choose any one of them by yourself The default is 220v Confirm the output voltage selecting interface After selecting numerical value press and hold the function setting key for more than half a second less than 2 seconds Now the OP
19. ds card Contact Relay Car Tr RS232 DB 9 2400 bps Communication Ports USB Table 11 Extended Battery Model EBP Model Configuration Battery Voltage For Power Ratings 1K EBP 36 Vdc 1000 VA 2K EBP RT Tower 72 Vdc 2000 VA 3K EBP 72 Vdc 3000 VA Table 12 UPS Model List All Models Model Power Level Rear Cover Diagram 1K Rackmount 1000 VA 900W Figure 30 2K Rackmount 2000 VA 1800W Figure 31 3K Rackmount 3000 VA 2700W Figure 32 1K Tower 1000 VA 900W Figure 33 2K Tower 2000 VA 1800W Figure 34 3K Tower 3000 VA 2700W Figure 35 64 Table 13 Weights and Dimensions All Models Model Rackmount UPS Dimensions W D H Weight 1K RT 440 430 86 5mm 18 7 kg 2K RT 440 690 86 5mm 31 3 kg 3K RT 440 690 86 5mm 33 0kg Model RT EBP Dimensions W D H Weight 1K RT 440 430 86 5mm 24 0 kg 2K RT 440 690 86 5mm 42 8kg 3K RT 440 690 86 5mm 46 0 kg Model Tower UPS Dimensions W D H Weight 1K Tower 144 409 215mm 13 kg 2K Tower 199 466 337mm 24 6 kg 3K Tower 199 466 337mm 25 5kg Model Tower EBP Dimensions W D H Weight 1K Tower 144 409 215mm 18 5 kg 2K Tower 199 466 337mm 35 5kg 3K Tower 199 466 337mm 39 1 kg Table 14 Electrical Input All Models Nominal Frequency 50 60 Hz auto sensing Frequency Range battery 45 55 Hz 50Hz 55 65Hz 60Hz before transfer to Bypass Voltage Range 5 10 15
20. en LED and battery yellow LED are on the buzzer beeps once every 4 seconds The warning red LED is on when beeping When the mains power down or instable UPS will turn to battery mode at once If the mains recovers the UPS will transfer to line mode If battery low_alarm activates the indicator of flashes If battery voltage reaches low limit UPS will turn off to protect the battery UPS will auto restart when the mains recover AANOTE The back up time of battery mode is subject to the load and EBP numbers Battery remaining time displayed on the LCD may not be accurate Bypass Mode Bypass yellow LED is on the buzzer beeps once every 2 minutes The warning red LED is on when beeping LCD displays are according to the exact load and battery capacity Bypass tolerance can be set by LCD Under below conditions the UPS will transfer to bypass mode 44 e BPS on set by user through LCD and the UPS is turned off e BPS on set by user through LCD and the UPS is plugged into utility but not turned on e Overload on line mode or ECO mode ANOTE When in bypass mode the load is not protected ECO Mode Both the inverter green LED and bypass yellow LED are on When ECO enabled and the utility is in range the UPS will work on ECO mode If the utility in out of ECO range but still in Line range the UPS will transfer to line mode Utility tolerance of ECO mode can be set
21. ener safe User Manual 1KVA to 3KVA Rack Tower conversion User s Guide ESOL RTH UPS Uninterruptible Power Supply Class B EMC Statements High Voltage Models up to 3000 VA FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures e Reorient or relocate the receiving antenna e Increase the separation between the equipment and the receiver e Connect the equipment into an outlet on a circuit different from that to which the receiver is connected e Consult the dealer or an experienced radio TV technician for help Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information RISK OF ELECTRIC SHOCK Observe the warning associated w
22. extract it then extract the other side with display see Fig 8 NOTE A ribbon cable connects the LCD control cover to the UPS Do not pull on the cable or disconnect it When remove the cover Operate as the following right Figure shows instead of the left one see Fig 8 fe fee E It is wrong that le His corectinot fe 3 extracting the front Les extracting the front t cover fiom the handie y cover from the panel x A ZN N Figure8 Extract UPS front cover 15 CAUTION A small amount of arcing may occur when connecting the internal batteries This is normal and will not harm personnel Connect the cables quickly and firmly 2 Connect the internal battery connector see Figure9 Connect red to red Press the connector tightly together to ensure a proper connection 3 If you are installing EBPS see the following section Connecting the EBP s before continuing with the UPS installation Figure9 Connecting the UPS Internal Batteries 4 Replace the UPS front cover To replace the cover verify that the ribbon cable is protected and if EBPS are installed the EBP cable is routed through the knockout on the bottom of the cover Put the front cover hooks of side with display to the cover port put another side to the other two ports then press it until the cover and the chassis are combined tightly 16 Top EBM Cable Knockout EBM Cover Hooks 4places Figure10 5 If you are installin
23. figuring Battery settings on page 41 to set the number of installed EBPs 12 To change any other factory set defaults see User settings on page 37 NOTE At initial startup the UPS sets system frequency according to input line frequency input frequency auto sensing is enabled by default NOTE At initial startup please set the output voltage needed before start up the UPS After the subsequent startup the UPS will output the setting voltage 13 If you installed an optional EPO test the EPO function Activate the external EPO switch Verify the status change on the UPS display Deactivate the external EPO switch and restart the UPS NOTE The internal batteries charge to 80 capacity in less than 5 hours However we recommend that the batteries should be charged for 48 hours after installation or long term storage If optional EBPs are installed see the recharge times listed in Table 21 on page 70 27 4 Operation This chapter contains information on how to use the UPS including front cover operation operating modes UPS startup and shutdown transferring the UPS between modes and configuring bypass settings load segments and battery settings Control Cover Functions The UPS has a three button segmental LCD with backlight It provides useful information about the UPS itself load status measurements and settings see Figure 18 Warning LED Bypass LED Battery LED Inverter LED Figure
24. for more than half a second to start UPS The operation of the UPS in the process of start is almost the same as that when mains power is in After finishing the self test the corresponding LED lights and the UPS is working in battery mode Turn off operation Turn off the UPS in line mode 1 Press and hold the OFF key for more than half a second to turn off the UPS and inverter After the UPS shutdown the LEDs go out and there is no output If output is needed you can set bps ON onthe LCD setting menu Turn off the UPS by DC without mains power 1 Press and hold the OFF key for more than half a second to turn off the UPS 46 2 When turning off the UPS it will do self testing firstly The LEDs light and go out circularly and orderly until there is no display on the cover UPS self test mute test operation 1 When the UPS is in line mode press and hold the self test mute key for more than 1 second the LEDs light and go out circularly and orderly The UPS comes to self test mode and tests its status It will exit automatically after finishing testing and the LED indication will go back to previous status 2 When the UPS is in battery mode press and hold the self test mute key for more than 1 second the buzzer stops beeping If you press and hold the self test mute key for one more second it will restart to beep again Configuring Battery Settings Set the UPS for the number of EBPs installed To en
25. ftware Suite CD NOTE Install UPSilon2000 power management software with the serial number attched on the cover of the CD When running the monitor software choose appropriate communication port If using RS232 choose COM1 2 and Megatec protocol If using USB choose megatec USB UPSilon2000 software provides up to date graphics of UPS power and system data and power flow It also gives you a complete record of critical power events and it notifies you of important UPS or power information If there is a power outage and the UPS battery power becomes low UPSilon2000 software can automatically shut down your computer system to protect your data before the UPS shutdown occurs 56 6 UPS Maintenance This section explains how to e Care for the UPS and batteries Replace Extended Battery Packs EBPs e Test new batteries e Recycle used batteries or UPS UPS and Battery Care For the best preventive maintenance keep the area around the UPS clean and dust free If the atmosphere is very dusty clean the outside of the system with a vacuum cleaner For full battery life keep the UPS at an ambient temperature of 25 C 77 F NOTE The batteries in the UPS are rated for a 3 5 year service life The length of service life varies depending on the frequency of usage and ambient temperature Batteries used beyond expected service life will often have severely reduced runtimes Replace batteries at least every 5 years to keep un
26. g power management software connect your computer to one of the communication ports or optional connectivity card For the communication ports use an appropriate cable 6 If your rack has conductors for grounding or bonding of ungrounded metal parts connect the ground cable not supplied to the ground bonding screw See Rear Covers for the location of the ground bonding screw for each model 7 If an emergency power off disconnect switch is required by local codes see Remote Emergency Power off REPO to install the REPO switch before powering on the UPS 8 Continue to UPS Initial Startup Connecting the EBP s To install the optional EBP s for a UPS 1 Remove the front cover of each EBP and UPS see Figure 11 17 It is the same with the installation of the front cover Refer To install the UPS itis wrong that Itis Correct thal en extracting the front extracting the front cover from the handle cover from the panel ye ZN F at e Figure11 Removing the EBP Front Cover 2 On the bottom of the UPS front cover remove the EBP cable knockout see Figure 12 7 Knock for 8M cable Figure12 Removing the UPS Cable Knockout 3 For the bottom or only EBP remove the EBP cable knockout on the top of the EBP front cover See Figure 13 for the location of the top EBP cable knockout 4 If you are installing more than one EBP for each additional EBP remove the EBP cable
27. he EBP S directly below the UPS so that all wiring between the cabinets Is installed behind the front covers and inaccessible to users NOTE Mounting rails are required for each individual cabinet 11 To install the rail kit 1 Assemble the left and right rails to the rear rails as shown in Figure4 Do not tighten the screws Adjust each rail size for the depth of your rack a Real Railis i x m f MS Butterfly y i ra Nutsi places N e M5 Umbiella 8 13 Nuts Splaces CS A tight Roll Left Rail Figure4 Securing the Rails Select the proper size in the rack for positioning the UPS see Figure 5 The rail occupies four positions on the front and rear of the rack Tighten four M5 Umbrella Nuts in the side of rail assembly see Figure 4 Fix one rail assembly to the front of the rack with one M5x12 pan head screw and one M5 cage nut Using two M5 cage nuts and two M5x12 pan head screws to fix the rail assembly to the rear of the rack 12 Tighten x adjustment nuts N after rail attachment 4 places each rail Ya amp i Bs o M5 Float a Y M5X12 Pan Head Nuts 8places Screws 8places Front Of Rack Figure5 Fixing the Rails 5 Repeat Steps 3 and 4 for the other rail assembly 6 Tighten the four butterfly nuts in the middle of each rail assembly 7 If installing optional cabinets repeat Step 1 through Step 6 for each rail kit 8 Place the UPS on a
28. herwise continue to UPS Initial Startup on page 26 23 Connecting the EBP s To install the optional EBP s for a UPS 1 On the rear of the UPS remove the cable retention clip covering the battery connector Retain the clip See Figure 17 2 Installations with one EBP only Remove the cable retention clip covering the right or upper battery connector Retain the clips 3 Installations with more than one EBP For all EBPs except the last EBP remove the cable retention clips covering both battery connectors Do not remove the clip from the second battery connector on the last EBP Retain the clips CAUTION A A small amount of arcing may occur when connecting an EBP to the UPS This is normal and will not harm personnel Insert the EBP cable into the UPS battery connector quickly and firmly 4 Plug the EBP cable s into the battery connector s as shown in Figure 17 Up to four EBPs may be connected to the UPS 5 Verify that the EBP connections are tight and that adequate bend radius and strain relief exist for each cable 6 Continue to UPS Initial Startup on page 26 Remove cable retention clip Plug in EBP cable Retain the clip 24 2KVA 3KVA Tower UPS and EBP S Figure17 Connecting the EBPS 25 UPS Initial Startup O To start up the UPS NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm 1 If optional EBPs are i
29. ing performance and reliability the UPS s unique benefits include True online double conversion technology with high power density utility frequency independence and generator compatibility Output power factor up to 0 9 Three segment charging mode to increase battery service life optimize recharge time e Selectable High Efficiency mode of operation e Cold start function to startup the UPS without utility e Standard communication options one RS 232 communication port one USB communication port and relay output contacts or SNMP card Power Shedding function may turn off uncritical load in battery backup to make longer backup time for critical load e Extended runtime with up to four Extended Battery Modules EBPs per UPS e Emergency shutdown control through the Remote Emergency Power off EPO port The content displayed on the interface is rich The capacity of 5 the loads and the battery can be seen directly and the FLASH pictures and fan rotating icon can be displayed while charging Enhance it is easy to know its operation status When UPS fails it can show the fault code therefore the UPS can be repaired as soon as possible by inquiring fault code table NOTICE In the manual RT is short for Rack Tower conversion Rack Tower convertible LCD design No matter what angle required only pressing the key slightly to reach your perspective needs For RT model it is equipped with hot swappable bat
30. ith the risk of electric shock symbol gt CAUTION need your attention x This symbol indicates that you should not discard the UPS or the UPS batteries in the trash This vat product contains sealed lead acid batteries and must be disposed of properly For more information contact your local recycling reuse or hazardous waste center This symbol indicates that you should not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center Table of Contents a ONE SR bte ee tt ten 5 2 Safety WANT ad A AT is se 7 Be LAS LES LUE RSR E E P AT EA EEE 9 gt Operati Neen enei to 28 SACO NC a ee eae ine E E E a a ET 48 6 UPS Mantis a del 57 P Specification A SR Sa nest 63 8 TOMADO IN 2 AS AA 73 1 Introduction This UPS protects your sensitive electronic equipment from most common power problems including power failures power sags power surges brownouts line noise high voltage spikes frequency variations switching transients and harmonic distortion Power outages might occur unexpectedly and power quality can be erratic These power problems have potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost productivity and expensive repairs With the UPS you can safely eliminate the effects of power disturbances and guard the integrity of your equipment Providing outstand
31. its running at peak efficiency Storing the UPS and Batteries If you store the UPS for a long period recharge the battery every 6 months by connecting the UPS to utility power The internal batteries charge to 80 capacity in less than 5 hours However we recommends that the batteries charge for 48 hours after long term storage If optional EBPs are installed see the recharge times listed in Table 21 on page 70 Check the battery recharge date on the shipping carton label If the date is expired and the batteries were never recharged do not use the UPS Contact your service representative 57 Replacing Batteries NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode The EBP can be replaced when UPS is ON but be aware that if the utility fails at that time the load of the UPS may NOT be protected If you prefer to remove input power to change the batteries see UPS Turn on and Turn off on page 46 e Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions Keep unauthorized personnel away from batteries e Batteries can present a risk of electrical shock or bum from high short circuit current Observe the following precautions 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries 4 Wear rubber gloves and boots e When replacing batteries replace with
32. ke effect under certain condition Below table describes how to set the UPS Table 6 User Settings Setting function serial Setting procedure LCD display number Enter the setting interface Press and hold the function setting key for more than 2 seconds then come to setting interface the letters ECO will flash Enter the ECO setting interface Press and hold the function setting key for more than half a second less than 2 seconds the letters ECO will stop flash The ON or OFF below the ECO will ECO function flash Press and hold the scroll setting 1 key or more than half a second less than 2 seconds to determine whether the ECO function is enabled or disabled Confirm the ECO selecting interface After selecting ON or OFF press and hold the function setting key for more than half a second less than 2 seconds Now the ECO setting function is completed and the ON or OFF below the ECO will light without flash If you choose OFF then go to step 7 otherwise go ahead to 37 step 5 Set the ECO tolerance range Short press the scroll key or for more than half a second shorter than 2 seconds to select the voltage range in percentage 5 10 15 25 default is 25 then short_ press function setting key gt for more than half a second shorter than 2 seconds to confirm the selection then to set the minus range
33. larm conditions 73 Table 22 rat case stan The INPUT Anti connection of letters on LCD mains live and neutral Re connect the input power cable display section or mains is out of and make a correct connection flashes Check UPS battery connect Battery capacity Battery low voltage or indicator flashes battery disconnected a A if battery damaged Mains normal but UPS input breaker UPS has no input Press the breaker for reset Keep UPS connecting with mains E fully power for more than 8 hours 9 recharge batter Check the usage of loads remove Short back up time UPS overload some redind neda ces When replace battery contact Battery aged franchiser to get battery and relative assembl Didn t press the combination keys of on eee UPS has no battery Connect UPS battery well if pressing the ON connected or battery battery voltage low please turn key voltage low and too off UPS and remove some loads loads connected then start UPS ate occurs inside Contact supplier for servicing Charger doesn t work normally or battery Contact supplier for servicing aged Press the two keys at the same time The icon of charger status on LCD display flashes and buzzer beeps once per second The following table describes typical faulty conditions 74 Table 23 Fault code Fault causation Fault Code Bus Fault 00 19 Inverter Fault 20 39 OverHeat Heat 40 44 44 Output a
34. n wall into the slot Insert the thin wall y into the slot Insert the thin wail into the slot ES lt d M4XB Pon Heads maxa Pon Head Screws 2places e Screws apioces Fig 26 The Installation for baffle of battery pack 4 Grasp the handle in front of the battery pack take out of it and hold it then remove the battery pack as fig 27 shown Dr RSR a U T E E L Els E COCE COACE REECE Fig 27 Remove the battery park 5 Hold the middle of the new battery pack insert it Once install the new battery pack make sure it is completely inserted into the chassis as fig 28 shown 60 Insert the thin wall into the slot Insert the thin wall into the slot gt Maxa Pon Head Screws 4pioces Fig 28 Installation for battery pack 6 If the fuse melting replace it directly as the following shows Take Out The Fuse Take Out The Fuse From Here From Here Fig 29 Replacement of fuse 61 Testing New Batteries To test new batteries 1 Plug the UPS into a power outlet for 48 hours to charge the batteries 2 Start up the UPS by pressing the start up combination button 3 Press the battery test combination button to activate the battery test The UPS starts a battery test if the batteries are fully charged the UPS is in Normal mode with no active alarms and the bypass voltage is acceptable During the batte
35. nstalled verify that the EBPs are connected to the UPS Tower models See Connecting the EBP s on page 24 2 Plug the equipment to be protected into the UPS but do not turn on the protected equipment 3 Make any necessary provisions for cord retention and strain relief 4 Plug the detachable UPS power cord into the input connector on the UPS rear cover 5 Plug the UPS power cord into a power outlet The UPS front cover display illuminates 6 The UPS will do self test when power on After that the charger will charge the battery If the output displayed on LCD is 0 there is no output If you need the UPS output the utility without starting the UPS when plug into the utility you need to set bPS option to ON on the setting mode refer to Page 38 7 Press the combination start up buttons on the UPS front cover for at least half a second The UPS will start up and the LED will turn on and off sequentially 8 Check the UPS front cover display for active alarms or notices Resolve any active alarms before continuing See Troubleshooting on page 73 If the AXindicator is on do not proceed until all alarms are clear Check the UPS status from the front cover to view the active alarms Correct the alarms and restart if necessary 26 10 Verify that the Y indicator illuminates solid indicating that the UPS is operating normally and any loads are powered 11 If optional EBPs are installed see Con
36. or the RS 232 communication port are identified in Figure 22 and the pin functions are described in Table 9 Figure 22 RS 232 Communication Port DB 9 Connector Table 9 RS 232 Communication Port Pin Assignment Pin Number Function Definition Direction from the UPS 1 46789 No use 2 RxD Transmit to external device Out 3 TxD Receive from external device In 5 GND Signal common Connectivity Cards Connectivity cards allow the UPS to communicate in a variety of networking environments and with different types of devices The 51 UPS has one available communication bay for the following connectivity cards e Web SNMP Card has SNMP and HTTP capabilities as well as monitoring through a Web browser interface connects to a twisted pair Ethernet 10 100BaseT network In addition a Environmental Monitoring Probe can be attached to obtain humidity temperature smoke alarm and security information e Relay Interface Card has isolated dry contact relay outputs for UPS status Utility failure Low battery UPS alarm OK or On bypass See Figure 20 21 on page 48 49 for the location of the communication bay UI LEY CONTACT FN A cn TA L Figure 23 Optional Connectivity Cards NOTE Before installing the connectivity card please remove the clip from the bay Refer to the user s manual of the appropriate cards Emergency Power off EPO is used to shut down the UPS from a dist
37. rchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage To file a claim for shipping damage or concealed damage 1 File with the carrier within 15 days of receipt of the equipment 2 Send a copy of the damage claim within 15 days to your service representative NOTE Check the battery recharge date on the shipping carton label If the date has expired and the batteries were never recharged do not use the UPS Contact your service representative Unpacking the Cabinet A CAUTION e Unpacking the cabinet in a low temperature environment may cause condensation to occur in and on the cabinet Do not install the cabinet until the inside and outside of the cabinet are absolutely dry hazard of electric shock e The cabinet is heavy see page 65 Be careful to unpack and move the cabinet 9 Carefully to move and open the carton Keep the components packaged until ready to install To unpack the cabinet and accessories 1 Open the outer carton and remove the accessories packaged with the cabinet 2 Carefully lift the cabinet out of the outer carton 3 Discard or recycle the packaging in a responsible manner or store it for future use Place the cabinet in a protected area that has adequate airflow and is free of humidity flammable gas and corrosion Checking the accessories It includes 9 UPS user s guide Software Suite CD USB ca
38. rly Press and hold this key for more than 2 seconds Circularly and orderly display the items every 2 seconds when press and hold the key for some time again it will turn to output status Function setting mode Press and hold the key for more than half a second less than 2 seconds Select the set option Setting entry Non function setting mode Press and hold the key for more than 2 seconds Function setting interface Function setting mode Press and hold the key for more than half a second less than 2 seconds Affirm the set option Press and hold the key for more than 2 seconds exit from this function setting interface 30 Table 3 The corresponding working status of indications Indication Working No S Ta ope free OS Peron 1 Line mode 1 Line mode CSC Mene oitade High low voltage Once protection every four turn to seconds battery mode Battery mode Once every four voltage ie A Once per second Once every two minutes Eliminate after voltage in starting the UPS bypass mode Main AC high Once a i every four seconds bypass mode Main AC low a C lo Once every four seconds voltage warning in bypass mode Battery disconnect warning Battery disconnect warning Once Affirm if the Bypass mode every four battery switch is seconds closed Inverting e Once Affirm if the 31 al NN ae mode seconds closed Affirm if the opera
39. ry test the UPS transfers to Battery mode and discharges the batteries for 10 seconds The LED indicators of the front cover stop cycling when the test is completed Recycling the Used Battery or UPS Contact your local recycling or hazardous waste center for information on proper disposal of the used battery or UPS e Do not dispose of the battery or batteries in a fire Batteries may explode Proper disposal of batteries is required Refer to your local codes for disposal requirements e Do not open or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes It may be toxic 62 CAUTION Do not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed properly For more information contact your local recycling reuse or hazardous waste center CAUTION Do not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center 7 Specifications Model Specifications This section provides the following specifications Communication options Model lists Weights and dimensions Electrical input and output Environmental and safety Battery 63 Table 10 Communication Options All Models Communication Bay available independent communication bay for connectivity cards Compatible SNMP card Contact Relay Card Connectivity Car
40. stic base installation two plastic base brackets 2 flatten it after intercrossing intercross as following Figure Plastic base bracket Plastic base bracket Plastic base bracket Plastic base bracket Figure 14 plastic base installation If an EBP is needed to be placed in the middle the assembly of plastic base is similar Figure 14 The difference is that two 1U plastic base extended boards are added in the middle as the following shows 20 1U plastic base bracket 1U plastic base bracket Plastic base bracket extended board Plastic base bracket extended board A B H SS 1U plastic base bracket extended board 1U plastic base bracket 1U plastic base bracket U plastic base bracket Plastic base bracket extended board Plastic base bracket extended board extended board CC D 1U plastic base bracket 1U plastic base bracket extended board extended board 1U plastic base bracket 1U plastic base bracket Plastic base bracket extended board extended board Plastic base bracket Plastic base bracket Plastic base bracket CE CF Figure 15 increase EBP plastic base installation 21 2 The installation between UPS and EBPS can be referred to Fig 16 N UPS Plastic base 4 Figure16 The installation for UPS and battery box 1 Install the base then place the RT UPS on the base one by one as Fig 16 shows 2 The cover installation
41. sure maximum battery runtime configure the UPS for the correct number of EBPs refer to Table 8 for the appropriate setting of battery numbers and type Use the up and down scroll keys to select the number of battery strings according to your UPS configuration Table 8 Battery number Configuration UPS only internal batteries 1 default UPS 1EBP 3 UPS 2EBPs 5 UPS 3EBPs 7 UPS 4EBPs 9 NOTE The UPS contains one battery string each EBP contains two battery strings 47 CAUTION e The following process must be performed if the UPS is connected with generator e First turn on the generator after it runs stably connect output power of the generator to UPS input terminal then turn on the UPS After the UPS is turned on please connect load one by one e It is recommended that the generator capacity is as twice as the UPS rated capacity e You had better not use the ECO mode when the quality of the input AC mains is not good 5 Communication This section describes the e Communication ports RS 232 and USB e Connectivity cards e Emergency Power off EPO e Load Segments e UPSilon2000 Power Management Software See Rear Covers on page 71 72 for rear cover diagrams for each model SEGMENT 1 SEGMENT 2 Figure19 48 Figure20 EPO USB INTELLIGENT SLOT So DODODOO Figure 21 Communication Options and Control Terminals 1KVA Tower model shown 49
42. t Six times battery is start connected well 5 Output overload protection os Twice per Remove the line od second uncritical loads Overload in lon Remove the line mode Beare uncritical loads protection Overload T R h warning in wice per emove the battery mode second uncritical loads Overload in battery Long Remove the mode beeps uncritical loads protection 5 vamos Once Remove the 5 yam in LE every 2 uncritical loads bypass mode seconds e Check if the fan ae fault aoe every 2 is blocked by icon flashing lo seconds object If display fault code and iconA lights Long contact for Fault mode beeps maintenance when you can t deal with e indicator lights for a long time _indicator flashes A _the status of indicator depends on other conditions 32 Display Functions As the default or after 5 minutes of inactivity the LCD displays the output parameters The backlit LCD automatically dims after 5 minutes of inactivity Press any button to restore the screen LCD display comprises numerical value section capacity graphics section fan status graphics section and charger status graphics section refer to Table 4 for detail Table 4 LCD display section Section Description Graphic Display the corresponding numerical value of inquiring items output load Numerical temperature input battery for value example as the graphics shows above section the output voltage is 230v the o
43. tery feature needed for 19 rack solution RT models in a space optimizing 2U size fits any standard 19 rack Figure2 The Rackmount EBP front view 6 Figure3 The Tower UPS and the EBP front view 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries Please read all instructions before operating the equipment and save this manual for future reference The UPS contains LETHAL VOLTAGES All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY There are NO USER SERVICEABLE PARTS inside the UPS A The UPS contains its own energy source batteries The UPS output may carry live voltage even when the UPS is not connected to an AC supply To reduce the risk of fire or electric shock install the UPS in a temperature and humidity controlled indoor environment free of conductive contaminants Ambient temperature must not exceed 40 C 104 F Do not operate near water or excessive humidity 90 maximum To reduce the risk of fire connect only to a circuit provided with branch circuit overcurrent protection in accordance with the National Electrical Code NEC ANSI NFPA 70 Output overcurrent protection and disconnect switch must be provided by o
44. the same type and number of batteries or battery packs Contact your service representative to order new batteries e Proper disposal of batteries is required Refer to your local codes for disposal requirements e Never dispose of batteries in a fire Batteries may explode when exposed to flame 58 A Replacing Tower EBPs The EBP is heavy Lifting the cabinet requires a minimum of two people 1 Unplug the EBP cable from the UPS If additional EBPs are installed unplug the EBP cable from the battery connector on each EBP 2 Replace the EBP s See Recycling the Used Battery or UPS on page 62 for proper disposal 3 For each replaced EBP remove the cable retention clip covering the battery connector s as shown in Figure 17 on page 25 Retain the clips 4 Plug the EBP cable s into the battery connector s as shown in Figure 17 on page 25 Up to four EBPs may be connected to the UPS 5 Retain the removed clips 6 Verify that the EBP connections are tight and that adequate bend radius and strain relief exist for each cable Replacing RT UPS and EBPS 1 If the battery fault the following steps are provided for modular unit to replace the new battery pack 2 Remove the front cover of the battery box 3 Remove the connection cables between battery box and UPS Release the screw of the baffle of the battery pack as the Fig26 shows then remove the baffle from the left or right 59 Insert the thi
45. the setting interface Press and hold function setting key for more than half a second 41 less than 2 seconds exit from the setting interface and return to main interface Load segment setting 5 Enter the setting interface Press and hold the function setting key for more than 2 seconds then come to setting interface Press and hold the scroll key for more than half a second less than 2 seconds select the function setting choose battery setting interface at the moment the letters Seg 1 will flash Enter the load segment setting interface Press and hold the function setting key for more than half a second less than 2 seconds then come to setting interface of load segment the letters Seg 1 will stop flashing The numerical value below the Seg 1 will flash Press and hold the scroll key for more than half a second less than 2 seconds select the battery voltage 10 5v 11 0v 11 5v default is 10 5v Confirm the power shedding shielding battery voltage setting After selecting numerical value press and hold the function setting key for more than half a second less than 2 seconds Now the load shielding battery voltage setting is confirmed Exit from the setting interface Press and hold function setting key for more than half a second less than 2 seconds exit from the setting interface and return to main interface 42 EPO Inp
46. thers To comply with international standards and wiring regulations the sum of the leakage current of the UPS and the total equipment connected to the output of the UPS must not have an earth leakage current greater than 3 5 milliamperes If installing optional rackmount EBP s install the EBP s directly below the UPS so that all wiring between the cabinets is installed behind the front covers and is inaccessible to users The maximum number of EBP s per UPS is four If the UPS requires any type of transportation verify that the UPS is unplugged and turned off and then disconnect the UPS internal battery connector CAUTION Batteries can present a risk of electrical shock or burn from high short circuit current Observe proper precautions Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions Keep unauthorized personnel away from batteries Proper disposal of batteries is required Refer to your local codes for disposal requirements Never dispose of batteries in a fire Batteries may explode when exposed to flame 8 3 Installation This section explains Equipment inspection Unpacking the cabinet Checking the accessory kit Cabinet installation Wiring installation e Initial startup Inspecting the Equipment O If any equipment received has been damaged during shipment keep the shipping cartons and packing materials for the carrier or place of pu
47. ut Polarity setting 6 Enter the setting interface Press and hold the function setting key for more than 2 seconds then come to setting interface Press and hold the scroll key for more than half a second less than 2 seconds select the function setting choose EPO Input polarity setting interface the letters EPO will flash Enter the EPO Input Polarity setting interface Press and hold the function setting key for more than half a second less than 2 seconds the letters EPO will stop flashing The letters below the EPO will flash Press and hold the scroll key for more than half a second less than 2 seconds select the EPO input polarity P open circuit execute EPO function or P short circuit execute EPO function Confirm the setting After selecting EPO input polarity press and hold the function setting key for more than half a second less than 2 seconds Now the setting is confirmed Exit from the setting interface Press and hold function setting key for more than half a second less than 2 seconds exit from the setting interface and return to main interface 43 Table 7 Operating Modes Mode Description Indicator Line Mode The inverter green LED is on When input AC mains is in line with the working conditions UPS will work in line mode charge the battery and protect the load Battery Mode Both the inverter gre
48. utput frequency is 50Hz Display the capacity of the battery and load Every pane represents 20 capacity As graphics shown above Capacity the capacity of the battery is 80 graphics 100 5 panes the load reaches section 40 60 3 panes When UPS is overloaded the icon will flash when battery is weak or disconnected the icon will also flash 33 Display if the fan works normally Fan status When the fan works normally it will graphics show the dynamic fan blades rotating section when the fan works abnormally the icon A will keep on flashing with the warning Display the status of the charger When charger works normally the corresponding icon will vary Charger status dynamically and orderly graphics when charger works abnormally the section icon will keep flashing When UPS is in battery mode the number of the icons of the charger state section will vary according to the changeable capacity of the battery pane Parameters inquiring Press and hold the scroll key oror more than half a second less than 2 seconds to inquire about items The inquired items include input battery output load temperature Press and hold the scroll key ODfor more than 2 seconds LCD begins to display the items circularly and orderly which transfer to another every 2 seconds Press and hold the key for some time again it will return to output status 34

Download Pdf Manuals

image

Related Search

Related Contents

  Reflectors  Istruzioni per l`uso LION 3000 LION 3001  RR4200059 MANUAL CV FAGOR BARRUKALDEA.indd  Todo lo que tienes que saber para empezar.  Chicco Oasys 2-3 FixPlus  Calculated Industries Scale Master Pro XE  

Copyright © All rights reserved.
Failed to retrieve file