1. 2 COM R R E IDENTIFICATION DAP IM TERMINALS Earth terminals Output to relay Common exit NA 1 alarm relays Input for PTC o FT resistor Output to relay NA 2 fi re wer RLI RL2 Ric Supply o D Pp DAP IM 230 VAC Supply 12VCA 1 2 COM TR e ON 12 VAC auxiliary supply Input for connection of REP IM connection outlet forthe REP IM a load current measuring repeater toroidal OUTLETS TO RELAY 1 Outlet to relay normally open that closes when an alarm is set off due to a fault in the insulation resistance transformer overloading no earth detection or overheating 2 Outlet to relay normally open that closes when an alarm is set off due to a fault in the insulation resistance Ba FUNCTIONING OF DAP IM LEDS This indicates that a temperature alarm has been set off Fixed yellow This indicates that an insulation transformer load alarm has been set off in 96A Fixed yellow This indicates that the LED lit up on the bar is greater than or equal to the 96A of the value shown Fixed red This indicates that the LED lit up on the bar is greater than or equal to the KQ of the value shown Fixed red This indicates that a KQ insulation resistance alarm has been set off fixed yellow or due to breakage in earth continuity flashing yellow It indicates that the unit is on Fixed green FUNCTIONING OF THE DAP IM
2. IM fixed led 96A in the DAP IM and fixed led Overload and Alarm in the REP IM and outlet to relay RL2 will be activated in the DAP IM The acoustic alarm can be turned off pressing the Horn key in the REP IM repeater The beep indicator will reconnect according to the time configured in the REP IM In the case of Detection of overheating in the insulation transformer an acoustic alarm is set off in the REP IM horn a luminous one in the DAP IM and REP IM fixed led Temp in the DAP IM and fixed Temperature and Alarm in the REP IM and the outlet to relay RL2 will be activated in the DAP IM The acoustic alarm can be turned off pressing the Horn key in the REP IM repeater The beep indicator will reconnect according to the time configured in the REP IM In the case of No earth detection an acoustic alarm is set off in the REP IM horn a luminous one in the DAP IM and REP IM flashing led KO in the DAP IM and flashing led Alarm in the REP IM and outlet to relay RL2 will be activated in the DAP IM The acoustic alarm cannot be turned off even if the Horn key is pressed in the REP IM repeater 163 CONNECTING DAP IM WITH A REP IM L1 L2 Consult Outputs to IMPORTANT Relay on page 8 If you do not use the PTC or FT to measure temperature the terminal 12 T1 and 11 T2 ofthe DAP IM must be bridged
3. DAP IM REP IM PERMANENT INSULATION DETECTION UNIT REPEATING UNIT USER MANUAL DETECTOR DE AISLAMIENTO PERMANENTE Neitherthe total nor partial reproduction ofthis manual is permitted nor its computer treatment norits transmission in any way orthrough any medium whether electronic mechanical by photocopy by recording or other methods withoutthe prior written consentofthe Copyrightholders AFEI Sistemas y Automatizaci n S A Composition and publication AF EI Sistemas y Automatizaci n S A Printing AFEI Sistemas y Automatizaci n S A The information contained in this manual may be subjectto changes withoutadvance notice and in under no circumstances represents a commitmenton the part ofthe seller FirstEdition une 2007 INDEX DAP IM technical characteristics sssl 2 REP IM technical characteristics sssssse 3 Safety warnings Storage and Installation aria 4 Maintenance Description of the units Description functioning of DAP IM 2Alarmisiqials aereis co eni ans Connection DAP IM with a REP IM Identification DAP IM terminals Functioning of DAP IM leds ssssseeee Functioning of DAP IM keyboard How to configure the DAP IM Functioning of REP IM leds esses How to configure the REP IM TrialtestDAP ML oorr Diagnosis o
4. 650 TO 450 3 250 Ex 50 A 20 Ko Once communications mode has been selected press the TEST button to validate Then you must configure insulation resistance alarm setting The KQ led of the DAP IM will flash Through the insulation resistance potentiometer select the alarm setting value the leds bar will graphically indicate the position of the switch 11 HOW TO CONFIGURE THE DAP IM Once the desired value has been selected press the TEST button to validate The unit will record the new configuration in its EEPROM memory and will start working in normal mode NOTE In the event that the DAP IM is on for more than 60 seconds without the TEST key being pressed it will go out of configuration mode and go back to normal working When you go out of configuration of the unit the parameters that have been modified will not be recorded so it will go back to having the previous values 12 FUNCTIONING OF REP IM LEDS It indicates that there is an alarm It indicates that the unit is fixed yellow and if earth connected Fixed green continuity is broken flashing yellow It indicates that an insulation resistance alarm has occurred Fixed yellow It indicates that a transformer charge alarm has occurred Fixed yellow It indicates that the led lit up on the bar is greater than or equal to the KQ of the value indicated This key for the horn Fixed red
5. It indicates that the led lit up It indicates that an alarm for on the bar is greater than or temperature has occurred Fixed equal to the 96A of the value yellow indicated Fixed red 13 HOW TO CONFIGURE THE REP IM The REP IM has three dips JP1 JP2 and JP3 to configure the reconnection time of the beep indicator if an alarm persists Depending on the bridges connected See TABLE 1 DIPS TABLE 1 Time Reconnection Without reconnection 5 minutes 10 minutes 15 minutes 20 minutes 25 minutes 30 minutes 35 minutes YES NO EM ee The manufactured unit comes with all the bridges connected in the DIPS therefore the sound reconnection time if an alarm persists will occur in 35 minutes If there is no bridge connected once the horn has been stopped by the unit key it does not reconnect 14 TRIAL TEST DAP IM If we press the TEST key of the DAP IM for more than 3 seconds we will carry out a system test This test will cause An equivalent leak greater than 45 KO without this affecting impedance of the system to earth Intensity greater than 100 of the selected setting A temperature alarm through disconnection of the PTC or FT A sound alarm Once we stop pressing the TEST key the trial Test in the unit will automatically finish and will return to normal working NOTE Ifthe system is working correcting all the ala
6. KEYBOARD INSULATION TRANSFORMER LOAD SWITCH Switch for setting the maximum value of the insulation transformer current TEST When this key is pressed a test of the unit s measuring systems is carried out INSULATION RESISTANCE POTENTIOMETER Potentiometer for setting the maximum resistance value between L1 L2 and earth 10 HOW TO CONFIGURE THE DAP IM Configuration of the DAP IM is done through its own keyboard and allows the following parameters to be configured The communication mode by manufacturing default the DAP IM is configured for connecting with a REP IM repeater and the alarm setting of insulation resistance Said setting can be programmed by the potentiometer or through the KQ leds bar of the unit if you wish to adjust it more accurately To do so follow the steps indicated below in this chapter for configuring the insulation resistance alarm setting To enter unit configuration the current should be turned on to the unit by pressing the TEST key for 5 seconds after which all the DAP IM alarm leds will flash In the first place the DAP IM must be configured with connection to a REP IM repeater Communications mode Select the 50 KO value on the insulation resistance potentiometer to configure the DAP IM communications with a REP IM repeater It will be indicated by viewing the 8 leds of the insulation resistance indicator bar DAP IM ALARM 100 1000 Ea 850 Lac
7. ature 55 C to 125 C Transport temperature sss 20 C to 70 C Relative humidity without condensation 0 to 95 2KV Weight and Measurements cn ge s 480 gr Type of box 6 track DIN Rail DIN 43880 Box measurements 105 x 85 x 70 mm REP IM TECHNICAL CHARACTERISTICS Internal 1 Communication port for connecting with the DAP IM One 8 led bar for indicating insulation resistance One 8 led bar for indicating the insulation transformer charge 5 functioning signalling LEDs 1 Horn key Horn Stop Viewing Detection Parameters Insulation resistance Viewing rank in KQ Insulation transformer current Charge viewing in 96A 20 to 100 Insulation detection Transformer overload detection Overheating detection Earth continuity detection 50 KQ to 1000KQ Electrical and Environmental Supply voltage Functioning temperature 10 C to 50 C Storage temperature 55 C to 125 C Transport temperature ss 20 C to 70 C Relative humidity without condensation 0 to 95 Type of connection cable 2 pairs min plated or with mesh of 0 25 or 0 50 section Weight and Measurements Weight ccc cecinere e ea 180 gr Measurements DIN Box of 116 9 x 116 9 mm Fronta
8. f errors and faults DAP IM TECHNICAL CHARACTERISTICS Internal 1 Potentiometer for KQ of insulation alarm between L1 L2 and earth 1 Switch for the transformer current scale background 1 Communication port for connecting with the REP IM repeater An 8 led bar to indicate insulation resistance in KQ An 8 led bar to indicate the insulation transformer charge in 96A 4 functioning signalling LEDs 1 TEST key Measurement Detection Parameters Insulation resistance Measurement rank in KQ 50 KO to 1000 KQ Insulation transformer current Measurement rank in A 10 A to 50A Viewing of charge A ne 20 to 100 Insulation detection Transformer overload detection Overheating detection by a PTC or FT Earth continuity detection Inputs Outputs 2 NA relay outlets Measurement transformer input PTC or FT input for measuring temperature 10A 250V 1000 coils Communication channel optoinsulated Supply outlet REP IM module 12VAC Electrical and Environmental e Supply voltage enr 230 VAC 20 50 60Hz Consumption at 230 VAC sssss 9 VA Impedance between phases and earth 400KQ Insulation voltage between phases and communications port Protection index 1P21 Working temperature 10 C to 50 C Storagetemper
9. l depth 9 mm Minimum panel depth 45 mm Dimensions for embedding repeater 108 x 108 mm SAFETY WARNINGS WARNING The symbol AN indicates that there is risk to the user so the manual should be consulted for information on the part indicated Any use of the unit in a manner not specified by the manufacturer may compromise the safety of the unit and affect the user s protection Handling or installation of the unit must be carried out with it disconnected from the mains STORAGE AND INSTALLATION It is recommended to store the unit in its respective packing boxes and taking into consideration a minimum of climatic conditions as indicated in the technical characteristics The DAP IM does not have a switch or a fuse so a switch or thermomagnet must be installed leaving a distance of over 3mm between open contacts No prior building work is required for installation All that is needed is the appropriate drill hole in the cupboard housing the unit The place where the unit is located must observe the minimum dimensions to allow ventilation and connection of the input output leads of the unit It is recommended to use lead with a maximum section of 2mm for connecting to the unit terminals The leads connected in the unit terminals must be held together using a nylon or similar flange in such a way that if any lead comes loose from a terminal it will not cause accidental contacts with mass or
10. lements must be provided It is necessary to take precautions to increase safety for example The functions not relevant for safety of the installation are controlled electronically The functions that on failing can cause considerable material or even personal damage are performed using conventional electro mechanical control elements These considerations are independent of the type manufacturer and country of origin a IESG SS FI AFEI Sistemas y Fiere fi S A Provenca 533LocalA 08025 BARCELONA S pain Tel 34 93 4463050 Fax 34 934463051 http www afeisa es email afei afeisa es Cod MUI750330070724 0 Design and printed in S pain
11. mer temperature and the insulation transformer charge Supply to the unit will be done through the same terminals by which insulation measurement is performed The user will programme a leakage current setting and an insulation resistance setting with the corresponding potentiometer and switch in the unit which will be used by it for comparison with the instantaneous value that it will be measuring and in the event that the value measured exceeds this limit it will show an alarm ALARM INDICATION The DAP IM indicates the following types of alarm Insulation leakage detection depending on the programmed setting Insulation transformer charge detection depending on the programmed setting No earth detection This alarm has priority over the others Detection of overheating in the insulation transformer In the case of Insulation Leakage Detection an acoustic alarm is set off in the REP IM horn a luminous one in the DAP IM and REP IM fixed led KQ in the DAP IM and fixed led Insulation and Alarm in the REP IM and outlets to relay RL1 and RL2 will be activated in the DAP IM The acoustic alarm can be turned off pressing the Horn key in the REP M repeater The beep indicator will reconnect according to the time configured in the REP IM In the case of Insulation transformer charge detection an acoustic alarm is set off in the REP IM horn a luminous one in the DAP IM and REP
12. other units MAINTENANCE The DAP IM does not require any type of special maintenance When carrying out revisions the points to check are A unit check can be done by carrying out a Trial Test Check the condition of the leads riveted terminals and tightness of the terminals To clean the front you should use a slightly dampened cloth not wet with water and neutral soap Do not use an abrasive cleaning agent DESCRIPTION OF THE UNITS DAP IM The DAP IM is a protection unit for insulated supply systems in hospitals that measures the following parameters Measuring insulation resistance between lines L1 L2 and earth This resistance will be seen on an 8 LED indicator bar Detecting earth continuity Measuring insulation transformer charge This current is seen as a percentage on the scale background on an 8 LED indicator bar Detecting overheating in the insulation transformer REP IM The REP IM repeater is a unit designed for working with one single DAP IM to carry out all the functions by remote control Communication will be performed through two wires It has two LED bars to indicate the level of insulation resistance and the level of insulation transformer charge as well as indication LEDS for alarms horn and horn stop key DESCRIPTION FUNCTIONING OF DAP IM The DAP IM is a unit that supervises the insulation resistance between any of the input phases and earth earth continuity transfor
13. rm leds of the DAP IM and REP IM will light up and the acoustic alarm will be set off in the REP IM repeater DIAGNOSIS OF ERRORS AND FAULTS THE POWER LED ON THE Check that the unit is correctly supplied in DAP IM DOES NOT LIGHT UP terminals 1 and 16 THE UNIT KEEPS RESETTING The supply current may be too low THE DAP IM DOES NOT Review the wiring of the repeater used COMMUNICATE OR DOES NOT Check the communication configuration in WORK CORRECTLY WITH THE the DAP IM REP IM TEMPERATURE ALARM Check the connection of the PTC or FT of the ALWAYS ACTIVE insulation transformer Check the real temperature of the transformer In the event of not using the PTC or FT bridge terminals 12 T1 and 11 T2 of the DAP IM In the event of failure or breakdown the unit should be sent to your distributor or directly to AFEI Sistemas y Automatizaci n S A for it to be repaired by the technical service 15 SAFETY SETTINGS This unit is designed according to standards IEC 61557 8 IEC 60364 7 710 EN60601 1 EN60601 1 1 EN60601 1 2 it includes EN 55011 and EN 61000 4 2 EN 61000 4 2 EN 61000 4 3 EN 61000 4 4 EN 61000 4 5 EN 60601 1 4 and is supplied in good condition The proper safe functioning of the product implies that transport installation and assembly are in accordance with the standards described in this User Manual The unit does not have a fuse Therefore appropriate protection e