1. See the Access levels section Acoustic indicators The control panel uses the following acoustic indicators e Alarm indicator constant internal buzzer e Fault indication intermittent internal buzzer FEC403EN User Manual 9 Operating modes Standby mode When the control panel is in standby mode only the Supply on LED is activated There is no acoustic indicator Pre alarm mode zone 1 or zone 2 in alarm A pre alarm is indicated as follows e The general Fire LEDs are activated e The general fire relay is activated e The corresponding zone Fire LED is activated for example first alarm in zone 1 confirmed alarm in zone 2 zone 1 LED flashing zone 2 LED steady e The Activated LED is activated flashing e The internal buzzer is activated constant e The stage 1 sounder and associated LED are activated The illuminated warning sign is activated e The auxiliary output relays are activated if enabled e The call fire brigade call fire brigade delay is activated if set If configured to stage 1 alarm Control panel operation in Pre alarm mode The following operations can be performed in this mode e Silence the internal buzzer press the Silence Buzzer button e Silence the first stage sounder press the Sounder 1 stop button Restart the sounders by pressing the button again e Reset the system press the Reset button Caution Access level 2 is required to silence first stage so
2. 7 Out of service A constant yellow LED indicates that the control panel has lost power and battery voltage is below the minimum required value 22 VDC 8 Supply on A constant green LED indicates that the control panel is powered up correctly by either the mains power supply or battery 9 Disable general A constant yellow LED indicates that one or more features of the control panel have been disabled The corresponding LED for the disabled feature will also be activated 10 Test general A constant yellow LED indicates that one or more features of the control panel are in test mode The corresponding LED for the feature being tested will also be activated FEC403EN User Manual 3 11 Manual mode A constant yellow LED indicates that the control panel is in manual mode Manual mode may only be activated using an external key operated manual call point In manual mode extinguishing can only be activated by a start manual call point the extinguishing process will not start automatically if a fire alarm is detected in zones 1 and 2 12 Start MCP fault A constant yellow LED indicates that the start extinguishing manual call point has been disabled A slow flashing yellow LED indicates that there is a fault with the start extinguishing manual call point line supervision open or short circuit A fast flashing yellow LED indicates that the start extinguishing manual call point has been activated 13 Released A consta
3. Fault A constant red LED ACT indicates that the fire brigade output has been activated the call fire brigade procedure has started A flashing yellow LED FLT indicates a fault in the line supervision open or short circuit A constant yellow LED FLT indicates that the feature has been disabled or is in test mode check the general Disable 9 and general Test LEDs 10 for verification 23 Sounder 1 stop Active Fault A constant red LED ACT indicates that the first stage sounder pre alarm has been activated zone 1 or zone 2 is in alarm A flashing yellow LED FLT indicates a fault in the line supervision open or short circuit A constant yellow LED FLT indicates that the feature has been disabled or is in test mode check the general Disable 9 and general Test LEDs 10 for verification FEC403EN User Manual 24 Sounder 2 stop Active Fault A constant red LED ACT indicates that the second stage sounder alarm has been activated zone 1 and zone 2 are in alarm or a start manual call point has been activated A flashing yellow LED FLT indicates a fault in the line supervision open or short circuit A constant yellow LED FLT indicates that the feature has been disabled or is in test mode check the general Disable 9 and general Test LEDs 10 for verification 25 Silence buzzer A constant yellow LED indicates that the internal buzzer has been silenced 26 Reset A constant yellow LED i
4. the panel is in activated mode the extinguishing process cannot be disabled 6 FEC403EN User Manual A fault on the hold extinguishing manual call point or the abort extinguishing manual call point will automatically disable the actuator If the actuator is disabled automatically due to a manual call point fault it will be enabled after resetting the control panel assuming the fault has been fixed If the actuator has been disabled manually the disabled state is not changed by resetting the control panel C Test This feature can only be used when the control panel is in standby mode Tests a control panel controlled feature or component Limited testing is available in access level 1 What can be tested with level 1 access e All control panel LEDS e Internal buzzer Access level 1 test procedure 1 Press the Test button and keep it pressed 2 terminate the test depress the Test button While the test is active the Test button is pressed all control panel LEDS will be lit and the internal buzzer will sound continuously What can be tested with level 2 access e Zones zone 1 2 or 3 e Start extinguishing manual call point e Hold extinguishing manual call point e Abort extinguishing manual call point e Pressure switch e Gas flow switch e First stage sounder pre alarm e Second stage sounder alarm e Fire brigade e Illuminated warning signs Access level 2 test procedure To test zone 1 zone 2 zo
5. 61000 3 3 The EN12094 1 standard includes basic and optional requirements The optional requirements this product meets are Table 1 EN12094 1 optional requirements Clause Description 4 17 Extinguishing agent release delay 4 18 Signal representing the flow of agent 4 19 Monitoring of the status of components 4 20 Emergency hold device mode A or B 4 23 Manual only mode 4 24 Triggering signals to equipment within the system 4 26 Triggering signals to equipment outside the system 4 27 Emergency abort device 4 30 Activation of alarm device with different signals ii FEC403EN User Manual European regulations for construction products This section includes both regulatory information and a summary on the declared performance according to the Construction Products Regulation 305 2011 For detailed information refer to the product Declaration of Performance DoP Table 2 Certification CE Certification body 1134 Manufacturer Year of first CE marking Declaration of Performance number EN 54 Product identification Intended use Essential characteristics UTC CCS Manufacturing Polska Sp Z 0 0 UI Kolejowa 24 39 100 Ropczyce Poland Authorized EU manufacturing representative UTC Fire amp Security B V Kelvinstraat 7 6003 DH Weert The Netherlands 09 360 3319 0199 EN12094 1 EN54 2 EN54 4 Environmental Class A See model number on product identification label See DoP point 3 See DoP poi
6. Disabled mode The control panel allows each zone and selected system features and components to be disabled and enabled independently Caution When a zone is disabled none of the indications or events that may occur within the zone will be reported to the control panel Disabled mode is indicated as follows e LED indicators for general disable flashing and or zone disable constant e LED indicator for the disabled feature component constant e Acoustic indicator intermittent Control panel operation in Disabled mode See the Disable procedures outlined in LED indicators buttons and acoustic indicators on page 2 Test mode The control panel allows each zone and selected system features and components to be tested independently Test mode is indicated as follows e 1 LED indicator for Test constant e 2 LED indicator for the feature component being tested constant e 3 Acoustic indicator intermittent level 1 test only Control panel operation in Test mode See the Test procedures outlined in LED indicators buttons and acoustic indicators on page 2 Out of service mode The control panel enters into an out of service mode only when the mains power is out and the battery voltage is below 22 V In this mode there is no alarm or fault warning e LED indicators Fault flashing and Out of Service constant e Acoustic indicator intermittent e Activation of outputs activation of fault rel
7. EDWARDS FEC403EN User Manual P N 10 4101 505 2FC1 01 ISS 22JAN15 Copyright Trademarks and patents Manufacturer Version Certification a Contact information 2015 UTC Fire amp Security All rights reserved The FEC403EN name and logo are trademarks of UTC Fire amp Security UTC CCS Manufacturing Polska Sp Z 0 0 UI Kolejowa 24 39 100 Ropczyce Poland Authorized EU manufacturing representative UTC Fire amp Security B V Kelvinstraat 7 6003 DH Weert Netherlands This document applies to FEC403EN version 3 0 ce 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information see www recyclethis info 2006 66 EC battery directive This product contains a battery that cannot be disposed of as unsorted municipal waste in the European Union See the product documentation for specific battery information The battery is marked with this symbol which may include lettering to indicate cadmium Cd lead Pb or mercury Hg For proper recycling return the battery to your supplier orto a designated collection point For more information see www recyclethis info For contact information see www utcfssecurityproducts eu Content Important inf
8. ay potential free Caution When mains power is re established the control panel returns to its former status If the mains failure lasts for an extended time the panel will indicate Out of Service when the battery voltage reaches 19 V All panel operation will then stop 12 FEC403EN User Manual Control panel operation in Out of service mode No controls are available in this mode Caution To prevent possible damage to batteries it is recommended that the control panel is disconnected from the batteries when in Out of service mode FEC403EN User Manual In the event of fire or fault General Caution You must be familiar with the control panel LED indicators and buttons in order to be able to react accordingly Keep calm In an alarm situation the control panel activates the sounders to warn users about the event It is very important to keep calm regardless the acoustic signal so the right decisions may be taken Keypad access To operate the control panel keypad the access key must be set to level 2 keypad unlocked Press the Silence Buzzer button The user may press the Silence Buzzer button to silence the internal buzzer This will help to think about what to do under better conditions Sounders may also be stopped by pressing the corresponding sounder stop button Identify the alarm cause The LED indicators on the front of the control panel will help to identify what kind of alarm or fault has caused the syste
9. ctions Check that there are no manual call points activated without a series resistance To enable the zone turn the key to the ON position and press the key of the disabled zone To enable the keypad turn the key to the ON position Problem Cause Action to be taken An output generates a fault The current limit for the output Reset the panel to cancel the when activated has been exceeded current protection and correct the current consumption for the output so as not to exceed the current limit The solenoid or Incorrect configuration of DIP Check configuration of DIP pyrotechnic output does switches system switches 2 and 3 HOE WONG Check voltage from the outputs 16 FEC403EN User Manual Maintenance The following maintenance procedures should be performed System maintenance To guarantee correct functioning of the system and compliance with EN54 standards the following checks are recommended Daily Verification Check that the system is in ready status If the above is not so take the appropriate measures e g verification of incidents alerts to maintenance etc Weekly Verification Check at least one detector or call point to confirm the functioning of the panel make sure you do not always check the same one Quarterly Verification Carry out a quarterly verification by personnel who are experts in fire systems This check must test one device per zone supervising the activation of the co
10. dicator is on and the buzzer is sounding intermittently The panel has no power supply from the mains and is working with batteries There is a battery failure The voltage from the power supply is not correct 28V or 5V The general fault and out of service LED indicators are on and the buzzer is sounding intermittently The panel has no power supply from the mains and the battery is below 22 V minimum working voltage The indicated zone device has a fault The general fault input output and zone failure LED indicators are on flashing and the buzzer is sounding intermittently The indicated zone is disabled The general disabled and zone disabled LED indicators are on and the buzzer is sounding intermittently The panel does not respond to the keypad The keypad is disabled FEC403EN User Manual Action to be taken Check power supply 230 VAC Check power supply fuse Check battery Check power supply 230 VAC Check power supply fuse Check battery connection Check that battery voltage correct Check battery charger voltage is 27 6 VDC Disconnect the battery and the power supply until the mains voltage or charged batteries can be supplied Check the cable connection between the power supply and the PCB Check the end of line resistance of the zone Check that there are no short or open circuits in the lines Check that there are no inverted polarity detector conne
11. e sounder is restarted by pressing the button again F Sounder 1 stop Stops the first stage pre alarm sounder The sounder is restarted by pressing the button again G FBRIG start Calls the fire brigade level 2 access required If enabled the call fire brigade procedure will be activated automatically in the event of a fire alarm Note If there is no fire alarm the call fire brigade procedure cannot be started manually H FBRIG delay Starts the programmed fire brigade delay after which the call fire brigade procedure will be activated A constant yellow LED indicates that the programmed fire brigade delay has been activated the fire brigade will be called after the delay The delay can be cancelled by pressing the FBRIG delay button the fire brigade will be called immediately J Silence buzzer Silences the internal buzzer K Reset Resets the system Any fault or alarm that has not been resolved will be highlighted again The control panel Reset button is blocked when extinguishing has been activated until the extinguishing agent is released During this time the extinguishing process can only be cancelled using the abort extinguishing manual call point The delay from activation to release is programmed at installation maximum 30 minutes During the activation delay the control panel can only be reset after the programmed reset delay has completed the constant yellow LED for reset is off L Access key
12. icted access protocol for increased security Access levels are controlled via the access key see Figure 1 Access levels are as follows Access level 1 When the key is turned to the locked position access level 1 is active This access level allows activation of the Silence Buzzer button and cancellation of any programmed fire brigade delay via the FBRIG delay button No other system controls are available in access level 1 Access level 2 When the key is turned to the unlocked position access level 2 is active This access level allows full control of the extinguishing control panel and features and is reserved for the user responsible for operating the system Starting up the panel The panel can start up in one of two ways normal startup and a special startup sequence used after an internal fault has been detected by the panel in accordance with EN12094 1 The EN12094 1 fault startup is indicated by the following e General fault LED flashing e System fault LED slow flash e Reset LED flashing When the panel is in this condition pushing the reset button will restart the panel If the panel continues to detect a fault the startup sequence will not be completed and sytem fault LED will be activated constant LED indicators buttons and acoustic indicators See Figure 1 for the location of all items A reference in square brackets for example 9 refers to the item listing in this figure LED indicators 1 Fi
13. m to enter in the current state Act Once the cause has been identified react according to the emergency plan that must be defined at every site System reset Once the problem has been solved the system may be reset Extinguishing the two zones that are linked to an extinguishing area enter into an alarm mode then the panel will automatically start the extinguishing process If a delay has been programmed there will be some time available to evacuate the room The extinguishing process can be stopped by activating the abort extinguishing or the hold extinguishing manual call points If the risk situation cannot be controlled the extinguishing process may be started by activating a start extinguishing manual call point if an abort extinguishing manual call point has not been activated 14 FEC403EN User Manual Troubleshooting maintenance support This section provides information to help you diagnose and solve various problems that may arise while configuring or using your UTC Fire amp Security product Caution This product must be installed and maintained by qualified personnel adhering to all applicable standards and local authority laws Troubleshooting Solutions to common problems can be found in the following table Table 4 Troubleshooting common problems Problem Cause The service LED indicator is not on The panel has no power The general fault and power supply failure LED in
14. ndicates that the reset button is blocked by an activation delay described later 27 Auxiliary disabled A constant yellow LED indicates that the auxiliary output has been disabled 28 Warning sign fault A flashing yellow LED indicates that there is a fault with the illuminated warning sign line supervision open or short circuit A constant LED indicates that the sign is disabled or in test mode check the general Disable 9 and general Test LEDs 10 for verification 29 Evacuate sign fault A flashing yellow LED indicates that there is a fault with the illuminated evacuate sign line supervision open or short circuit A constant LED indicates that the sign is disabled or in test mode check the general Disable 9 and general Test LEDs 10 for verification 30 Released sign fault A flashing yellow LED indicates that there is a fault with the illuminated extinguishing released sign line supervision open or short circuit A constant LED indicates that the sign is disabled or in test mode check the general Disable 9 and general Test LEDs 10 for verification Buttons A Zones Z1 Z2 Z3 Enables disables a zone A disabled zone is indicated by a constant yellow LED B Disable extinguishing Used with the disable sequence described in Disable general Disables the extinguishing area and prevents activation of the extinguishing process Caution If extinguishing has been activated via a manual call point or if
15. ne 3 extinguishing fire brigade and stage 1 or stage 2 sounders 1 Press the Test button marked C in Figure 1 and the button of the function feature to be tested at the same time for example press Test and the Z1 button together to test zone 1 2 Repeat this process to terminate the test For the remaining level 2 test options 1 Press the Test button marked C in Figure 1 for 3 seconds and then select the feature component to be tested by pressing the Test button repeatedly until the LED for the desired feature component flashes quickly FEC403EN User Manual 7 2 To activate the test for the selected feature component turn the keyswitch to level 1 and then back to level 2 The corresponding output input will be activated for 3 seconds after which the system will be reset automatically While the test is active the feature component LEDs are ON constant There is no acoustic signal D Disable general Disables a control panel controlled feature or component Level 2 access is required Note This feature can be used when the control panel is in standby fault or pre alarm mode It cannot be used when the control panel is in alarm mode The control panel allows primary function disable and secondary function disable options Table 3 Primary and secondary disable functions Primary disable functions Secondary disable functions Zone 1 zone 2 and zone 3 Start extinguishing manual call point Exting
16. nt 9 FEC403EN User Manual FEC403EN User Manual User guide Keyboard layout Figure 1 Keyboard layout 00 O O O O 0 C_ C 0 OO 000 OO 0 000G Fire LEDs general zone Fault LEDs general zone Maintenance LED Fault return LED Supply fault LED System fault LED Out of service LED Supply on LED Disable LED general Test LED Manual mode LED Start MCP fault LED Released LED Extinguishing activated LED NR ID 2 42 2 2 42 ark Extinguishing fault disable LED 16 Hold MCP LEDs Active Fault 17 Abort MCP LEDs Active Fault FEC403EN User Manual 18 Gas pressure LEDs Active Fault 19 Gas flow LEDs Active Fault 20 Door monitor LEDs Active Fault 21 FBRIG delay LED 22 FBRIG start LEDs Active Fault 23 Sounder 1 stop LEDs Active Fault 24 Sounder 2 stop LEDs Active Fault 25 Silence buzzer LED 26 Reset LED 27 Auxiliary disabled LED 28 Warning sign fault LED 29 Evacuate sign fault LED 30 Released sign fault LED 6969 A Zone buttons 21 22 23 B Disable extinguishing button C Test button D Disable button general E Sounder 2 stop button F Sounder 1 stop button G FBRIG start button H FBRIG delay button J Silence Buzzer button K Reset button L Access key level 1 level 2 Access levels In accordance with EN54 guidelines the FEC403EN uses a restr
17. nt red LED indicates that the extinguishing agent has been released A flashing red LED indicates that the actuators have been activated and the panel is waiting for confirmation if the gas flow switch is configured 14 Extinguishing activated A flashing red LED indicates a pre alarm zone 1 or zone 2 is in alarm A constant red LED indicates an activated state zone 1 and zone 2 are in alarm or a start manual call point has been activated and that any configured extinguishing delay is running Note A delay of between 5 and 60 seconds may be programmed during installation for the extinguishing agent release 15 Extinguishing fault disable A constant yellow LED indicates that the automatic extinguishing process has been disabled via the control panel A flashing yellow LED indicates a fault in the extinguishing actuator circuitry 16 Hold MCP Active Fault A fast flashing yellow LED ACT indicates that the extinguishing process has been delayed by a hold extinguishing manual call point A flashing yellow LED FLT indicates a fault 17 Abort MCP Active Fault A fast flashing yellow LED ACT indicates that the extinguishing process has been cancelled by an abort extinguishing manual call point A flashing yellow LED FLT indicates a fault 18 Gas pressure Active Fault A fast flashing yellow LED ACT indicates that the gas pressure input has been activated the pressure in the gas bottles is low For some in
18. ormation ii Limitation of liability ii Agency compliance il European regulations for construction products iii User guide 1 Keyboard layout 1 Access levels 2 Starting up the panel 2 LED indicators buttons and acoustic indicators 2 Operating modes 0 In the event of fire or fault 14 General 14 Extinguishing 14 Troubleshooting maintenance support 15 Troubleshooting 15 Maintenance 17 Contacting technical support 7 FEC403EN User Manual Important information Limitation of liability Installation in accordance with this manual applicable codes and the instructions of the authority having jurisdiction is mandatory UTC Fire amp Security shall not under any circumstances be liable for any incidental or consequential damages arising from loss of property or other damages or losses owing to the failure of UTC Fire amp Security products beyond the cost of repair or replacement of any defective products UTC Fire amp Security reserves the right to make product improvements and change product specifications at any time While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents UTC Fire amp Security assumes no responsibility for errors or omissions Agency compliance This product has been designed according to the following standards e EN54 2 EN54 4 e EN60950 1 e EN12094 1 e ANPITN121 EMC Immunity EN50130 4 e EMC Emissions EN61000 6 3 EN61000 3 2 EN
19. re general Two red LEDs indicate an alarm in the system Flashing LEDs indicate that a detector has activated the alarm Constant LEDs indicate that a manual call point has activated the alarm 2 FEC403EN User Manual 1 Fire zone The zone in alarm is indicated by a red LED above the zone button zone 1 2 or 3 2 Fault general zone A constant yellow LED indicates that the zone is either disabled or in test mode A flashing yellow LED indicates a fault The zone in fault is indicated by a yellow LED above the corresponding zone button zone 1 2 or 3 Test or disabled status can be determined by the general Disable 9 or Test 10 LEDs described later in this section 3 Maintenance This feature is for installations using Clean Me enabled detectors only A constant yellow LED indicates that detector maintenance is required The detector zone is displayed when the Silence Buzzer button J is pressed for more than three seconds 4 Fault return A slow flashing yellow LED indicates a fault on the input A fast flashing yellow LED indicates that the input has been activated 5 Supply fault A constant yellow LED indicates a battery or mains power supply fault As a single LED is used to indicate both types of fault ensure that both mains and battery fuses are checked when a supply fault is indicated 6 System fault A constant yellow LED indicates that a software fault in the control panel has been detected
20. rresponding outputs verification of batteries and their load voltage Annual Verification All system devices must be checked annually Visually inspect all electrical connections to make sure that they are securely fastened that they have not been damaged and that they are appropriately protected Battery maintenance The batteries must be replaced periodically as recommended by the manufacturer The useful life of the battery is approximately 4 years Avoid the total discharge of the batteries Cleaning Keep the outside and inside of the panel clean Carry out periodic cleaning using a damp cloth for the outside Do not use products containing solvents to clean the unit Do not clean the inside with liquid products Contacting technical support For assistance installing operating maintaining and troubleshooting this product please contact your local supplier Be ready at the equipment before calling for technical support FEC403EN User Manual 17 18 FEC403EN User Manual
21. stallations this input is connected to the weight switch 4 FEC403EN User Manual A flashing yellow LED FLT indicates a fault in the line supervision open or short circuit A constant yellow LED FLT indicates that the feature has been disabled or is in test mode check the general Disable 9 and general Test LEDs 10 for verification 19 Gas flow Active Fault A fast flashing yellow LED ACT indicates that the gas flow input has been activated the gas is flowing from the bottles A flashing yellow LED FLT indicates a fault in the line supervision open or short circuit A constant yellow LED FLT indicates that the feature has been disabled or is in test mode check the general Disable 9 and general Test LEDs 10 for verification 20 Door monitor Active Fault A fast flashing yellow LED ACT indicates that the door monitor input has been activated In standby with the system in automatic mode the input is activated if the monitored door is open or if the system is in manual mode if the door is closed In activated or released state the input is activated if the door is open A flashing yellow LED FLT indicates a fault in the line supervision open or short circuit 21 FBRIG delay A constant yellow LED indicates that any programmed fire brigade delay has been activated Note A delay of between 1 and 10 minutes may be programmed for this feature during installation 22 FBRIG start Active
22. tivated e The illuminated warning sign is activated The two stage 1 alarm relays are activated if auxiliary outputs are enabled e The call fire brigade call fire brigade delay is activated if set e The general fire alarm relay is activated e The zone 3 fire alarm relay is activated Subject to configuration Control panel operation in Alarm mode zone 3 in alarm The following operations can be performed in this mode e Silence the first stage sounder press the Sounder 1 stop button Restart the sounders by pressing the button again e Reset the system press the Reset button Caution Access level 2 is required to silence first stage sounders and reset the control panel It is not recommended to reset the system until the location and cause of the alarm has been established Fault mode Faults are indicated as follows e LED indicators general fault flashing LED zone fault flashing LED power fault constant LED or sounder fault flashing LED e Acoustic indicator intermittent e Output activation of the fault relay potential free Control panel operation in Fault mode The following operations can be performed while the control panel is in fault mode e Silence the internal buzzer press the Silence Buzzer button e Reset the system press the Reset button Note Investigate the cause of the fault and make any required repairs before resetting the system FEC403EN User Manual 11
23. uishing Pressure switch Fire brigade Gas flow switch Stage 1 or stage 2 sounders actuators will be Illuminated warning signs automatically disabled Auxilliary output To disable a primary function 1 Press the general Disable button marked D in Figure 1 and the button of the function feature to be disabled at the same time for example press Disable and the Z1 button together to disable zone 1 Repeat this process to enable a disabled primary function For further details on disabling extinguishing see the Disable extinguishing section To disable a secondary function 1 Press the Disable button marked D in Figure 1 for 3 seconds and then select the feature component to be disabled by pressing the Disable button repeatedly until the LED for the desired feature component flashes quickly 2 To activate the disable option for the selected feature component turn the keyswitch to level 1 and then back to level 2 To enable a feature disabled in this way repeat the above procedure The disabled state is not changed by resetting the control panel While the feature component is disabled the general disable and feature component LEDs are ON constant Note If a disabled feature or component is enabled in alarm mode any programmed extinguishing delay will be activated before the extinguishing agent is released 8 FEC403EN User Manual E Sounder 2 stop Stops the second stage alarm sounder Th
24. unders and reset the control panel It is not recommended to reset the system until the location and cause of the alarm has been established Alarm mode zone 1 and zone 2 in alarm or a manual call point activated An alarm in zones 1 and 2 is indicated as follows e The general Fire LEDs are activated e The corresponding zone Fire LEDs are activated e The Activated LED is activated constant e The internal buzzer is activated constant e The stage 2 sounder and associated LED are activated e The illuminated evacuate sign is activated e The extinguishing agent release delay is activated if configured e The door monitor timer is cancelled if configured e The call fire brigade call fire brigade delay is activated if set e The Reset button is blocked and associated LED is activated Control panel operation in Alarm mode zone 1 and zone 2 in alarm 10 FEC403EN User Manual The following operations can be performed in this mode e Silence the internal buzzer press the Silence Buzzer button e Silence the second stage sounders press the Sounder 2 stop button if the panel is in released state Restart the sounders by pressing the button again Requires level 2 access Alarm mode zone 3 in alarm An alarm in zone 3 is indicated as follows e The general Fire LEDs are activated e The zone 3 Fire LED is activated The internal buzzer is activated constant e The stage 1 sounder and associated LED are ac