Home

OPC90 Server User Manual

image

Contents

1. Enter the desired value to be written in the current value field and click on the write button The entered value will be written The tag properties can also be modified Right click on the tag name and select the properties option The following dialog will be displayed Tag Properties Name Description Location Data Type amuryy v Simulation Constant Cancel This dialog allows the default native data type representation to be changed When simulation is enabled the type of signal to be applied can also be specified Note that changes to the data type and simulation signal apply globally to all blocks of the same type In other words if the native type or simulation signal for the OUT tag is changed for the AIL block the change applies to all AIL blocks 5 4 2 View Status Select Status Bar to enable and disable the program status bar When OPC90 is not in runtime mode the status bar presents tag summary information about the last RoviSys Company Copyright 1999 2015 Page 35 OPC90 Server User Manual V8 2 1 selected database entity When in monitor mode it presents the operational state of the selected database entity The status bar also presents the state of database shadowing off on current number of attached OPC clients total groups and tags those OPC clients have setup along with the current OPC data exchange rate for those tags A field shows if OPC90 is running as a service pr
2. RoviSys Company Copyright 1999 2015 Page 64 OPC90 Server User Manual V8 2 1 7 5 Data Acquisition Digital DADIG The DADIG OPC90 block is used to retrieve the exception reported output from Bailey Data Acquisition Digital blocks function code 21 1 Restrictions This OPC90 block cannot be used with NETWORK 90 interfaces It is valid for all INFI 90 interface types TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address ADDR NODE Bailey node address ADDR MODULE Bailey module address ADDR BLOCK Bailey block address OUTLSDO Output state zero logic state descriptor OUTLSD1 Output state one logic state descriptor MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor FACE TYPE Faceplate type value of DADIG block S17 ALARM Alarm active indicator ALARM TOGGLE Return alarm toggle indicator OPC STATUS OPC status value see OPC status section QUALITY Current quality of Bailey values 0 good 1 bad COMMAND VT_ 12 Read Write Bailey DADIG block control as follows note 1 0 Reset custom input 1 Set custom input 2 Select custom input 3 Select primary input 4 Select alternate input 5 Enable alarm suppression 6 Disable alarm suppression 7 Clear alarm latch 8 Disable exception reports from this block 9 Enable exception reports
3. 1 Off On Reset Set Zero One False and True Writing any of these strings is case insensitive 2 ERR CODE attribute indicates error codes when a bad start or fault condition arises The following error codes can be returned 0 no error 5 interlock 4 input 1 stop input 6 feedback 1 input is 0 2 interlock 1 input 7 feedback 2 input is 0 3 interlock 2 input 8 feedback 1 input is 1 4 interlock 3 input 9 feedback 2 input is 1 3 The FAULT_ACK tag should be set true 1 to acknowledge a fault or bad start condition and the Bailey RMC block will reset it to false 0 after acknowledgment is accepted RoviSys Company Copyright 1999 2015 Page 138 OPC90 Server User Manual V8 2 1 7 29 Remote Manual Set Constant RMSC The RMSC OPC90 block is used to retrieve and control the exception reported output from Bailey Remote Manual Set Constant blocks function code 68 Restrictions This OPC90 block can be utilized with all Bailey interface types except serial port module SPM amp CPMO2 Warning Do not use a series of these blocks to provide bulk transfer of data between the OPC client and ABB Bailey controller Instead use the OPC90 AOL block to source the OPC client data and ABB Bailey AI I FC 121 or Al L FC 26 blocks in the controller to receive the data TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address ADDR NODE Baile
4. Configure mode when writing blocks DELETE Enter the address of a block in the addressing section and click on this button to delete it from the ABB Bailey controller Note the module must be in Configure mode to delete blocks SAVE Click on this button to save the currently addressed module If no file name is entered in the File area the file name will automatically be based on the current ring node and module address For the above example it will be 00100103 C90 If the CFG radio button is selected it will be 10103 CFG to match Bailey CADEWS naming syntax This convention makes it easy to identify what Bailey module the file corresponds with Configuration data can be saved in one of two file formats The format is selected with the C90 and CFG radio buttons When the C90 radio button is selected the function block configuration data is saved into files that have a C90 extension This is the OPC90 file format The C90 files are stored in the ABB subdirectory unless an alternative directory path is included as part of a user inputted file name When the CFG radio button is selected the function block data is saved into files that have a CFG extension These files must already exist and are of the format generated by the ABB Bailey CADEWS software and its derivatives The CFG files are also stored in the ABB subdirectory unless an alternative directory path is incl
5. MB RX BYTE VT Ul4 Read Total number of bytes received from the module bus per second includes bytes of messages received and replies received MB RX MSG VT Ul4 Total number of messages received from module bus per second AVG MB RX MSG VT Ul4 Read Average total number of messages received from module bus per second MB TX BYTE VT Ul4 Read Total number of bytes sent to module bus per second includes bytes of messages sent and replies sent MB TX MSG VT Ul4 Read Total number of messages sent to module bus per second AVG MB TX MSG VT Ul4 Read Average total number of messages sent to module bus per second Notes 1 By writing to these tags the OPC client can set the NIS node address to be monitored Use the INTERVAL tag to set how often the communication statistics are read OPC90 will enforce valid ranges for these tags but it is the client s responsibility to write valid addresses of NIS nodes that actually exist The INTERVAL tag specifies how often the NIS statistical information are attempted to be read The minimum value it can be set to is 100 milliseconds The recommended interval setting is no less than the total number of NISMON and PCUMON blocks times 10000 Setting the INTERVAL to zero disables reading any information Up to 73 different statistics can be read based on the settings of the ENABLE NIS ENABLE NPS ENABLE MEM ENABLE XR ENABLE SYNC and ENABLE MAP tags Collection of this information is acc
6. TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Config Bailey PCU ring address see note 1 Read Write ADDR_NODE Config Bailey PCU node address see note 1 Read Write DEFAULT VT_BOOL Read Write Setup the default block settings when set RoviSys Company Copyright 1999 2015 Page 126 OPC90 Server User Manual V8 2 1 INTERVAL VT Ul4 Config Read Write MY BLOCK TYPE VT BSTR Read ENABLE CSV LOG VT BOOL Read Write ENABLE LOOP VT BOOL Read Write ENABLE NODE VT BOOL Read Write ENABLE NIS VT BOOL Read Write ENABLE MB VT BOOL Read Write THROTTLE MUXCIU VT Ul4 Read Write THROTTLE PCUMON VT Ul4 Read Write THROTTLE POLL VT Ul4 Read Write THROTTLE _SPEC VT Ul4 Read Write THROTTLE BLK VT Ul4 Read Write THROTTLE MODSTAT VT BOOL Read Write lt J N MESSAGE VT_BSTR Read TAG VT_BSTR Read TAGLONG VT_BSTR Read TAGDESC VT_BSTR Read OPC_STATUS cal Read QUALITY VT_BOOL Read SAMPLES VT Ul1 Read Write THROTTLE OVR VT BOOL Read THROTTLE VT BOOL Read COMM PCT VT Read COMM PCT AVG VT Read Desired update interval expressed as milliseconds see note 2 Indicates the OPC90 block type Enable logging of collected PCU statistics to a CSV log file see note 3 Enable collection of loop statistics see note 2 Enable collection of node statistics see note 2 Enable collection of NIS statistics see note 2 Enable collection of module bus statistics see note 2 MUXC
7. ccececsessscccececsesscecececeesesscesececeeseseseceeeceesenssaeeeeeceenes 184 12 24 OPC90 WILL ONLY RUN IN DEMO MODE cc scccscceceessseeececsessaececececcenesecececececseseaeceeecsesennsaeeeeseeenes 184 12 25 BORCING A GIU RESTART eerte ette atte acere E ARI eic dea 185 RoviSys Company Copyright 1999 2015 Page 4 OPC90 Server User Manual V8 2 1 1 Introduction The RoviSys Company has developed a tightly integrated interface between OPC clients and a Bailey DCS that promotes future plant upgrades using OPC This interface is called the OPC90 Server It allows easy and extremely user intuitive replacement of Bailey operator consoles with Windows based OPC client consoles It also provides an open migration path from the Bailey control platform to OPC as plant time resources and schedule permits The OPC90 Server enables seamless DCS access to the Bailey Controls Command Series NETWORK 90 INFI 90 Harmony and Symphony Distributed Control Systems The server can communicate at the network level via the appropriate Computer Interface Unit NCIUOX Plant Loop to Computer Interface INPCIOX Infi net to Computer Interface INICIO1 INICIOS INICI12 INICI13 IIMCP01 02 or within a single Process Control Unit via a Computer Interface Command CICO1 Serial Port Module NSPMO1 IMSPMO1 and Computer Port Module CPMO2 03 The bottom line is OPC90 can communicate with all interfaces available for NETWORK 90 INFI 90 Harmon
8. All Messages 50095 H Exception Reports 30770 0 Poll Messages 2138 0 Poll Block Output Values 1901 0 Block Spec Read Cycles 190 Turbo Exception Report Specs 190 Total Configured Blocks 5078 Active Messages Queued 35 Stale Error Responses 142 Note that the Time Sync DCS button shown on this faceplate only appears if the Device block has been setup to participate in time syncing It will appear gray while waiting for the proper conditions needed to request a DCS time sync to occur The CIU must be communicating not in standby operation and the current time sync master has been determined This is indicated by a non zero node number appearing for the current time sync master The current time sync master accuracy rating is also shown Note that if the accuracy setting configured in the DEVICE block properties is less than the current time sync master accuracy rating the CIU associated with this OPC90 cannot become time sync master The faceplate shows the total number of error responses received from the CIU The error response button can be clicked to generate a snapshot report of all current error counters and command counters since startup of OPC90 This report provides context specific suggestions based on the presence of particular errors as can be seen from the following example Block gt CIU Port gt S3000 Device INICIO3 G 3 RoviSys Company Copyright 1999 2015 Page 86 OPC90 Server User Manual V8 2 1 Total
9. PRE POS or SNP which corresponds to standard summary RoviSys Company Copyright 1999 2015 Page 141 OPC90 Server User Manual V8 2 1 pre fault post fault and snapshot type logs Note that Bailey blocks based on FC 243 generated by the INSEMO1 module only support standard and summary type events Consider the following examples 9 100 0420200702 STD 9 101 0228200701 SUM 9 102 0308200701 PRE 2 3 103 0308200701 POS 2 3 104 1225200699 SNP _2 _2 23 1 1 2 1 3 1 4 1 5 1 Example 1 is the 2nd standard SOE log captured on April 20 2007 by the SOE block at ring 1 node 2 module 3 and block address 100 Example 2 is the 1st summary SOE log captured on February 28 2007 by the SOE block at ring 1 node 2 module 3 and block address 101 Example 3 is the 1st pre fault SOE log captured on March 8 2007 by the SOE block at ring 1 node 2 module 3 and block address 102 Example 4 is the 1st post fault SOE log captured on March 8 2007 by the SOE block at ring 1 node 2 module 3 and block address 103 Example 5 is the 99th snapshot SOE log captured on December 25 2006 by the SOE block at ring 1 node 2 module 3 and block address 104 Note that this naming convention supports up to 99 capture files a a a a xxxxxxxx01 STD a a a a xxxxxxxx99 STD for each given log type to be recorded per day After generation of the 99 log file a a a a xxxxxxxx99 STD it will wrap back around to the b
10. amp 2il d 5 a Xa e Ad M KY A C D E F G H 1 POINT DATE TIME QUALITY ALARM SCAN VALUE TYPE NAME 2 3 09 26 2007 13 53 43 039 D 0 O Standard Burner Flame 4 E 5 09 26 2007 13 53 43 040 Standard Undefined 4 31 09 26 2007 13 53 43 041 Standard Undefined 5 11 09 26 2007 13 53 43 042 Standard Undefined 6 15 09 26 2007 13 53 43 043 Standard Undefined 7 19 09 26 2007 13 53 43 044 Standard Undefined 8 29 09 26 2007 13 53 43 045 Standard Undefined 9 33 09 26 2007 13 53 43 046 Standard Undefined 0 116 09 26 2007 13 53 43 047 Standard 2EL XSTOO M 4 gt 4X1 1 3 5700 0926200701 Bie Ready NUM eojojmij1mlojojojo Cco0o0oO0O0 4 OoimdpDimmDoiojojojo o O o The SOE EVENT tag is used control browsing of SOE log files The OPC client sets this tag to indicate its need to look at SOE log file data When SOE EVENT is set the most current SOE log file for the given log type is automatically opened Note that if the OPC client has not set SOE EVENT and a Bailey SOE block capture event occurs the SOE EVENT tag will automatically set The SOE FILE tag indicates the currently opened file SOE COUNT the number of records in that file SOE RECORD the current record number and SOE_POINT_ provides all of the point information contained by that record The SOE NEXTREC tag can be set to advance to the next record within the current file or SOE RECORD written to a specific record number within the file The SOE NEXTF
11. by the following E Local Security Settings File Action View Help x gle E BA Security Settings 49 Account Policies 2 Local Policies GQ Audit Policy 39 User Rights Assignment Security Options 4 Public Key Policies E Software Restriction Policies E 3 IP Security Policies on Local Computer Policy Security Setting RE Network access Do not allow storage of credentials or NET Pa RE Network access Let Everyone permissions apply to anonymous RE Network access Named Pipes that can be accessed anonymously 8 Network access Remotely accessible registry paths letwork access Shares that can be accessed anonymously letwork access Sharing and security model for local accounts Re Network security Do not store LAN Manager hash value on ne Network security Force logoff when logon hours expire RE Network security LAN Manager authentication level RE Network security LDAP client signing requirements RA Mehuinek serrit Minimin ceccinn ceciwity For NTI M SSP hace Disabled Disabled COMNAP COMNODE SQL QUERY SPOOLSS LLSR System CurrentControlSet Control ProductOptio COMCFG DF5 Classic local users authenticate as themselves Disabled Disabled Send LM amp NTLM responses Negotiate signing Mo minimi in Double click on Network access Sharing and security set it to Classic as shown by the following dialog model for local accounts and Network access Sha
12. A space must be included between the command and user name or code Command entry including the user name is not case sensitive The result of the command is returned in this tag The following example shows the three tags associated with red tagging along with the results of the set command TurboListAnalysis cfg OPC90 Server Ds e BIO e Tw E ue Name Location Data Type Access Value Description Last Update Write a Tag Value to Bailey x X PID BLOCK 1 1 3 800 SHORT RW 807 PID SMITH block address 04 17 2012 07 31 28 134 PV 1 1 3 800 FLOAT R 76 000000 Current Process Variable 04 17 2012 07 32 26 771 TagName RED CMD PV BLOCK 1 1 3 800 SHORT R 820 Process variable block address 04 17 2012 07 31 28 134 3 PV_HI_LIM 1 1 3 800 FLOAT R Description Red tag command PV LO LIM 1 1 3 800 FLOAT R OPC Tag Data 3k QUALITY 1 1 3 800 BOOLEAN R 3 RED CMD 1 1 3 800 STRING Ri Curent Value Set Joel RED TAG 1 1 3 800 BOOLEAN R Off Red tag indicator 04 17 2012 07 32 26 771 p RED USERS 1 1 3 800 STRING R None Current red tag users 04 17 2012 07 33 35 834 Current Quality Good RI 1 13 800 FLOAT R 0 000000 Ratio Index 04 17 2012 07 32 26 771 R R R R RI R 876 000000 PY high Limit 04 17 2012 07 32 36 448 76 000000 PY low Limit 04 17 2012 07 32 36 448 Good Quality 0 Good 1 Bad 04 17 2012 07 32 26 771 Red tag command 04 17 2012 07 33 35 834 r SP 1 1 3 800 FLOAT 294
13. DEFINE SYSTEM NODE 61 Always returns a ACK response 7 17 1 MUXCIU Virtual Port API The OPC90VPort API allows third party applications that utilize the CIU for non database type of activities to safely and easily share the CIU with OPC90 without the need for a physical connection The third party application can be running on the same PC as OPC90 or on another PC that is on the same network as the OPC90 PC This API is implemented as a C class and contains three functions These functions are OPC90Connect OPC90CommandCIU and OPC90Disconnect These three functions are callable in the OPC90VPort dll See the OPC90Vport h header file for details of calling each function That header must be included in the third party applications development environment along with the OPC90VPort lib file OPC90Connect is used to establish a virtual connection with a specific MUXCIU block configured in the OPC90 database and setup for virtual communication Once connected the third party application is granted exclusive use of that block OPC90CommandCIU is used to send CIU commands to the actual CIU via the MUXCIU block virtual connection These commands are of the format of fully byte stuffed array that would normally be ready to send to the physical CIU by the third party application The return from this function is the response for the command OPC9O0Disconnect is used to give up the virtual connection with the MUXCIU block The OPC
14. TAGDESC Indicates the block descriptor COMM STATUS Communication channel status A value of zero indicates good and one means bad MSG TOTAL VT I4 Running count of total messages being exchanged with the external Bailey configuration software MSG RATE Messages per second being exchanged with the external Bailey configuration software NAK TOTAL VT l4 Read Running count of total negative acknowledgments sent to the external Bailey configuration software RoviSys Company Copyright 1999 2015 Page 100 OPC90 Server User Manual V8 2 1 The following diagram shows the logical connections when utilizing the MUXCIU block RoviSys OPC90 Server WinCAD Composer i MUXCIU E xc ou DEVICE M 9 Any ER E mE M Port E EB COM or SCSI i Port DBDOC lt gt MUXCU COM Port Block Up to 8 COM Ports RCAD lt gt MUXCU COM Port Block The following table lists some of the Bailey interface commands supported by the MUXCIU block Commands not supported will receive a Command Not Supported NAK 3 response When the Read only operation option is enabled commands that cause changes in the ABB Bailey DCS will not be sent to the CIU and a Command Not Supported NAK 3 response will be generated Command Command Code Response RE READ REPLY 9 Resends the last command response MODULE OPERATION 12 ACK NAK code indicating requested result REA
15. The RMC type code is a number used by the Bailey consoles to identify characteristics of its RCM faceplate display Currently a value of zero is the only valid code 3 When the Device block Set bad quality of max exception timeout property is enabled the QUALITY tag of this block will be set bad if writes to the block input s do not occur within the Exception Report Output Max Time setting of the block When this occurs bad quality will also be written to the CIU and therefore propagated to the users of the block data within the ABB Bailey system The quality can also be set bad by writing a one 1 to this tag 4 The RMC ERR CODE codes are defined as 0 no error 1 stopped by logic 2 interlock one is not set 3 interlock two is not set 4 interlock three is not set 5 interlock four is not set 6 feedback one is not reset 7 feedback two is not reset 8 feedback one is set 9 feedback two is set The appropriate error code must be written when a bad start or fault condition occurs Application The OUT tag reports the state of the device as off 0 or on 1 This block does not support mode The RED TAG tag allows the OPC client to indicate the device is currently under a red tag condition It is always considered to be in manual mode and under both logic and operator control Before a device can be commanded to the on state its four interlock inputs and two start permissive inputs must all be set The in
16. The second is monitoring for the absence of GetStatus messages that OPC clients typically send to servers Do not set this option if there are a mixture of OPC clients on the same PC running OPC90 and external PCs It is ok to set if all OPC clients are on the same PC as OPC90 or all OPC clients are on external PCs to the one running OPC90 Setting abandon dead client causes OPC90 to give up memory associated with a declared dead OPC client as detected by either of the two dead OPC client monitoring options 5 4 View The view menu option allows selection of monitor mode status bar startup in runtime and run as service options The following picture shows these available View menu items RoviSys Company Copyright 1999 2015 Page 33 OPC90 Server User Manual V8 2 1 pBDocTestWithXrps cfg RoviSys OPC90 Server Runtime Mode File Add Edit JEJA Utilities Help Dele fa v Monitor v Status Bar gt a H ciu Last Update v Startup in Runtime 3001 INT All Comm Status 0 Good 1 Bad 09 16 2015 15 11 21 031 v Run as Service 2 A S3001 INT Block specification read cycles completed 09 16 2015 15 11 21 031 S3001 INT Indicates data should now be available 0 Yes 1 No 09 16 2015 15 11 21 031 Lockout OPC Access d S3001 STRING RW CSV file to import 09 16 2015 15 11 21 031 Refresh A J 3001 BOOLEAN RW Request read of the import CSV file 0 Done 1 Read 09 16 2015 15 11 21 031 X IMPORT RESULT S3001 STRING R Resu
17. Name FD Fan 3 Point 003 Name FD Fan 4 Point 004 Name Soot Blower 1 Point 005 Name Soot Blower 2 Point 006 Name Soot Blower 3 Point 007 Name Soot Blower 4 Point 008 Name Pulverizer 1 Point 009 Name Pulverizer 2 Point 010 Name Pulverizer 3 Point 011 Name Pulverizer 4 Point 012 Name 1st Stage Turbine Vibration Point 013 Name 2nd Stage Turbine Vibration Point 014 Name 3rd Stage Turbine Vibration Point 015 Name Low Pressure Header Point 016 Name High Pressure Header DOO FD Fan 1 Set Delete Cancel SET 02 RoviSys Company Copyright 1999 2015 Page 25 OPC90 Server User Manual V8 2 1 Select the current set SET 01 to SET 04 to be defined using the list box at the bottom right of the dialog The current point definition for that set is displayed in the large list box The point number and name is displayed Click on a point number to be edited Its point number and name are displayed at the bottom of the dialog Type in the point name and click the Set button to define that point Use the tab key to signify entry of a new value Click the Delete button to undefined the selected point Point names must be unique within each set SOE point definition can also be accomplished using the OPC90 import feature Consult the CSV file format section for specific information on how to define SOE point names 5 3 8 Properties Select Edit g
18. Note that communication with the INICIO3 interface can be either RS232 or SCSI RoviSys is extremely knowledgeable on the use of the various Bailey interfaces and has implemented a single driver that can utilize the following types of interfaces Bailey Interface Max Number Exception Control Bailey Blocks Reporting Operation NSPMO01 500 No No IMSPMO 1 500 No No IMCPMO2 500 No No IMCPMOS 500 Yes Yes NCICO1 500 Yes Yes NCIUO1 500 Yes Yes NCIUO2 2 500 Yes Yes NCIUOS 5 000 Yes Yes NCIU04 10 000 Yes Yes INPCIO1 500 Yes Yes INPCIO2 5 000 Yes Yes IIMCPO1 10 000 Yes Yes IIMCPO2 30 000 Yes Yes INICIO 1 10 000 Yes Yes INICI12 see note 1 10 000 Yes Yes INICI13 see note 1 30 000 Yes Yes INICIOS see note 1 30 000 Yes Yes IET800 see note 2 30 000 Yes Yes 1 When using these interfaces the ABB Bailey semAPI software environment is not required The INICI12 INIC13 and INICIOS do not support dual channel serial communication When using serial communication to the INICI12 INICI13 and INICIO3 make sure the cable is attached to the port labeled terminal on the ABB Bailey termination unit or termination module See the sections Add and Device Definition Block for information regarding SCSI communication with the INICIO3 RoviSys Company Copyright 1999 2015 Page 8 OPC90 Server User Manual V8 2 1 a INICIO3 sites containing INICTOS3A firmware revision F must upgrade to revision G or later or down
19. Note that text message number mapping can also be defined using the Import CSV program feature The Bailey TEXT block F C 151 exception reports text message numbers that can be received and reported as OPC tags with the OPC90 TEXT block This block provides both a message number tag called MSG OUT and message string tag called MSG OUT TEXT When this menu item is selected the following dialog is displayed RoviSys Company Copyright 1999 2015 Page 22 OPC90 Server User Manual V8 2 1 Text Messages D Set Delete Cancel The text message number to string value mapping is global to all OPC90 TEXT blocks Use of the MSG_OUT_TEXT OPC tag is optional Its purpose is to simplify OPC client display of Bailey text messages Note that text message mapping is changeable online while OPC90 is providing data to attached OPC clients The maximum string size for a text message is 132 characters Up to 10 000 message numbers can be mapped 5 3 6 Red Tag Users Select Edit gt Red Tag Users to define users for the Bailey red tag system OPC90 supports the definition of 128 red tag users This dialog is used to assign a user code to a username Note that red tag user mapping can also be defined using the Import CSV program feature The Bailey red tag system allows users to mark blocks to be in the red tag state The Bailey red tag system supports up to 3 simultaneous users to have a given block marked in the red tag state Within th
20. OPCServer GetltemID OPCGroup Validateltems OPCServer BrowseAccessPaths OPCGroup Removeltems OPCGroup SendCancelCallback OPCServer GetltemD ata OPCGroup SetActiveState OPCGroup Advise OPCS erver QueryAvailableProperties OPCGroup SetClientH andles CEnumltemlDs OPCS erver GetltemProperties OPCGroup SetDatatypes CEnumltem ttributes OPCS erver LookupltemlDs OPCGroup CreateE numerator Trace Enable OPCServer SetLocalelD OPCGroup DAdvise OPCServer GetLocalelD OPCGroup DUnadvise Alon OPCServer QueryAvailableLocalelDs OPCGroup EnumDAdvise All Off OPCServer SetClientName OPCGroup QueryGetData OPCGroup GetData OPCGroup UpdateClients OPCGroup AsyncUpdate OPCGroup CreateD ataStream OPCGroup CreateD ataT imeStream OPCGroup Refresh2 OPCGroup Cancel2 OPCGroup SetEnable OPCGroup GetEnable OPCGroup SendOPCD ataCallback OPCGroup Send4synclO2Callback S1111113 11117 e r r v P r r r r r r r r r r WTI iti ISISISET M Trace OPC functions When the error detection log is enabled OPC90 logs all errors returned to OPC clients It will also log all fatal errors encountered such as CIU communication faults The maximum size of the log file can be set in the range of 1 to 100 megabytes When the log file reaches the maximum size it is closed and a new one opened This is also true of the first category of logs previously mentioned Error logs both categories are automatically
21. The block type and address is also provided The block description is beneath the block name Also the block tree location is automatically selected and opened in the OPC90 main program window After searching is complete exit the dialog by clicking done which saves the search setup data for the next time the searching is invoked Click on cancel to exit the dialog without saving the search setup data RoviSys Company Copyright 1999 2015 Page 41 OPC90 Server User Manual V8 2 1 6 Groups There are two different types of groups to keep in mind The first is the OPC90 Server organization of blocks within groups This is created within the OPC90 Server configuration and is simply a collection of OPC90 Server blocks or other groups An OPC90 Server group can be compared to a directory within a file system Where in this case the root directory is always an OPC90 DEVICE block An OPC90 group is only used to store other OPC90 groups or collections of similar OPC90 blocks No tags exist within an OPC90 group tags only exist within an OPC90 block When OPC90 is not in runtime operation it supports drag and drop at the group and block level A block can be moved from one group to another by dragging it to another group and dropping it there Likewise dragging an entire group is also supported All blocks within that group are included in the drag and drop operation The drag and drop feature is also disabled when a second instance of OPC90 is
22. XRP TX PACK PCT When ENABLE NPS COMM PCT AVG COMM PCT GMI RX AVG GMI RX GMI TX AVG GMI TX XRP RX AVG XRP RX XRP TX AVG XRP TX LOOP TX BYTE LOOP TX MSG AVG LOOP TX MSG NODE RX BYTE NODE RX MSG AVG NODE RX MSG NODE TX BYTE NODE TX MSG AVG NODE TX MSG NIS RX BYTE NIS RX MSG VT Ul4 VT Ult Read Read Exception transmit packet count Exception receive pack percentage see note 4 VT Ult Exception transmit pack percentage see note 4 EE Node Performance Statistics VT UM Read Percentage of this node s communication d iudi module processing power currently being used Average percentage of this node s communication module processing power currently being used VT_ eed Number of GMI messages per second being received by this node Average number of GMI messages per second being received by this node Number of GMI messages per second being transmitted by this node Average number of GMI messages per second being transmitted by this node Number of exception report values per second being received by this node Average number of exception report values per second being received by this node Number of exception report values per second being transmitted by this node Average number of exception report values per second being transmitted by this node Total number of bytes transmitted forwarded and originated by this node per second VT_UI4 Read Total number of messages transmit
23. module see note 2 STAT BYTEO to VT I2 Read Bailey module status bytes Only the first 5 STAT BYTE16 are valid for Command Series and Network 90 systems All sixteen are valid for Infi 90 RoviSys Company Copyright 1999 2015 Page 95 OPC90 Server User Manual V8 2 1 systems STAT BYTEO1 BITOto VT BOOL Read Bailey module status bytes broken apart into STAT BYTE16 BIT7 individual bits All eight bits are presented for all sixteen module status bytes Bit 0 is the least significant bit Notes 1 When retrieving the module status of a CIU interface special attention must be given to the settings of ring node and module For all CIU interfaces except the CIUO1 the ring must match the ring address of the CIU node must match the node address of the CIU and module must be set to a value of two For the CIUO1 interface ring and node must be set to a value of zero and module to a value of two Failure to follow these rules will result in improper or no module status returned for the CIU interface The status of the Bailey module is returned as a string in the following format lt Type gt State lt Errors gt where type indicates the module type AMM MFC COM etc state indicates its current state of operation Execute Configure Error and errors are a summary of any current errors it is experiencing The text for module state and type are defined in the OPC90 BLY INI file stored in the w
24. range of 0 2 where 0 manual 1 auto and 2 RoviSys Company Copyright 1999 2015 Page 73 OPC90 Server User Manual V8 2 1 AUTOMATIC SEND STN Boolean Config CPU OK NODEO 1 to NODE63 o mE AUTO DISCONNECT Boolean Config cascade ratio This representation is the same regardless of the current station operating level local or computer The station level is monitored and controlled using the STN LEVEL tag Setting this option changes the STN mode representation to be in the range 0 5 where 0 local manual 1 local auto 2 local cascade ratio 3 computer manual 4 computer auto and 5 computer cascade ratio This option allows OPC clients to control STN mode and level via the STN MODE tag Instructs OPC90 to send CPU OK messages to any STN block that is in computer level control The frequency of these messages will be 34 of the current STN block computer watchdog time setting Defines the node map required for ABB Bailey Network 90 systems when the time synchronization option has been enabled see note 2 For each possible node number one of the following choices must be selected Vacant 1 4K Tag OIU PCU CIUO1 Other The node map must be accurately defined for time synchronization to function correctly on Network 90 based systems These attributes are ignored when time synchronization is disabled or an Infi 90 system has been specified or detected Two types of simula
25. receives a trip signal The OPERATION tag can be used to change the current operating mode of any Bailey controller The MODE tag can be used to monitor the module s current mode of operation It will return a text message indicating the current operating mode WARNING changing the operating mode of a controller from execute to configure can cause a plant trip or major outage to occur For this reason writing to the OPERATION tag has been placed under password control When the OPC90 BLK is configured a case sensitive password is assigned to it Before OPC90 will accept writes to the OPERATION tag the OPC client must first write the correct password to password has never been received or the received password is incorrect The PASSWORD tag returns the text when the correct password has been received After password validation writes to OPERATION will cause the currently addressed module set using the ADDR RING ADDR NODE and ADDR MODULE tags to transfer to the requested operating mode The following OPERATION tag writes are supported 1 Request module to perform a software reset 2 Request module to enter the configure mode of operation 3 Request module to enter the execute mode of operation 4 Request module to initialize clear its current block configuration RoviSys Company Copyright 1999 2015 Page 52 OPC90 Server User Manual V8 2 1 Completion of the requested module operation is flagged when the OPE
26. slowdown OPC90 polling activities should reduce that influence If it doesn t the XRP RX LEVEL can be adjusted downward to restore normal OPC90 polling rates Monitoring for this condition can be disabled by setting XRP RX LEVEL to zero XRP RX LEVEL to a value of negative one also disables the condition check and stops periodic reading of XRP RX RoviSys Company Copyright 1999 2015 Page 130 OPC90 Server User Manual V8 2 1 14 The node transmitted exception report rate XRP TX is periodically read by this block when XRP TX LEVEL is greater than 1 Each value is submitted to a moving average calculation made available as the XRP TX AVG tag If the value of the XRP TX AVG tag becomes less than the XRP TX LEVEL tag setting a THROTTLE condition slowdown polling is declared While in this condition the throttle factors see note 3 will be applied to the OPC90 polling activities If OPC90 polling activities is reducing the PCU node s ability to exchange exception reports the throttled slowdown OPC90 polling activities should reduce that influence If it doesn t the XRP TX LEVEL can be adjusted downward to restore normal OPC90 polling rates Monitoring for this condition can be disabled by setting XRP TX LEVEL to zero XRP TX LEVEL to a value of negative one also disables the condition check and stops periodic reading of XRP TX Application This block s faceplate is very useful for observing the node performance statistics and set
27. state 1 two state 2 and three state 3 Writing any of these values to REQ STATE commands the MSDD to that associated state If the controller MSDD block has pulsed outputs enabled S22 non zero the REQ STATE will automatically reset to the default state 0 when the pulsed outputs return to the default state This feature can be disabled by turning off the OPC90 Device block MSDD Pulse Out Handling property Text strings can be written to this tag to control the MSDD requested state Valid text strings are the GSLSDO GSLSD1 GSLSD2 and GSLSDS settings along with Default 0 1 2 3 State 0 State 1 State 2 State 3 StateO State1 State2 and State3 Writing any of these strings is case insensitive Travel indicator is not actually received from Bailey but composed by the driver for display indication purposes lt is set for the interval of time between commanding a new requested state and waiting for the good state to arrive at the requested state while no alarm has been flagged by the Bailey MSDD block Page 98 OPC90 Server User Manual V8 2 1 7 17 Multiplex CIU MUXCIU The MUXCIU OPC90 block allows a configuration utility program requiring communication access to the Bailey system to share the CIU device associated with the OPC90 DEVICE block This block does not support programs that need to establish points in the CIU Use this block to allow the G Michaels DBDOC Ba
28. throughput The decision of Bailey node address assignment should be based on whether or not any OPC90 Server AOLs DOLs ODDs OMSDD ORCMs ORMCs ORMSCs or OSTNs blocks are to be utilized When they are used the Bailey interfaces should be assigned the same node address Otherwise when AOLs DOLs ODDs OMSDD ORCMs ORMCs ORMSCs and OSTNs are not used unique node addresses should be assigned to take advantage of the extra throughput When the interfaces are assigned unique addresses exception report collection will be temporarily stopped on the secondary interface when loop tuning software has one or more STN blocks in fast update mode This allows the use of that interface for the required STN fast update poll commands This feature helps facilitate tuning of fast loops that typically require 4 or more updates per second even Page 78 OPC90 Server User Manual V8 2 1 when the active database is very large When the STN blocks are taken out of fast update mode exception report collection on the second interface will resume m The DEVICE definition block support selection of several time syncing options Note that the ability for time syncing to function correction depends on several factors The most important being that the ABB Bailey interface supports the time syncing feature Those interfaces that do not support time syncing are NSPMO1 IMSPM01 IMCPMO2 NCIUO1 and INPCIO1 Note also that time syncing will not work properly on Netwo
29. 000000 Current Control Set Point 04 17 2012 07 32 26 771 TimeStamp ii SP HI LIM 1 1 8800 FLOAT 640 000000 SP high limit 04 17 2012 07 32 36 448 recu DNUNE 3 SP LO LIM 1 1 3 800 FLOAT 40 000000 SP low limit 04 17 2012 07 32 36 448 SP TRACKING 1 1 3 800 BOOLEAN Off Set point tracking indicator 04 17 2012 07 32 26 771 3 STN_LEVEL 1 1 3 800 BOOLEAN Off STN level 0 Local 1 Computer 04 17 2012 07 32 26 771 wame STN OK 1 1 3 800 BOOLEAN off STN computer OK indicator 0 Bad 1 Good 04 17 2012 07 32 26 771 3 STN TIMER 1 1 3 800 INT R 0 STN time seconds since last computer write 04 17 2012 07 32 26 771 Close X STN TYPE 1 3 800 SHORT R 4 STN Type 1 Basic 2 Ratio 4 Cascade 04 17 2012 07 32 26 771 V 0 of Clients 31 Groups 61 Tags 27795 Rate 2105 Service Run STN ONLINE 5 3 7 SOE Point Names Select Edit gt SOE Point Names to define sequence of event point names referenced by the OPC90 SOE blocks Definition of four sets of SOE point names is supported Each set defines 512 points When SOE data is received from the ABB Bailey system that data identifies points by their number 0 511 Those numbers are associated with point names defined by this dialog The various SOE files generated by OPC90 contain both the point number and point name When this menu item is selected the following dialog is displayed SOE Point Names Point 000 Name FD Fan 1 Point 001 Name FD Fan 2 Point 002
30. 05 Compliant License Information Serial Number 2522 Remaining Days 0 Payment Past Due Maximum OPC Clients No Limit Maximum Blocks CIU Capacity Maximum MUXCIU Blocks Total Free COM Ports Wise Men Lay Up Knowledge Free Disk Space 1484784 KB Free on C Available Memory 2097151 KB Copyright 1999 2012 The RoviSys Company If the software has been purchased directly from RoviSys please ask your company s accounts payable department payment to issue payment If the software was purchased from a reseller please contact them about why they have not paid for the software Once payment is received by RoviSys the license day limit will be removed Until that occurs restart OPC90 every 8 hours Note that the hardware key does not have to be returned to RoviSys The license update is handled via email A license update file is emailed This file is used to immediately update the hardware key to remove the day limit 12 19 SCSI Addresses Different Between Two Shadowed PCs The SCSI address of ABB Bailey INICTOSA 13A modules must be identical between shadowed OPC90 PCs The address assigned to SCSI devices has three components which are port number card number and device on that card For example the address S2107 indicates port two card one and device seven Windows automatically assigns the port number based on when new hardware is added Therefore sometimes this port number assignment can end up being different betw
31. 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 Clients 31 Groups 61 Tags 27795 Rate 3785 Service Run CIU ONLINE Unlimited v7 5 1 The File menu item supports generation of new databases opening an existing database saving a database enabling disabling auto save creation of database points by importing a CSV file and saving of the database in CSV file format The Add menu item supports addition of new database devices groups and blocks The Edit menu item supports deletion of database entities devices groups and blocks definition of communication port parameters mapping of engineering unit strings definition of text messages setting up red tag users and viewing of database entity properties The View menu item supports selection of monitor mode program status bar starting up in run time mode and enabling or disabling OPC90 as a service The Utilities menu item can be used to run the Windows service manager or DCOMONFG programs along with viewing OPC90 log files RoviSys Company Copyright 1999 2015 Page 13 OPC90 Server User Manual V8 2 1 The Help menu item is used to find blocks invoking online help and determine program version number 5 1 File The following pictur
32. 1P IP address here Port Secondary Pott TCP 1 S v IP address here Port When setting up a Lantronix device part of that setup includes assigning an IP address to it By definition the Lantronix first port number at that IP address will be 10001 This information is available from the Lantronix Devicelnstaller and or CPR Manager software When setting up the Lantronix device make sure to define the default baud rate and serial communication settings to match the settings of the CIU it is being cabled with The recommended settings are 19200 baud 8 data bits 1 stop bit no parity Define the Lantronix device IP and port number in the OPC90 DEVICE block Primary Port and Secondary Port if using dual port configuration property area It will look like this Device Properties Name CILI Description Infi 90 CIU COMMUNICATION PARAMETERS Scheme Redundant Channel v Primary Port TCP 1P E 172 24 210 77 10001 Secondary Port TCP_1S 172 24 210 77 10002 RoviSys Company Copyright 1999 2015 Page 84 OPC90 Server User Manual V8 2 1 Note this example is using a CIU that supports two serial ports so the redundant channel scheme is shown Most installations only use the Single Interface scheme so only the Primary TCP port would need to be defined for that case Definition of this information must be done on each PC running OPC90 The TCP IP addresses and port numbers are saved in the registry and not in
33. 90 OPC90 Server User Manual V8 2 1 7 11 Harmony Analog Input HAI The HAI OPC90 block is used to retrieve the exception reported output from Bailey Harmony Analog Input function code 222 blocks Restrictions This OPC block is only valid for Bailey interface types INICIO3 INICI12 and INICI13 TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address ADDR NODE Bailey node address ADDR MODULE Bailey module address ADDR BLOCK Bailey block address MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor CHAN NAME Channel name assigned to this point CHAN TYPE Channel type code CHAN STATE Channel state 0 Ok 1 Open 2 Short 3 Overdrive ALARM CODE Alarm code OPC STATUS OPC status value see OPC status section QUALITY Current quality of Bailey values 0 good 1 bad QUAL PROP Propogated Quality 0 Good 1 Bad OUT Current output value from Bailey HIGH High signal value in Engineering Units LOW Low signal value in Engineering Units SIG CHANGE Significant change in 96 of range EU Engineering Units Code EU TEXT Engineering Units String HI LIM VT R4 Read Write Alarm limit used to detect the high alarm condition Writing to this value tunes the alarm limit of the associated Bailey block LO LIM VT R4 Read Write Alarm limit used to de
34. 92 7 13 HARMONY DIGITAL INPUT HDI ersteren ae renee seitin eneee o e nennen netter ie er rier eren ens 93 7 14 HARMONY DIGITAL OUTPUT D O a a a e aaa ETET 94 AIS MODULE STATUS MO DS T AT eee a a eere nre et ilie E e edle irt e e eren 95 7 16 MULTI STATE DEVICE DRIVER MSDD 0 ccccccesssececsssceceeseeecsensececseneeceesaececseaaececseaeeseesaeeecneaeeeeneaeeeess 97 7 17 MUETIPLEX CIU MUXCIU 5 4 pee E eter ede E EER SERERE De EER E TR Sek perce 99 TAk SOMUXCIU Virtual POYtAPL us i eto t e t ra be i e i 102 7 18 NETWORK INTERFACE SLAVE MONITOR NISMON esses ener ener enne enne 104 LAS OUTPUT DEVICE DRIVER ODD eis cess rie HE ise a RA aire ade ete teca 112 7 20 OUTPUT MULTI STATE DEVICE DRIVER OMSDD esses enne ener inneren nnne 114 7 21 OUTPUT REMOTE CONTROL MEMORY ORCM cccsssscesseseecesssececseseececsececeesaeeecseaeeeessseeecseaeeeeneneeeess 117 7 22 OUTPUT REMOTE MOTOR CONTROL ORMC cccccceesseceesssceceesececseseececeeeecsesaececseaeeeeeseeecseaeeecseaeeeess 119 7 23 OUTPUT REMOTE MANUAL SET CONSTANT ORMSC cecssccesssececseseececenececeeaececesaeecesseeeeseeeeenenaeeess 121 7 24 OUTPUT STATION CONTROL OSTN u c cccccssssecesssececsessececseceecseeeeecsecaececseeecsesaececseaaeeseseeecseaeeeenenaeeess 123 7 25 PCU COMMUNICATION STATISTICS MONITOR PCUMON ccseccecssssecesseeeceesececsesaecesseeeceeaeeesneneeeess 126 1 26 POLL ANY BLEOCK PO
35. ACCESS a aaa a aaa aa aa a a a a REEE SEE EER ESTERS 37 5 4 6 View Refresh aec aid t t p te m eee t ee et dev 37 5 4 7 View Inactivity Te iiec a ix ERR EIER sa yu dona EK TO EA AUSSER NEM EEE SPENGE virens 37 5 3 UTES e ELE 38 5 5 1 A AUAM LINL A EE E E E E E 38 5 5 2 DCOM Configuration 5 Ae gau ea rure EN p b Ee 38 5 5 3 View My L085 2 ru oe bti a ye rit epa a aee aaa ir ep ete eR E T S 38 5 6 BLOCK FACEPEATES eure ttr steel pee n eei ete eet eee eR err b pere te Boulos 38 Dur TELE 5 idees hr PRU RR ERE E RED PERPE ERE EP RH as aba aden ssh Pep tite d ER 39 5 7 1 Lib FINO E EE 40 GROUPS ptss SEa 42 RoviSys Company Copyright 1999 2015 Page 2 OPC90 Server User Manual V8 2 1 FEE OLB do 43 7 1 ANALOG INPUT LOOP AIL 3 Rec ern eie ipae Le UG E deri 46 7 2 ANALOG OUTPUT LOOP AOL 3 4 iiie epo teet cie hae RESTORE 47 7 3 BLOCK DATA BIER eer eteran tenere ee teeth pec ce e eee etii e eI Es 49 7 3 1 Re ding Bailey Block osi e D I E OE EE CERE eS RR TREE HERREN 51 7 3 2 Tuning a Baily Block i tice iet Ee er tete SEO ee RE eo e Ee dede eb ede ea pesos 51 7 3 3 Reading the Entire Bailey Configuration eese eene nennen nennen rennen 51 7 3 4 Changing Bailey Controller Module Modes eee eene nennen rennen 52 7 3 5 Writing Bailey Controller Blocks eee
36. Bailey system This property should only be used when OPC clients writing the input values to these blocks does so on a regular basis even when the value has not changed see next property With this option set an input write to any AOL DOL ODD OMSDD ORCM ORMC PRMSC and OSTN block reset the internal bad quality maximum timer for all of these blocks This option is useful when digitals are not changing and therefore not being written on a regular basis whereas analogs usually are A write to any input value becomes the indicator the OPC client is still alive Turbo polling messages return values of zero when the quality of the block being read is bad To enable the ability to see polled bad quality values the turbo polling logic drops back to polling them with single block output reads If it is more desirable to not see these values and maintain the efficiency that reading them with turbo polling provides this operation can be overridden by enabling this property Instructs OPC90 to report all data change tags at the data change cycle even when they have not changed from the last reported value This option is useful when interfacing to OPC clients that mark OPC data stale or bad when it is not received on a regular basis Most OPC clients do not need this option to be set Supervisory control writes to DD MSDD RCM RMC RMSC and STN blocks are sent directly to the Bailey system without updating the OPC tag RoviSys Company C
37. Company Copyright 1999 2015 Page 142 OPC90 Server User Manual V8 2 1 The third record is point 46 which was logged by the Bailey block on February 1 2007 at 23 23 50 203 It has good quality its in alarm has not been deleted from the scan and has a value of one The point type is pre fault and it called Compressor 1 The fourth record is point 9 which was logged by the Bailey block on February 1 2007 at 23 23 50 987 It has bad quality its not in alarm has not been deleted from the scan and has a value of zero The point type is pre fault and it called Compressor 2 In addition to the above file format a CSV comma separated variable file for each SOE block is generated The format of this file is compatible for opening by Microsoft Excel The file name is the system address of the block ring node module block separated with an underscore character followed by date of capture followed by a two digit 01 99 sequence code with an extension of CSV The number of points logged is implied by the total lines within the file Also the first line is the titles for the columns within the file The CSV capture files are stored in the C Program Files OPC90 Serve SOE directory This directory is also included in the OPC90 database shadowing feature Consider the following example CSV file opened with Excel EA Microsoft Excel 1 1 3 5700 0926200701 CSV File Edit Yiew Insert Format Tools Data Window Help Da ST SmBg amp
38. Enable collection of node performance statistics see note 2 Enable collection of module memory utilization see note 2 Enable collection of module exception statistics see note 2 VT BOOL Read Write Enable collection of loop topology map see note 3 VT BOOL Read Write Enable collection of current time sync master ID see note 2 VT UM Read Write Number of samples for calculating moving averages VT BSTR Indicates the block operational message Indicates the block name Indicates the block long OPC path name Indicates the block descriptor OPC status value see OPC status section VT BOOL Read Current quality of PCU node communication statistics 0 good 1 bad NIS Firmware revision PCU address switch setting Loop ring address switch setting Loop ring mode switch setting VT Ul LED display expander bus address switch setting Loop Ring Topology VT Ul4 Read Write How often to read the topology data in ms 0 disable see note 3 VT BSTR Topology of the currently addressed loop see note 3 Resettable NIS Event and Error Counters VT Ul4 Read Write Time milliseconds since last module or command reset Write 0 to this tag to reset event and error counters Channel 1 receive errors Channel 2 receive errors Transmit errors Messages lost to receive queue overflow VT UI4 Messages dumped with circulation count errors VT Ul4 Read Messages dumped with message
39. Example2 File lt OPCUnit2 csv gt Importing the following CSV file will cause the OPC90 Server configurator to create a DEVICE block called ClU4 configured for port COM2 All subsequent lines in this file will declare blocks to be added to that device CIU DEVICE COM Test INICIO3 100 0 1000 4 10 1000 0 0 0 0 0 0 0 0 0 1 0 10 4 0 0 1 1000 7 0 1 0 3660 0 0 0 1 0 0 100 4 CIUA AIL1 AIL 1 1 5 31 0 0 0 0 0 0 0 0 ClU4 AOL1 AOL 40 Test AOL Block 10 13 4 2 1000 2000 1 5 900 10 CIUA4 ODD1 ODD 41 Test ODD Block 60 0 1 CIUA BLK1 BLK 1 1 3 86 0 0 0 0 0 0 0 0 ClU4 DAANG1 DAANG 1 1 3 48 0 0 0 0 0 0 0 0 ClU4 DIL1 DIL 1 1 3 155 0 0 0 0 0 0 0 0 CIU4 MODSTAT1 MODSTAT 1 1 5 0 0 0 0 0 0 0 0 CIUA POLL 1 POLL 1 2 3 4 Poll Block 21 2134 ClU4 SPEC2 SPEC 1 1 3 86 Spec Block 2 CIUA STN1 STN 1 1 3 86 Station RoviSys Company Copyright 1999 2015 Page 158 OPC90 Server User Manual V8 2 1 10 Setting up OPC Client Access of OPC90 The RoviSys website www rovisys com contains additional documents that provide specific instructions on how to setup OPC90 to work with a variety of commercially available OPC clients If your OPC client is not listed please consider writing a short Using OPC90 With document and submit to spafford rovisys com Windows DCOM must be properly configured to allow OPC clients running on the local and or remote PCs to gain access of OPC90 The Windows program called DCOMCNFG EXE is used to configure
40. MY DEVICE MY RING MY NODE SHADOW OK SHADOW MASTER f VT I4 VT I4 VT I4 A ea lc esit d AG mw VT l4 Total read block output values read VT M Read block output values second m Ring address of the Bailey interface Node address of the Bailey interface Shadowing OK 0 Good 1 Bad or Disabled Currently Shadow Master 0 No 1 Yes SHADOW PRI STATUS VT I4 SHADOW SEC STATUS VT I4 VT I4 VT I 4 VT I4 VT I4 VT I4 VT I4 Read No This tag is a combination of the logical or of tags ALL STATUS STARTUP along with not of ONLINE Its purpose is for simplistic OPC clients that only allow one tag to be referenced as the decision maker for its failover mechanism This is a counter that bumps each time all blocks requiring background specification reads has been completed The time between each counter update can be shorten or lengthen with adjustment to the device Maximum Block Specifications Read Sec setting On startup the initial cycle takes much longer because all DAANG DADIG DD MSDD SPEC and STN blocks must have their block specifications read Thereafter only the STN and SPEC blocks require reading on an ongoing basis This value indicates how many messages have been queued and waiting for available keys to get sent It should hover in a single digit number The indication that the Maximum Block Specifications Read Second is set to a value higher than the particular CIU type c
41. Nak Code Serious Nak Description 652180 0 No Command complete 472726 1 No Keyed command is being processed 1 105 No Undefined block number block is valid but not configured 1 110 No Module not responding Notes Nak codes 0 and 1 are actually positive acknowledgements and do not indicate an error condition Nak codes 100 112 are related to module configuration data There existence does not Indicate a serious problem but could be a bad database configuration or a problem with ABB Bailey controllers Remember that most Nak codes are transient and recoverable No serious Naks have been detected Total ome Code Command Description 5 Establish point 1 i 0 Output value 441291 13 Read block 1 19 CIU restart 12430 20 Read block output 472724 25 Dequeue keyed command 11157 27 Demand module status 56213 34 Read work flag 673 43 Read system time date 3367 49 Establish and connect point 332 60 Set system time date 123422 63 Read data exception reports 346 66 Read data exception report specifications 1 69 Read environment 1 101 CIU online 2903 113 Extended read block 3 126 Extended support inquiry RoviSys Company Copyright 1999 2015 Page 87 OPC90 Server User Manual V8 2 1 7 9 Digital Input Loop DIL The DIL OPC90 block is used to retrieve the exception reported output from Bailey Digital Output Loop blocks function code 45 and Digital Output Loop With Deadband function code 67 It can also be used to r
42. Output Station Control used to source PID control data to a Bailey STN console tag The Bailey console can issue PID control commands set point control output mode to this block with the OPC client responds back with process variable and other STN indicators RoviSys Company Copyright 1999 2015 Page 12 OPC90 Server User Manual V8 2 1 5 OPC90 Server Application Menu Items The following picture shows the OPC90 Server main menu items available to the program user for managing databases editing the database selecting run time activities and accessing program information along with online help TurboListAnalysis cfg OPC90 Server File Add Edit View Utilities Help Dale LSA ss e el e tff ciu E AnyBlock AOLs BRC BRC AIL 1000 E BRC XRPs Goo Ca Dls ors MFP 3 MFP Seconds MSDD BS MUX2 BS MUx3 BS MUX7 E muxe PCU STAT ERM C3 RMC C3 Saws Sec 3 Name Location Data Type Access Description Last Update ALL STATUS BLOCK CYCLE IMPORT FILE 3 IMPORT READ 3 IMPORT RESULT 3 MESSAGE MSG QUEUE MSG RATE MSG TOTAL MY BLOCK TYPE MY DEVICE k MY NODE 3 MY RING 3 NAK TOTAL 3 POINT TOTAL POLL OUT RATE 3 POLL OUT TOTAL 3X POLL RATE POLL TOTAL PRI STATUS SEC STATUS SHADOW MASTER SHADOW MY DEVICE k SHADOW MY NODE SHADOW MY RING SHADOW OK k SHADOW PR
43. Predictor controller tuning time constant see note 4 KD me R4 PID block derivative action time constant or e Predictor process model deadtime see note 4 KDLAG inal R4 Read Write Advance PID only block derivative lag action time constant or SMITH Predictor aia model lag time constant see note AO BYPASS VT BOOL AL iod output bypass indicator DS BAD VT BOOL Read Analog output associated with Digital station hard DCS station bad indicator see note 6 Notes 13 N e OPC90 can control the STN block in both local and computer level The STN LEVEL tag indicates the current STN block level 0 local 1 computer The STN block level can be commanded to local or computer by writing the respective values O or 1 to STN LEVEL When an OPC client commands the STN block to the computer level it must satisfy the Bailey STN block computer ok timer This is accomplished by periodically issuing supervisory control writes of the mode set point or ratio index values The OPC client can also periodically write a value of 1 to STN OK or STN LEVEL to satisfy the Bailey STN block computer ok timer see Device block AUTOMATIC SEND STN CPU OK setting to delegate management of computer ok to OPC90 The STN OK tag reports the status of the Bailey STN block computer ok timer The OPC client can monitor the STN TIMER tag to determine the elapsed time that has transpired since the last computer level supervisory control mode set po
44. Re alignment of status buffer 0000000001 NIS poll messages acknowledged by this node 0000000000 Re alignment of receive buffer requests NODE RX 7 8 306 0000000000 NIS poll messages busy not acknowledged by this node 0000000000 Re alignment of status buffer requests 7 2 118 0021895139 Expander bus to NIS handshake messages 0000000000 Status buffer message overflow node status MENTS 17 2 110 0009747762 Expander bus message to transmitt buffer signals 0000000000 Spurious level 7 interrupts MB Rx 0 0 346 0000000000 Expander bus PCU status requests 0000000000 Spurious level B interrupts amp MT oO ro 00001 73539 Expander bus NIS status requests 0000000000 Spurious level 5 interrupts 0000017946 Expander bus interrupts with invalid status GMI RX 3 J 4 XRP TX 54 Points Sec Resettable Module Exception Report Statistics Time Sync Master Memory Usage XRPRX 3 3 Points Sec iv 14Days 01 14 14 903 since last reset or rollover jv Ring 1 Iv CPUUse 22 733 x 0000000252 Receive rate peak points second Node 200 Total 339360 0000330035 Receive count total points Accuracy 3 Temp pue Node RX 10 of loop total Show Average 0000060062 Receive packet count total packets Xip RX Pack 2 i E Available 192436 TTT 0000000705 Transmit rate peak points second Node TX 19 of loop total 0054601481 Transmit count total points Xip TX Pack 4 Fee 482 Li ri LLLI 0006464652 Transmit packet count tot
45. TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor CHAN NAME Channel name assigned to this point CHAN TYPE VT I2 Channel type code CHAN STATE VT BOOL Channel state 0 Ok 1 Open 2 Short 3 Overdrive ALARM CODE Alarm code OPC STATUS OPC status value see OPC status section QUALITY Current quality of Bailey values 0 good 1 bad QUAL PROP Propogated Quality 0 Good 1 Bad OUT Current output value from Bailey HIGH High signal value in Engineering Units LOW Low signal value in Engineering Units SIG CHANGE Significant change in 96 of range EU Engineering Units Code EU TEXT Engineering Units String HI LIM VT R4 Read Write Alarm limit used to detect the high alarm condition Writing to this value tunes the alarm limit of the associated Bailey block LO LIM VT R4 Read Write Alarm limit used to detect the low alarm condition Writing to this value tunes the alarm limit of the associated Bailey block HI ACT VT BOOL High alarm active indicator LO ACT VT BOOL Low alarm active indicator OVR ENABLE Override allowed 0 No 1 Yes OVR VALUE Override value OVR STATUS Value overridden 0 No 1 Yes STAT INHIBT Status inhibit 0 No 1 Yes SUSPECT Value suspect 0 No 1 Yes DRIVEN LO Low overdriven value 0 No 1 Yes DRIVEN HI High overdriven value 0 No 1 Yes CONFIG ERR Configuration error exists 0 No 1 Yes READBACK Readback status 0 Good 1 Bad REF
46. Units String PID BLOCK VT I2 The Bailey PID SMITH Predictor block address associated with this control station see note 2 SP TRACKING Set point tracking indicator SP Current control station set point SP HI LIM SP high limit SP LO LIM SP low limit PV Current control station process value PV BLOCK Process value block address RI Current control station ratio index value OUT TRACKING Control output tracking indicator OUT VT R4 Read Write Current control output value received from RoviSys Company Copyright 1999 2015 Page 147 OPC90 Server User Manual V8 2 1 OUT HI LIM OUT LO LIM RED CMD RED TAG RED USERS HI ACT LO ACT PV HI LIM PV LO LIM HI LIM LO LIM DV LIM DV HI ACT DV LO ACT KFAST KGET KFC KTYPE KTYPE NUM KDIR KIONLY KI LIM TYPE Bailey VT R4 Read Write OUT high limit see note 3 VT R4 Read Write OUT low limit see note 3 VT BSTR Read Write Red tag command see red tag users section VT BOOL Read Red tag indicator 0 no 1 yes VT BSTR Red tag users current user names or codes VT BOOL PV High alarm active indicator VT BOOL PV Low alarm active indicator VT R4 PV high limit VT R4 PV low limit VT R4 Read Write The setting for the alarm limit used to detect the PV high alarm condition The setting for the alarm limit used to detect the PV low alarm condition PV Deviation limit High deviation alarm active indicator
47. VALUE tags The S01 through S63 tags are also updated with a description of each returned specification The FC tag will return the block function code number and the FCNAME tag will return the name of the function code Completion of the next read operation is flagged when the NEXT tag is reset to FALSE The MESSAGE tag will also return a text message indicating completion of the next read operation or the reason for failure if the next read cannot be completed When the ACKNAK tag is zero the request was successful non zero indicates an error occurred A search for specific function codes could be implemented by monitoring the FC tag while stepping through a Bailey configuration 7 3 4 Changing Bailey Controller Module Modes Bailey controller modules are always in one of three operating modes These modes are execute configure and error When in the execute mode the controller runs its block configuration In this mode of operation existing blocks can be tuned see section 7 3 2 but new blocks cannot be added and existing blocks cannot be modified or deleted When in the configure mode the controller is not running its block configuration In this mode of operation existing blocks can be modified or deleted and new ones can be added A controller module enters the error mode of operation when it detects a configuration error on transition to the execute mode A controller can also enter the error mode when a trip block Bailey Function Code 32
48. Value Description ALL STATUS COMi0 INT R Good All Comm Status 0 Good 1 Bad 3 BLOCK CYCLE COM10 INT R 122 Block specification read cycles completed PO vile 0 mof Clients 31 Groups 61 Tags 27795 Rate 2540 Service Run CIU ONLINE Unlimited Select New Device to add a new device to the database A database must have at least one device definition The name given to the device becomes the first part of the OPC tag name used by OPC clients when accessing a piece of OPC data from OPC90 A device defines operational characteristics that OPC90 uses when communicating with the physical Bailey interface often generically called a CIU Computer Interface Unit One of the most important communication characteristics that must be considered is the physical PC communication channel that has been attached to the CIU Typically this channel is an RS232 port that must be setup using the Edit gt Ports menu item For the INICIO3 interface the communication channel could be RS232 or SCSI When it is a SCSI channel no additional communication setup is required beyond selecting the SCSI port that has been cabled to the INICIO3 INICTO3A module See the DEVICE block for more details Select New Group to defined a folder under a device in which collections of other OPC90 groups and blocks can be configured Groups allow data organization within the OPC90 database They are not required but if used the name given to the group becomes part of
49. actual device state to the GOOD STATE tag as a number 0 3 A request for a new device state occurs by a write to the REQ STATE tag The RED TAG tag allows the OPC client to indicate the device is currently under a red tag condition This block supports mode When in auto mode logic the OPC client controls the state change requests written to the REQ STATE tag with operator commands to this tag being ignored In manual mode the operator writes the REQ STATE tag OPC90 will receive the write request from the Bailey system and transfer this request to the OPC client by writing the new requested state to the REQ STATE tag When the OPC client detects a state change has been requested GOOD STATE lt gt REQ STATE the OPC client must update the feedback tags F1 through F4 and GOOD STATE tag to reflect successful arrival of the device at the requested state If feedback cannot be confirm the OPC client must set the ALARM tag and leave the GOOD STATE unmodified Likewise the OPC client must reset the ALARM flag when a new device state transition is requested and only set it again if feedback cannot be confirmed The Bailey implementation of the MSDD block defines the required states of the feedback signals for the four possible device states along with a feedback wait time The feedback wait time is the amount of RoviSys Company Copyright 1999 2015 Page 115 OPC90 Server User Manual V8 2 1 time to wait before doing feedback confirmation fo
50. additions and deletions So for example when blocks are added using the file import feature those blocks are also added to the other OPC90 server database Configuration shadowing will dynamically determine which OPC90 is operating as the Shadow Master and Shadow Slave Data such as the CIU communication status state online or standby number of current OPC connections and OPC90 start time determine this role Determination of the role goes like this The OPC90 with the most communicating CIUs is the master If they are equal the OPC90 with the most CIUs online is the master If RoviSys Company Copyright 1999 2015 Page 28 OPC90 Server User Manual V8 2 1 they are equal the OPC90 with the most OPC connections is the master If they are equal the OPC90 that started up first is the master These factors are being determined as part of startup and shared between the two OPC90s This means some of these factors change as part of startup and therefore the shadow roles may swap back and forth between the two OPC90s a couple of times when starting up This is normal and expected especially when using same address CIU setups Quickly the roles will lock in and stay that way until something changes with the communication state between OPC90 and the CIUs The Device block has a tag that reports the current role Although no adverse effects will occur if editing is done on the shadow slave it is best to do this on the OPC90 currently op
51. bad DISC ACT Alarm active indicator OUT VT BOOL Read Last discrete input value reported to Bailey Notes 1 Make sure the block number attribute is unique with respect to the other other DOL AOL ODD OMSDD ORCM ORMC ORMSC and OSTN OPC90 blocks associated with the same Bailey Interface Definition block The block number attribute must also be defined within the range of 1 to maximum number of allowed outputs set up within the associated OPC90 Interface DEVICE block The Bailey system will receive data from this block at the ring and node address of the Bailey CIU interface module two and block number defined by the BLOCK attribute RoviSys Company Copyright 1999 2015 Page 89 OPC90 Server User Manual V8 2 1 2 This attribute is used to setup output alarming states A value of 0 indicates flag alarm when output state is zero A value of 1 indicates flag alarm when output state is one A value of 2 indicates never flag an alarm 3 When the Device block Set bad quality of max exception timeout property is enabled the QUALITY tag of this block will be set bad if writes to the block input s do not occur within the Exception Report Output Max Time setting of the block When this occurs bad quality will also be written to the CIU and therefore propagated to the users of the block data within the ABB Bailey system The quality can also be set bad by writing a one 1 to this tag RoviSys Company Copyright 1999 2015 Page
52. being bad It returns 1 when running and CIU communication is good otherwise it can be setup to return 2 fault when CIU communication is bad Also optionally the GetStatus return code can be configured to return RPC E FAULT 2 147 549 444 when communication with all CIU s is bad The settings for the GetStatus server state and return code are configured using the Edit Error Logging dialog 5 3 11 Error Detection It is important to understand the two distinct types of log files that OPC90 is capable of generating The first type of log is related to diagnosing communication problems with the ABB Bailey CIU device This log type is enabled by right clicking on the device block within the OPC90 program window and enabling the type of information to log TurboListAnalysis cfg RoviSys OPC90 Server Runtime Mode PRISES File Add Edit View Utilities Help olee Bl v lela me tf Access Value Restart X ALL STATUS 3003 INT R X BLOCK CYCLE 3003 INT R X IMPORT FILE 3003 STRING RAI X IMPORT READ S3003 BOOLEAN RW X IMPORT RES 53003 STRING MESSAGE S3003 STRING New Block X MSG QUEUE 3003 INT MSG RATE 3003 INT i 2 i n MSG TOTAL 53003 INT si 0G ven MY_BLOCK_T 53003 STRING G v Log CIU Messages MY DEVICE 3003 STRING i Log OPC Reads MY I 3003 INT l Log OPC Writes MY S3003 INT NAK TOTAL 3003 INT Properties ONLINE 53003 INT Faceplate ui gt zu N
53. being used as the user interface when running as a service or embedded started automatically by an OPC client access The other type of group is created by and exists within an OPC client and is referred to as the OPC client group The OPC client creates this group after it has successfully connected to the OPC90 Server in runtime The OPC client group is an interface into the server After an OPC client group is created OPC tags can then be added to it in runtime Thus the OPC client group acts as a collection of tags not blocks OPC90 Server address space can be browsed and then OPC90 Server tags selected in runtime These tags are then placed into the OPC client group An OPC client group does not have to match an OPC90 Server group When the OPC client disconnects from the server all tags are disestablished and the OPC client group does not exist anymore RoviSys Company Copyright 1999 2015 Page 42 OPC90 Server User Manual V8 2 1 7 Blocks The following sub sections define the OPC90 Server blocks available for interfacing with Bailey systems For ease of access the blocks are presented in alphabetical order It is important to note that a Device Block DEVICE must be configured for the OPC90 Server to successfully communicate with the Bailey system This block declares an instance of the Bailey driver and its operational characteristics The remaining OPC90 Server blocks provide access to the various Bailey exception report bloc
54. by this attribute HI LIM Config The setting for the alarm limit used to derive Read Write the high alarm condition see note 2 LO LIM The setting for the alarm limit used to derive Read Write the low alarm condition see note 2 MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor IN Input value to be exception reported to Bailey OPC STATUS OPC status value see OPC status section QUALITY VT BOOL Current quality see note 3 of Bailey values 0 good 1 bad OUT Last input value reported to Bailey HI ACT High alarm active indicator LO ACT VT BOOL Read Low alarm active indicator RoviSys Company Copyright 1999 2015 Page 47 Notes 1 OPC90 Server User Manual V8 2 1 Make sure the block number attribute is unique with respect to the other AOL DOL ODD OMSDD ORCM ORMC ORMSC and OSTN OPC90 blocks associated with the same Bailey Interface Definition block The block number attribute must also be defined within the range of 1 to maximum number of allowed outputs set up within the associated OPC90 DEVICE Block The Bailey system will receive data from this block at the ring and node address of the Bailey CIU interface module two and block number defined by the block attribute This attribute is normally configured when the block is first defined Since it is associated with the alarm lim
55. calculated averaged values are used for determining a throttle condition is in effect Each positive level setting is compared to its corresponding averaged value to determine if a throttle condition should be flagged The THROTTLE tag is an OR of all of these level condition checks The faceplate will indicate which watch is contributing to the throttle condition by blinking its label between black and gray As can be seen for the above example both GMI RX and XRP TX are flashing notice they are gray in the example This is because the GMI RX level setting is at 20 messages per second but the average value indicates that level is exceeded so a throttle condition is flagged This is also true for the XRP TX level setting since it is at 65 but the average value is less which means the PCU transmitted exception report rate has dropped so a throttle condition is declared It is important to remember that the throttle factors only apply to the GMI polling activity being generated by OPC90 If a node other then OPC90 is causing the throttle condition to occur slowing down OPC90 s GMI activity will not clear that condition RoviSys Company Copyright 1999 2015 Page 132 OPC90 Server User Manual V8 2 1 7 26 Poll Any Block POLL The POLL OPC90 block is used to retrieve polled output values from any Bailey function block output This includes blocks that have floating point outputs and discrete outputs Its primary usage is intended for node lev
56. deleted when they become older than the number of days configured in the device property The default setting is 7 days The response of the OPC GetStatus function is configurable from this dialog It can be enabled to return a failed server status when communication with all CIUs is bad While running in simulation mode the running in test mode status is normally returned This can be changed to return server running instead should the OPC client s have problems with the test mode status The returned server status is often used by OPC clients to take corrective actions such as connecting with an alternative OPC server if a faulty status is received OPC90 returns the following possible statuses OPC STATUS RUNNINGi is the normal expected return status This will be returned even when communication with the DCS is bad unless the indicate fault when CIU bad option is enabled If this option is enabled and CIU communication is completely lost the return status will indicate failure RoviSys Company Copyright 1999 2015 Page 32 OPC90 Server User Manual V8 2 1 OPC STATUS FAILED is returned when the indicate fault when CIU bad option is enabled and CIU communication is completely lost OPC STATUS NOCONFIG is returned when the database has not been setup yet or something is preventing OPC90 from loading its database OPC STATUS TEST is returned when OPC90 simulation is enabled This status is an indication the data being received is
57. determine its type FC 99 or 243 and based on the type setup the OPC90 SOE BLOCK TYPE tag Bailey function code 243 is the INSEMO1 executive block Its base address is always 5000 and is used to retrieve Standard sequence of events Its 5001 block address is used to retrieve Summary sequence of events The SOE SOE DATA tag indicates the Bailey system is capturing an SOE event when it goes to the one state When this occurs OPC90 will read the sequence of event data and store it in SOE files automatically generated within the C Program Files OPC90 Server SOE directory The SOE OFLOW tag indicates the Bailey SOE block experienced an overflow condition when 1 and the block buffer size must be increased to clear this condition SOE SOE DATA will reset when the SOE event capture is complete The current capture file can be closed and a new one opened by writing a zero to this tag Note that a value of one can only be written to the SOE SOE DATA tag when the SOE block type is Summary requesting a summary report to be generated If OPC90 device simulation is enabled a one and then zero can be written regardless of the SOE block type This will cause a simulated SOE log file to be generated By definition file names are the system address of the block ring node module block separated with an underscore character _ followed by date of capture followed by a two digit 01 99 sequence code The capture file types are STD SUM
58. e e d eee e teda ee i 53 7 3 6 Modifying Bailey Controller Blocks eese eee enne en trennen rennen 53 7 3 7 Deleting Bailey Controller Blocks eee eee eee entren nennen rennen 54 7 3 8 Configuration Command Processing eese eee ete eene nennen trennen trennen ene 54 7 3 9 BLK Configuration Faceplate tr ith le to RH costae aure tb suede cn ead Res 59 7 4 DATA ACQUISITION ANALOG DAANG ccccecccesssecesesseeceseeeecseaaececseceecsssaeeecsenaececeeeecesaueeeceeaaeeeseeaeeeneaee 63 7 5 DATA ACQUISITION DIGITAL DADIG ccccccccesssecesesscecesseececsenaececeeceecesseeecseaaececeeeeceesaeeecseaaeeesneeeeenenee 65 7 6 DATA BEOCK DATA eve ie cete rtt iet e grt eem Be ate 67 qui DEVICE DRIVER DD sg ERREUR REIR AE 68 7 8 DEVICE DEFINITION BLOCK DEVICE ccccccsssccecsssceceesseeecssaeececseeecsesaececseceeceesueeecsesaececeeseeeessneseesaas 70 7 8 1 SCSL Communication cu es tacere EEE ATE CE EE E ETEA 61 7 8 2 TCP COMMUNIC ALON v ee e Wette a Sa sees ea Base UA 63 7 8 3 Device Communication Faceplate see tee ie rt tete tees tb EEE SECTE iE 65 7 9 DIGITAL INPUT LOOP DIL nter erre teet rein eaves Reit AEE A tne ee REPRE e eade ee Ro eee ve Da eee Ld 88 7 0 JDIGITAE OUTPUT LOOP DOD nr trt epe e mienne des 89 7 11 HARMONY ANALOG INPUT HA re ae eia aaa Eea RE E E EE E E EEE 91 7 12 HARMONY ANALOG OUTPUT MAO e a arae ear e e aE iae a e e rennen ener sre n rennen
59. foundation specification concerning sync reads When enabled OPC90 overrides the DCS timestamps to the current PC timestamp for all points read by OPC clients using the sync read function 2 When the ABB Bailey DCS is an Infi 90 system the DEVICE block allows definition of a property called Accuracy rating This property is used to define the clock accuracy rating of its PC CIU Accuracy rating is used when time syncing is enabled OPC90 will allow the node with the highest accuracy rating to become the time sync master It will not accept time from any node with an accuracy rating less than its own The accuracy rating can be set to any value between 0 255 Systems with OIS consoles interpret RoviSys Company Copyright 1999 2015 Page 79 OPC90 Server User Manual V8 2 1 accuracy rating as 0 lowest accuracy 3 low accuracy battery backed clock 6 high accuracy battery backed clock and 12 satellite clock For these systems setting the accuracy rating higher than 12 will guarantee OPC90 becomes the time sync master node io The Y2k Time Warping option allows the PC time to remain in the present year 2000 through 2021 while time syncing the ABB Bailey DCS to calendar years prior to year 2000 in the range of 1980 to 1999 OPC90 will set the DCS time to pre 2000 years that have calendars that match the present day calendar This option is useful for ABB Bailey systems having controller firmware that is not Y2
60. from this block 10 Force an exception report from this block IN CTRL PR R4 Read Write dd conditioning mode control see FC 211 IN TREF hull Read Write TR conditioning time reference seconds see FC 211 S7 IN CREF Input conditioning digital filter count reference see FC 211 S8 ALARM CTRL Alarm mode control see FC 211 S9 ALARM TREF Alarm time reference seconds see FC 211 S10 ALARM_TCOUNT VT_R4 Read Write Alarm digital filter transition count reference see FC 211 S11 RTP_REF VT_R4 Read Write Return alarm de alarm time period reference see FC 211 12 OUT VT_BOOL Bailey discrete output value OUT TEXT VT BSTR Bailey discrete output value as a string OVHR STATUS VT BOOL Read Status override indicator RoviSys Company Copyright 1999 2015 Page 65 OPC90 Server User Manual V8 2 1 SUSPECT VT BOOL Read Alarm suspect indicator E STOP Emergency stop indicator IN SELECT Input is selectable indicator note 2 IN ALTERNATE Alternate input active indicator request note 2 IN CUSTOM Custom input active indicator request note 2 IN PRIMARY Primary input active indicator request note 2 LATCH Alarm latch indicator reset request note 3 SUPPRESS Alarm suppress indicator set reset note 4 XRP OFF VT BOOL Read Write Exception report off indicator set reset request note 5 Notes 1 The COMMAND attribute can be used to send various commands
61. has this one so skip if yours does not o Add these users Everyone ANONYMOUS LOGON o Select COM Security Tab Under Launch and Activation Permissions click on Edit Default button o Add these users ANONYMOUS LOGON INTERACTIVE o Select COM Security Tab Under Launch and Activation Permissions click on Edit Limits button not all operating systems has this one so skip if yours does not o Add these users ANONYMOUS LOGON INTERACTIVE Reboot the PC RoviSys Company Copyright 1999 2015 Page 171 OPC90 Server User Manual V8 2 1 12 Troubleshooting Hints This section is provided to help the user identify and correct problems that may arise as a result of incorrectly setting up the OPC90 Server interface It is provided as a general guide to allow the user to decipher normal and abnormal operation If this does not help OPC90 Server can be enabled to post additional error messages to OPC90 Server log files using the DEVICE block DEBUG LOG attributes To change these attributes right mouse click on the Device block and select or deselect Show Receive Show Send Show Errors and or Show Events Note these flags can be changed in runtime Remember to save the configuration if these flags are to be saved Use these DEBUG LOG attributes to track down tough problems and discover hard to find configuration errors Afterwards remember to disable all of its options except Errors since leaving them enabled can con
62. import exception reported values are identified with an arrow pointing left into the device symbol Blocks that export exception reported values are identified with an arrow pointing right out from the device symbol The definition of each block in the following sub sections includes the symbol associated with that block It is important to note that the names given to devices groups and blocks determine the OPC client tag name used to access OPC data In the above example the OPC client tag name CIU A Import AIL_point OUT RoviSys Company Copyright 1999 2015 Page 44 OPC90 Server User Manual V8 2 1 will access the output value of the block named AIL point To read and write a set point value of the block named STN point the OPC client tag name for the above example would be CIU A Import STN point SP RoviSys Company Copyright 1999 2015 Page 45 OPC90 Server User Manual V8 2 1 7 1 Analog Input Loop AIL The AIL OPC90 block is used to retrieve the exception reported output from Bailey Analog Output Loop function code 30 Analog Output Loop With Deadband function code 48 Analog Point Definition function code 70 and Enhanced Analog Point Definition function code 158 blocks Restrictions This OPC block can be utilized with all Bailey interface types except serial port module SPM amp CPMO2 TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address ADDR NODE Bailey node add
63. in a particular engineering unit Those blocks responsible for returning exception reported analog values also identify the engineering units using a predefined RoviSys Company Copyright 1999 2015 Page 21 OPC90 Server User Manual V8 2 1 Bailey code in the range of 0 255 The OPC90 blocks designed to return these values also include two OPC tags called EU and EU TEXT The EU tag returns the Bailey EU code associated with the analog value The EU TEXT tag returns the Bailey engineering units code converted to a string value Bailey predefines the first 16 codes The following dialog is displayed when this menu item is selected Use this dialog to define the mapping between Bailey engineering unit codes and the string to be associated with each code Note that engineering unit mapping can also be defined using the Import CSV program feature The map is global to all OPC90 blocks that return exception reported analog values Use of the EU TEXT OPC tag is optional Its purpose is to simplify OPC client display generation and allow the source of engineering unit definition to remain singularly at the Bailey module level Note that engineering unit code to string mapping is changeable online while OPC90 is providing data to attached OPC clients The maximum string size for an engineering unit code is 16 characters 5 3 5 Text Messages Select Edit 2 Text Messages to defined Bailey text message number to text message string mapping
64. insensitive OPC90 AIL Ail ail stn STN AOL Server Block Type as one of the following RMSC strings AIL AOL BLK DEVICE DAANG DADIG DIL DOL HAI HAO HDI HDO MODSTAT MSDD ODD OMSDD ORCM ORMC ORMSC OSTN POLL ROM RMC RMSC SPEC STN TXT TEXTSTR RoviSys Company Copyright 1999 2015 Page 155 OPC90 Server User Manual V8 2 1 Location Specifies the Bailey address as 1 1 2 1000 Bailey ring address 1 1 2 1000 Bailey node address 1 1 4 200 Bailey ring address 200 for AOL DOL ODD Bailey block address OMSDD ORCM ORMC Address fields must be separated by a dot ORMSC OSTN not a comma 200 for AOL DOL ODD For AOL DOL ODD OMSDD ORCM OMSDD ORCM ORMC ORMC ORMSC and OSTN blocks simply ORMSC OSTN require the bailey block 1 1 2 200 for AOL DOL For MODSTAT blocks simply require the ODD OMSDD ORCM ring node module ORMC ORMSC OSTN where The address can be encased in quotation the 1 1 2 is disregarded marks if desired COM1 for DEVICE 1 1 5 for MODSTAT 1 1 5 12 for MODSTAT where block 12 is disregarded Port Description For DEVICE blocks this field specifies the Com Port such as COM1 COM2 COMS or COM4 Description User Defined description of the block This Unit 1 Boiler Exhaust Flow field cannot have any commas in it unless it PID1024 is encased in double quotes For example Test Block Description This is a block description with acomma i
65. is zero the request was successful non zero indicates an error occurred 7 3 6 Modifying Bailey Controller Blocks To modify a Bailey function block the controller must be in the configure mode of operation See section 7 3 4 to understand how to change Bailey controller modes of operation There are three easy steps an OPC client must follow to modify a Bailey function block First it must read the function block to be modified See section 7 3 1 RoviSys Company Copyright 1999 2015 Page 53 OPC90 Server User Manual V8 2 1 to understand how to read a block The second step is to change the appropriate specifications from their current values to the values to be modified This is accomplished by writing to the S01 VALUE through S63 VALUE tags Note that these tags are always written as floating point values OPC90 will automatically take care of translating the values to the appropriate types required by the Bailey function block The third and last step is to request the block modification by setting the WRITE tag TRUE The value of the S01 VALUE through S63 VALUE tags appropriate for the block function code are translated to the correct data types required for the Bailey function code and the block modification occurs Completion of the modification operation is flagged when the WRITE tag is reset to FALSE The MESSAGE tag will also return a text message indicating completion of the modification operation or the reason for failure if the mod
66. light conditions are always the result of faulty hardware Make sure network interruptions are not occurring If configuration shadowing is turned off for systems setup with same address CIUs while the standby OPC90 is communicating with the CIU it will command its CIU online resulting in the aforementioned CIU red light condition to occur The only way to avoid this from happening is to disconnect all OPC clients from OPC90 and command it out of runtime mode of operation before turning off configuration shadowing If the red light condition does occur after configuration shadowing is re enabled just physically reset the red lit CIU to put it back into operation RoviSys Company Copyright 1999 2015 Page 29 OPC90 Server User Manual V8 2 1 5 3 10 2 OPC Client Access of Redundant Servers With redundant OPC90 Servers the OPC client must implement logic to decide which server to access the data from A common method is to base the decision on two OPC90 data points The first is the state of the OPC90 Device block ALL_STATUS tag When the value of this tag is zero OPC90 communication with the CIU is valid The second is to monitor OPC90 server status OPC clients utilize the OPC GetStatus method to read a servers status This function returns several data items regarding the status of the server One of those items is the server state which can be used to determine if the server is running or faulted due to communication with all the CIU s
67. lowers the loading effect of block output polling by consolidating block output reads and thus reducing the total number of messages required to poll the data This feature works for both SCSI and serial interfaces but is most effective with SCSI even for systems having high exception report traffic Its effectiveness for serial interfaces with high exception report traffic is much more pronounced when using the redundant channel communication scheme Turbo polling does not support getting alarm bits from blocks that have such data Therefore it should only be disabled if the alarm bit polling information is required This setting causes all GMI type messaging to occur using non keyed messages Use of this option should be limited to SCSI CIU configurations containing MUXCIU blocks connected with G Michaels DBDOC and or ABB Composer Its use with databases receiving exception reported values works best for the redundant channel or dual interface communication scheme Use of this option with plant loop system NETWORK 90 is not recommended Supervisory control write lock When True 1 locks out all operator write requests supervisory control write from the other OPC90 Server blocks that support write capability If write locks are only needed on an individual block basis don t use this setting but instead using the read only setting when configuring each individual block Commands interface on line before establishing the points U
68. marked as bad quality by the Bailey system Frequency in milliseconds at which exception report availability is read from the Bailey interface device Settings in the range of 500 to 3000 milliseconds RoviSys Company Copyright 1999 2015 Page 70 OPC90 Server User Manual V8 2 1 OUTPUT XRP UPDATE 32 Bit Config UINT MAX KEYS PER PCU 32 Bit UINT BLOCK SPECIFICATION 32 Bit READ PERIOD UINT SECONDS MAX BLOCK 32 Bit SPECIFICATIONS READ UINT PER PERIOD Config Config Config are common Frequency in milliseconds at which output exception reports are written to the Bailey interface device Output exception reports are values written to AOL DOL ODD OMSDD ORCM ORMC ORMSC and OSTN blocks by OPC clients Settings in the range of 500 to 3000 milliseconds are common Messages that read block outputs and block specifications use a CIU mechanism called keyed messages These messages allow the CIU to be working on getting that data while still responding to other requests such as exception report reading This setting determines the maximum number of keys that will be used per PCU for keyed type messages The settable range is 0 or 4 32 When set to 0 all possible keys relevant for the particular type of CIU device could be used For most applications the default setting of 4 is optimal Defines the period in seconds for how often read block specification messages are generated This period along
69. master OPC90 becomes the master by setting the DCS time equal to the PC time OPC90 continues to monitor the SYNC DCS tag for being set and PC clock for changes in time that exceed 2 minutes When either of these occurs OPC90 will become the time sync master by setting the DCS time to the PC time The second time syncing option is PC Get Bailey System Time This option enables OPC90 to keep the PC time equivalent to the DCS time but keeps OPC90 from ever setting the DCS time This option is handy for keeping the PC time equal to the DCS time that is being maintained by another time sync source c When the ABB Bailey DCS is an Infi 90 system and either time syncing option is selected the Use DCS Timestamp option may also be enabled This option causes the OPC time stamps associated with each data value to be set to the time stamp generated within the DCS Normally per the OPC foundation specification OPC90 generates the OPC value time stamp when the value is sent to the OPC client This option allows more precise time stamping data to be associated with each value It should be noted this occurs at the expense of slightly reduced exception report throughput since each exception reported value received from the interface will also include a 6 byte DCS time stamp This option provides sub second time stamp accuracy versus the 1 2 second time stamp accuracy when not enabled The Allow DCS timestamp Override option can be enabled to comply with OPC
70. module The INICIO3 or INICI13A must be powered up configured to utilize its SCSI communication channel and attached to a PC SCSI host adapter card Just about any PC SCSI card that supports external connection to the INICIO3 IMMPIO1 module s 50 pin SCSI socket or INICI13A SCSI 50 pin high density socket should work ok Of course the SCSI card driver provided by SCSI card manufacturer must also be installed Here is a table of SCS cards and supported operating systems that are being used with the Bailey INICIO3 and INICI13A interfaces PC Bus Win Win 2003 2008 Server 2008 SCSI Card Type 2000 XP Server Server R2 Win 7 Adaptec 2915 2930LP PCI v 32 Adaptec ASC 2930LPE PCI Express v 32 Adaptec AHA 2940AU PCI v 32 v 32 LSI Logic LS120320IE PCI Express v 32 v 32 Adaptec 29320LPE PCI Express v 32 v 32 amp 64 V 32 amp 64 V 32 amp 64 Adaptec 29160LP PCI v 32 v 32 amp 64 v 32 amp 64 V 32 amp 64 Adaptec 29320ALP R PCI X v 32 amp 64 v 32 amp 64 v 32 amp 64 v 32 amp 64 HP SC11Xe PCI Express v 32 amp 64 v 32 A single SCSI card must be dedicated to communication with a single ABB Bailey SCSI CIU Do not use the SCSI card to also communicate with other SCSI type devices such as hard disks scanners etc Adjustment to the SCSI BIOS might be necessary The BIOS setup can be configured when the PC is booting Following are general guidelines for typical settings Depending on the type of SCSI card all
71. number used by the Bailey consoles to index into a table of text strings representing the engineering units of the set point value 3 When the Device block Set bad quality of max exception timeout property is enabled the QUALITY tag of this block will be set bad if writes to the block input s do not occur within the Exception Report RoviSys Company Copyright 1999 2015 Page 121 OPC90 Server User Manual V8 2 1 Output Max Time setting of the block When this occurs bad quality will also be written to the CIU and therefore propagated to the users of the block data within the ABB Bailey system The quality can also be set bad by writing a one 1 to this tag Application The OPC client uses the SP tag to report the current block value The operator is allowed to command the SP to a new value as long as the SP TRACKING tag is not set OPC90 will receive the write request from the Bailey system and transfer it to the OPC client by writing the new requested value to the SP tag The OPC client is responsible for indicating set point tracking by setting the SP TRACKING tag While in SP TRACKING the OPC client also updates the SP tag to the currently tracked value Updates to the SP tag will be constrained between the configured set point zero and span RoviSys Company Copyright 1999 2015 Page 122 OPC90 Server User Manual V8 2 1 7 24 Y Output Station Control OSTN The OSTN OPC90 block interfaces with Bailey consoles as a Bailey
72. of these settings or the terminology might be different SCSI Parity Checking Enabled Host Adapter SCSI Termination Automatic Initiate Sync Negotiation Yes IDs 0 7 Max Sync Transfer Rate 20 MB Sec IDs 0 7 Enable Disconnect Yes IDs 0 7 Send Start Unit Command No IDs 0 7 RoviSys Company Copyright 1999 2015 Page 81 OPC90 Server User Manual V8 2 1 BIOS Multiple LUN Support No IDs 0 7 Include in bios scan Yes IDs O 7 Plug and Play SCAM support Disabled Reset SCSI Bus at IC Init Disabled Extended bios Translate for DOS ICs Enabled BIOS support for Int 13 extensions Enabled Depending on the operating system OPC90 utilizes the Advanced SCSI Programming Interface ASPI or SCSI Pass Through Interface SPTI to communicate with the INICIO3 or INICI13A via the host controller driver If your system does not have ASPI it can be loaded by double clicking on the ASPI32 EXE file installed in the same directory as OPC90 Do NOT install ASPI32 EXE with Windows 2000 Windows ME Windows XP Easy CD Creator 4 x or with Windows Media Player 7 0 If you have one of these applications or operating systems you will be using a different ASPI layer that will conflict with the one provided in this file The only other driver that needs to be loaded is the standard manufacturer driver provided with the SCSI card or the resident driver recommended by Windows It is not necessary to load th
73. off 5 4 6 View Refresh The database tree list is maintained in alphabetical order Changing a group or block name affects that list This option can be selected to force the tree list to be re alphabetized with the updated changed names 5 4 7 View Inactivity Time This selection displays the following dialog which allows definition of the inactivity time Inactivity Time Minutes that must expire with no user activity before 2nd instance of OPC90O will automatically exit Range can be 0 1440 minutes A setting of zero disables this Feature It is also disabled when the database has been modified but not yet saved 480 cea RoviSys Company Copyright 1999 2015 Page 37 OPC90 Server User Manual V8 2 1 This feature is intended to reduce unnecessary processing requests on the OPC90 service It is especially useful in terminal service environments when multiple users are logged in monitoring OPC90 server and they forget to exit the 2 instance when they are done using it 5 5 Utilities The utilities menu option can be used to easily run the Windows service manager or DCOMONFG program It can also be used to view OPC90 device and error detection log files The following picture shows these available View menu items TurboL istAnalysis cfg OPC90 Server File Add Edit View RUJE Help nig 7g a CX A Service Manager DCOM Configuration Location Data Type Access Value Description Last Update X ALL
74. or two feedback signals The operating mode of the device can be reported as auto controlled by logic or manual under operator control Restrictions This OPC block can be utilized with all Bailey interface types except CIUO1 serial port module SPM CPM02 amp CPMO03 and computer interface command series CIC TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey CIU ring address ADDR NODE Bailey CIU node address ADDR MODULE Bailey CIU module address ADDR BLOCK VT I2 Config Read Block number to establish this point at within the Bailey interface see note 1 DD TYPE VT l2 Config Read Bailey DD type code to use when establishing this point see note 2 MAX TIME VT I4 Config Read If OUT never changes it will be reported at the maximum time interval seconds defined by this attribute MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor OPC STATUS OPC status value see OPC status section QUALITY VT BOOL Read Write Current quality see note 3 of Bailey values 0 good 1 bad MODE VT l2 Read Write Mode of this control loop expressed as 0 Manual 1 Auto OUT Value of discrete output RED TAG Device red tag indicator ALARM Indicates alarm condition F1 Current state of first feedback signal F2 Current state of second feedback
75. read Poll Message Rate messages sec Total Poll Messages Primary Comm Status 0 Good 1 Bad Secondary Comm Status D Good 1 Bad or Not Used Currently Shadow Master D No 1 Yes or Disabled Shadow My Device Shadow Interface Node Address Shadow Interface Ring Address Shadowing OK 0 Good 1 Bad or Disabled Shadow Primary Comm Status 0 Good 1 Bad or Not Used Shadow Secondary Comm Status 0 Good 1 Bad or Not Used CIU Startup Phase 0 Done 1 CIU Startup Time Sync the DCS flag 1 Request sync Time Sync Master Node Time Sync Master Ring Total active blocks in the turbo database Total active turbo polled blocks that are stale Total active and non active blocks in the turbo database Exception Report Rate exceptions sec Total Exceptions Total Exception Report Specs 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53 062 04 17 2012 07 35 53
76. section shows the ring and node address of the current time sync master along with its accuracy rating The NISMON observing logic is monitoring the time sync master and will generate a log when it changes The Memory Usage section presents memory factors associated with the node Specifically it reports the total memory size any temporary memory in use how much memory is available in bytes and percent The NISMON observing logic is also monitoring percent free memory and will generate a log entry if it becomes low The Current Topology section shows the order of the current nodes that are online Collection of this topology information can be disabled by unchecking its check box RoviSys Company Copyright 1999 2015 Page 110 OPC90 Server User Manual V8 2 1 The Observations section shows the last thirty observations that have been added to the NISMON log file This section is useful for seeing the most recent observations but the log file can be viewed using a text editor to see all of them logged each day RoviSys Company Copyright 1999 2015 Page 111 OPC90 Server User Manual V8 2 1 7 19 Output Device Driver ODD The ODD OPC90 block interfaces with Bailey consoles as a Bailey Device Driver block function code 123 Note that this block does not received data from a DD block running in a Bailey controller Use the OPC90 DD block for that purpose The ODD is used to indicate on off control of a discrete device with one
77. signal FB STATUS Current state of feedback status 0 good 1 bad OVR STATUS VT BOOL Read Write Current state of override status condition 1 Make sure the block number attribute is unique with respect to the other AOL DOL ODD OROM ORMC ORMSC and OSTN OPC90 blocks associated with the same OPC90 DEVICE block The block number attribute must also be defined within the range of 1 to maximum number of allowed outputs set up within the associated OPC90 DEVICE block The Bailey system will receive data from this block at the ring and node address of the Bailey CIU interface module two and block number defined by the block attribute 2 The DD type code is a number used by the Bailey consoles to identify characteristics of its DD faceplate display Currently a value of zero is the only valid code RoviSys Company Copyright 1999 2015 Page 112 OPC90 Server User Manual V8 2 1 3 When the Device block Set bad quality of max exception timeout property is enabled the QUALITY tag of this block will be set bad if writes to the block input s do not occur within the Exception Report Output Max Time setting of the block When this occurs bad quality will also be written to the CIU and therefore propagated to the users of the block data within the ABB Bailey system The quality can also be set bad by writing a one 1 to this tag Application The OUT tag reports the state of the device as off 0 or on 1 The RED TAG tag all
78. sufficient details to determine successful problem operation lt Untitled ICONICS OPC DataSpy File Edit View Go Action Help Da EB e E 2 OPC Items Name Value Quality Timestamp My Computer 1 Rovisys OPC9OServeriCIU 3 M5G TOTAL 436316 VT_I4 Good Non specific 14 11 28 332 Yes d OPC Data Access E ICONICS ModbusOPCServer3 89 ICONICS ModbusOPCServer3 28 ICONICSInc IniFileRuntimeDA p ICONICSInc IniFileRuntimeDA 2 Intellution iFixOPCClient x Intellution OPCEDA Intellution OPCiFIX Matrikon OPC OPCLogger i RoviSys OPC90Server CIU 3 CIU 4 2 OPC Alarms amp Events OPC Historical Data Access Br Network Neighborhood ge Connected i RoviSys OPC90Server Group01 100 msec 1 CIU 3 M5G_TOTAL 1 RoviSys OPC90Server CIU 3 MSG_TOTAL Calling lOPCServer AddGroup OK OxO0000000 The operation completed successfully Calling IConnectionPointContainer FindConnectionPoint OKk OxO0000000 The operation completed successfully Calling IConnectionPoint Advise OK 0x00000000 The operation completed successfully Calling IOPCItemMgt Addltems OK Qx00000000 The operation completed successfully For example if an error is posted for the IConnectionPoint Advise call that would be an indication that the OPC90 PC does not have sufficient access privileges to setup call back functions within the OPC client PCs address space This would indicate a
79. the OPC client to indicate the device is currently under a red tag condition This block does not support mode It is always considered to be in manual mode Both operators and logic can simultaneously control this block The operator is allowed to command the OUT tag set when the SET PERM tag has been set by the OPC client OPC90 will receive the write request from the Bailey system and transfer this request to the OPC client by writing the new requested state to the OUT tag When a state change occurs the OPC client must update the F1 feedback tag to reflect successful arrival of the device at the requested state F1 must be set when OUT is set and F1 is reset when OUT is reset The OPC client must set the ALARM tag to indicate the feedback does not agree with the requested device state Likewise the OPC client must reset the ALARM flag when a new device state transition is requested and only set it again if feedback cannot be confirmed The OPC client reports the state of the set and reset logic inputs using the respective SET INPUT and RESET INPUT tags The Bailey RCM block includes a feature that allows a block input to control the output value based on the occurrence of a control override condition This condition occurs when the SET PERM SET INPUT and RESET INPUT tags are all in the set state The OPC client indicates the override state condition by setting the OVR STATUS tag RoviSys Company Copyright 1999 2015 Page 118 OPC90 Server
80. the OPC tag name used by OPC clients when accessing OPC data from OPC90 Select New Block to add an OPC90 block to a device or in a device group OPC90 blocks are given a name that typically identifies its purpose and becomes part of the OPC tag name used by OPC clients when accessing OPC data from OPC90 The block type defines what type of data to expect from the Bailey system for the given block and the address at which it resides The Multiply selection allows bulk duplication of the last selected block to be added to the database t has limited use in real world applications most typically used to automatically generate a series of output type blocks suitable for OPC client programmatic generated output values RoviSys Company Copyright 1999 2015 Page 16 5 2 1 Device OPC90 Server User Manual V8 2 1 When the add device item is selected the following dialog is displayed Device Properties Name ciu Description ABB Bailey CIU Connection Cancel Default gt COMMUNICATION PARAMETERS Scheme Single Interface X Primary Port COM1 Secondary Port Mil i gt DEVICE PARAMETERS FOR INICIO3 G 3 Max out block AOL DOL OSTN etc f 000 Watchdog timer in 2 5 second counts 0 p HO msecs Fax msecs f 5 R 4 f oo Non keyed output polling Import exception report request rate Export exception report send rate Block specification read period seconds Max block specification r
81. the database If that is not the problem make sure the dongle is properly installed Select the OPC90 program menu option RoviSys Company Copyright 1999 2015 Page 180 OPC90 Server User Manual V8 2 1 Help About and verify it reports the dongle serial number in the first line of the about dialog If the dongle is not being recognized or the demo version is being used that line will only state the program version number and release date If the demo version was being utilized prior to purchasing a licensed copy it must be uninstalled and the licensed copy installed About OPC90 Server About OPC90 Server iJ Unlimited Version 7 5 1 April 16 2012 iJ Demo Version 7 5 1 April 16 2012 OPC DA 1 0 2 0 and 2 05 Compliant X OPC DA 1 0 2 0 and 2 05 Compliant License Information License Information Serial Number 2522 Serial Number Netlicensed Remaining D ays Infinity Remaining Days oo Maximum OPC Clients No Limit Maximum OPC Clients J NoLimit Maximum Blocks CIU Capacity Maximum Blocks Cl Capacity Maximum MUXCIU Blocks Total Free COM Ports Maximum MUXCIL Blocks Total Free COM Ports Righteousness Exalteth a Nation THIS IS A TIME LIMITED DEMO VERSION Free Disk Space 1484884 KB Free on C Free Disk Space 1484368 KB Free on C Available Memory 2097151 KB Available Memory 2097151 KB Copyright 1999 2012 The RoviSys Company Copyright 1933 2012 The RoviSys Company Licensed Version Help A
82. the section that deals with CSV file formats for additional information This function will be blocked if OPC clients are currently attached to OPC90 or it is currently operating in monitor mode 5 1 7 Reimport CSV Select Reimport CSV to import the last CSV file that had been previously imported This function will be blocked if OPC clients are currently attached to OPC90 or it is currently operating in monitor mode 5 1 8 Export CSV Select Export CSV to save the current database in Comma Separate Variable format The OPC90 convention is to store these files in the CSV directory This function is useful for saving the database in a format that can be later imported after making bulk editing changes to it or when upgrading from one version of OPC90 to another where additional tags have been defined for any given OPC90 block type See the section entitled Trouble Shooting Hints Cannot See all documented block attributes for further discussion 5 1 9 Reexport CSV Select Reexport CSV to save the current database in CSV format under the previously exported name This feature is like a fast save RoviSys Company Copyright 1999 2015 Page 15 OPC90 Server User Manual V8 2 1 5 2 Add The following picture shows the available Add menu items TurboListAnalysis cfg OPC90 Server Edit View Utilities Help D NewDevice creo g m v New Group Ctrl G id New Block Ctr Name Location Data Type Access
83. to any of the other K tags see note 4 The fast update interval is canceled automatically when the fast update interval for the STN block has transpired or a value of zero is written to the KFAST attribute Some applications may want to have direct control of the KFAST feature and not have writes to the other K values automatically turn it on This can be accomplished by turning off the DEVICE block Set KFAST on K writes property When the analog output associated with a digital control station is bad the STN block is locked into manual mode Attempted mode changes when the DS BAD value indicates bad will be rejected RoviSys Company Copyright 1999 2015 Page 150 OPC90 Server User Manual V8 2 1 7 33 Text Selector TXT The TXT OPC90 block is used to retrieve the exception reported output from Bailey Text Selector blocks function code 151 Restrictions This OPC90 block can be utilized with all Bailey interface types except serial port module SPM amp CPMO2 TAGNAME TYPE ACCESS DESCRIPTION ADDR_RING Bailey ring address ADDR_NODE Bailey node address ADDR_MODULE Bailey module address ADDR_BLOCK Bailey block address MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor OPC STATUS OPC status value see OPC status section QUALITY Current qualit
84. to start OPC90 This program is installed in the C Program Files OPC90 Server directory Write a batch command file that gets run by the auto logon startup The batch file should contain the following line C Program Files OPC90 Server Startme exe C Program Files OPC90 Server OPC90Server exe 10000 The above command line instructs the STARTME program to start OPC90 in 10000 milliseconds Note that the start delay time may have to be adjusted to give the operating system more time to start all of the services 12 2 Validating State Of Individual OPC90 Server Blocks All OPC90 Server blocks have an attribute called MESSAGE The purpose of this attribute is to help diagnose the operational state of the block This attribute cannot be connected to from an OPC client but can be displayed in Monitor mode in the bottom status pane when the block is selected This attribute can take on the following messages OFFLINE OPC90 is not currently in monitor mode so the block is not being scanned or OPC90 is unable to communicate with the Bailey interface to receive the block data WAITING ON DEVICE The block is waiting for its associated DEVICE block to complete startup of the Bailey interface and make itself available to the other OPC90 Server blocks ESTABLISHING POINT The block has requested its associated DEVICE to establish the point in the Bailey interface WAITING FOR DATA FROM BAILEY The point has been established in the Bailey interfa
85. window If configuration shadowing reports Bad or Off on either OPC90 both will attempt to command their CIU online resulting in this red light condition After configuration shadowing has been properly setup and working correctly reset the CIU in the red light state to recover its use 12 24 OPC90 Will Only Run in Demo Mode The OPC90 downloaded from the RoviSys OPC Foundation and OPC Training Institute websites is the demo only version By design that version can only run in demo mode Verify the demo version is not installed by looking at the OPC90 Help About dialog If it states THIS IS A TIME LIMITED DEMO VERSION purchase a licensed version from RoviSys If a licensed version has been installed but it is still running as demo there are several things to check 1 Make sure the USB license key is plugged into the PC 2 Run License Manager desktop short cut and select Report button Verify it reports the license serial number 3 Run Windows Service Manager and verify the RoviSys License Service is running If it is not running start it and then restart OPC90 restart OPC90 service 4 Stop RoviSys License Service and then set the compatibility of C Program Files RoviSys LicenseManager RVSService exe or C Program Files x86 RoviSys LicenseManager RVSService exe to Run as an administrator Start the service back up and restart OPC90 restart OPC90 service 5 Re run the C Program Files RoviSys LicenseManager Sent
86. 000000164 Channel 1 receive errors 60 Samples in Averages Sw3 0x48 0057125357 Total messages received and forwarded by this node 0000000159 Channel 2 receive errors Get now Sw4 0x10 0002628310 Total messages put into receive buffer and retained 0000000047 Transmit errors 0010142185 Total messages originated by this node including retries 0000000111 Transmit message watchdog timeouts Node Performance Statistics 0000000234 Total messages originated by this node retried 0000000000 Number of loop failures v Messages Average Bytes 2063438207 Total bytes received and forwarded by this node 0000000000 Messages lost to receive queue overflow AS nyc ros 1462970244 Total bytes originated by this node including retries 0000000000 Messages dumped with circulation count errors p g H 0053865300 Multicast messages received excluding original 0000000001 Messages dumped with type or destination count errors LOOP TX 68 73 10968 0082689676 Multicast destinations received 0000000003 Messages dumped with source state errors NIS TX 75 j 87 2307 0000000165 Broadcast messages received excluding original 0000000002 Messages dumped with source sequence mismatch 0000012403 Time sync messages received excluding original 0000000000 Re alignment of transmit buffer due to invalid contents NIS Rx 196 227 2007 0000024819 Read time sync buffer requests 0000000000 Re alignment of receive buffer NODE TX 18 j 16 1444 0003247467 NIS poll messages received excluding original 0000000000
87. 3003 INT Log OPC Writes MY S3003 INT NAK TOTAL 53003 INT Properties ONLINE 53003 INT Faceplate zl gt New Group ONLINE Unlimited V 52 6531 DEVICE INICIOS G 3 30 70 70 70 70 70 720 20 20 20 20 70 v U of Clients 6 Grops2 Note that if OPC90 is not currently in run time mode of operation the Restart option will be grayed out Corporate Headquarters The RoviSys Company 1455 Danner Drive Aurora Ohio 44202 330 562 8600 www rovisys com RoviSys Company Copyright 1999 2015 Page 185
88. 4 AIL My black type 04 17 2012 07 33 35 834 192 OPC status value 04 17 2012 07 56 52 389 46 001095 Current Output Value from Bail 04 17 2012 07 56 52 389 Good Quality 0 Good 1 Bad 04 17 2012 07 56 52 389 200 000000 Span in EngUnits 04 17 2012 07 32 30 480 Sine 002 Short Tag Name 04 17 2012 07 33 35 834 Tag Descriptor 04 17 2012 07 33 35 834 CIU Sines Long Tag Name full OPC path 04 17 2012 07 33 35 834 100 000000 Zero in EngUnits 04 17 2012 07 32 30 480 sa E 3X Sine 007 MESSA STRING 3 MY BLC STRING 3 OPC S SHORT RO Properties ad 3k QUALTT e BOOLEAN E Sine 011 X SPAN Tiside FLOAT E Sine 012 3 TAG 1 1 3 102 STRING E Sine 013 TAGDESC 1 4 3102 STRING E Sine D14 TAGLONG 1 3 102 STRING E Sine 015 ZERO 1 1 3 102 FLOAT EA cine NIA E Sine 008 E Sine 009 E Sine 010 m0722222m75 0 Do Clients 31 Groups 61 Tags 27795 Rate 3046 Service Run Sine 002 ONLINE Some tag values have write access and can be written from within the OPC90 program window when monitor mode is active Simply right click on the tag name and select the write option The following dialog will be displayed RoviSys Company Copyright 1999 2015 Page 34 OPC90 Server User Manual V8 2 1 Write a Tag Value to Bailey TagN ame HI_LIM Description High Alarm Limit DPC Tag Data Current Value IEEE Curent Quality Good TimeStamp 01 14 2009 14 58 09 Message ONLINE were Close
89. 5 INTEGER_2 7 INTEGER_4 6 REAL_4 8 STRING RoviSys Company Copyright 1999 2015 Page 146 OPC90 Server User Manual V8 2 1 7 32 Station PID Control STN The STN OPC90 block is used to retrieve and control the exception reported outputs from Bailey Control Station blocks function codes 21 22 23 amp 80 Restrictions This OPC90 block can be utilized with all Bailey interface types except serial port module SPM amp CPMO2 TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address ADDR NODE Bailey node address ADDR MODULE Bailey module address ADDR BLOCK Bailey block address MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor OPC STATUS OPC status value see OPC status section QUALITY VT Midi Current quality of Bailey values 0 good 1 bad STN_TYPE E l2 LL Station type 1 Basic 2 Ratio 4 Cascade STN LEVEL VT BOOL Read Write Station level see note 1 O Local 1 Computer STN_OK Station computer ok indicator see note 1 0 Bad 1 Ok STN_TIMER posses l4 pee Station time in seconds since last computer p see note 1 MODE mE l2 Read Write The mode of the Bailey block see note 1 0 Manual 1 Auto 2 Cascade MODE_LOCK Locked into current mode indicator EU Engineering Units Code EU_TEXT Engineering
90. 60 OPC90 Server User Manual V8 2 1 The last section is Command Center This section is used to request the various configuration activities Some configuration activities are under password control The Password area is used to enter the password assigned to the BLK block It displays The Command area allows expert users to bypass the button commands See the preceding section entitled Configuration Command Processing for details on what commands can be entered Most users will use the button commands described by the following table BUTTON Description READ Enter the address of a block in the addressing section and click on this button to read the function block data NEXT Click on this button to read the next function block data from the currently addressed block TUNE Enter new tunable specification values in the specification data section and click on this button to tune those values within the ABB Bailey controller Note the module must be Execute mode when tuning blocks DEFAULT Enter a function code number in the addressing section and click on this button to retrieve the default specification settings for that function code WRITE Enter the desired specification settings for the function block in the specification data section and click on this button to write the function block data to the ABB Bailey controller If the block already exists it will be modified Note the module must be in
91. 90VPortTester utility included with OPC90 uses this API and can be used to test a virtual port connection with a MUXCIU block It is also a useful utility for general purpose polling of block outputs within a given ABB Bailey controller module Here is an example of connecting and disconnecting with a MUXCIU block Note that an application should connect do all of its communication using the OPC90CommandCIU call and when finished disconnect include OPC90VPort h COPC90VPort opc90 WORD result DWORD sessionlD connect with the MUXCIU block result opc90 OPC90Connect OPC90PC name of OPC90 PC RoviSys Company Copyright 1999 2015 Page 102 OPC90 Server User Manual V8 2 1 BLOCKNAME long tag name of MUXCIU block 30000 time out in 30000 milliseconds no activity amp sessionlD session ID needed by the other calls disconnect from the MUXCIU block result opc90 OPC90Disconnect sessionID RoviSys Company Copyright 1999 2015 Page 103 OPC90 Server User Manual V8 2 1 7 18 Network Interface Slave Monitor NISMON The NISMON OPC90 block is used to retrieve general network interface slave NIS information topology data event and error counters memory usage and various node performance statistics NISMON is typically used to return topology data but also network diagnostic information to help find failing node hardware Each NISMON block automatically maintains a daily log in th
92. A 7 2008 2012 Server operating systems It is implemented as a collection of blocks that are specific to each type of exception report block found within a Bailey system This collection of blocks is stored as an OPC90 Configuration A special block called the Device block DEVICE is configured to setup the communication port s used to access the Bailey interface define required update rates and report various statuses of the communication channels All other OPC90 Server blocks are linked to a DEVICE that provides the necessary information it needs to manage communication with the Bailey system The various other OPC90 Server blocks linked to the DEVICE contain the address within Bailey where the exception report block is located The DEVICE uses this address and block type to determine how the point is established and managed within the Bailey interface As data is received from the Bailey interface for each of the established points it is parsed and copied to the appropriate tags within the corresponding OPC90 Server block This implementation has several advantages e Extremely intuitive to Bailey users e Developed with an industrial grade OPC toolkit manufactured by an OPC Foundation Charter Member company insures 10096 compliance to the OPC 1 0 2 0 and 2 05 specifications e Self validated using the OPC Foundation testing tools e Point capacity is not limited by type of points utilized by the plant but only by the type of Bailey inter
93. ADDR RING Bailey CIU ring address ADDR NODE Bailey CIU node address ADDR MODULE Bailey CIU module address ADDR BLOCK VT I2 Config Read Block number to establish this point at within the Bailey interface see note 1 MSDD TYPE VT I2 Config Read Bailey MSDD type code to use when establishing this point see note 2 MAX TIME VT l4 Config Read If OUT never changes it will be reported at the maximum time interval seconds defined by this attribute MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor OPC STATUS OPC status value see OPC status section QUALITY VT BOOL Read Write Current quality see note 3 of Bailey values 0 good 1 bad MODE VT I2 Read Write Mode of this control loop expressed as 0 Manual 1 Auto RED TAG VT BOOL Read Write Device red tag indicator GOOD STATE VT l2 Read Write Current good state see note 4 REQ STATE VT l2 Read Write Current requested state see note 4 OUT Value of discrete output ALARM Indicates alarm condition F1 Current state of first feedback signal F2 Current state of second feedback signal F3 Current state of third feedback signal F4 Current state of fourth feedback signal OVR_CONTROL Current state of control override OVR_STATUS VT_BOOL Read Write Current state of override status
94. ADIG Device Driver DD Digital Output Loop DOL DOLDB Harmony Analog Input Harmony Analog Output Harmony Digital Input Harmony Digital Output Module Status Multi State Device Driver MSDD Multiplexes a PC COM port to Bailey Interface for configuration related software i e Bailey CADEWS Composer G Michaels DBDOC etc Provides detailed node diagnostic information and the communication loop Logs potential problems Monitors performance of a PCU node Poll Value POLL Remote Control Memory RCM Remote Motor Control RMC Remote Manual Set Constant RMSC Sequence of Events Specification SPEC Control Station STN Text Selector TEXT Text String TEXTSTR 30 48 70 158 any function code 177 211 123 45 67 222 223 224 225 any module 129 any function code any node any PCU node any block 62 136 68 99 243 any block 21 22 23 80 151 194 The common Bailey computer interfaces used to gain access to the Bailey exception report blocks presented in the above table also support the ability to allow a system to emulate and output most of these same point types They are called output report block types Bailey consoles receive the point type exception reported data directly from the Bailey interface in the same format as if it was coming from an equivalent Bailey controller This allows the predefined Bailey console faceplates for each of these control point types to b
95. ANYBlock WE DATA E MUXCOMG ES PCUMON POLL point EE SPEC point SPAN TAG TAGDESC 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 FLOAT STRING STRING STRING FLOAT B6400 000000 AIL point Reads Bailey AOL block value Span in EngUnits Short Tag Name Tag Descriptor Long Tag Name full OPC path Zero in EngUnits 04 17 2012 08 56 53 373 04 17 2012 08 55 07 514 04 17 2012 08 55 07 514 04 17 2012 08 55 07 514 04 17 2012 08 56 53 373 TAGLONG ZERO CIU A Import AIL point 0 000000 7777777777272 0070702010m Uu ofr Clients 0 Service Run AIL point ONLINE This example shows a device called CIU A Three groups have been configured under this device called Export Import and Misc The Import group contains sample blocks for receiving exception reported values from the ABB Bailey system The Export group contains sample blocks for responding to the ABB Bailey system as the indicated exception report block The Misc group contains sample blocks for reading tuning ABB Bailey block configuration information multiplexing the COM6 port as a CIU port polling a block output and providing specification information for a particular block As noted from this example the device has a unique symbol lU identifying it as a device Groups are identified with the folder symbol Each block type has a unique symbol identifying the functionality of that block Generally blocks that
96. All possible statistics that can be collected are logged to the file Those statistics that are not currently enabled for collection are logged with a value of negative one 1 The log file includes a header definition identifying each statistical column It also contains hourly and daily averages for all logged data followed by the data collected at each interval The file layout is designed So it can be opened and saved in the Excel format and then statistical analysis of the data can be setup and performed by time which is also a statistical column in the file Files older than the Device block Days to Retain Debug Logs setting will automatically be deleted to avoid using up unnecessary disk space These throttle factors are applied when any of the conditions have been determined that warrant throttling slowdown of OPC90 polling activities The throttle factors are applied to polled type messages directed to the PCU node being monitored The THROTTLE MUX setting applies to MUXCIU block messages This factor delays command replies by the specified milliseconds The THROTTLE _PCUMON setting applies to this block This factor is in milliseconds and is added to the blocks INTERVAL setting The THROTTLE POLL setting applies to POLL blocks This factor is in milliseconds and is added to the POLL block INTERVAL setting The THROTTLE SPEC setting RoviSys Company Copyright 1999 2015 Page 129 OPC90 Server User Manual V8 2 1 applies to SPE
97. C blocks This factor is in milliseconds and is a delay added in between each request for specification data The THROTTLE _BLK setting applies to BLK blocks This factor is in milliseconds and is a delay added in between each read or write block request that occurs when module configurations are saved or restored When this throttle factor is set true all MODSTAT blocks will be searched looking for those associated with controllers within the PCU node being monitored If any of those MODSTAT blocks indicate the controller is not in execute mode declaration of the optimize condition will be suspended The THROTTLE_OVR tag indicates the optimization override is in effect This is important since one or more controllers not in execute mode will not be contributing to exception report traffic which means lower average levels and therefore a faulty declaration of the throttle state Obviously for this factor to be effective MODSTAT bocks for all controllers within the PCU node being monitored should be configured in the OPC90 database 10 The communication module processing power utilization COMM PCT is periodically read by this block when COMM LEVEL is greater than 1 Each value is submitted to a moving average calculation made available as the COMM PCT AVG tag If the value of the COMM PCT AVG tag exceeds the COMM LEVEL tag setting a THROTTLE condition slowdown polling is declared While in this condition the throttle factors see note 3 will
98. C90 block is valid for INFI 90 Harmony and Symphony systems It can be utilized with Bailey interface CIU types that include an INICTO3A or INICT13A module The node to be monitored must have INNPMO 1 firmware revision C 1 or later Note that the OPC90 MODSTAT block can be used to determine the firmware revision level of the INNPMO 1 if it is not known All INNPM22 firmware revisions are supported for nodes so equipped TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey PCU ring address see note 1 Read Write ADDR NODE Bailey PCU node address see note 1 Read Write INTERVAL How often to read the data in ms 0 disable Read Write see note 2 GET NOW VT BOOL Read Write Set to request an immediate read of the enabled data INTERVAL must also be non zero MY BLOCK TYPE VT BSTR Indicates the OPC90 block type ENABLE NIS VT BOOL Read Write Enable collection of NIS event and error RoviSys Company Copyright 1999 2015 Page 104 OPC90 Server User Manual V8 2 1 ENABLE NPS ENABLE MEM ENABLE XRP ENABLE MAP ENABLE SYNC SAMPLES MESSAGE TAG TAGLONG TAGDESC OPC STATUS QUALITY FIRMWARE SW1 SW2 SW3 SW4 When ENABLE_MAP TOPOLOGY_INTERVAL TOPOLOGY When ENABLE_NIS TIME_IRQ CHAN1_RX_ERR CHAN2_RX_ERR TX_ERR LOST_RQ_OVERFLOW DMP_CIR_CNT_ERR DMP_TYPE_CNT_ERR DMP_SRC_STATE_ERR DMP_SRC_SEQ_ERR MULTI_CAST_RX MULTI CAST DEST RX TIME SYNC RX BROADCAST RX counters see note 2
99. D BLOCK 13 Returns requested block data READ NEXT BLOCK 14 Returns next block requested block data READ DEFAULT BLOCK 15 Returns default block data WRITE BLOCK 16 ACK NAK code indicating requested result TUNE BLOCK 17 ACK NAK code indicating requested result DELETE BLOCK 18 ACK NAK code indicating requested result READ BLOCK OUTPUT 20 Returns value of requested block output READ PROBLEM 26 Returns requested problem report data REPORT DEMAND MODULE 27 Returns requested module status STATUS READ EXTENDED 46 Returns requested extended problem report PROBLEM REPORT data TREND DATA POLL 48 Returns requested trend block data CIU RESTART 19 Returns response from when OPC90 DEVICE RoviSys Company Copyright 1999 2015 Page 101 OPC90 Server User Manual V8 2 1 block driver originally issuing this command READ WORK FLAG 34 Always return ACK and flags indicating no additional work is required ENVIRONMENT 69 Returns response from when OPC90 DEVICE block driver originally issuing this command READ SYSTEM 43 Returns requested time date response Time TIME DATE Stamp and Wall Clock offset are always zero SET SYSTEM TIME DATE 60 Always returns a ACK response DEQUEUE 25 Always returns a ACK response CIU CALLUP 41 Always returns a ACK response CIU HANGUP 42 Always returns a ACK response CIU ONLINE OFFLINE 44 Always returns a ACK response CANCEL KEY COMMAND 50 Always returns a ACK response
100. DCOM or user account setup error Review the DCOM settings Also remember that if the local and remote PCs are members of a domain make sure the user account that is running OPC90 and the OPC clients have sufficient privileges Power Users minimum or Administrator If the PCs are members of a workgroup they both must run OPC90 and the OPC clients from user accounts that are the same on both PCs 11 Migrating OPC90 to a Windows 64 Bit Environment OPC90 can run in a Windows 64 bit environment Follow these steps when migrating from a 32 bit to 64 bit environment RoviSys Company Copyright 1999 2015 Page 170 OPC90 Server User Manual V8 2 1 Before Installation Log into a privileged account Turn off UAC User Access Control o If you don t know how do a search from Windows help for UAC and the results will provide a link to do this Run the setup from the OPC90 CD or downloaded installer After Installation Using Windows explorer set the properties of C Program Files x86 OPC90 Serve OPC90Server exe compatibility to Windows XP SP3 o Right click on this file and select properties and select the compatibility tab If running Windows 7 using Windows explorer set the Run as administrator properties of C Program Files x86 OPC90 Server OPC90Server exe o Right click on this file and select Run as administrator Copy your current database file from the XP PC to the new 64 bit PC o C Program Files OPC90 Serve CFG to C Prog
101. ERENCE Reference status 0 Good 1 Bad CALIBRATION VT BOOL Read Calibration status 0 Good 1 Bad RoviSys Company Copyright 1999 2015 Page 92 OPC90 Server User Manual V8 2 1 SIM ENABLE VT BOOL Read Write Simulation enable 0 No 1 Yes SIM BLOCK VT l2 Read Simulation value block number 7 13 Harmony Digital Input HDI The HDI OPC90 block is used to retrieve the exception reported output from Bailey Harmony Digital Input function code 224 blocks Restrictions This OPC block is only valid for Bailey interface types INICIO3 INICI12 and INICI13 This OPC block does not support the reception of Harmony digital input sequence of events data TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address ADDR NODE Bailey node address ADDR MODULE Bailey module address ADDR BLOCK Bailey block address OUTLSDO Output state zero logic state descriptor OUTLSD1 Output state one logic state descriptor MY_BLOCK_TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor CHAN_NAME Channel name assigned to this point CHAN_STATE VT_BOOL Read Channel state 0 Ok 1 Open 2 Short 3 Overdrive ALARM CODE Alarm code OPC STATUS OPC status value see OPC status section QUALITY Current quality of Bailey values 0 good 1 bad QUAL PROP Propogated Quali
102. Enables additional logic that handles MSDD blocks configured for pulsed output operation The MSDD pulse output time specification 822 is read on startup If non zero whenever changes to the requested state are made the OPC90 MSDD block REQ STATE tag will be reset to zero after the configured pulse output time has transpired Remember any changes made to MSDD block pulse output times after startup of OPC90 are not recognized until OPC90 is restarted Supports defining the type of ABB Bailey system and time syncing related options see note 2 Accuracy rating assigned to the PC running OPC90 and its CIU This rating can be 0 255 CIU nodes with the highest accuracy rating are allowed to become the time sync master if time syncing is enabled for that node This setting can be used to define which OPC90 should be favored as the time sync master node see note 2d Defines the fast update interval in minutes and poll rate in milliseconds for all STN blocks belonging to this device When a STN K attribute is written or STN KFAST see STN block description is set the server automatically polls for STN PV and STN CO values for the interval and rate defined by this setting This feature is very useful for loop tuning software Setting the fast update interval to zero will disable it When set any write to the PID tuning tags K OUT HI LIM AND OUT LO LIM will automatically turn KFAST on Normally the STN block represents mode in the
103. F This document has been installed in the C Program Files OPC90 Server directory To run DCOMOCNFG select Start Run and type in DCOMCNFG or start it from the OPC90 Utilities menu selection Based on the Windows operating system being used one of the two following program windows will be displayed Distributed COM Configuration Properties E 2 x 1 Component Services Applications Default Properties Default Security Default Protocols Action View Window Help mm x ea e DCOM Config 182 object s e Component Services Application ID Computers E al My Computer COM Applications a DCOM Config Applications elp MsoHelp AW Search Dialog MsoHelp Key Search Dialog MSVS Local Event Concentrator Class Pocrsver 1 0 Object D79D876B 7741 offrrovio 7C61BC39 AAB1 S opc2oiF 1x 3C570292 EBSE pcEnum OPCTESTDA and OPCTESTAE Buk Nessge Athen Sil Distributed Transactic ees Server 2508F89D 3490 PH Document 5 Running Processes dimid 113486D44 4821 enel Automation CLSID StubMarshale zi G Event Viewer Local Outloo Message 1 0020D09 0000 E E Services Local outlook Office Fin 0006FO1F 0000 Paintbrush 1D3E34821 9D75 lt gt Properties Select OPC90 Server which can be found under the Application tab list box or under Components Computers My Computer DCOM Config Click on the properties button or right click on OPC90 S
104. I STATUS SHADOW SEC STATUS STARTUP SYNC DCS SYNC NODE SYNC RING TURBO ACTIVE TURBO STALE TURBO TOTAL XRP_RATE XRP_TOTAL XRPS_TOTAL COMI10 COMI10 COM10 COM10 COM10 COM10 COM10 COMI10 COMI10 COMI10 COMI10 COMI10 COMI10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 COM10 INT R INT R STRING BOOLEAN STRING STRING INT INT INT STRING STRING INT INT INT INT INT INT INT INT INT INT BOOLEAN STRING INT INT BOOLEAN INT INT BOOLEAN BOOLEAN INT INT INT INT INT INT INT INT Good Off ONLINE Unlimited v7 5 1 12 8 4798 DEVICE INICIO1 E O 16 1 3 1016 1 652 t 762 Good Good Disabled Not Used 0 o Not Used Not Used Bad off off 0 0 4 4 4 282 20197 1200 All Comm Status 0 Good 1 Bad Block specification read cycles completed CSV file to import Request read of the import CSV file 0 Done 1 Read Result of the CSV file import request Device Status Total Messages In Queue Needing Keys Message Rate messages sec Total Messages My black type My Device Interface Node Address Interface Ring Address Total Negative Acknowledgments Received Total Blocks Poll black output value rate values sec Total block output values
105. ILE tag can be set to advance to the next oldest SOE log file or SOE FILE can be written to look at a specific file Note that writes to SOE FILE do not require path information but can be included if the SOE log files have been moved to an alternative location Note also that SOE NEXTREC and SOE NEXTFILE will automatically reset to indicate the requested action has been completed All of these tags are utilized to implement the following OPC90 SOE block faceplate RoviSys Company Copyright 1999 2015 Page 143 OPC90 Server User Manual V8 2 1 SOE_5600 1 1 3 5600 Ready to Capture Standard SOE Block JV View Event Data File E 3 5500 0326200704 5TD Next File SOE Record 2 of 51 Record 2 Previous Record Point 0008 Standard Undefined 22 17 23 052 09 26 2007 Good OnScan Reset ONLINE RoviSys Company Copyright 1999 2015 Page 144 OPC90 Server User Manual V8 2 1 7 31 Specification Block SPEC The SPEC OPC90 block is used to retrieve block specification data for any configured Bailey function block This block is similar to the OPC90 Server block BLK with the exception that the OPC client does not have to send a command to read the specifications and cannot browse blocks using a NEXT tag The SPEC block retrieves block specification information through background polling activity The block address is configured in the RING NODE MODULE and BLOCK attributes of this block in the OPC90 Serve
106. IU block throttle factor to be applied when need for OPC90 polling slowdown condition exists Expressed in milliseconds see note 4 PCUMON block throttle factor to be applied when need for OPC90 polling slowdown condition exists Expressed in milliseconds see note 4 POLL block throttle factor to be applied when need for OPC90 polling slowdown condition exists Expressed in milliseconds see note 4 SPEC block throttle factor to be applied when need for OPC90 polling slowdown condition exists Expressed in milliseconds see note 4 BLK block throttle factor to be applied when need for OPC90 polling slowdown condition exists Expressed in milliseconds see note 4 No throttle when MODSTAT blocks for any controller within the PCU indicate failed or configure mode see note 5 Indicates the block operational message Indicates the block name Indicates the block long OPC path name Indicates the block descriptor OPC status value see OPC status section Current quality of PCU node communication statistics 0 good 1 bad Number of samples to retain for calculating moving averages of the overload conditions being monitored Flags whether or not the throttling of OPC90 polling activities has been overridden because one or more controllers within the PCU are not in execute mode see note 5 Flags whether or not the throttling slowdown of OPC90 polling activities is in effect due to communication module processing power utilizat
107. K block Operation Command Use this command to change the current operating mode of a controller See section 7 3 2 entitled Changing Bailey Controller Module Modes for a detailed discussion on these modes The command argument can be the name of the mode or its corresponding mode number f the address arguments are omitted the current address specified in the ADDR_RING ADDR_NODE ADDR_MODULE tags will be used as the destination address for the operation Following are some example operation commands Command Action OPERATION CONFIGURE Changes currently addressed module to configure mode OPERATION CONFIGURE 136 Changes ring 1 node 3 module 6 to configure mode RoviSys Company Copyright 1999 2015 Page 55 OPC90 Server User Manual V8 2 1 OPERATION 2 Changes currently addressed module to configure mode OPERATION 2 1 37 Changes ring 1 node 3 module 7 to configure mode OPERATION EXECUTE 137 Changes ring 1 node 3 module 7 to execute mode OPERATION INITIALIZE 1 3 6 Initializes the configuration of ring 1 node 3 module 6 Save Command Use this command to save a Bailey module function block configuration to a file Note that only the function blocks are saved BASIC programs or C programs with any associated data files are not included in the save Contact RoviSys if your needs include saving programs Any file name can be specified If the filename contains spaces it must be enclosed i
108. K parameter 12 10 Cannot see all documented block attributes 12 11 Occasionally new attributes are added to a block definition that were not defined in an earlier release of OPC90 If you notice a documented block attribute does not appear when the block is selected it could be a new attribute One such attribute is RED TAG It was added in OPC90 Version 2 1 Configurations saved prior to version 2 1 did not have this attribute defined so therefore it does not automatically appear when the software is upgraded To make new attributes appear you must export the configuration using the File gt export function request a new configuration using File gt new and than import the configuration just exported OPC90 Server Will Not Time Sync Bailey 1 Verify that the Bailey interface device is not a NSPMO1 or NCIUO1 These devices do not allow a computer to send time synchronization commands to Bailey If the Bailey interface device is one of these types disable time synchronization 2 Verify that time synchronization has been enabled This can be found under the properties of the OPC90 Device fl block RoviSys Company Copyright 1999 2015 Page 178 OPC90 Server User Manual V8 2 1 3 For ABB Bailey Network 90 systems verify that the node map is configured correctly for ALL nodes in the system regardless of whether or not data is being exchanged with any particular node This can be found under the properties of the OPC90 Device f
109. LE Bailey module address Read Write ADDR_BLOCK Bailey block address Read Write MY_BLOCK_TYPE Indicates the OPC90 block type MESSAGE VT_BSTR Read Message indicating result of the last configuration related request TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor READ VT_BOOL Read Write Set to request the specifications for the addressed block to be read The driver will reset this attribute when the read request is completed NEXT VT BOOL Read Write Set to request a read of the specifications for the next block from the current one The driver will reset this attribute when the next block read request is completed and update the BLOCK attribute to reflect the next block read TUNE VT_BOOL Read Write Set to request a tune operation for any specifications that have been changed after reading them The driver will reset this attribute when the tune read request is completed DEFAULT VT_BOOL Read Write Set to request a read of the default specification settings for the function code indicted by the FC attribute The driver will reset this attribute when the read default request is completed PASSWORD VT_BSTR Read Write Password to unlock the OPERATION attribute and some commands supported by the COMMAND attribute Will indicate 2 2 2 when locked and when unlocked FILE TYPE VT BOOL Read Write When reset the config
110. LL ice oett pe eec ce i ce SOK iet Se e eme Ga ee 133 7 27 REMOTE CONTROL MEMORY RCM isses seen enne enne nennen a nennen tense nennen nnne nnns 135 7 28 REMOTE MOTOR CONTROL RMC cccssccesssscecesssececeeseececseceecsesaececsesaececseeecsesaececseaaeeseseeeceeaeeseneneeeess 137 7 29 REMOTE MANUAL SET CONSTANT RMSC cccssccccsessececsssceceessececsesaeeecseeecsesaececseeaeeecaeeecseaeeecseneeeess 139 7 30 SEQUENCE OF EVENTS SOB J 35 eee ici edet eee eie ep e iud eee cede Te e pu eere gd 140 7 31 SPECIEICATION BEOCK SPEC eic eet reete riter ee idee eee e ente e t eai ipee 145 7 32 STATION PID CONTROL STN esc eee deae ed ed pe eed 147 7 33 STEXT SEEEGTOR A tnter e enn anbieten eor re eS 151 1 34 TEXT STRING TEXTSTR n eerte deeem tete ete Utere De eee ve EUER 152 OPC STATUS erc H 153 9 lt CSV FILE FORMATS osoei ocio eie reete tese totos epo ette et eb Pe VERSUS EET ERN PE YS eT Ule sep ES Pane Cep Ge eS E Sp se eX OT exeo eR Een ever eade 154 10 SETTING UP OPC CLIENT ACCESS OF OPC90 c eeeeeee eese eene teens eene en sense toss tane ta setas etas e tosta 159 RoviSys Company Copyright 1999 2015 Page 3 OPC90 Server User Manual V8 2 1 10 1 CONFIGURING DCOM ON THE LOCAL OPC90 PC ssssesesssseeseeeeenenee enne nennen eene terns sesenta nnns 159 10 2 CONFIGURING DCOM ON THE REMOTE OPC CLIENT PC ccceccccccececsesseseceeececsesssaec
111. LOCK ADDRESS ALREADY USED BY ANOTHER BLOCK is not posted in the MESSAGE attribute in any of the OPC90 Server blocks not receiving data If such a message is found you have two or more OPC90 Server blocks pointing to the same address within Bailey Eliminate the duplication 3 Verify WAITING FOR DATA FROM BAILEY is not posted in the MESSAGE attribute in any of the OPC90 Server blocks not receiving data If such a message is found it usually indicates the OPC90 block type does not match the ABB Bailey function block type An example would be to have an OPC90 AIL block trying to receive data from an ABB Bailey function code 222 block For this problem the OPC90 block type needs to be HAI 4 Verify EXCEEDED OPC90 Server POINT LICENSE is not posted in the MESSAGE attribute in any of the OPC90 Server blocks not receiving data If such a message is found you have exceeded the lite version block capacity Purchase the non lite version RoviSys Company Copyright 1999 2015 Page 176 OPC90 Server User Manual V8 2 1 6 Make sure none of the Bailey controllers have addresses less than two 7 Indices or memory capacity of the Bailey interface has been exceeded It is unlikely that you will encounter this error unless your application has a very large number of OPC90 Server blocks and the Bailey interface device is a NCIUO1 or INCICO1 Enable the Device DEBUG LOG error reporting option and search the OPC90 log file messages for s
112. Low deviation alarm active indicator Indicates PID SMITH STN block is in fast update mode see note 5 VT BOOL Read Write Setting this tag requests an immediate read of the PID SMITH tuning parameters K tags It is automatically reset when the read has been completed This tag cannot be set until after the STN block PID SMITH function code KFC has been determined VT R4 PID SMITH function code number VT BSTR Read PID SMITH type informational string p interprets KDIR KIONLY and KTYPE NUM into string format VT l2 Read PID algorithm type Version OX original 1X new Type XO classical X1 non interacting X2 Classical with external reset X3 manual reset non interacting VT R4 Read Write PID direction switch see note 4 0 reverse acting SP PV 1 direct acting PV SP or SMITH predictor external reference flag not writeable for SMITH predictor 0 normal 1 use external reference VT R4 Read Write PID set point modifier see note 4 ro 1 integral only on set point change PID integral limit type 0 quick saturation recovery 1 conventional saturation recovery VT R4 Read Write Overall PID block gain term or SMITH RoviSys Company Copyright 1999 2015 Page 148 OPC90 Server User Manual V8 2 1 predictor process model gain see note 4 KP ie block proportional gain value see note Kl VT_R4 Read Write PD block integral action time constant or m ems SMITH
113. N ADDR RING Bailey ring address ADDR NODE Bailey node address ADDR MODULE Bailey module address ADDR BLOCK Bailey block address F1LSDO Feedback 1 state zero logic state descriptor F1LSD1 Feedback 1 state one logic state descriptor F2LSDO Feedback 2 state zero logic state descriptor F2LSD1 Feedback 2 state one logic state descriptor OUTLSDO Output state zero logic state descriptor OUTLSD1 Output state one logic state descriptor MY_BLOCK_TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor FACE_TYPE Faceplate type value of DD block S10 DISC_ACT Alarm active indicator OPC_STATUS OPC status value see OPC status section QUALITY VT_BOOL Read Current quality of Bailey values 0 good 1 bad OUT Bailey discrete output value OUT_TEXT VT_BSTR Bailey discrete output value as a string see note 1 MODE VT I2 Read Write The mode of the Bailey block mE 1 Auto MODE LOCK Indicates mode is locked in auto 0 no 1 yes RED CMD Red tag command see red tag users section RED TAG Red tag indicator 0 no 1 yes RED USERS Red tag users current user names or codes F1 State of feedback number 1 F1 TEXT State of feedback number 1 as a string F2 State of feedback number 2 F2 TEXT State of feedback number 2 as a string BAD FEEDBACK Feedback ba
114. OL Text string lock 0 Off 1 On TEXTSTR MAX VT I2 Maximum text string size allowed TEXTSTR SEQ VT I2 Read Comm system text string sequence number Notes 3 When ALARM REQ is set 1 and a write occurs to TEXTSTR the write will specify the string is in alarm 4 The text string value can be written when the block is in manual mode the text string lock is not on and the TEXTSTR application and or block configuration supports writes RoviSys Company Copyright 1999 2015 Page 152 OPC90 Server User Manual V8 2 1 8 OPC Status All blocks that exchange data with the ABB Bailey system include an OPC tag called OPC STATUS This tag provides the value of the OPC status The value is defined with three sub fields The two most significant bits define the OPC quality The next four bits define the sub status for the current quality The two least significant bits define the limit bits for the current quality and sub status The tag value is defined as the logical OR of the following definitions OPC Quality codes define QUAL BAD 0x0000 define QUAL UNCERTAIN 0x0040 define QUAL GOOD 0x00CO Limit Bit Field define QUAL NOT LIMITED 0x0000 define QUAL LOW LIMITED 0x0001 define QUAL HIGH LIMITED 0x0002 define QUAL CONSTANT 0x0003 Substatus code for all define QUAL NON SPECIFIC 0x0000 Substatus code for GOOD define QUAL LOCAL OVERRIDE 0x0018 Substatus code for BAD define QUAL CONFIGURATION ERR
115. OM ports This will bypass the communication being channeled through the Lantronix driver and instead OPC90 will setup a direct TCP socket connection with the Lantronix device The DEVICE block supports definition of up to 16 TCP ports These ports are referenced as TCP 1P through TCP 8P and TCP 1S through TCP 8S with the P signifying Primary and S Secondary RoviSys Company Copyright 1999 2015 Page 83 OPC90 Server User Manual V8 2 1 The intent of this range of TCP ports is for organizational purposes only Typically the first DEVICE block would be assigned TCP 1P and TCP 1S if using redundant channel setup The second DEVICE block TCP 2P and TCP 2S and so on In actuality any TCP port can be assigned in any order but just must be unique amongst all configured DEVICE blocks The list of TCP ports can be selected in the DEVICE block properties dialog and are found within the Primary and Secondary port list boxes They appear after the list of 128 COM ports and any detected SCSI ports The idea is to associate the TCP xP ports with the Primary port and TCP xS ports with Secondary port when Redundant Channel or Dual Interface communication schemes are being used When a TCP port is initially selected it will not have an IP address and port number defined yet The definition will look like this Device Properties Name CIU Description Infi 90 CIU COMMUNICATION PARAMETERS Scheme Redundant Channel M Primary Port TCP
116. OPC90 Server User Manual V8 2 1 o Set Bad Output Quality on Boolean Config Max Exception Timeout Any Input Write Applies to Boolean Config All Output Blocks Allow turbo reads for bad Boolean Config quality blocks CONTINUOUS OPC Boolean Config UPDATES XRP WRITE CONFIRM Boolean Config condition it will automatically be connected by the CIU reported and then disconnected by OPC90 This option is very useful for large databases that have blocks that OPC clients aren t interested in getting data from It saves communication bandwidth but keeps the blocks available as needed in the future Some redundancy schemes that may rely on both servers having the same data should not run with this option enabled This option also applies to polled type of block values such as SPEC and POLL blocks It has no effect on block output values being polled via MUXCIU block connections Normally the STARTUP device tag resets when all of the points are established in the CIU Setting this option delays the STARTUP reset condition until after all of the blocks receive initial values from the ABB Bailey DCS The QUALITY tag will indicate bad for AOL DOL ODD OMSDD ORCM ORMC ORMSC and OSTN blocks when writes to the input tags do not occur within the block s exception report output max time setting When this occurs the bad quality condition is also written to the CIU and therefore propagated to the users of these data points in the ABB
117. OR 0x0004 define QUAL NOT CONNECTED 0x0008 define QUAL DEVICE FAILURE 0x000C define QUAL SENSOR FAILURE 0x0010 define QUAL LAST KNOWN VALUE 0x0014 define QUAL COMM FAILURE 0x0018 define QUAL OUT OF SERVICE 0x001C Substatus codes for UNCERTAIN define QUAL LAST USABLE VALUE 0x0004 define QUAL SENSOR NOT ACCURATE 0x0010 define QUAL ENG UNITS EXCEEDED 0x0014 define QUAL SUB NORMAL 0x0018 So the OPC status value of bad out of service would equal decimal 28 hex 1C which is QUAL BAD with QUAL OUT OF SERVICE RoviSys Company Copyright 1999 2015 Page 153 OPC90 Server User Manual V8 2 1 9 CSVFile Formats This section is provided to help the user quickly setup an OPC90 Server configuration A CSV file is an ASCII Text based file containing fields delimited by a comma Miscrosoft Excel can be used to create this file and simply export it in the CSV file format Each line row in Excel in the file declares exactly one OPC90 block OPC90 groups and tags are not defined within the file Groups and tags will be created automatically based on the block name and type File formats for each line in the CSV file are given below If you are still unsure about the exact format after reviewing the following tables consult the SamplePoints CSV included with the OPC90 installation You can also configure an example of a block using OPC90 Server itself and than export that database to a CSV file In addition to configuring OPC90 blocks
118. RATION tag is reset to a value of zero 0 The MESSAGE tag will also return a text message indicating completion of the module operation or the reason for failure if the requested operating mode cannot be completed When the ACKNAK tag is zero the request was successful non zero indicates an error occurred If for example a request to enter the execute mode actually results in error mode the MESSAGE tag will display a message indicating why this occurred and the Bailey block that caused the error For security it is highly recommended that once an OPC client has completed its use of the OPERATION tag it should lock it by sending an invalid password to the PASSWORD tag Note that OPC90 will automatically invalidate the PASSWORD tag after 60 minutes transpires with no OPC client write activity to the OPC90 BLK block 7 3 5 Writing Bailey Controller Blocks To write Bailey function blocks to a controller it must be in the configure mode of operation See the preceding section to understand how to change Bailey controller modes of operation There are five easy steps an OPC client must follow to write a Bailey function block First it writes the function code number of the intended new block to the FC tag Second it writes the new block number to the ADDR BLOCK tag Third it requests the default specification settings for the function code by setting the DEFAULT tag to TRUE The number of specifications is returned in the SPEC COUNT tag the default
119. RM tag but without the associated feedback waiting time In other words the OPC client uses the FB STATUS tag as a cycle to cycle indication that the feedback signals match or do not match the device state indicated by OUT The ALARM tag indicates a mismatch condition only after a feedback waiting time expires after the device transition The Bailey DD block logic includes a condition in which feedback status is essentially ignored and always considered good regardless of its actual state in comparison to the OUT tag The OPC client indicates this condition by setting the OVR STATUS tag RoviSys Company Copyright 1999 2015 Page 113 OPC90 Server User Manual V8 2 1 7 20 Output Multi State Device Driver OMSDD The OMSDD OPC290 block interfaces with Bailey consoles as a Bailey Multi State Device Driver block function code 129 Note that this block does not received data from a MSDD block running in a Bailey controller Use the OPC90 MSDD block for that purpose The OMSDD is used to indicate multiple state control of discrete devices having up to four runtime states reported by up to four feedback signals The operating mode of the device can be reported as auto controlled by logic or manual under operator control Restrictions This OPC block can be utilized with all Bailey interface types except CIUO1 serial port module SPM CPM02 amp CPMO03 and computer interface command series CIC TAGNAME TYPE ACCESS DESCRIPTION
120. S63 TYPE 2 S01 VALUE to VT R4 Read Write Value for specifications 1 through 63 S63 VALUE Since Bailey function blocks can have up to 63 specifications tags exist for the maximum number of specifications The actual number of valid specifications for any given block read can be determined by examining SX COUNT or the descriptions RoviSys Company Copyright 1999 2015 Page 145 OPC90 Server User Manual V8 2 1 assigned to them in tags SO1 to S63 Null descriptors indicate the specification number is not valid for the block read Some Bailey specifications can be modified while the block is executing These are called tunable specifications and are indicated as such by the specification description having the T character in front of it The tags S01 VALUE through S63 VALUE can be used to change the value of tunable specifications Notes 1 The format of how the specification data is returned can be selected utilizing the SPEC FORMAT attribute The following choices are available e 0 SxName Value Format includes spec number its name and current value e 1 Name Value Format includes spec name and its current value e 2 SxName Format includes spec number and its name e 3 Name Format includes just the name of the spec 2 The specification type is defined according to the following values Tunable specifications will be indicated by 100 added to these values 1 REAL 2 2 REAL 3 3 BOOLEAN 4 INTEGER 1
121. STATUS COM10 INT R Good All Comm Status 0 Good 1 Bad 04 17 2012 07 58 36 012 X BLOCK CYCLE COM10 INT R 498 Block specification read cycles completed 04 17 2012 07 58 36 012 View My Logs D of Clients 31 Groups 61 Tags 27795 Rate 2826 Service Run CIU ONLINE Unlimited 5 5 1 Service Manager Selecting the Utilities Service Manager menu option results in the Windows Service Manager to run That program allows the OPC90Server service properties to be modified and the service started The service manager is automatically run by OPC90 when it has been requested to set itself up as a service see View Run as Service 5 5 2 DCOM Configuration Selecting the Utilities DCOM Configuration menu option results in the Windows DCOMCNFG program to run That program allows DCOM to be setup for the computer and OPC90 5 5 3 View My Logs Selecting the Utilities View My Logs menu option displays a file open dialog allowing a specific OPC90 device or error log file to be selected and viewed by opening it in notepad 5 6 Block Faceplates Block faceplates are a handy engineering feature that allows real time monitoring and control of any block in the database These faceplates are available whenever OPC clients are attached to OPC90 the startup in runtime option is enabled or it is in monitor mode Simply right click on the block and select faceplate A faceplate dialog will be displayed that corresponds to the block type selected
122. Save Days Enhanced Analog Precision Flag MSDD Pulse Out Handling Flag Override DCS Time Stamp Flag SOE Save Days Automatic STN CPU_OK Flag Extended STN MODE range Tag Startup Complete on XRP Set STN KFAST on STN K Writes Set Output Block Types QUALITY Bad When No Inputs Max GMI per Second Max Keys to Use Turbo Poll Enable Accuracy Rating Set Last Tag Value Auto Disconnect Block Specification Read Period seconds Allow Bad Quality Turbo Polling Block Name Block Type Location Description OUTLSDO OUTLSD1 RoviSys Company Copyright 1999 2015 Page 154 OPC90 Server User Manual V8 2 1 D Block Name Block Type Location only block Description Max Time Initial Value Alarm State HAI L HAI Block Name Block Type Location Description Read Only Flag Block Name Block Type Location Description Read Only Flag Block Name Block Type Location Description OUTLSDO OUTLSD1 Block Name Block Type Location Description OUTLSDO OUTLSD1 Block Name Block Type Location ring node module Description Block Name Block Type Location Description FILSDO F1LSD1 F2LSDO F2LSD1 F3LSDO FSLSD1 FALSDO F4LSD1 GSLSDO GSLSD1 GSLSD2 GSLS3 Read Only Flag Block Name Block Type Location Description Update Interval Topology Interval Samples EnableNis EnableNps EnableMem EnableXrp EnableMap EnableSync ODD Block Name Block Type Location only block Description Max Time 0 Faceplate Type
123. Station block function codes 21 22 23 amp 80 Note that this block does not received data from a STN block running in a Bailey controller Use the OPC90 STN block for that purpose The OSTN is used to indicate control of an analog PID control loop The operating mode of the PID control loop can be reported as manual operator writes the set point and control output values auto operator writes the set point value with the control output calculated by the PID algorithm or cascade logic determines the set point value with the control output calculated by the PID algorithm Restrictions This OPC block can be utilized with all Bailey interface types except CIUO1 serial port module SPM CPM02 amp CPMO03 and computer interface command series CIC The other Bailey interfaces do not support being the source of PID tuning parameters Therefore PID loop tuning of this point from Bailey consoles is not possible TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey CIU ring address ADDR NODE Bailey CIU node address ADDR MODULE Bailey CIU module address ADDR BLOCK Block number to establish this point at within the Bailey interface see note 1 EU CODE Bailey engineering units code to use when establishing this point see note 2 STN TYPE Bailey station type code to use when establishing this point see note 3 ZERO Zero of PV and SP values in engineering units SPAN VT R4 Config Read Span of PV and SP values in engin
124. T FILE tag The default directory of C Program Files OPC90 Server CSV will be assumed unless otherwise specified with the file name Setting the IMPORT READ tag will request the CSV file to be imported OPC90 will reset this flag when the import has been completed The result of the import will be written to the IMPORT RESULT tag A log file that summarizes the result of the import will also be generated It is stored in the same directory as the CSV file imported It has the same name as the CSV file but with a LOG extension The log file is a standard text file that can be viewed using NOTEPAD After completion of the import the OPC90 database is automatically saved RoviSys Company Copyright 1999 2015 Page 80 OPC90 Server User Manual V8 2 1 7 8 4 SCSI Communication The DEVICE definition block supports SCSI communication with the INICIO3 and INICI1T3A When a device block is configured OPC90 will automatically detect the currently installed SCSI bus adapter s and search each adapter bus for INICIO3 INICI13A devices Detected devices will appear in the primary and secondary port list boxes that are part of the DEVICE block properties They are listed as devices like 0001 80002 etc The S indicates SCSI followed by the adapter card number adapter bus number adapter logical unit number and INICIO3 SCSI target ID Note that the target ID is the value set by switches on the Bailey INICIO3 INICI13A module or INICI13A INICT13A
125. TED BLOCK ATTRIBUTES cccccccsesessssecececeeseececececeesesseaesececeenesaeeeeeeeenes 178 12 11 OPC90 SERVER WILL NOT TIME SYNC BAILEY cccssssscccececeesssseececeesensececececeesesseaeceeeceeserseaeseeeceees 178 12 12 OPC CLIENT DOES NOT SEE ANY OPC SERVERS WHEN BROWSING REMOTE PC s 179 12 13 OPC CLIENT CONNECTS BUT DOES NOT RECEIVE DATA csessssssecececsesseceeececeesesseaeeeeeceenenssaeeeeeeeenes 179 12 14 VIEWING DATA IN MONITOR MODE DOES NOT WORK ccecsessssesecececsensscecececeesenssceceeeceesenssaeeeeseeenes 180 12 15 WRITING RMSC BLOCKS CAUSE CONTROLLER OR NODE OFFLINE CONDITION cene 180 12 16 LAST SAVED DATABASE NOT AUTOMATICALLY RESTORED ON PROGRAM START cccceeeessseeeeeeeees 180 12 17 DATA UPDATES STOP AFTER 2 HOURS 4er eco bee te ea Aee E coop ave duet E 180 12 18 DATA UPDATES STOP AFTER 8 HOURG sssssssccececsesssscecececsenssececececsenesecesececsesesecesececsenenssaeeeeeeeenes 181 12 19 SCSI ADDRESSES DIFFERENT BETWEEN TWO SHADOWED PCS cccsessscceececeesseaececeeessssececeeeceeneaees 182 12 20 OPC90 RUNNING AS A SERVICE RANDOMLY STOPS OR CRASHES eese ener nne 183 12 21 CAN T RUN AS A SERVICE UNDER WINDOWS 7 0 cccseesesseceeececeesseaeceeceeseseeesececeeseaeaeseceeeesenssaeeeeeceenes 183 12 22 BLK AND SPEC BLOCKS Do NOT REPORT CORRECT SPECIFICATION NAMES ener 183 12 23 CIU RED LIGHTS WITH LEDS 1 4 5 AND 6 ON u
126. The following example faceplate corresponds to the STN block type RoviSys Company Copyright 1999 2015 Page 38 OPC90 Server User Manual V8 2 1 SIN point 1 1 3 800 Example STN point used for PID control 422 377 325 All faceplates have a title which will be the block name followed by the address in ring node module block format The block description appears immediately under the title Along the bottom is the block operational status The remaining indicators and controls that appear will be specific to the block type 0 Some faceplates allow numbers to be entered These types of entries should be completed by pressing the Tab key although the Enter key also works for all blocks except the Device block If an entry is not completed within a few seconds it will revert back to the original setting Many blocks have alarm and other operational indicators These indicators are in the inactive state when gray and active when black For this example both the high deviation and high alarm is active It is important to note that all faceplates have been designed to only utilize OPC tags available from its corresponding block type This means the faceplates for each block type can serve as a good example on how a faceplate might be implemented in any given OPC client accessing the block data 5 7 Help The following picture shows the available Help menu items TurboListAnalysis cfg OPC90 Server File Add Edit View U
127. User Manual V8 2 1 7 22 amp Output Remote Motor Control ORMC The ORMC OPC90 block interfaces with Bailey consoles as a Remote Motor Control block function code 136 Note that this block does not received data from a RMC block running in a Bailey controller Use the OPC90 RMC block for that purpose The ORMC is used to indicate on off control of a discrete device with interlock signals up to two reported start permissive signals and up to two reported feedback signals It also reports bad start conditions due to lack of proper interlock signals and a fault condition upon loss of feedback signals after the device is enabled Restrictions This OPC block can be utilized with all Bailey interface types except CIUO1 serial port module SPM CPM02 amp CPMO03 and computer interface command series CIC TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey CIU ring address ADDR NODE Bailey CIU node address ADDR MODULE Bailey CIU module address ADDR BLOCK VT I2 Config Read Block number to establish this point at within the Bailey interface see note 1 RMC TYPE VT I2 Config Read Bailey RMC type code to use when establishing this point see note 2 MAX TIME VT l4 Config Read If OUT never changes it will be reported at the maximum time interval seconds defined by this attribute MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indic
128. VICE 528K RoboHelp exe Joel 21 064 K taskmgr exe Joel 4 660 K agent exe Joel 384K alg exe LOCAL SERVICE 52K cidaemon exe SYSTEM 408 K cidaemon exe SYSTEM 200 K ISUSPM exe Joel 456K mmc exe Joel 3 508 K Directcd exe Joel 812K mdm exe sys 1 576K iLicenseSvc exe SYS 44K vptray exe Joel 956K Support exe Joel 772K gearsec exe SYSTEM 44K Aafiuskeh AA CWwCTCh AAV Show processes from all users End Process Processes 50 CPU Usage 1 Commit Charge 540M 1247M If OPC90 has been configured to run as a service a single instance of the program should be observed prior to running any OPC client If multiple instances of OPC90 are found running after two or more OPC clients have been started and OPC90 has not been manually run this is an indication of a DCOM setup error This condition must be corrected before OPC90 can be properly utilized to serve its data to more then one OPC client Failure to do so will result in only the first OPC client to run receiving data from OPC90 Manually running OPC90 after it has been started as a service or by an OPC client connection will result in a second instance of the program to be observed in Windows Task Manager This is by design and not an indication of an error condition Under this condition a progress dialog will be briefly displayed when it is first started reporting that it is attaching itself to the first instance Afterwards the second instance becomes a user interface to the
129. VISYS Independent Automation Solutions OPC90 Server For Bailey amp amp Command Series NETWORK 90 INFI 90 NETWORK 90 and INFI 90 are registered trademarks of ABB Formerly Bailey Controls Company 6 OPC90 Server User Manual V8 2 1 INTRODUCTION ip 9 5 FUNCTIONAEILDESCRIPTION 5 2 0 656 5P oro SR Roo EYE EN PEL Se F ao PUER AERE R ERAN ER PESUER aseta Fe USE ERES Fe E ERE RNC Teo eo rosa aud 6 INSTALLATION c 7 BAILEY COMMUNICATION OVERVIEW e ecce ee eese ases eo osea aoo eoo eaae estos sean esto P sese esso o eaae estne e anos eoo e 8 OPC90 SERVER APPLICATION MENU ITEMS 4 ee ee ee ee ee eee ee een seen nest tn seen eee ta setas esten seta sesta se 13 5 1 jg c RU 14 5 I I ni rcx HS 14 5 1 2 0p 14 5 1 3 VE et e e teet tM bi Nt vats usec on bee do e M Lr tto tt dri Eti 14 5 1 4 Save Ass a eec uo ea ca ue n iret eee a i uv uide eet 14 5 1 5 AULO SAVE Sod aem vetita TE ERB NH 15 5 1 6 Inmiport C SV sitae ele eode aget dee ge eee seed c dde wet dee 15 3 L7 Reimport CSV rid re er e ER oases cash aE aE EE E Oiee OER PASET PA E REUS EP ears PESEE 15 5 1 8 ExpOrt CSV ou ster o et ttd ene enn 15 5 1 9 Reexport CSV adt aO OSEE REUS TENEKE AE ere aere 15 5 2 ADD 3er etie e HERREN E EA I EEUU EUR Goeth Seacee Me Fer PERO EMEN eae SERERE OR ERRARE ORIREEINY 16 5 2 1 JB AVI C S
130. VT BOOL Channel state 0 Ok 1 Open 2 Short 3 Overdrive ALARM CODE Alarm code OPC STATUS OPC status value see OPC status section QUALITY Current quality of Bailey values 0 good 1 bad QUAL PROP Propogated Quality 0 Good 1 Bad OUT Current output value from Bailey OUT TEXT Discrete Output Value as Text DISC LIM Discrete alarm state DISC ACT Alarm active indicator OVR ENABLE Override allowed 0 No 1 Yes OVR VALUE Override value OVR STATUS Value overridden 0 No 1 Yes STAT INHIBT Status inhibit 0 No 1 Yes SUSPECT Value suspect 0 No 1 Yes CONFIG ERR Configuration error exists 0 No 1 Yes READBACK Readback status 0 Good 1 Bad SIM ENABLE Simulation enable 0 No 1 Yes SIM BLOCK VT l2 Read Simulation value block number RoviSys Company Copyright 1999 2015 Page 94 OPC90 Server User Manual V8 2 1 7 15 Module Status MODSTAT The MODSTAT OPC90 block is used to retrieve module status summary information and detailed module problem reports This block is designed to work with all Bailey node and module types Restrictions This OPC90 block can be utilized with all Bailey interface types except serial port module SPM amp CPMO2 TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address note 1 ADDR NODE Bailey node address note 1 ADDR MODULE Bailey module address note 1 MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG I
131. VT BOOL Low deviation alarm active indicator see note 6 MODE VT I2 Read Write Mode of this control loop expressed as 0 Manual 1 Auto 2 Cascade MODE LOCK VT BOOL Read Write Indicates locked into current mode when set PV VT R4 Read Write Process variable OUT VT_R4 Read Write Control output range is limited to 5 0 to 105 0 OUT_TRACKING VT BOOL Read Write Indicates output tracking when set RED TAG VT BOOL Read Write Device red tag indicator SP VT R4 Read Write Set point SP TRACKING VT BOOL Read Write Indicates set point tracking when set RI VT R4 Read Write Ratio index only used for ratio station types AO BYPASS VT BOOL Read Write Indicates analog output bypass when set DS BAD VT BOOL Read Write Indicates bad digital control station Bailey hard DCS station when set 1 Make sure the block number attribute is unique with respect to the other AOL DOL ODD ORCM ORMC ORMSC and OSTN OPC90 blocks associated with the same OPC90 DEVICE block The block number attribute must also be defined within the range of 1 to maximum number of allowed outputs set up within the associated OPC90 DEVICE block The Bailey system will receive data from this block at the ring and node address of the Bailey CIU interface module two and block number defined by the block attribute The engineering units code is a number used by the Bailey consoles to index into a table of text strings repres
132. Write The amount the alarm value must lower below en eed the current high alarm level limit before the associated active current alarm condition clears HI HI HI LIM The setting for the alarm limit used to detect the high high high alarm condition HI HI LIM The setting for the alarm limit used to detect the high high alarm condition HI LIM The setting for the alarm limit used to detect the high alarm condition LO LIM The setting for the alarm limit used to detect the low alarm condition LO LO LIM The setting for the alarm limit used to detect the low low alarm condition LO LO LO LIM The setting for the alarm limit used to detect the low low low alarm condition LO HYS The amount the alarm value must raise above the current low alarm level limit before the associated active current alarm condition clears NEXT HI Next high alarm limit to be reached NEXT LO Next low alarm limit to be reached LIMITED Value is limited indicator CALC Using calculated input indicator OUT RANGE Out of range detected indicator SCAN OFF Scan disabled indicator RATE ACT Rate alarm indicator SUP ACT Suppress alarm indicator VAR ACT Variable alarm indicator HW FAIL IND Hardware Failure indicator HI REF High display reference value DAANG S1 MID REF Middle display reference value DAANG S2 LO REF Low display reference value DAANG S3 HI CONST High constraint limit DAANG S4 LO CONST VT R4 Read Low constraint limit DAANG S5
133. _ ORCM Block Name Block Type Location only block Description Max Time 0 Faceplate Type O A Block Name Block Type Location only block Description Max Time 0 Faceplate Type Block Name Block Type Location only block Description Max Time EU code Zero Span Significant Change Block Name Block Type Location only block Description Max Time EU code Zero Span Significant Change High Alarm Limit Low Alarm Limit Deviation Alarm Limit Station Type Block Name Block Type Location Description Update Interval Samples EnableLoop EnableNode EnableNis EnableMb CommLevel GmiRxLevel GmiTxLevel XrpRxLevel XrpTxLevel FactorMuxCiu FactorPoll FactorSpec FactorBlk FactorPcuMon FactorModStat Block Name Block Type Location Description F1 LSDO F1LSD1 OUTLSDO OUTLSD1 Read Only Flag RMC Block Name Block Type Location Description F1LSDO F1LSD1 F2LSDO F2LSD1 PERM1LSDO PERM1LSD1 PERM2LSDO PERM2LSD1 OUTLSDO OUTLSD1 Read Only Flag The following table is a guide to understanding the various block fields used when defining OPC90 blocks FIELD NAME FIELD DESCRIPTION Examples Block Name Contains the case insensitive full block ClU4 Group1 STN1 name not the tagname The full block Device1 DIL23 name includes the device name followed by CIUA all groups followed lastly by the block name CIUA Unit1 Boiler Turbine Mtr1 see notes Block Type Specifies the case
134. a The Shadow input data option should be checked when output type blocks are configured AOL DOL ODD OMSDD ORCM ORMC ORMSC and OSTN and the OPC client that writes to these blocks does not implement hot redundancy This means it only writes input values to the output type blocks on the primary OPC90 and not the standby With this option set the input values being written to the primary OPC90 will also be sent by the primary to the standby OPC90 This allows the standby OPC90 to take over using the latest OPC client written values The state of configuration shadowing is displayed in the OPC90 program window status bar as follows Off lt 5 Good Bad Bad Versions The Device block also has tags that can be accessed by OPC clients to monitor the state of configuration shadowing See the Device block for more details of what can be monitored Configuration shadowing has been designed to keep the standard OPC90 ABB CFG CSV and SOE directories synced between two OPC90 servers running on different PCs These are sub directories of the C Program Files OPC90 Serven directory or the alternative path setup during program installation Therefore if the user stores files outside of these locations configuration shadowing should not be used In addition to keeping the above mentioned sub directories synced with each other configuration shadowing also copies runtime changes to the database such as block modifications
135. ailey SCSI interface is correctly cabled to one of the PC SCSI cards This cable connects to the Bailey SCSI interface with a standard 50 pin connector and to the back of the PC SCSI card with a high density 50 pin connector some cards might use a standard 50 pin connector ABB sells this cable or it can be obtain from a company such as Black Box www blackbox com 2 After reviewing step 1 reboot the PC 3 If running on Windows 7 OPC90 must be set to XP compatibility mode This is accomplished by right clicking on the C Program Files OPC90 Server OPC90Server exe file and select properties and then XP compatibility mode 12 4 No Communication If the Bailey interface LEDs do not sequence this means the driver is not able to successfully communicate with the N90 interface 4 Verify the OPC90 Server DEVICE block Primary Port and Secondary Port are associated with the same COM port to which the Bailey interface has been cabled 5 Verify the port communication settings match those setup within the Bailey interface Select Edit Ports and select the correct port for which to verify 3 Verify the Bailey interface device termination unit module serial port jumpers are setup correctly 4 Verify RS232 cable is connected to the correct Bailey termination unit module connector Generally this is labeled as the terminal port for the primary channel and printer port for secondary channel when the DEVICE block SCHEME attribute is set
136. al packets Current Topology F Loop 1 N30 gt N200 gt N100 gt N2 gt N1 gt back to N30 a Observations 15 35 20 515 05 21 2014 Node 100 is online RoviSys Company Copyright 1999 2015 Page 109 OPC90 Server User Manual V8 2 1 The Data Collection section is used to show and configure how often data is collected There are two collection periods that can be defined The first is for the counters and statistics collection and is defined in milliseconds Setting it to zero will disable collection of those values The second period is how often the topology is collected and is also defined in milliseconds Setting it to zero will disable topology collection The Get Now check box instructs the NISMON block to collect the data immediately each time it is clicked NISMON computes moving averages for the Node Performance Statistics The moving averages are computed for all tags that show messages per second data values The number of samples 1 255 to use in those averages can be defined The Firmware section shows the firmware revision read from the node s NIS It also presents the NIS Switch settings as hexadecimal numbers The Resettable NIS Event and Error Counters section presents various events and error counters read from the node s NIS Collection of the data in this section can be disabled by unchecking its check box This section includes a time since the last NIS hardware reset occurred This time s
137. ally append the CFG extension if it is missing Including the CFG extension in the file name will override the current FILE TYPE tag setting The CFG files are loaded from the ABB subdirectory unless an alternative directory path is included as part of the file name Following are some example load commands Command Action LOAD Load currently addressed module LOAD SLC Load currently addressed module from a file called SLC C90 LOAD SLC CFG Load currently addressed module from a file called SLC CFG LOAD ROLLER 146 Load ring 1 node 4 module 6 from a file called ROLLER C90 Cancel Command Use this command to cancel a previously started command Some commands like SAVE or LOAD might take minutes to complete The cancel command can be sent to cancel the previously started command Command Action CANCEL Cancels the previously entered and active command Read Command Use this command to read an existing function block configured in a Bailey module Following are some example read commands Command Action READ Read currently addressed function block READ 30 Read function block 30 from currently addressed module READ 40 1 10 20 Read function block 40 from ring 1 node 10 module 20 Get Command RoviSys Company Copyright 1999 2015 Page 57 OPC90 Server User Manual V8 2 1 Use this command to read default function block data for the a
138. alues within a second If the database was much larger such as 5000 blocks and 1096 changing significantly per second serial versus SCSI takes on new meaning The effective data load would be 500 values per second It would take the serial interface 2 2 seconds to read 500 values whereas the SCSI interface could read them in 0 5 seconds From this analysis we see that from a practical standpoint the advantage of SCSI over serial becomes apparent only for large databases The performance for databases of 2000 blocks or less can be considered only marginally better Note that a few of the above mentioned devices do not support exception reporting Specifically the NSPMO1 IMSPMO1 IMCPMO1 and IMCPMO2 Data collection from these devices is basically limited to the OPC90 Server blocks that poll to get the block values The names of these blocks are POLL BLK and SPEC The remaining interfaces support the following OPC90 Server blocks and associated Bailey exception report block types RoviSys Company Copyright 1999 2015 Page 9 OPC90 Server User Manual V8 2 1 OPC90 Server Block Type Bailey Block Name F C Number AIL ex BLK DAANG EE DADIG DD E DIL HAI fi HAO i HDI S HDO it MODSTAT MSDD F MUXCIU E NISMON M PCUMON POLL RCM RMC W RMSC SOE EE SPEC EE SIN V TXT M TEXTSTR M Analog Output Loop AOL AOLDB Bailey Block Configuration Data Acquisition Analog DAANG Data Acquisition Digital D
139. ame The Access column defines how the OPC client may use the tag name A value of Config Read defines the entry as an attribute attributes are also identified with italicized text A value of Read Write means the OPC client is expected to provide the value for that tag name A value of Read Write means the OPC client can both read and write the value which is also sourced by the Bailey system For this type of tag access values received from the OPC client will be written to Bailey but OPC90 will also look for values received from the Bailey system and write them to the OPC client via the associated tag name The Description column gives the purpose for each attribute and tag name Included with the OPC90 installation is a sample configuration file called SamplePoints cfg This file contains examples of all blocks supported and can be RoviSys Company Copyright 1999 2015 Page 43 OPC90 Server User Manual V8 2 1 viewed by selecting OPC90 File gt Open The following picture presents an example of the sample point configuration SamplePoints cfg OPC90 Server File Add Edit View Utilities Help DSe Eaj lele e ele H ciu A 2 3 Export E AOL point E DOL point E ODD point E3 OMSDD point 9 ORCM point 8i ORMC point E ORMSC point Wl OSTN point Import E AIL point EE DAANG point E DADIG point 8 DD point Name Location Data Type Access Value Description Last Upda
140. an For AOL ORMSC and OSTN only 2000 0 Specifies the value of the span in engineering units Significant For AOL ORMSC and OSTN only 1 5 Change Specifies the value of the significant change in engineering units HI LIMIT For AOL and OSTN only Specifies the 900 0 value for the alarm limit used to derive the high alarm condition LO LIMIT For AOL and OSTN only Specifies the 100 0 value for the alarm limit used to derive the low alarm condition DV ALARM For OSTN only Specifies the Station 10 0 deviation alarm difference between SP and PV Station Type For OSTN only Specifies the Station type 0 code as follows Basic with SP Ratio Cascade Basic without SP Basic with Bias Notes 1 Aline for each DEVICE block should be declared in the CSV file otherwise they will automatically be created given the first field in the Block Name For example Block name of CIU4A Unit1 Block1 will automatically create a DEVICE block with the name of CIUA at port COM1 if a line for that device block was not already declared within the file 2 If the DEVICE block name is missing within the block name field 1 then a DEVICE block will be automatically created with the default name of Device1 Thus you can simply enter a name for each block and they will be added under the Device1 device You can then change the name of the device block in the configurator For example if PID1024 is specified for field 1 then the driver will place
141. an handle will be the queue value climbing into double digits Other polling requirements such as POLL SPEC and STN blocks or BLK blocks doing a save or load may also be responsible for more temporarily queued messages which is normal and expected Running count of total messages being exchanged with the Bailey interface Messages per second being exchanged with the Bailey interface Running count of total exception report specifications received from the Bailey interface Running count of total exception reports exchanged with the Bailey interface Exception reports per second being exchanged with the Bailey interface Running count of total values polled from the Bailey interface Polled values per second being read from the Bailey interface Running count of total negative acknowledgments received from the Bailey Interface Text message indicating the ABB Bailey interface type i e INICIO3 CICO1 etc and firmware revision Shadowed CIU primary communication channel status A value of zero indicates good and one means bad or not used Shadowed CIU secondary communication channel RoviSys Company Copyright 1999 2015 Page 77 OPC90 Server User Manual V8 2 1 SHADOW MY RING SHADOW MY NODE SHADOW MY DEVICE SHADOW ONLINE SYNC DCS SYNC RING SYNC NODE IMPORT FILE IMPORT READ IMPORT RESULT TURBO ACTIVE TURBO TOTAL TURBO STALE status A value of zero indicates good and one means bad Shad
142. and the OPC client s are intended to run on the same PC and both run within the local system account If remote OPC client s need to access OPC90 running as a service it should be changed to run in a specific privileged account The same is true if the configuration shadowing feature is to be enabled Use the Windows service manager to change the OPC90 service to run in that specific account If using a workgroup the remote OPC client s must also be setup to run within the same account name and password on their respective PC s OPC90 has special logic that allows a second instance of the program to detect the service is running and attaches a user interface to the service Therefore allowing it to interact with the desktop is not required Note that this special logic is supported for Windows 2000 XP 2003 Server VISTA 7 2008 2012 Server Running OPC90 as a service along with the Start In Runtime and Monitor option is ideal for automatic system startup after a PC reboot and continuous runtime mode even after all OPC clients detach from the server On startup OPC90 will establish its database with the Bailey system prior to any OPC clients attaching to it reducing the RoviSys Company Copyright 1999 2015 Page 36 OPC90 Server User Manual V8 2 1 time it takes to gain initial access to database points After all OPC clients attach and detach runtime will not be stopped if monitor is still enabled If monitor mode is not
143. ange the operating mode of the currently addressed module to the mode indicated by the radio buttons The current operating mode of the module is displayed below the mode selection radio buttons FILE Click on this button to open a configuration file open dialog that allows selection of existing C90 or CFG files stored in the C Program Files OPC90 Server ABB directory RoviSys Company Copyright 1999 2015 Page 62 OPC90 Server User Manual V8 2 1 7 4 Data Acquisition Analog DAANG The DAANG OPC90 block is used to retrieve the exception reported output from Bailey Data Acquisition Analog blocks function code 177 Restrictions This OPC90 block can be utilized with all Bailey interface types except serial port module SPM amp CPMO2 TAGNAME TYPE ACCESS DESCRIPTION ADDR_RING Bailey ring address ADDR_NODE Bailey node address ADDR_MODULE Bailey module address ADDR_BLOCK Bailey block address MY_BLOCK_TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor OPC_STATUS OPC status value see OPC status section QUALITY VT_BOOL Current quality of Bailey values 0 good 1 bad COMMAND ee I2 Read Write Command attribute to request Bailey DAANG block as follows only valid when mode is Auto 0 Use Auto Input 1 Use Calculated Input 2 Suppress Al
144. arms 3 Un suppress Alarms 4 Turn Scan Off 5 Turn Scan On ALARM CTRL VT R4 Read Write Alarm control see FC 177 S20 SIG CHANGE e R4 ms Significant change to force an exception report see FC 177 S30 TBA PERIOD ME based alarm period see FC 177 S31 HI RATE High rate of change value see FC 177 S32 LO RATE Low rate of change value see FC 177 S33 TSA COUNT Time sequence alarm count see FC 177 S34 OUT HI LIM VT R4 OUT high limit OUT LO LIM VT R4 OUT low limit OUT Current output value received from Bailey EU Engineering Units Code EU TEXT Engineering Units String MODE VT l2 Read Write The mode of the Bailey block dimi 1 Auto RED CMD Red tag command see red tag users section RED TAG Red tag indicator 0 no 1 yes RED USERS Red tag users current user names or codes HI HI HI ACT High high high alarm active indicator HI HI ACT High high alarm active indicator HI ACT High alarm active indicator HI RATE ACT High alarm rate active indicator LO RATE ACT Low alarm rate active indicator LO ACT VT BOOL Read Low alarm active indicator RoviSys Company Copyright 1999 2015 Page 63 OPC90 Server User Manual V8 2 1 LO LO ACT VT BOOL Read Low low alarm active indicator LO LO LO ACT Low low low alarm active indicator DV LIM Deviation alarm limit DV HI ACT Deviation high alarm active indicator DV LO ACT Deviation low alarm active indicator HI HYS VT R4 Read
145. ates the block long OPC path name TAGDESC Indicates the block descriptor OPC STATUS OPC status value see OPC status section QUALITY Current quality see note 3 of Bailey values 0 good 1 bad OUT Value of discrete output RED TAG Device red tag indicator ALARM Indicates alarm condition F1 Current state of first feedback signal F2 Current state of second feedback signal PERM1 Current state of first start permissive signal PERM2 VT_BOOL Read Write Current state of second start permissive signal BAD_START Indicates a bad start condition FAULT Indicates a fault has occurred ERR CODE VT I2 Read Write Indicates error code for bad start and fault conditions see note 4 HOLD STATUS VT BOOL Read Write Indicates control status holding state due to an ALARM or FAULT condition FAULT ACK VT BOOL Read Write Fault acknowledgment 1 Make sure the block number attribute is unique with respect to the other AOL DOL ODD OROM ORMC ORMSC and OSTN OPC90 blocks associated with the same OPC90 DEVICE block The RoviSys Company Copyright 1999 2015 Page 119 OPC90 Server User Manual V8 2 1 block number attribute must also be defined within the range of 1 to maximum number of allowed outputs set up within the associated OPC90 DEVICE block The Bailey system will receive data from this block at the ring and node address of the Bailey CIU interface module two and block number defined by the block attribute 2
146. be applied to the OPC90 polling activities If OPC90 polling activities are the cause of the increased communication module processing power utilization the throttled slowdown OPC90 polling activities may lower that utilization If it doesn t the COMM LEVEL can be adjusted upward to restore normal OPC90 polling rates Checking for this condition can be disabled by setting COMM LEVEL to zero Setting COMM LEVEL to a value of negative one also disables the condition check and causes COMM PCT to not get read 11 The node received GMI message rate GMI RX is periodically read by this block when GMI RX LEVEL is greater than 1 Each value is submitted to a moving average calculation made available as the GMI RX AVG tag If the value of the GMI RX AVG tag becomes higher than the GMI RX LEVEL tag setting a THROTTLE condition slowdown polling is declared While in this condition the throttle factors see note 3 will be applied to the OPC90 polling activities If OPC90 polling activities are reducing the PCU node s ability to communicate exception reports the throttled slowdown OPC90 polling activities should reduce that influence If it doesn t the GMI RX LEVEL can be adjusted upward to restore normal OPC90 polling rates Monitoring for this condition can be disabled by setting GMI RX LEVEL to zero Setting GMI RX LEVEL to a value of negative one also disables the condition check and stops periodic reading of GMI_RX 12 The node transmitted GMI m
147. bout Demo Version Help About Note that if the dongle was not properly installed OPC90 must be restarted after the dongle is installed If the dongle has been properly installed but OPC90 still is not recognizing it the Sentinel Protection Installer program must be re run The OPC90 setup program normally runs this setup but on some systems it has been observed to occasionally fail This program can be found in the C Program Files OPC90 Server SuperPro directory Stop OPC90 and run the Sentinel Protection Installer program Restart OPC90 and verify it now correctly reports the dongle serial number If not try rebooting the PC and checking it again If that doesn t work contact RoviSys regarding replacement of the dongle 12 18 Data Updates Stop After 8 Hours An OPC90 license is being used that has not been paid for Some OPC90 hardware keys are shipped with a licensed number of days the server is allowed to run Failure to pay for the server within that amount of time causes the license to expire Expired licenses will only communicate with the ABB Bailey system for eight hours each time OPC90 is restarted Check the Help About menu option to verify this has happened When the serial number is displayed and the remaining days indicate zero the license is expired RoviSys Company Copyright 1999 2015 Page 181 OPC90 Server User Manual V8 2 1 About OPC90 Server EET Unlimited Version 7 5 1 April 16 2012 OPC DA 1 0 2 0 and 2
148. ce and is waiting to receive its initial data from the Bailey system ONLINE The block has received its first data update from the Bailey system RoviSys Company Copyright 1999 2015 Page 173 OPC90 Server User Manual V8 2 1 ILLEGAL BLOCK NUMBER The OPC90 Server AOL or DOL block has been configured with a block number that has exceeded the DEVICE MAX OUTPUTS attribute setting BLOCK ADDRESS ALREADY USED BY ANOTHER BLOCK Another OPC90 Server block has been configured for the Bailey address set within this block EXCEEDED BAILEY INTERFACE INDEX CAPACITY More OPC90 Server blocks have been configured than can be handled by the Bailey interface EXCEEDED OPC90 Server POINT LICENSE More OPC90 Server blocks have been configured than are allowed by the current license RoviSys Company Copyright 1999 2015 Page 174 OPC90 Server User Manual V8 2 1 12 3 SCSI Port Not Visible In Device Block Properties Comm Port List Box When the PC is first booted up the SCSI cards scan their buses to determine what devices are present OPC90 Server scans each SCSI card device list looking specifically for Bailey interfaces SCSI port addresses associated with ABB Bailey interfaces are only posted in the Device block properties primary and secondary communication port list boxes if they were found in the SCSI cards device lists 1 Make sure the ABB Bailey SCSI interface is powered up and not in the red light condition Also verify the ABB B
149. ch causes the MUXCIU block to request replies to commands it anticipates the attached software will be asking next This allows module save and restore operations to occur at a maximum possible rate considering the double transmission nature of using the MUXCIU block This option should be disabled when the COM port connection between the MUXCIU and attached software such as Composer are using the G Michaels Consulting Virtual Port to Virtual Port feature Commands that would be detrimental to the operation of OPC90 communication with the Bailey interface are handled directly by the MUXCIU block For example a common command that a configuration utility program typically sends upon initially starting up is the CIU RESTART command The MUXCIU block intercepts this command and does not actually send it to the OPC90 DEVICE driver Instead it simply returns the response originally received when the OPC90 DEVICE block driver had previously sent the CIU RESTART command The MUXCIU block has attributes to monitor communication health and statistics Italicized names indicate attributes configured within the OPC90 Server which cannot be connected to via OPC Restrictions None TAGNAME TYPE ACCESS DESCRIPTION Port Name of the COM port to be multiplexed as a CIU port MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name
150. ch data to be used for each of those conditions The block type search can be for all block types or a specific block type Both the block name and description can be for an exact match not case sensitive or partial strings using the wildcard character The following wildcard combinations are supported substring1 substring 1 substring 1 substring 1 substring2 substring 1 substring2 The address search condition can also include a wildcard for any of the address fields ring node module and block So for example the following setup searches for OPC90 STN blocks with block names starting with STN and having 00 in the name one or more characters past STN but not at the end of the name The module address for the OPC90 block must be module 3 RoviSys Company Copyright 1999 2015 Page 40 OPC90 Server User Manual V8 2 1 Find Block Search By Search Data Iv Block Type STN Find Next Done Cancel iv Block Name STN 00 Description E v Address Ring E Node E Module 3 Block E Result Found CIU STNs STN 0002 STN 1 1 3 7010 Coming from MFP The search starts at the beginning of the database when the find button is clicked Click the next button to continue the search from the previous block that matched the search condition When a block is found matching the requested search condition it is shown in the results section The block name is given prefixed by its full path position
151. cify the defined order for loading thes services As another example each SCSI miniport service has a unique Tag value that is used as an identifier in the SCSI miniport value under th GroupOrderList subkey to define which SCSI adapter to load first 12 20 OPC90 Running as a Service Randomly Stops or Crashes RoviSys has taken every effort to develop a bug free OPC server Nevertheless sometimes unforeseen problems exist caused by loading random hardware glitches or other factors such as misbehaving OPC client software These types of problems are usually very difficult to duplicate and isolate Verify the latest version of OPC90 is installed Make sure the Windows Dr Watson program is active on the system Email the Dr Watson log to RoviSys for analysis 12 21 Can t Run as a Service Under Windows 7 To run OPC90 as a service under Windows 7 it must be set to XP compatibility mode and run as an administrator This is accomplished by right clicking on the C Program Files OPC90 ServenOPC90Server exe or C Program Files OPC90 Server x86 OPC90Server exe file and select properties and then XP compatibility mode and also run as an administrator 12 22 BLK and SPEC Blocks Do Not Report Correct Specification Names Sometimes when running OPC90 under a 64 bit Windows operating system the BLK and SPEC blocks may not report the correct specification names Instead the names are repo
152. ck description for further details on each of these settings 5 2 2 Group When the add group item is selected the following dialog is displayed Name Groug RoviSys Company Copyright 1999 2015 Page 17 OPC90 Server User Manual V8 2 1 A group name can be defined describing the purpose of the blocks configured within the group The group name becomes part of the OPC tag name 5 2 3 Block When the add block item is selected the following dialog is displayed Create a New OPC90 Block Name TO Cancel Description CO Block Type AIL _ Validate Type Read only ADDRESSING Ring 1 Node 2 Module 4 Block 2504 Analog Output Parameters Digital Output Parameters Sig Change Initial Value id EU Code Alarm State E Init Value Faceplate Type Code Zero Span r Exception Report Outputs Lo Alarm Max Time seconds Hi Alarm Dev Lim Poll Block Parameter STN Type gt Poll Interval milliseconds Logic State Descriptors Zero State One State Dutput State0 Feedback 1 State 1 state Feedback 2 State 2 ate Feedbak3 Of On State3 Stte3 Feedback 4 or On Permissive 1 Permissive 2 D Dr This dialog is used to add all block types supported by OPC90 A block name must be defined which becomes part of the OPC tag name used to access the various block data tags An optional block descriptor can be entered that documents the purpose o
153. condition 1 ORCM ORMC ODD and OMSDD OPC90 blocks associated with the same OPC90 DEVICE block The block number attribute must also be defined within the range of 1 to maximum number of allowed outputs set up within the associated OPC90 DEVICE block The Bailey system will receive RoviSys Company Copyright 1999 2015 Page 114 OPC90 Server User Manual V8 2 1 data from this block at the ring and node address of the Bailey CIU interface module two and block number defined by the block attribute 2 The MSDD type code is a number used by the Bailey consoles to identify characteristics of its MSDD faceplate display Currently a value of zero is the only valid code 3 When the Device block Set bad quality of max exception timeout property is enabled the QUALITY tag of this block will be set bad if writes to the block input s do not occur within the Exception Report Output Max Time setting of the block When this occurs bad quality will also be written to the CIU and therefore propagated to the users of the block data within the ABB Bailey system The quality can also be set bad by writing a one 1 to this tag 4 The GOOD STATE and REQ STATE tags are used to indicate the actual GOOD STATE state of the device and its last requested state REQ STATE The states are indicated as numbers in the range of 0 through 3 By definition the zero state is considered the default or safe state of the device States 1 through 3 are consider
154. d indicator OVR STATUS VT BOOL Read Override status indicator Notes 1 Text strings can be written to this tag to control the DD output Valid text strings are the OUTLSDO and OUTLSD 1 settings along with 0 1 Off On Reset Set Zero One False and True Writing any of these strings is case insensitive RoviSys Company Copyright 1999 2015 Page 68 OPC90 Server User Manual V8 2 1 RoviSys Company Copyright 1999 2015 Page 69 7 8 lU Device Definition Block DEVICE OPC90 Server User Manual V8 2 1 The DEVICE Definition OPC90 block is used to declare an instance of the Bailey driver and define its interfacing data This block must be defined for each Bailey interface or redundant pair of interfaces that the OPC90 Server is to communicate with The DEVICE block has a number of tags used to monitor driver communication health and statistics Italicized names indicate attributes configured within the OPC90 Server which cannot be connected to via OPC These attributes are the device properties Device properties are configured when the block is first added They are also be changed by right clicking on the device block and selecting properties ATTRIBUTE TYPE TAGNAME SCHEME 8 Bit UINT uu n MAX OUTPUTS 16 Bit Config UINT WATCHDOG 8 Bit UINT INPUT XRP UPDATE 32 Bit UINT ACCESS Config DESCRIPTION Desired communication scheme see note 1 Single interface Singl
155. des 26 121 and analog Bailey console tags Digital DOL 45 Digital Output Loop used to source a digital value to ER Bailey function codes 42 122 and digital Bailey console tags Digital ODD 123 Output Device Driver used to source device driver 2 data to a Bailey DD console tag The Bailey console can issue on or off commands to this block with the OPC client indicating results using a set of feedback indicators Digital OMSDD 129 Output Multi State Device Driver used to source EX multi state device driver data to a Bailey MSDD console tag The Bailey console can issue state commands to this block with the OPC client indicating results using a set of feedback indicators Digital ORCM 62 Output Remote Control Memory used to source gt remote control memory data to a Bailey RCM console tag The Bailey console can issue on or off commands to this block with the OPC client indicating results using a feedback indicator Digital ORMC 136 Output Remote Motor Control used to source remote RE motor control data to a Bailey RMC console tag The Bailey console can issue start or stop commands to this block with the OPC client indicating results using a set of permissive and feedback indicators Analog ORMSC 68 Output Remote Manual Set Constant used to source EE remote manual set data to a Bailey RMSC console tag The Bailey console can issue set point values to this block for use by the client Analog OSTN 21 22 23 80 PID control loops OSTN stands for
156. e Select Auto Save to enable disable automatic database saving Auto save must be enabled when using configuration shadowing Otherwise both OPC 90 Servers will always run as the database master It is best to run with this feature enabled to avoid accidental loss of database changes When enabled the database will automatically be saved whenever OPC90 is currently communicating with the DCS By default auto save will occur every 60 seconds whenever changes have been made to the database or new real time specification data has been received The default auto save time can be changed when this feature is enabled It will also keep the database current with the latest snap shot of real time values Values such as alarm limits ranges spans engineering units and others received as exception report specifications when the interface starts up and after they are tuned These values are restored from the database when OPC90 is first started thus replacing default settings for actual system settings while waiting for interface startup to complete 5 1 6 Import CSV Select Import CSV to define a new database after selecting File gt New or add additional points to an existing database The OPC90 convention is to import CSV files stored in the subdirectory called CSV Comma Separated Variable files CSV can be generated in a program such as Microsoft Excel or a text editor like Notepad Each line in these files define OPC90 devices and blocks See
157. e Bailey semAPI driver Note that for some plug and play systems the INICIO3 or INICI13A will be listed as Another Device when the system is first booted up This is normal Accept it as another device and request it to be used enabled even though a specific driver for that device has not been loaded The properties for this other device will list the INICIO3 as follows BAILEY IIMCPO2 SCSI Processor Device Properties 2 x General Driver e BAILEY IIMCPO02 SCSI Processor Device Device type Other devices Manufacturer Unknown Location Bus Number 0 Target ID 1 LUN 0 r Device status The drivers for this device are not installed Code 28 To reinstall the drivers for this device click Reinstall Driver id Device usage Use this device enable z Notice that the INICIO3 and INICI13A identifies itself to the SCSI adapter card as BAILEY IIMCPO2 SCSI Processor Device Again this is normal You do not need to reinstall a driver for this device type Also notice the location of the device is given by RoviSys Company Copyright 1999 2015 Page 82 OPC90 Server User Manual V8 2 1 the above dialog For this example the OPC90 will assigned S0001 as the device identity For systems that don t support plug and play default NT installations the INICIO3 or INICI13A device will appear under control panel SCSI Adapters as follows SCSI Adapters 2 x Devices Drivers e SCSI adap
158. e Bailey system red tag users are managed as user codes in the range of 1 to 65535 This dialog allows these codes to be assigned user names Use of this name mapping is optional When a red tag code is encountered that is not mapped to a name the code will be reported instead of aname When this menu item is selected the following dialog is displayed RoviSys Company Copyright 1999 2015 Page 23 OPC90 Server User Manual V8 2 1 Red Tag Users User 001 Code 00111 Name Joel Code 00222 Name Raul Code 00333 Name Lunchroom Code 00444 Name Checkout Code 65535 Name JR Code 01234 Name Big Earl Code 00888 Name George Code 00000 Name Undefined Code 00000 Name Undefined Code 00000 Name Undefined Code 00000 Name Undefined Code 00000 Name Undefined Code 00000 Name Undefined Code 00000 Name Undefined Code 00000 Name Undefined Code 00000 Name Undefined Code 00000 Name Undefined nno oel Set EZ x Cancel Use the list box to select a specific user 1 128 to be defined The user code and name can be edited in the fields below the list box Use the tab key to signify entry of a new value Click on the set button to set the user code name Click on the delete button to delete the user code name definition Red tag user definition can also be accomplished using the OPC90 import feature Consult the CSV file format s
159. e OPC90 log directory The block includes logic that constantly observes the received data looking for possible problems If a potential problem is detected it is added to the NISMON daily log file The 30 most recent log entries can also be viewed from the NISMON faceplate The NISMON block is typically used to return loop topology information When reading of the topology is the only purpose for using this block only one needs to be configured per communication loop All nodes in a communication loop share a node map with each other that defines the topology for the loop Therefore when the NISMON block is only being used to read the topology and the other data it returns is not required configuration of only one block per loop is necessary In this case it is recommended that all of the enable tags be turned off except topology enable This will eliminate unnecessary data collection Cautions This block can be useful as a diagnosis tool for INFI 90 Harmony and Symphony communication system Be careful with the INTERVAL setting especially when multiple NISMON blocks are configured After completing an analysis of a node operational state set INTERVAL to a higher value or zero to disable data collection if it is currently not needed This block uses polling to get the data which means it does use a portion of the available polling bandwidth between OPC90 and the ABB Bailey CIU device and also the node it is addressed too Restrictions This OP
160. e interface redundant channels Dual interfaces Name of the COM SCSI see SCSI communication sub section or TCP see TCP communication sub section port attached to the primary interface channel Name of the COM SCSI see SCSI communication sub section or TCP see TCP communication sub section port attached to the secondary interface channel Note that this attribute is ignored if the SCHEME attribute is set to single interface Maximum number of output blocks AOLs DOLs ODDs OMSDD ORCMs ORMCs ORMSCs and OSTNs the driver should reserve point indices block numbers for within the Bailey interface device It is important to note that these indices are specified as part of the AOLs DOLs ODDs OMSDD ORCMs ORMCs ORMSCs and OSTNs block definition and must always fall in the range of one to the maximum outputs defined by this attribute Desired watchdog timer to be initiated between the driver and Bailey interface device The timer is expressed in 2 5 second counts A value of zero disables the watchdog timer The maximum value is 255 which is equivalent to 637 5 seconds When the watchdog timer is enabled the Bailey interface device will remove itself from the communication loop if the elapsed time in which the driver communicates with it exceeds the watchdog timer value Driver output block values AOLs DOLs ODDs OMSDD ORCMs ORMCs ORMSCs and OSTNs being received by Bailey controllers will thereafter automatically be
161. e shows the available File menu items TurboL istAnalysis cfg OPC90 Server WGF Add Edit View Utilities Help PH Name Location Data Type Access Value Description ALL STATUS COM10O INT R Good All Comm Status 0 Good 1 Bad X BLOCK CYCLE COM10 INT R 117 Black specification read cycles completed IMPORT FILE COM10 STRING RW CSV file to import X IMPORT READ COM10 BOOLEAN RW Off Request read of the import CSV file 0 Done 1 Read Import CSV 3k IMPORT RESULT COM10 STRING Result of the CSV file import request Reimport CSV 3 MESSAGE COM10 STRING ONLINE Unlimited V7 5 1 Device Status 3X MSG QUEUE COM10 INT 8 Total Messages In Queue Needing Keys Export CSV 3 MSG RATE COM10 INT 4 Message Rate messages sec Miscell MSG_TOTAL COMIO INT 6681 Total Messages 1 TurboListAnalysis cfg MY BLOCK TYPE COM10 STRING DEVICE My block type 3 MY DEVICE COM10 STRING INICIO1 E 0 My Device Exit MY NODE COM10 INT 16 Interface Node Address Y um lt gt Automatically save database when communicating with DCS t off Clients 31 Groups 61 Tags 27795 Rate 3627 Service Run CIU ONLINE Unlimited 5 1 1 New Select New to create a new database The current database will be closed If any database entities had been changed without being saved the user is given the opportunity to save the database before completing the new database request 5 1 2 Open Select Open to open a database that had been
162. e the Run application on this computer checkbox Click on the Security tab and the following dialog will appear RoviSys Company Copyright 1999 2015 Page 161 OPC90 Server User Manual V8 2 1 OPC90 Server Properties UT General Location Security Endpoints Identity Launch and Activation Permissions Use Default C Customize Access Permissions Use Default C Customize Configuration Permissions C Use Default Customize Edit Make the following selections e Use default access permissions e Use default launch permissions e Use customized configuration permissions Click on the Identity tab and the following dialog will appear OPC90 Server Properties General Location Security Endpoints Identity Which user account do you want to use to run this application C The interactive user The launching user This user User MY DOMAINNSOPCSO Browse Password Confirm password C Select this user and type in the account information that will be used to run the OPC90 application The account information must include the domain controller computer name or local PC name for workgroup based systems backslash character and user RoviSys Company Copyright 1999 2015 Page 162 OPC90 Server User Manual V8 2 1 account that will be used to run OPC90 This example shows MY DOMAINYOPCO9O Use the actual domain or workgroup computer name and user account name
163. e types except CIUO1 serial port module SPM CPM02 amp CPMO03 and computer interface command series CIC TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey CIU ring address ADDR NODE Bailey CIU node address ADDR MODULE Bailey CIU module address ADDR BLOCK VT I2 Config Read Block number to establish this point at within the Bailey interface see note 1 ADDR RING VT l2 Config Read Bailey CIU ring address RCM TYPE VT I2 Config Read Bailey RC type code to use when establishing this point see note 2 MAX TIME VT I4 If OUT never changes it will be reported at the maximum time interval seconds defined by this attribute MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor OPC STATUS OPC status value see OPC status section QUALITY Current quality see note 3 of Bailey values 0 good 1 bad OUT Value of discrete output RED TAG Device red tag indicator ALARM Indicates alarm condition F1 Current state of feedback signal SET PERM VT BOOL Read Write Set permissive see note 4 SET INPUT VT BOOL Read Write Indicates state of set input RESET INPUT VT BOOL Read Write Indicates state of reset input OVR STATUS VT BOOL Read Write Indicates override status condition 1 Make sure the block number attribute is unique with res
164. e utilized when receiving data from the OPC90 Server RoviSys Company Copyright 1999 2015 Page 10 OPC90 Server User Manual V8 2 1 report point types Instead of addressing the tags to a block in a Bailey controller they are addressed to a block number assigned within the Bailey interface that OPC90 is communicating The ring and node address to use is that assigned to the interface with a fixed module address of two The following table presents a list of Bailey interfaces supporting the output report block types Max Number Supported by Bailey Interface Bailey System of points OPC90 Server NCIUO2 Network 90 2 500 Yes NCIUOS Network 90 5 000 Yes NCIU04 Infi 90 10 000 Yes INPCIO2 Infi 90 Symphony 5 000 Yes IIMCPO1 Network 90 Infi 90 10 000 Yes Symphony IIMCPO2 Infi 90 Symphony 30 000 Yes INICIO1 Infi 90 Symphony 10 000 Yes INICI12 Infi 90 Symphony 10 000 Yes INICI13 Infi 90 Symphony 30 000 Yes INICIOS Infi 90 Symphony 30 000 Yes RoviSys Company Copyright 1999 2015 Page 11 OPC90 Server User Manual V8 2 1 The following table summarizes the output report block types supported by OPC90 Server These blocks enable OPC clients to source these Bailey tag types to the Bailey system OPC90 Responses Data Type Block as Bailey Type Function Description Code Analog AOL 30 Analog Output Loop used to source an analog value ps to Bailey function co
165. e write commands Command Action WRITE Write one function block to the currently addressed module WRITE 200 Write one function block at block 200 to the currently addressed module WRITE 100 10 Starting at block 100 write ten function blocks to the currently addressed module WRITE 500 36 Starting at block 500 write three function blocks incrementing the written block number by 6 for each write to the currently addressed module This end result is writing blocks 500 506 and 512 WRITE 1000 202146 Starting at block 1000 write twenty function blocks incrementing the written block number by 2 for each write to ring 1 node 4 module 6 Modify Command Use this command to modify an existing function block in a Bailey module Remember the module must first be in configure mode before a block can be modified First use the READ command to read the block to be modified Next change the specification settings by writing to the SO1 VALUE through S63 VALUE tags After the specifications have been changed to the desired new values enter this command Following are some example modify commands Command Action MODIFY Modify one function block in the currently addressed module MODIFY 300 Modify one function block at block 300 in the currently addressed module RoviSys Company Copyright 1999 2015 Page 58 OPC90 Server User Manual V8 2 1 MODIFY 50 5 Starting at block 50 modify five funct
166. eads per period Max keys per PCU 0 device defined Max GMI per second per PCU node v Enable turbo polling M Screen exception reports Enhanced analog precision Establish points online MV MSDD pulse out handling STN BLOCKS Fast update for f 0 minutes every E 000 msecs Set KFAST on K tag writes Automatically send CPU_OK Represent mode as 0 5 3 Accuracy rating TIME SYNCHRONIZATION Infi90 IV Network 99 Define Nodes iv PCget amp setDCS time M PC get DCS time fu Y2k time warping SUPERVISORY CONTROL wRITE LOCKS Lock out all operator write requests from OPC clients Se SMa Enable Ls s i d ack inputs U factor TAG CONDITIONS v Startup complete after data received Auto disconnect unused blocks IV Restore last analog and digital tag values Set bad quality on max exception timeout Any input write applies to all output blocks Allow turbo reads for bad quality blocks Startup C Good Uncertain Bad MISCELLANEOUS Continuous OPC client updates Iv XRP write confirmation 7 Days to retain debug logs Days to retain SOE logs 3660 M Group output writes A device name should be defined that usefully identifies it The device name becomes part of the OPC tag name An optional device description can be defined to provide additional device information For most installations the default settings for the device properties are appropriate See the DEVICE blo
167. ecific security needs 10 1 Configuring DCOM On The Local OPC90 PC The first step is to select or setup a user account that at a minimum is a member of the Power Users group but preferably the Administrator group This account will be used by DCOM to run OPC90 as a service or when an access request is received from a remote OPC client If such an account does not exist create one called OPC90 assign it to the Administrator group and assigned a valid Windows password to the account such as opc90server When both local and remote PCs have been setup to exist within a domain both should use the same domain user account to run OPC90 and the clients that will attach to it If the PCs are setup in a workgroup the user account and password selected to run OPC90 on the local PC must be duplicated on the remote PC and the OPC clients on the remote run under that same account RoviSys Company Copyright 1999 2015 Page 159 OPC90 Server User Manual V8 2 1 If Windows XP 2003 Server is being utilized with Service Pack 2 or later and the Windows firewall is enabled OPC90 and the OPC clients must be added to the list of firewall exceptions for each PC running OPC90 or the OPC client Also a port named DCOM with port number 135 associated with TCP must be added to the local and remote PCs This is setup by running ControlPanel Windows Firewall For additional information consult the document entitled OPC With DCOM With XP SP2 PD
168. eco be aa esea ou E E E EN i Ba I DG E 17 5 2 2 Groups his RU ad d e ERU eq ee a as A ae 17 5 2 3 DBlOCK3 Est alvo iet OSV asics eo SAAE IO eive EN 18 5 3 EDIT 5d estet ep ter EO tbe ipee eive n det eet i nee ibt ie NEU RR 19 5 3 1 IDILA NO A sau qti CTE TORT ETP ente IP uin 19 5 3 2 COMP OTES ci tiet nnde eter eie eden ne ite sd rui E 19 5 3 3 TCPIPOFIS S us OE EEE E EO E EET OE E E EE E E E ES 20 5 3 4 Engineering UNS nonesa n egeta A E eere A A A A A ee in OEE 21 5 3 5 Text Messdgas i e REI DR EUER a a a a a MEE EHE ERR UE A 22 5 3 6 Red Tage Use iU RU RENE RUBER e e Ren 23 5 3 7 SOE Point Names s e eme EE a eeu dom 25 5 3 8 Properties ias SB WD eene en aene 26 5 3 9 Jug HE 26 5 3 10 Configuration Shadowing Between Redundant Servers eene 26 5 3 10 1 Redundant Same Address CIUS ss nann sree etie p Pe RR WR SERRE RR Ee A A EA O XR RRETUR 29 5 3 10 2 OPC Client Access of Redundant Servers sss eene eene ennt enne nnne nennen nnne 30 DAT 4 EXFOF Delection ooa t ens eden educ EOE BIN UM IN 30 5 4 VIEWS ihe I whet RR ERU RESET RR guest oth TR E TET ERE RE E E HIEMIS EARUEMIR EUER UR 33 5 4 I VIEW MONO ise RE E RR Ra una a un d hbet atest 34 5 4 2 VIEW STOlWs sere e e RR RR ER ORE EE e e ee NEN Na 35 5 4 3 View Start In Runtime adeo neant adt emt teu 36 5 4 4 View Run As Service dite utei ie o ieee E iive ledio E on iode eter ede Ede e ER EE edo 36 5 4 5 View Lockout OPC
169. ection for specific information on how to define red tag users OPC90 includes three OPC tags associated with managing red tags These tags are RED TAG RED CMD and RBED USERS These tags are valid for the DAANG DD MSDD RCM RMC and STN blocks The RED TAG OPC tag reports whether or not the block is currently in the red tag state When set the block is red tagged This tag value is an exception reported value The RED USERS OPC tag reports the users that currently have the block in the red tag state As previously mentioned up to three users can have the block red tagged This is a string tag and will report the users separated by commas f a user code is returned that has not been mapped by this dialog the user code will be reported instead of a name The red tag user codes are not exception reported and must be polled Whenever a block is in the red tag state the user codes will be polled once per minute This allows OPC90 to determine red tag users generated outside of OPC90 such as from a ABB Bailey operator console The RED_CMD OPC tag is used to command red tag users to attach and detach with the block The format of the command is simple The command name is followed by the red tag user name or code The commands for attaching red tag users are ON RoviSys Company Copyright 1999 2015 Page 24 OPC90 Server User Manual V8 2 1 SET or TAG The commands for detaching red tag users are OFF RESET or UNTAG
170. ed daily log files are generated in the OPC90 program directory Leaving all but the error option enabled for extended periods of time can consume a lot of disk space The four logging options supported are Errors post miscellaneous errors Events post communication events Sends post messages sent to interface Receives post messages received from interface Number of days the debug logs should be retained us older than the number of days indicated by this setting will be automatically deleted iul Indicates the OPC90 block type VT BSTR Read pee l4 pese i Li l4 Read p 14 Bec Text message indicating overall status of the device Total blocks this DEVICE block has been EE to exchange data with the Bailey system Primary and secondary communication channel status AND value of the two status where a value of zero indicates at least one is good and one means both are bad Primary communication channel status A value of zero indicates good and one means bad WEN communication channel status A value of zero indicates good and one means bad or not used VT I4 CIU online state 0 No 1 Yes VT l4 Read Indicates data should now be available 0 Yes 1 RoviSys Company Copyright 1999 2015 Page 76 OPC90 Server User Manual V8 2 1 BLOCK CYCLE MSG QUEUE MSG TOTAL MSG RATE XRPS TOTAL XRP TOTAL XRP RATE POLL TOTAL POLL RATE POLL OUT TOTAL POLL OUT RATE NAK TOTAL
171. ed the operational states of a device like slow medium and fast An operator request to go to a given state is written to the REQ STATE tag Writing the REQ STATE tag value to the GOOD STATE tag value indicates arriving at the requested state The two tags not being equal and the ALARM tag not being set indicate a travel condition Application The Bailey implementation of the MSDD block contains three discrete outputs used as control signals to a field device typically having more than two states For example a variable speed motor might have a stopped slow medium and fast states By definition the MSDD has four device states These states are the default condition and states one through three Setup of the MSDD block defines the output values of the three discrete outputs for each of the four device states For example the default state typically defines the three outputs to be reset state one could be the first output set and the other two reset and state 3 might be all three outputs are set For compatibility with the Bailey exception report format this block has an OUT tag which reports the output value of the first of the three discrete outputs This output is essentially useless for determining the actual device state but is included for compatibility with existing Bailey implementation Instead the Bailey console uses the GOOD STATE and REQ STATE tags to determine the actual device state and its new requested state The OPC client writes the
172. ee note 7 Number of GMI messages per second being transmitted by this node Moving average of the number of GMI messages per second being transmitted by this node Maximum node transmitted GMI messages per second level to begin OPC90 polling throttle see note 8 Number of exception report values per second being received by this node Moving average of the number of exception report values per second being received by this node Minimum node received exception report values per second level to begin OPC90 polling throttle see note 9 Number of exception report values per second being transmitted by this node Moving average of the number of exception report values per second being transmitted by this node Minimum node transmitted exception report values per second level to begin OPC90 polling throttle see note 10 Total number of bytes transmitted forwarded and originated by this node per second Total number of messages transmitted forwarded and originated by this node per second Total number of bytes received by destined for this node per second Total number of messages received by this node per second Total number of bytes sent originated by this node per second Total number of messages sent by this node per second Total number of bytes transferred on the expander bus from NIS to the communications module per second Total number of messages transferred on the expander bus from NIS to the commu
173. eeececsesseaeeeseeeeseneaaees 166 10 3 VALIDATING OPC CLIENT ACCESS OF OPC90 cccsecsccccecsesessecececececsesseaececececsesaaececececeessaeeeeeeeceeneaaees 168 11 MIGRATING OPC90 TO A WINDOWS 64 BIT ENVIRONMENT ccsssscssssssssscssscssssscssscssssseees 170 12 TROUBLESHOOTING HINTS wis secssiceccsnsicesscsenesseassdcocsensscscessesecoensvensdesescessasserocsensdceseestbecesentscnstastecesees 172 12 1 SENTINEL SYS CAUSES PC BLUESCREEN ON BOOTUD sssssssecececsesessscececcceesenseaecececeesesseaeeeeeesesensaaes 173 12 2 VALIDATING STATE OF INDIVIDUAL OPC90 SERVER BLOCKS eese enne nennen ener 173 12 3 SCSI PORT NOT VISIBLE IN DEVICE BLOCK PROPERTIES COMM PORT LIST BOX eene 175 12 4 NO COMMUNICATION iie eese tette aeu teet eee oe evi rele ee pee te no eee epe todo exe eee dr reet 175 12 5 APPEARS TO BE COMMUNICATING BUT NO DATA IS BEING RECEIVED cccceesessscecececeesscteceeeeeceeneaees 176 12 6 NOT ALL BLOCKS ARE RECEIVING DATA eese enne tennnn essen ette tena nsns esee tate an assess enean nnn 176 12 7 RANDOM BLOCKS ARE RECEIVING BAD QUALITY INDICATION ceeeseeeeeeee eene enne ener enne 177 12 8 SPORADIC DATA TRANSFER OF EXPORT BLOCKS TO BAILEY c ccccccecsesssseceeececsenssaeceeececeessneeeeeeeeeeneaees 177 12 9 CANNOT EXPORT OR CONTROL DATA WITHIN BAILEY ccsesescecececeesennececeeeceesenseaecececeesesssaeeeeceeesensaaeas 178 12 10 CANNOT SEE ALL DOCUMEN
174. een two PCs based on the order in which new hardware is discovered f this occurs between shadowed OPC90 PCs use the following procedure to re align the port address Using Regedit go to the key named HKEY LOCAL_MACHINE HARDWARE DEVICEMAP Scsi in the registry Find the branch that contains the Bailey interface Click the Scsi Port at the top of the branch and look for the Driver name RoviSys Company Copyright 1999 2015 Page 182 OPC90 Server User Manual V8 2 1 Go to HKEY LOCAL MACHINENSYSTEMNCurrentControlSet Services arivername for both the device ahead of you and for the SCSI device you want to be first and look at the TAG value You need to change the tag value so that the device you want listed first as 1000 is a lower value than the device that is forcing it to S2000 Detailed explanation of what this procedure accomplishes follows as gleaned from the Microsoft web site Tag REG DWORD Specifies a load order within a given group The value of Tag specifies a number that is unique within the group of which the service is a member The related GroupName entry under the Control GroupOrderList subkey specifies a list of tags in load order For example the following services that are members of the Primary Disk group could have these values Tag 4 for the Abiosdsk subkey Tag 2 for Atdisk Tag 1 for Cpqarray and Tag 3 for Floppy The value for Primary Disk under the GroupOrderList subkey will use these Tag values to spe
175. eering units SIG CHANGE VT R4 Amount that PV or SP must change cycle to cycle before it will be reported to Bailey Expressed as a percentage of the SPAN MAX TIME VT l4 Config Read If PV SP or OUT never changes significantly it will be reported at the maximum time interval seconds defined by this attribute HI LIM VT R4 Config The setting for the process variable alarm Read Write limit used to derive the high alarm condition see note 4 LO LIM VT R4 Config The setting for the process variable alarm Read Write limit used to derive the low alarm condition see note 4 DV_LIM VT_R4 Config The setting for the deviation alarm limit Read Write between the process variable and set point used to derive the deviation alarm condition see note 4 MY BLOCK TYPE VT BSTR Indicates the OPC90 block type MESSAGE VT BSTR Indicates the block operational message TAG VT BSTR Read Indicates the block name RoviSys Company Copyright 1999 2015 Page 123 OPC90 Server User Manual V8 2 1 TAGLONG VT BSTR Read Indicates the block long OPC path name TAGDESC Indicates the block descriptor OPC STATUS OPC status value see OPC status section QUALITY VT BOOL Current quality see note 5 of Bailey values 0 good 1 bad HI ACT PV High alarm active indicator see note 6 LO ACT PV Low alarm active indicator see note 6 DV HI ACT VT BOOL Read High deviation alarm active indicator see note 6 DV LO ACT
176. eginning a a a a xxxxxxxx01 STD The capture files are stored in the C Program Files OPC90 Serve SOE directory This directory is also included in the OPC90 database shadowing feature The data in the log file is stored in a space separated ASCII format The first line is a count of the number of SOE records contained by the file Each subsequent line is a SOE record containing the point number date string time string its quality alarm state scan state value point type string and point name string Consider the following example data stored in the file 1 2 3 102 0201200701 PRE 4 1 2 01 2007 23 23 50 120 0 0 0 1 Pre fault Pump A 2 2 01 2007 23 23 50 125 0 0 1 0 Pre fault Pump B 6 2 01 2007 23 23 50 203 0 1 0 1 Pre fault Compressor 1 9 2 01 2007 23 23 50 987 1 0 0 0 Pre fault Compressor 2 The log is the first one to occur on February 1 2007 for pre faulted data points It contains four SOE records as indicated by the first line The first record is point 1 which was logged by the Bailey block on February 1 2007 at 23 23 50 120 It has good quality its not in alarm has not been deleted from the scan and has a value of one The point type is pre fault and it called Pump A The second record is point 2 which was logged by the Bailey block on February 1 2007 at 23 23 50 125 It has good quality its not in alarm has been deleted from the scan and has a value of zero The point type is pre fault and it called Pump B RoviSys
177. el data acquisition when the Bailey interface type is a serial port module CPMO2 or CIC The POLL block can be used to duplicate the Bailey console ad hoc block output queries Usage of this block with Bailey interfaces other then serial port modules CPM or CIC should be limited to those few Bailey block output values not currently being exception reported Data is obtained by polling Since Bailey is optimized for exception reporting polling for Bailey outputs is inefficient and should not be used for a large number of values TAGNAME TYPE ACCESS DESCRIPTION ADDR RING VT I2 Config Bailey ring address see note 1 Read Write ADDR_NODE Bailey node address see note 1 Read Write ADDR_MODULE Bailey module address see note 1 Read Write ADDR_BLOCK Bailey block address see note 1 Read Write INTERVAL VT l4 Config Desired polling interval expressed as milliseconds Read Write see note 1 OPC STATUS OPC status value see OPC status section MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor QUALITY Current quality of Bailey values 0 good 1 bad OUT The polled Bailey block output value see note 2 OUT TEXT The polled Bailey block output value as a string see note 2 HI ACT High alarm active indicator see note 3 LO ACT Low alarm active indica
178. ely accessible registry paths letwork access Shares that can be accessed anonymously letwork access Sharing and security model for local accounts Re Network security Do not store LAN Manager hash value on ne Network security Force logoff when logon hours expire RE Network security LAN Manager authentication level RE Network security LDAP client signing requirements RA Mehuinek serrit Minimin ceccinn ceciwity For NTI M SSP hace Disabled Disabled COMNAP COMNODE SQL QUERY SPOOLSS LLSR System CurrentControlSet Control ProductOptio COMCFG DF5 Classic local users authenticate as themselves Disabled Disabled Send LM amp NTLM responses Negotiate signing Mo minimi in Double click on Network access Sharing and security set it to Classic as shown by the following dialog model for local accounts and Network access Sharing and security model for local mR Local Security Setting Network access Sharing and security model for local accounts Classic local users authenticate as themselves OK Cancel Double click on Network access Let Everyone permissions apply to anonymous users and set it to Enabled as shown by following dialog RoviSys Company Copyright 1999 2015 Page 164 OPC90 Server User Manual V8 2 1 Network access Let Everyone permi AE Local Security Setting Explain This Setting i Network access Let Everyone permissions apply to anonymo
179. en declared to have a THROTTLE condition The throttle factors are ignored when the MODSTAT throttle override is enabled and MODSTAT blocks are found indicating one or more controllers within the PCU are not in execute mode The CSV Log On button switches between CSV file logging On and Off each time it is clicked The Default Settings button resets all of the settings to default values The Watch and Throttle section is used to setup throttle conditions to watch for This data includes transmit TX and receive RX watches for general polled type messages GMI and exception reported XRP data The communication module processing power utilization can also be included as a watch and throttle condition Watching for any of these conditions can be disabled by entering 1 for the level setting Setting the level to zero enables watch but not throttle condition detection Positive level values enable both watch and throttle monitoring So for example when the PCU receives a large number of GMI RX messages those requests must be passed on to the various destination controllers within the PCU That processing takes time and can temporarily slowdown the number of exception reports the PCU reads from each controller thus slowing down the exception report transmission rate XRP TX It is important to note that it is natural for the various watch values to move around based on what is happening at any specific moment in time Therefore the
180. enabled and all OPC clients detach runtime will be stopped As soon as one or more OPC clients attach runtime is automatically started again Note that it is not absolutely necessary to run OPC90 as a service since OPC by definition automatically starts the server when any OPC client makes a request for its data Therefore if problems are encountered with OPC clients attaching to OPC90 running as a service that cannot be resolved by also running the OPC client as a service or within the same account the OPC90 service is running then running as a service should be disabled 5 4 5 View Lockout OPC Access This selection is a toggle which enabled disables the Lockout OPC Access feature When OPC access is in the lockout state OPC90 rejects all attempts by OPC clients to attach with it This feature is useful when attempting to open a different database Opening a database is not allowed when OPC clients are attached In some situations it is difficult to stop all OPC clients so this lockout feature can be enabled to stop the OPC clients from making a connection It can also be enabled prior to running a QuickUpdater when the QuickUpdater fails because the OPC clients are restarting OPC90 before it can be updated Do not leave this feature enabled since it defeats the purpose of what OPC90 is designed to do It is included as a setup and maintenance feature If accidently left on each time OPC90 is started the user will be prompted to turn it
181. ent FILE TYPE tag setting The CFG files are also stored in the ABB subdirectory unless an alternative directory path is included as part of the file name If the save command is cancelled or it fails the file will not be generated and any original file of that name that had been previously saved will remain unchanged Saving a configuration also generates a second file that documents all of the blocks just saved This list includes the block number function code type and specification settings The name of this file is the saved file name with BLOCK LISTING CSV appended to it Microsoft Excel can be used to open the file and look at the blocks contained by the configuration Following are some example save commands Command Action SAVE Saves currently addressed module SAVE MFP01 Saves currently addressed module to a file called MFP01 C90 SAVE MFP01 CFG Saves currently addressed module to a file called MFP01 CFG SAVE DIGESTER 1 35 Saves ring 1 node 3 module 5 to a file called DIGESTER C90 Load Command Use this command to load a Bailey module function block configuration from a previously saved file Remember the module must first be in configure mode before it can be loaded with a new configuration It should also be initialized before loading the RoviSys Company Copyright 1999 2015 Page 56 OPC90 Server User Manual V8 2 1 new configuration see OPERATION command BASIC p
182. enting the engineering units of the process variable and set point values The station type code is a number used by the Bailey consoles to identify characteristics of its station faceplate display Valid codes are 1 Basic with SP 2 Ratio 4 Cascade 8 Basic without SP and 16 Basic with Bias This attribute is normally configured when the block is first defined Since it is associated with the alarm limits of value an OPC client is permitted to write new alarm limits in run time Care should be taken to not continuously change the limit value since each change necessitates dis establishing the point from the ABB Bailey interface and than re establishing it with the new limit value When the Device block Set bad quality of max exception timeout property is enabled the QUALITY tag of this block will be set bad if writes to the block input s do not occur within the Exception Report Output Max Time setting of the block When this occurs bad quality will also be written to the CIU and therefore propagated to the users of the block data within the ABB Bailey system The quality can also be set bad by writing a one 1 to this tag The alarm active indicators are automatically calculated based on the last process variable and set point value written by the OPC client RoviSys Company Copyright 1999 2015 Page 124 OPC90 Server User Manual V8 2 1 Application Bailey implements analog control loops as a combination of two fu
183. erating as the shadow master The current shadow state can also be determined from the Device block faceplate 5 3 10 1 Redundant Same Address CIUs Configuration shadowing shares the communication state and address of CIUs between the two OPC90 servers This data is useful when using OPC90 AOL DOL ODD OMSDD ORCM ORMC ORMSC and OSTN blocks Nodes within the ABB Bailey system that need to receive data from these blocks do not need to be concerned with getting the block data from two different CIU addresses The redundant OPC90 servers can be setup with CIUs having the same address Only one CIU will be commanded online The other will have the database downloaded to its CIU and ready to be commanded online when communication with the other OPC90 server fails or the other OPC90 server communication with its CIU fails For this type of setup it is important to configure the OPC90 Device block watchdog time to a non zero value Settings in the range of 2 4 are common See the device block for more information about the watchdog time Note that a network failure will cause the backup OPC90 server to command its CIU online if configuration shadowing cannot communicate with the other OPC90 server By design this will occur between one and two minutes after the network failure occurs If the other CIU is still online the backup being commanded online will fault with a code indicating a same address was detected Therefore don t conclude that CIU red
184. erver and select properties and one of the two following dialogs will appear RoviSys Company Copyright 1999 2015 Page 160 OPC90 Server User Manual V8 2 1 OPC90 not as a Service OPC90 as a Service OPC90 Server Properties kJ OPC90 Server Properties lt T General Location Security Endpoints Identity General Location Security Endpoints Identity General properties of this DCOM application General properties of this DCOM application Application Name OPCB Server Application Name OPC90 Server Application ID 2508F89D 3490 11D3 9236 0040339FD 356 Application ID 2508F89D 3490 11D3 9236 0040339FD 356 Application Type Local Server Application Type Local Service Authentication Level Default x Authentication Level Default Local Path C Program Files OPC90 ServerNOPCS0Server Service Name OPC90S erver 7 Under the General tab set the Authentication Level to Default Click on the location tab and the following dialog will appear OPC90 Server Properties General Location Security Endpoints Identity The following settings allow DCOM to locate the correct computer for this application If you make more than one selection then DCOM uses the first applicable one Client applications may overide your selections Run application on the computer where the data is located IV Run application on this computer Run application on the following computer ml Enabl
185. eset input SET_INPUT VT on Read o State of set input RED_CMD Red tag command see red tag users section RED_TAG Red tag indicator 0 no 1 yes RED_USERS Red tag users current user names or codes F1 State of feedback F1 TEXT State of feedback number 1 as a string SET PERM Set permissive OVR STATUS VT BOOL Read Override status indicator Notes 1 OPC90 uses pulse reset and pulse set commands when commanding the state of the RCM output When writing a zero to reset the output a pulse reset command 5 is actually sent to the RCM block by OPC90 Likewise writing one to set the output a pulse set command 6 is sent Some older style drivers force the OPC client to sent a 5 and 6 to reset and set the RCM output For compatibility when converting from such older style drivers to OPC90 it can be configured to RoviSys Company Copyright 1999 2015 Page 135 OPC90 Server User Manual V8 2 1 also accept values of 5 and 6 for commanding the output reset and set To enable this ability the RCM OUT parameter type must be changed from its default setting of BIT to another multi bit type such as INT Right click on the RCM OUT attribute and select properties to make this change Note that OPC90 will always report the value of OUT as 0 or 1 regardless of whether it is written as O 1 5 or 6 2 Text strings can be written to this tag to control the RCM output Valid text strings are the OUTLSDO and OUTLSD1 settings along w
186. essage rate GMI_TX is periodically read by this block when GMI_TX_LEVEL is greater than 1 Each value is submitted to a moving average calculation made available as the GMI_TX_AVG tag If the value of the GMI TX AVG tag becomes higher than the GMI TX LEVEL tag setting a THROTTLE condition slowdown polling is declared While in this condition the throttle factors see note 3 will be applied to the OPC90 polling activities If OPC90 polling activities is reducing the PCU node s ability to communicate exception reports the throttled slowdown OPC90 polling activities should reduce that influence If it doesn t the GMI TX LEVEL can be adjusted upward to restore normal OPC90 polling rates Monitoring for this condition can be disabled by setting GMI TX LEVEL to zero Setting GMI TX LEVEL to a value of negative one also disables the condition check and stops periodic reading of GMI TX 13 The node received exception report rate XRP RX is periodically read by this block when XRP RX LEVEL is greater than 1 Each value is submitted to a moving average calculation made available as the XRP_RX_AVG tag If the value of the XRP_RX_AVG tag becomes less than the XRP RX LEVEL tag setting a THROTTLE condition slowdown polling is declared While in this condition the throttle factors see note 3 will be applied to the OPC90 polling activities If OPC90 polling activities is reducing the PCU node s ability to exchange exception reports the throttled
187. essages X IMPORT READ COM12 BOOLEAN Red Tag Users X IMPORT RESULT COM12 STRING SOE Point Names MESSAGE COM12 STRING X MSG QUEUE COM12 INT Properties MSG RATE COM12 INT X MSG TOTAL COM12 INT rini 3MY BLOCK TYPE COM12 STRING 3 MY DEVICE COM12 STRING CSV file to import Off Request read of the import CSV file 0 Done 1 Read Result of the CSV file import request ONLINE Unlimited v8 2 1 Device Status Total Messages In Queue Needing Keys 30 Message Rate messages sec 9166 Total Messages DEVICE My block type IET800 A 1 My Device 30 Interface Node Address v 7 707 77 70707020220 0 Configuration Shadowing 3 MY NODE COM12 INT Error Detection lt gt 0 off Clients 7 Groups 3 Tags 692 Rate 40 Service Run CIU ONLINE Unlimited V8 2 1 5 3 1 Deletion Select Edit gt Delete to delete the selected block group or device Be careful when selecting this item If a group is deleted all blocks under that group are included in the deletion If a device is deleted all groups and blocks under that device are included in the deletion Device deletion is not allowed when in runtime mode of operation Block deletions are allowed in runtime mode of operation as long as they are not providing data to connected OPC clients This rule is enforced across shadowed databases So for example if an OPC client is connected to a block on one shadowed server but not the other the bloc
188. etrieve digital inputs defined within Bailey Logic Master Modules Group I O definitions Restrictions This OPC90 block can be utilized with all Bailey interface types except serial port module SPM amp CPMO2 TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address ADDR NODE Bailey node address ADDR MODULE Bailey module address ADDR BLOCK Bailey block address OUTLSDO Output state zero logic state descriptor OUTLSD1 Output state one logic state descriptor MY_BLOCK_TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor OPC_STATUS OPC status value see OPC status section QUALITY Current quality of Bailey values 0 good 1 bad DISC_LIM Discrete alarm state DISC_ACT Alarm active indicator OUT Bailey discrete output value OUT_TEXT VT BSTR Read Bailey discrete output value as a string RoviSys Company Copyright 1999 2015 Page 88 OPC90 Server User Manual V8 2 1 7 10 Digital Output Loop DOL The DOL OPC90 block is used to send an exception reported output generated by updates to the block input tag IN Note that this block does not received data from a DOL FC 45 block running in a Bailey controller Use the OPC90 DIL block for that purpose The exception reports generated by this block can be received by a Bailey console digital ta
189. evice block Enhanced Analog Precision must also be enabled to allow reading of real 4 values If the configuration software associated with the MUXCIU block does not support real 4 values this option should be disabled The Virtual port connection option enables virtual connections to this MUXCIU block OPC90 includes a simple application programming interface DLL called OPC90VPort DLL that allows applications such as the DBDOC CIUMON program to connect with OPC90 MUXCIU blocks virtually The virtual connection can be local to the OPC90 PC or by remote PCs residing on the same network as the OPC90 PC RoviSys Company Copyright 1999 2015 Page 99 OPC90 Server User Manual V8 2 1 The No turbo option can be used to turn off turbo polling of block output reads being channeled through the MUXCIU block It is useful for disabling turbo for a specific MUXCIU while leaving it on for others and OPC90 in general note the device block properties is used to enable turbo polling globally An example reason for turning turbo off would be with Composer communicating through a MUXCIU block and the need to see alarm bits that are available from polling exception report block outputs Since turbo polling does not include that information it could be turned off so it is available in Composer The Prefetch option enables the MUXCIU to use parallel pre fetch logic when it detects a module save or restore operation occurring Parallel pre fet
190. ew Group ONLINE Unlimited V 52 6531 DEVICE INICIOS G 3 30 AAADAAADAADADA Off Clients 6 Groups 2 RoviSys Company Copyright 1999 2015 Page 30 OPC90 Server User Manual V8 2 1 In the above example logging of general CIU errors along with data associated with communication with the CIU has been requested to be logged The logs are text files viewable by notepad and can be found in the C Program Files OPC90 Server Log directory These log file names begin with OPC90 and include the device name along with the time and date the log was generated The file name OPC90 CIU Log Mon Jan 10 14 40 52 2011 log is an example of this log type It is important to remember that enabling disabling logs of this type become permanent whenever the database is saved So for example to log all of the CIU communication on OPC90 startup enable those logs save the database and restart OPC90 Afterwards those logs can be turned off and the database saved again so the next time OPC90 is restarted the logging of the startup information will not occur Note that restarting OPC90 is not required to enable and disable these logs The example given was the procedure to log communication on startup of OPC90 The second type of log file is useful when trying to isolate data exchange problems with OPC client software This log file is enabled disabled using the OPC90 Edit Error Detection menu item These logs are text file
191. ey Controller Configuration Addressing Ring 1 Node 1 Module 3 Block 800 FC 80 Control Station Specification Data 820 01 Block address of PV gt gt 820 807 02 Block address of SP track signal S29 SP track switch gt gt 807 Block address of auto signal gt gt 807 Block address of control output track signal TR gt gt 5 Block address of control output track switch T5 gt gt 687 Initial mode of station after start up gt gt 5 400 SO T PY high alarm point in engineering units gt gt 400 120 508 T PV low alarm point in engineering units gt gt 120 75 09 T PY SP deviation alarm point in engineering units For console gt gt 75 800 10 Signal span of PV in engineering units gt gt 800 76 511 Zero value of PV in engineering units gt gt 76 3 512 PW engineering units identifier NOTE For console only gt gt 3 5 513 Signal span of SP in engineering units gt gt 5 514 Zero value of SP in engineering units gt gt 0 8 15 SP engineering units identifier for OIS console only gt gt 8 255 518 Control station address gt gt 255 2 j Command Center Current Mode Execut Next Tune Default Write Delete Save Load Exit cb eae C Password 7 File c90 C CFG p Configure C Initialize Command None C Reset Request Block read complete WARNING incorrect use of this faceplate can cause a plant trip or major outage to occur Make sure you understand ABB Bailey configu
192. f the block The block type list box allows selection of the specific block type being RoviSys Company Copyright 1999 2015 Page 18 OPC90 Server User Manual V8 2 1 defined The addressing section is used to define the address within the Bailey system that provides the block data The other field definitions will be enabled based on the block type selected See the blocks section for further details on each specific setting When adding a block while OPC90 is currently communicating with the ABB Bailey system the validate type check box will also be displayed It is best to leave this validation enabled since it will verify the block type being added actually exists within the ABB Bailey system The import exception report block types will also show the read only check box This setting blocks any type of write to the block that causes a change in the ABB Bailey controller It allows individual blocks to be marked as read only instead of using the global lock found in the Device block properties 5 3 Edit The following picture shows the available Edit menu items DBDocTest cfg RoviSys OPC90 Server Runtime Mode File Add View Utilities Help TIM COM Ports Name Location Data Type Access value Description TCP Ports ALL STATUS COM12 INT R Good All Comm Status 0 Good 1 Bad BLOCK CYCLE COM12 INT 1 Block specification read cycles completed Engineering Units IMPORT FILE COM12 STRING Text M
193. face available typically up to 10 000 tags e Alarm levels are set in real time by data received from the Bailey system eliminates the need to maintain alarm level settings in two areas e Includes ability to tune Bailey control loops from OPC client applications e Supports redundant Bailey interfaces or redundant communication channels to a single Bailey interface e Supports the ability to easily import and export OPC90 function blocks to from comma delimited csv files The CSV file can be easily created using Microsoft Excel and then simply imported into the OPC90 Server to create an OPC90 configuration RoviSys Company Copyright 1999 2015 Page 6 OPC90 Server User Manual V8 2 1 3 Installation The installation procedure utilizes the industry standard Install shield Setup program Do the following procedure to install OPC90 This procedure assumes that the OPC90 Server is being installed on a Windows 2000 XP 2003 Server VISTA Windows 7 2008 2012 Server operating system 1 Log into a user account with administrator privilege 2 Insertthe OPC90 Server installation CD into the CD drive 3 Run the setup program found in the root directory of the CD a Rightclick on it and select Run as Administrator 4 Follow the instructions given by the Setup program 5 If using hardware licensing insert the RoviSys USB license key 6 If using software licensing run the RoviSys License Manager program and request a licen
194. first instance Warning manually running OPC90 should not be attempted until after all the OPC clients have been started Failure to heed this warning could result in an OPC client connecting with the second instance of OPC90 that is only serving as a user interface to the first instance Under this situation that OPC client will not receive the data being collected by the first instance Installation of OPC90 includes two different OPC test clients They are useful for validating local and remote PC OPC client connection with OPC90 The first test client is called OPC Expert It requires Microsoft NET 3 5 framework to be installed on the PC Double click on C Program Files OPC90 Server OPC Expert exe RoviSys Company Copyright 1999 2015 Page 169 OPC90 Server User Manual V8 2 1 or C Program Files x86 OPC90 Server OPC Expert exe to run it The second OPC test client is called DataSpy It must first be installed before it can be used Double click on C Program FilesNOPC90 Server opc_dataspy901 exe or C Program Files x86 OPC90 Server opc_dataspy901 exe to install it After installation run it from Start Iconics OPC Data Spy OPC DataSpy If OPC client connection problems occur try establishing an OPC connection using the DataSpy OPC client shown by the following dialog Select View Output so that it will post OPC messages to a list view box at the bottom of its program window These messages give
195. for the specific system OPC90 has been installed Next select the DCOM properties of My Computer and set the following default properties My Computer Properties Default Protocols MSDTC COM Security General ptions Default Properties v Enable Distributed COM on this computer Enable COM Intemet Services on this computer Default Distributed COM Communication Properties The Authentication Level specifies security at the packet level Default Authentication Level Connect The impersonation level specifies whether applications can determine who is calling them and whether the application can do operations using the client s identity Default Impersonation Level Identify v Security for reference tracking can be provided if authentication is used and that the default impersonation level is not anonymous Provide additional security for reference tracking Select the COM Security tab shown as follows My Computer Properties General Options Default Properties Default Protocols MSDTC COM Security Access Permissions You may edit who is allowed default access to applications Y ou may also set limits on applications that determine their own permissions Edit Limits Edit Default Launch and Activation Permissions You may edit who is allowed by default to launch applications or activate objects You may also set limits on applications that determine their own permissions E dit Limit
196. from a command prompt type OPCEnum Service to install OPCEnum as a service Depending on the operating system a reboot of the PC might be necessary The DCOM settings of OPCEnum might also need to be adjusted 12 13 OPC Client Connects But Does Not Receive Data Improper DCOM settings can cause multiple instances of OPC90 to run on the local PC Only the first instance can communicate with the Bailey interface Verify that a single OPC90 process is displayed in the task manager process list Note that when a user runs OPC90 manually it may run as a second instance This is normal If multiple OPC90 processes still show up in the task RoviSys Company Copyright 1999 2015 Page 179 OPC90 Server User Manual V8 2 1 manager list after the manually run instance is exited improper DCOM settings are causing this problem 12 14 Viewing Data in Monitor Mode Does Not Work 1 Verify the Bailey interface does not require a physical reset Click on the Device block and look for this message in the program status section lower right side of the program window 2 Verify Data does not exist in first program instance is not being displayed in the program status section This message indicates the OPC90 service or embedded instance is not in sync with the second instance This error is rare but could occur if database changes were made and not saved Stop and start the OPC90 service 12 15 Writing RMSC Blocks Cause Controller or Node Offline C
197. g Bailey Digital Input Loop blocks function code 42 and Digital Input Infinet blocks function code 122 The OPC90 DOL block will automatically generate the appropriate quality and alarming status based on the value presented at the block input Restrictions This OPC90 block can be utilized with all Bailey interface types except serial port module SPM amp CPMO2 and computer interface command series CIC TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey CIU ring address ADDR NODE Bailey CIU node address ADDR MODULE Bailey CIU module address ADDR BLOCK Block number to establish this point at within the Bailey interface see note 1 MAX TIME If IN never changes it will be reported at the maximum time interval seconds defined by this attribute DISC LIM VT eee eene The setting for the Bailey alarm limit used to pus pus the alarm condition see note 2 INIT VALUE VT BOOL Config Read The IN value used to send initially when me MAX TIME is exceeded if an OPC client has not written to it MY BLOCK TYPE Indicates the OPC90 block type MESSAGE VT BSTR Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor IN Discrete input value to be exception reported to Bailey OPC STATUS OPC status value see OPC status section QUALITY VT BOOL Current quality see note 3 of Bailey values 0 good 1
198. g sure it has a valid PID SMITH block number Until an actual PID SMITH block is determined the OUT HI LIM OUT LO LIM K KFC KTYPE KDIR KIONLY KP KI KD and KDLAG remain unknown OUT HI LIM and OUT LO LIM are the high and low limit specifications read from the Bailey PID SMITH block associated with the Bailey Control Station block Writing these values from OPC90 causes the driver to automatically tune them in the appropriate Bailey PID SMITH block specification K KDIR KIONLY KP KI KD and KDLAG are specifications read from the Bailey PID SMITH block associated with the Bailey Control Station block Writing these values from OPC90 causes the driver to automatically tune them in the appropriate Bailey PID SMITH block specification RoviSys Company Copyright 1999 2015 Page 149 5 OPC90 Server User Manual V8 2 1 When any of the K KDIR KIONLY KP KI KD and KDLAG tags are written even writing the same value OPC90 Server automatically puts the STN block into the fast update state This state causes OPC90 Server to acquire the STN PV and STN CO values with a polling command instead of exception reporting This operation is very useful for loop tuning software The duration for the fast update state and polling interval are device settings see DEVICE block The KFAST attribute indicates the fast update state is in effect The fast update interval can be refreshed by writing a one to the KFAST attribute or writing a new value
199. g the client s identity Default Impersonation Level Identify v Security for reference tracking can be provided if authentication is used and that the default impersonation level is not anonymous Provide additional security for reference tracking Select the COM Security tab shown as follows My Computer Properties General Options Default Properties Default Protocols MSDTC COM Security Access Permissions You may edit who is allowed default access to applications You may also set limits on applications that determine their own permissions E dit Limits Edit Default Launch and Activation Permissions You may edit who is allowed by default to launch applications or activate objects Y ou may also set limits on applications that determine their own permissions Edit Limits Edit Default RoviSys Company Copyright 1999 2015 Page 166 OPC90 Server User Manual V8 2 1 Click on Edit Default for the Access Permissions and add the following list of users Make sure allow access for both local and remote is enabled for all of these users ANONYMOUS LOGON Everyone INTERACTIVE NETWORK NETWORK SERVICES Self SYSTEM Distributed com users These users are not supported on earlier Windows operating systems There are two local security options policies that need to be setup Run Control Panel Administrative Tools Local Security Policy and select Security Options as displayed
200. grade to revision E b INICI13 is comprised of the INICT13A and INNISO1 modules The default factory settings for the INICT13A SWA are incorrect The INICT13A SW4 Poles 6 7 8 must be open 1 when using SCSI with this module 2 Contact RoviSys regarding the IET800 Throughput of the supported Bailey CIU devices is difficult to calculate empirically since the data is received and sent by exception and varies according to the total blocks in the database data types of those blocks and what has changed significantly at any given time The exception reporting rate per general data type for RS232 and SCSI interfaces is presented in the following table Data Type RS232 19 2k SCSI values second values second Analog 260 161 1080 1059 Digital 310 260 1230 1206 Control Loop 106 91 618 606 Average 225 170 976 957 Rate when the device block Use DCS Timestamp option is enabled A practical method for considering the use of serial versus SCSI is based on the total number of blocks in the database So for example assume the total number of blocks is around 1000 and also assume 10 of those blocks are changing significantly That would be a very active plant which would generate 100 exception reported values per second For this example performance of both the serial and SCSI based CIUs would practically be identical in terms of data updates per second since both can read 100 v
201. h processing import exception reports There are four possible solutions to this ABB Bailey CIU problem 1 Use combinations of OPC90 and Bailey RMSC and RCM blocks to send analog and digital data 2 Move the OPC90 export blocks onto a separate ABB Bailey CIU dedicated for these types of blocks 3 Upgrade the ABB Bailey CIU to a newer model RoviSys Company Copyright 1999 2015 Page 177 OPC90 Server User Manual V8 2 1 4 Determine if ABB Bailey has a newer CIU firmware revision that might correct this problem 12 9 Cannot Export or Control Data Within Bailey 1 Verify that the Bailey interface device supports this type of activity 2 Verify the allowable ranges for the attribute being written match those configured within Bailey For example you cannot write an OUT value that exceeds the OUT SCALE limits Co Verify the Bailey interface does not have monitor mode enabled very unlikely Monitor mode is set using an ASCII terminal attached to the termination unit module printer port and that port selected for the utility mode consult Bailey interface manual Normally monitor mode is disabled when a Bailey interface is received from the Bailey factory It is unlikely that monitor mode is enabled unless someone had attached an ASCII terminal at one time and was experimenting with the available options within the Bailey interface utility menus 4 Verify the Device is not locked by looking at the Device LOC
202. ics can be read based on the settings of the ENABLE LOOP ENABLE NODE ENABLE NIS ENABLE MB and the LEVEL tags Collection of the PCU node communication statistics is accomplished via individual poll messages directed at the node NPM module These messages are not as time consuming as poll messages directed to controllers within the PCU node but do consume CIU communication bandwidth and a minimal amount of NPM bandwidth Therefore it is recommended that the INTERVAL tag ENABLE and LEVEL tags settings be used judiciously to minimize the impact of this blocks data collection on CIU and NPM communication performance This is especially important when configuring multiple blocks of this type and using database shadowed OPC90 installations When specifically diagnosing a particular node turn on all of the ENABLE flags and reduce the INTERVAL setting to see timely updates of the statistical data for diagnosing performance After completion of the diagnoses turn the ENABLE flags off and increase the INTERVAL tag setting back to its original setting When the ENABLE CSV LOG tag is enabled all of the PCU statistics that are being collected are logged to a CSV file called PCUMON Rx Ny Date Block CSV where Rx is the ring number and Ny is the node number of the PCU address Date is the date of the log file and Block is the name of the PCUMON block generating the log The location of the CSV file is in the C Program Files OPC90 Server og directory
203. ification cannot be completed When the ACKNAK tag is zero the request was successful non zero indicates an error occurred 7 3 7 Deleting Bailey Controller Blocks To delete a Bailey function block the controller must be in the configure mode of operation See section 7 3 4 to understand how to change Bailey controller modes of operation There are two easy steps an OPC client must follow to delete a Bailey function block First it must read the function block to be deleted See section 7 3 1 to understand how to read a block The second step is to request the block deletion by setting the DELETE tag to a value of TRUE Completion of the delete is flagged when the DELETE tag is reset to FALSE The MESSAGE tag will also return a text message indicating completion of the delete operation or the reason for failure if the deletion cannot be completed When the ACKNAK tag is zero the request was successful non zero indicates an error occurred 7 3 8 Configuration Command Processing The COMMAND tag allows the OPC client to perform a variety of Bailey configuration related activities using simple text commands The OPC client sends the text command to the COMMAND tag It can monitor completion of the requested command using the COMMAND ACT tag The MESSAGE tag will contain a text message showing the result of the command when it has finished The following table presents an overview of the supported commands Command Argume
204. ifications to be sent every 60 seconds Let s say there are only 10 STN blocks in the configuration It will take 300 seconds to cycle through reading the PID gains RoviSys Company Copyright 1999 2015 Page 71 OPC90 Server User Manual V8 2 1 MAX GMI PER SECOND 32 Bit Config PER PCU NODE UINT ENABLE TURBO Boolean POLLING ESTABLISH ONLINE Boolean NON KEYED Boolean Config MESSAGING Config associated with those STN blocks GMI stands for general message interface They are messages such as block output polling block configuration specification reading problem report reading and others Basically any message not related to exception report collection Sending too many GMls to a PCU node could cause that node to slow down the number of exception reports it needs to send This setting can be used to throttle the number of GMI messages that OPC90 is allowed to send per second to PCU nodes Normal use of OPC90 does not need this parameter to be changed When used with MUXCIU blocks servicing DBDOC and Composer it may need lowered if exception report slowdowns are noticed while Composer is doing downloads or verifies This occurrence in most cases won t be seen when using serial CIU communication but could happen for SCSI CIUs Turbo polling significantly increases the amount of data that can be polled using the POLL block the STN KFAST feature and poll requests received via the MUXCIU block Turbo polling
205. iley CADEWS naming syntax This convention makes it easy to identify what Bailey module the file corresponds with Configuration data can be loaded from one of two file formats The format is selected with the C90 and CFG radio buttons When the C90 radio button is selected the function block configuration data is loaded from files that have a C90 extension This is the OPC90 file format The C90 files are found in the ABB subdirectory unless an alternative directory path is included as part of a user inputted file name When the CFG radio button is selected the function block data is loaded from files that have a CFG extension These files must already exist and are of the format generated by the ABB Bailey CADEWS software and its derivatives The CFG files are also found in the ABB subdirectory unless an alternative directory path is included as part of a user inputted file name Click on the STOP button to stop the load operation Note that if a user inputted file name or directory path is entered that contains spaces it must be enclosed within quotes C Program Files OPC90 Server ABB Name With Spaces When a user file name is entered it is not necessary to include its extension The default extension selected by the C90 CFG radio button will automatically be appended to the file Including the C90 or CFG file extension overrides the default type CHANGE Click on this button to ch
206. iley CADEWS or Composer software to communicate with the Bailey system via the OPC90 DEVICE block driver To accomplish this task connect a RS232 serial cable between the COM port specified by the MUXCIU PORT attribute and the COM port to which the configuration utility program expects the Bailey CIU interface to be attached Note that this connection must be made with a null modem cable The MUXCIU block receives CIU commands sent by the configuration utility program via the assigned serial port It channels those commands to the Bailey system through the OPC90 DEVICE block driver The CIU reply is then returned to the configuration utility program via the assigned serial port All commands not associated with points established in the Bailey interface are supported Configuration of this block includes four options The read only operation option filters commands that make changes in the ABB Bailey DCS This option can be enabled by clicking on the Read only operation as shown by the following block properties dialog Edit Existing OPC90 Block Name COMPOSER Cancel Description Composer communication Block Type z ADDRESSING Readonly M AlowR4 MV Prefetch Port COM2 Virtual port T No turbo This option should be enabled when using this block with DBDOC Do not enable it when using with Bailey CADEWS or Composer software The Allow R4 option allows polled block outputs to be read as real 4 values Note that the D
207. indows base directory It may be edited to customize message generation The MODULE STATE section defines the text for module state The MODULE TYPE section defines the text for module type You may edit the names or add new type codes and associated names that correspond to new Bailey modules introduced after any given revision to the OPC90 Connect Bailey RoviSys Company Copyright 1999 2015 Page 96 OPC90 Server User Manual V8 2 1 7 16 Multi State Device Driver MSDD The MSDD OPC90 block is used to retrieve and control the exception reported output from Bailey Multi State Device Driver blocks function code 129 Restrictions This OPC90 block can be utilized with all Bailey interface types except serial port module SPM amp CPMO2 TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address ADDR NODE Bailey node address ADDR MODULE Bailey module address ADDR BLOCK Bailey block address F1LSDO Feedback 1 state zero logic state descriptor F1LSD1 Feedback 1 state one logic state descriptor F2LSDO Feedback 2 state zero logic state descriptor F2LSD1 Feedback 2 state one logic state descriptor F3LSDO Feedback 3 state zero logic state descriptor F3LSD1 Feedback 3 state one logic state descriptor FALSDO Feedback 4 state zero logic state descriptor FALSD1 Feedback 4 state one logic state descriptor GSLSDO Good state zero logic state descriptor GSLSD1 Good state one logic state descriptor GSLSD2 G
208. inel Protection Installer 7 x x exe or C Program Files x86 RoviSys LicenseManager Sentinel RoviSys Company Copyright 1999 2015 Page 184 OPC90 Server User Manual V8 2 1 Protection Installer 7 x x exe file and allow it to re install or fix itself Restart the PC 12 25 Forcing a CIU Restart Although forcing a CIU restart is rarely needed OPC90 supports such action Let s say a CIU stops updating a set of points or it just doesn t appear to be running normal The OPC90 program window can be used to request the CIU to be restarted This is accomplished by right clicking on the DEVICE block called CIU in this example and selecting Restart The user will be prompted to make sure a restart is really wanted before it is done Restarting a CIU will temporarily cause the tag value statuses OPC90 is providing to OPC clients set to bad Data flow values for those tags will also temporarily be paused while the restart occurs TurboListAnalysis cfg RoviSys OPC90 Server Runtime Mode File Add Edit View Utilities Help Diele SIA lola gt e n Jr Access Value Restart X ALL STATUS 3003 INT X BLOCK CYCLE 3003 INT X IMPORT FILE 3003 STRING X IMPORT READ 53003 BOOLEAN Off X IMPORT RES 3003 STRING X MESSAGE 53003 STRING New Block X MSG QUEUE 3003 INT Log CIU Errors X MSG RATE 53003 INT X MSG TOTAL 3003 INT Log CIU Events X MY BLOCK T 3003 STRING v Log CIU Messages MYI 53003 STRING Log OPC Reads a 5
209. int ratio index STN OK or STN LEVEL write occurred This timer is active when STN LEVEL indicates computer level and STN OK indicates ok When writing mode OPC90 first checks the current level of the STN block and sends out the appropriate new mode command based on the current level So for example if you command the STN block mode to auto by writing a value of 1 and the STN level is currently computer manual OPC90 will send out the appropriate mode command for computer auto The important thing to remember is the values used to indicate and control Bailey STN block mode are always 0 manual 1 auto 2 cascade regardless of STN block level local or computer The default value of zero instructs the driver to automatically determine the PID SMITH block number associated with the Bailey control station block It follows the block input stream starting with the STN S3 input looking for the existence of a PID of type FC 18 19 156 or SMITH Predictor FC 160 If one is found it s block number is written to this tag Otherwise the value is set to 1 to indicate PID SMITH block not found This will be the case if a PID SMITH is not configured or two or more PID SMITHs are found in the STN input stream In this circumstance the user must write the associated PID SMITH block number to this tag to make the other STN K tuning items functional It is important to note that if the other STN K tags are not functioning check the value of this tag makin
210. ion blocks in the currently addressed module MODIFY 750 4 3 Starting at block 750 modify four function blocks incrementing the modifying block number by 3 for each modification in the currently addressed module This end result is modifying blocks 750 753 756 and 759 MODIFY 800 1031 107 Starting at block 800 modify ten function blocks incrementing the modifying block number by 3 for each modification in ring 1 node 10 module 7 Delete Command Use this command to delete one or more existing function blocks configured in a Bailey module Remember the module must first be in configure mode before blocks can be deleted Following are some example delete commands Command Action DELETE Delete currently addressed function block DELETE 30 Delete function block 30 from currently addressed module DELETE 30 40 Delete function blocks 30 through 40 from currently addressed module DELETE 100 120 1 1020 Delete function blocks 100 through 120 from ring 1 node 10 module 20 7 3 9 BLK Configuration Faceplate The BLK block includes a faceplate that allows the user to configure ABB Bailey controller logic It incorporates many of the features found in the Bailey TXTEWS and CLS programs To display the faceplate right click on the BLK block and select Faceplate The following faceplate will be displayed RoviSys Company Copyright 1999 2015 Page 59 OPC90 Server User Manual V8 2 1 ABB Bail
211. ion is too high or exception report rates have dropped too low see notes 6 7 8 9 10 Note that throttle declaration does not occur until the device block indicates startup has been completed Percentage of this node s communication module processing power currently being used Moving average of the percentage of this node s communication module processing power currently being used RoviSys Company Copyright 1999 2015 Page 127 OPC90 Server User Manual V8 2 1 COMM PCT LEVEL GMI RX GMI_RX_AVG GMI_RX_LEVEL GMI_TX GMI_TX_AVG GMI_TX_LEVEL XRP_RX XRP_RX_AVG XRP_RX_LEVEL XRP_TX XRP_TX_AVG XRP_TX_LEVEL LOOP_TX_BYTE LOOP_TX_MSG NODE_RX_BYTE NODE_RX_MSG NODE_TX_BYTE NODE_TX_MSG NIS_RX_BYTE NIS_RX_MSG NIS_TX_BYTE VT Read Write VT l4 Read VT l4 Read VT l4 Read Write VT l4 Read VT l4 Read VT l4 Read Write VT l4 Read VT I4 Read VT l4 Read Write VT l4 Read VT l4 Read VT l4 Read Write VT l4 Read VT l4 Read VT l4 Read VT l4 Read VT l4 Read VT l4 Read VT l4 Read VT l4 Read VT l4 Read Communication module processing power utilization percentage level to declare OPC90 polling throttle see note 6 Number of GMI messages per second being received by this node Moving average of the number of GMI messages per second being received by this node Maximum node received GMI messages per second level to begin OPC90 polling throttle s
212. iptors indicate the specification number is not valid for the block read 7 3 2 Tuning a Bailey Block Some Bailey specifications can be modified while the block is executing These are called tunable specifications and are indicated as such by the specification description having the T character in front of it The tags S01 VALUE through S63 VALUE can be used to change the value of tunable specifications When the TUNE tag is set TRUE any tunable S01 VALUE through S63 VALUE tag that was changed by the OPC client will be included in the Bailey block tune operation Completion of the tune operation is flagged when the TUNE tag is reset to FALSE The MESSAGE tag will also return a text message indicating completion of the tune operation or the reason for failure if the tune cannot be completed When the ACKNAK tag is zero the request was successful non zero indicates an error occurred 7 3 3 Reading the Entire Bailey Configuration The entire Bailey configuration can be read using the READ and NEXT tags also see save command processing First start by using the ADDR RING ADDR NODE RoviSys Company Copyright 1999 2015 Page 51 OPC90 Server User Manual V8 2 1 ADDR MODULE ADDR BLOCK and READ tags to read block zero which is the start of any given module configuration Each time the NEXT tag is set TRUE the next block from the last one just read will be retrieved The returned specification values are copied to the S01 VALUE through S63
213. it under the Device1 DEVICE block 3 Groups should not be included within the CSV file For example if there are 200 AIL blocks that need to be imported into the configuration and you wanted to group them you may put them in a single group called AREA1 for example Block Names such as CIU4 AREA1 AIL1 to CIUA AREA1 AIL200 would be found in the CSV file However you do not need to add a line for the AREA group itself such as CIU4 AREA1 The group will be automatically created 4 If the logic state descriptors associated with digital blocks are not defined they will be defaulted to values of Off and On Example File lt OPCUnit1 csv gt Importing the following CSV file will cause the configurator to create a default device block called Device1 All the the blocks defined within this file will then be placed under that DEVICE block Note fields 5 to12 are omitted 1BLKULD DIL 1 1 4 6003 BLOCK UNIT LOAD DEC Reset Set RoviSys Company Copyright 1999 2015 Page 157 OPC90 Server User Manual V8 2 1 1BLCKTURBD DIL 1 1 4 6004 BLOCK TURBINE DEC Stopped Running AFDRSPD STN 1 1 4 6009 A FEEDER SPEED STATION 1BIDINDEV DIL 1 1 4 6029 B ID FAN INLT DMPR DEV Off On CFDRSPD STN 1 1 4 6061 C FEEDER SPEED STATION 1CFDRBCKE RCM 1 1 4 6068 C FEEDER RUNBACK BAD GOOD Stopped Run UNIT GROSS MWAAIL 1 1 4 663 UNIT GROSS MW UNIT GROSS MVAR AIL 1 1 4 664 UNIT GROSS MVAR GEN VOLTS AIL 1 1 4 665 GENERATOR VOLTS
214. ith 0 1 5 6 Off On Reset Set Zero One False and True Writing any of these strings is case insensitive RoviSys Company Copyright 1999 2015 Page 136 OPC90 Server User Manual V8 2 1 7 28 amp Remote Motor Control RMC The RMC OPC90 block is used to retrieve and control the exception reported output from Bailey Remote Motor Control blocks function code 136 Restrictions This OPC90 block can be utilized with all Bailey interface types except serial port module SPM amp CPMO2 ADDR NODE ADDR MODULE ADDR BLOCK F1LSDO F1LSD1 F2LSDO F2LSD1 PERM1LSDO PERMILSD1 PERM2LSDO Indicates the block long OPC path name QUALITY VT BOOL Read Current quality of Bailey values 0 good 1 bad OUT_TEXT VT_BSTR Read Write Bailey RCM discrete output value as a string see note 1 RED_CMD VT_BSTR Read Write Red tag command see red tag users section RED_TAG VT_BOOL Red tag indicator 0 no 1 yes RED USERS VT BSTR Read Red tag users current user names or codes F1 F1 VT BOOL Read _ State of feedback number1 RoviSys Company Copyright 1999 2015 Page 137 OPC90 Server User Manual V8 2 1 BAD START VT BOOL Bad start indicator HOLD STATUS VT BOOL Status on hold indicator Notes 1 Text strings can be written to this tag to control the RMC output Valid text strings are the OUTLSDO and OUTLSD1 settings along with 0
215. its of value an OPC client is permitted to write new alarm limits in run time Care should be taken to not continuously change the limit value since each change necessitates dis establishing the point from the ABB Bailey interface and than re establishing it with the new limit value When the Device block Set bad quality of max exception timeout property is enabled the QUALITY tag of this block will be set bad if writes to the block input s do not occur within the Exception Report Output Max Time setting of the block When this occurs bad quality will also be written to the CIU and therefore propagated to the users of the block data within the ABB Bailey system The quality can also be set bad by writing a one 1 to this tag RoviSys Company Copyright 1999 2015 Page 48 OPC90 Server User Manual V8 2 1 7 3 Block Data BLK The BLK OPC90 block provides Bailey function block configuration capabilities It supports reading Bailey configuration tuning specifications changing module modes writing new blocks modifying existing blocks deleting blocks and saving and restoring module configurations The BLK block is designed to allow MMI OPC clients to easily set up a Bailey function block programming environment Restrictions None this OPC90 block can be utilized with all Bailey interface types TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address Read Write ADDR_NODE Bailey node address Read Write ADDR_MODU
216. k compatible but having control events that must occur based on a specific day of the week Monday Tuesday Wednesday etc Note that this option is mutually exclusive with the use DCS Timestamp option previously discussed There are two important factors that must be considered when using this option The first is that it must be enabled for all PCs running OPC90 that have the time syncing option enabled The second is its use is not recommended for systems that also have other nodes present like ABB Bailey consoles that are configured to participate in time syncing or are using the ABB Bailey distributed trending functionality The following table presents the time warping algorithm used by this option Present Year Mapped to Past Year 2000 2006 2017 1995 2001 2007 2018 1990 2002 2013 2019 1991 2003 2014 1997 2004 1999 1998 2005 2011 1994 2008 1980 2009 2015 1998 2010 1999 2012 1984 2016 1988 2020 1992 2021 1999 1 1 2004 thru 2 28 2004 are mapped to 1998 calendar year 2 29 2004 is mapped to 3 1 1998 matches day of the week 3 1 2004 thru 12 31 2004 are mapped to 1999 calendar year 3 An OPC client can use these tags to import a CSV file into the OPC90 database The CSV file can only contain new blocks to be added within an existing device Lines that reference existing blocks or new devices will be ignored The file to be imported is specified by the IMPOR
217. k remains undeletable 5 3 2 Com Ports Select Edit gt Com Ports to define the communication characteristics of any given PC COM port assigned to a device When this item is selected the following dialog is displayed RoviSys Company Copyright 1999 2015 Page 19 OPC90 Server User Manual V8 2 1 Port Properties pot com e Cancel Baud Rate 19200 _ Cancel Parity None Flow None Data Bits 8 RTU Stop Bits 1 OPC90 uses the communication characteristics setup with this item and not those configured under the windows global port settings Most Bailey interfaces utilize the settings shown by this dialog The exception is the CIC module which has a maximum baud rate capability of 9600 baud 5 3 3 TCP Ports Select Edit gt TCP Ports to edit the 16 available OPC90 TCP ports When this item is selected the following dialog is displayed RoviSys Company Copyright 1999 2015 Page 20 OPC90 Server User Manual V8 2 1 TCP Port Addresses Enter TCP IP and Port TEPIP 172 24 210 77 10001 Tepis 172 24 210 77 10002 Tcp 2P 172 24 210 66 10001 Tcp 2s 172 24 210 66 10002 Tcp 3P 172 24 210 66 10003 TCcP 35 172 24 210 66 10004 Tcp 4P 172 24 210 88 10001 Tcp 4s 172 24 210 8 10002 TCP SP iPaddresshere Port TCP 55 iPaddresshere Port TCP 6P iPaddresshere Port TCP 65 IP addresshere Port TCP 7P IP addresshere Port TCP 75 IP addresshere Po
218. ks polling outputs of non exception reported blocks system status configuration reading and tuning of any Bailey block in the system and the output report block types Note that the output report block types can only be used with the Bailey NCIUO2 03 04 INPCIO2 and INICIxx interfaces Each OPC90 Server block definition includes a table which summarizes the attributes and tag names supported by the block type This table contains four columns which are Attribute Tag Name Data Type Access and Description Attributes are fields that must be setup as part of defining the block within the OPC90 database Most of these fields are not available to the OPC client as an OPC tag OPC90 supports online changes to some of these attributes via the block properties available by right clicking on the block and selecting properties This feature is handy for correcting block address definition problems when OPC90 is currently online providing data to OPC clients Note that the block properties dialog is the same one used to configure new blocks see preceding add block section Just enter the correct address and OPC90 will re establish the point within the ABB Bailey interface Once the update has been confirmed to correct the addressing problem don t forget to save it using the OPC90 File gt Save menu selection Tag Names are fields available to the OPC client The Data Type column gives the default OPC tag type for each defined tag n
219. l block 4 For ABB Bailey Infi 90 systems time synchronization does not start until after 9 minutes have transpired after OPC90 Server first starts communicating with its interface This delay is 3 minutes for ABB Bailey Network 90 systems 5 The PC running OPC90 Server automatically becomes the time synchronization master whenever its clock is changed by two minutes or more 6 Note that OPC90 Server gives precedence to MCS and OIS nodes as becoming the time synchronization master if its accuracy rating is less than the accuracy rating of those console types The accuracy rating of the current time sync master can be viewed from the Device block faceplate The accuracy rating of the OPC90 CIU is set within the Device block properties dialog 12 12 OPC Client Does Not See Any OPC Servers When Browsing Remote PC A service called OPCEnum must be running on the PC to enable browsing of its OPC servers Check if this process is running using the Task Manager process list If it is running make sure the Windows Network access Let Everyone permissions apply to anonymous users local security policy is enabled The OPC90 install set does not install OPCEnum It does however include the OPC Foundation Core Components installation MSI file This file can be found in the C Program Files OPC90 Servern OPC Foundation directory Double click on the MSI file to install these core components which includes the OPCEnum program Afterwards
220. ld condition by setting the HOLD STATUS tag It should be reset on the next start request The OPC client uses the FAULT ACK tag to indicate a fault has occurred and receive an acknowledgment of that fault when the Bailey console writes a value of zero to FAULT ACK RoviSys Company Copyright 1999 2015 Page 120 OPC90 Server User Manual V8 2 1 7 23 Output Remote Manual Set Constant ORMSC The ORMSC OPC90 block interfaces with Bailey consoles as a Remote Manual Set Constant block function code 68 Note that this block does not received data from a RMSC block running in a Bailey controller Use the OPC90 RMSC block for that purpose The ORMSC is used to indicate an operator settable analog set point value Operators can only write set point values to this block within the range specified by its attributes A set point track indicator indicates logic determination of the set point value Restrictions This OPC block can be utilized with all Bailey interface types except CIUO1 serial port module SPM CPM02 amp CPMO03 and computer interface command series CIC TAGNAME TYPE ACCESS DESCRIPTION ADDR RING VT l2 Config Read Bailey CIU ring address ADDR NODE VT l2 Config Read Bailey CIU node address ADDR MODULE VT l2 Config Read Bailey CIU module address ADDR BLOCK VT I2 Config Read Block number to establish this point at within the Bailey interface see note 1 EU CODE VT I2 Config Read Bailey engineering units c
221. le interface redundant channel communication scheme With single interface redundant channel the driver issues exception report read requests to both channels resulting in increased throughput If loop tuning software has one or more STN blocks in fast update mode exception report reading on the second channel is temporarily stopped and instead it is used for polling the STN block process variable and control outputs This feature helps facilitate tuning of fast loops that typically require 4 or more updates per second even when the active database is very large When the STN blocks are taken out of fast update mode exception report collection on the second channel will resume The second redundant scheme is dual interfaces single channel This scheme utilizes two Bailey interfaces Each Bailey interface can be assigned the same node address on the Bailey communication highway or given unique addresses When the Bailey interfaces are configured for the same node address the driver commands the primary interface online to the Bailey communication loop and commands the secondary interface offline The database is downloaded to both interfaces so the secondary can be considered to be in a warm standby mode ready to be commanded online if the primary interface fails When the Bailey interfaces are configured for different node addresses the driver commands both interfaces online receiving exception report data from each This increases the effective data
222. lized with all Bailey interface types except serial port module SPM amp CPMO2 TAGNAME TYPE ACCESS DESCRIPTION ADDR_RING Bailey ring address ADDR_NODE Bailey node address ADDR_MODULE Bailey module address ADDR_BLOCK Bailey block address MY_BLOCK_TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor BLOCK TYPE VT udi EE Type of SOE log block Undefined Standard Summary Pre fault Post fault IEEE Snap shot OPC_STATUS inii 12 OPC status value see OPC status section QUALITY VT P Read Current quality of Bailey sequence of events recorder 0 good 1 bad A value of 0 indicates good otherwise the point address is wrong the Bailey controller is not communicating with the RA 3800 SER or INSEMO1 module SOE DATA VT BOOL Read Write Indicates whether or not the SOE block has newly captured SOE data present 0 empty waiting for a capture event 1 capturing data OFLOW VT BOOL Read The SOE data overflowed the Bailey SOE block buffer capacity COUNT VT l4 Read Total points logged to the currently selected RoviSys Company Copyright 1999 2015 Page 140 OPC90 Server User Manual V8 2 1 SOE capture file EVENT Signals that a SOE event has been captured 0 armed and waiting 1 captured and locked FILE indicates
223. lt of the CSV file import request 09 16 2015 15 11 21 031 v Inactivity Time gt I loff Clients 6 Groups 10 Tags 323 Rate 201 Service Run CIU ONLINE Unlimited 5 4 1 View Monitor Select Monitor to request that OPC90 go into the monitor mode of operation In this mode the real time values being received from Bailey are displayed in the program window Monitor mode is useful for instructing OPC90 to begin collecting data from the ABB Bailey system even when no OPC clients are connected This feature allows the OPC90 configuration to be validated prior to developing any OPC client connections The following picture shows monitor mode of operation viewing the tag values of a block named Sine 002 TurboListAnalysis cfg OPC90 Server File Add Edit View Utilities Help ose mlaj sele e eim Q Sines Name Location Data Type Access Value Description Last Update E Sine_001 EU 1 1 3 102 SHORT R Engineering Units Code 04 17 2012 07 32 30 480 E Sine n02 EU TEXT 1 1 3 102 STRING R Engineering Units Text 04 17 2012 07 32 30 480 E Sine D03 HI ACT 1 1 3 102 BOOLEAN R Off High Alarm Active Indicator 04 17 2012 07 56 52 389 E Sine 004 LIM 11 3 1012 FLOAT Rw 90 000000 High Alarm Limit 04 17 2012 07 32 30 480 E Sine 005 LO AC BOOLEAN R Off Low Alarm Active Indicator 04 17 2012 07 56 52 389 E Sine 006 3 LO LIM FLOAT 90 000000 Low Alarm Limit 04 17 2012 07 32 30 480 ONLINE Block Status 04 17 2012 07 33 35 83
224. mode it is important to make database changes using the current OPC90 running as shadow master This can be determined by looking at the device block SHADOW MASTER tag while in monitor mode Configuration shadowing works with the File Import and Export features and all selections available from the Add and Edit menu selections Its purpose is to minimize the engineering effort required to maintain redundant OPC90 servers The File Auto Save feature is not shadowed and must be individually setup for each server Select Edit gt Configuration Shadowing to enable disable configuration shadowing When this menu item is selected the following dialog is displayed Configuration Shadowing ES Name of PC running the other OPCS0 Server jws2303 v Enable configuration shadowing iw Shadow polled data v Shadow input data Cancel Type the name of the other PC that is running OPC90 Configuration shadowing is enabled when the Enable configuration shadowing checkbox is checked It is disabled when unchecked RoviSys Company Copyright 1999 2015 Page 27 OPC90 Server User Manual V8 2 1 The Shadow polled data option should normally be checked This enables the PC running OPC90 as the shadow slave to acquire all polled data from the PC running OPC90 as the shadow master This feature keeps polling load on the ABB Bailey PCU nodes limited to a single instance of redundant OPC90 servers instead of both polling for the same dat
225. more on this feature at the end of this section It is important to setup the two redundant OPC90 servers with the same database file before turning configuration shadowing on This is easily accomplished by copying the database file from one OPC90 PC to the other and opening that file up in the other PC RoviSys Company Copyright 1999 2015 Page 26 OPC90 Server User Manual V8 2 1 to set it as the working database The database files are found in the C Program Files OPC90 Server CFG directory Configuration shadowing must only be used between OPC90 servers of the same revision level Unpredictable results will occur when shadowing between two unlike software revision levels Configuration shadowing may not work when the redundant OPC90 servers are running as a service from the system account If the connection status indicates gt Bad shown in the program status bar the service must be changed to run from a privileged user account Whether to use system account or privilege account is dependent on how operating system network service security is setup so trying it either way may be required IMPORTANT If configuration shadowing remains bad on either PC make sure file sharing is enabled on both PCs Also check the Windows local security policy for the existence of a Network access Restrict anonymous access to Named Pipes and Shares policy If it exists make sure it is disabled on both PCs When operating in runtime
226. n Unit 1 2 Combined MW it Note that the double quotes will be parsed out Don t use any commas in the description if it is not encased by double quotes MaxTime or Only used for AOL DOL ODD OMSDD Interval ORCM ORMC ORMSC OSTN and POLL blocks Specifies the MaxTime in seconds for AOL DOL ODD OMSDD ORCM ORMC ORMSC and OSTN blocks Poll Interval Used for POLL blocks specifying the polling 1000 interval in milliseconds Read only flag Used for AIL DAANG DADIG DD HAI 0 2 noor 1 read only HAO MSDD MUXCIU RCM RMC RMSC SPEC STN and TEXTSTR blocks to set its operation to read only When this flag is set all writes to the block that change data in ABB Bailey controllers are rejected InitialValue Only for AOL and DOL blocks Specifies the 12 456 initial value for these blocks Must be 0 or 1 for DOL defined as 0 for ODD OMSDD ORCM ORMC block Must not be defined for ORMSC and OSTN blocks EU or Specifies the EU Units integer value for 10 AlarmState or AOL ORMSC and OSTN blocks For DOL 0 1 or 2 for DOL FaceplateType blocks this field specifies the AlarmState 0 alarm when 0 1 alarm when 1 2 alarming disabled For ODD OMSDD ORCM and ORMC blocks this field specifies the faceplate type code RoviSys Company Copyright 1999 2015 Page 156 OPC90 Server User Manual V8 2 1 Zero For AOL ORMSC and OSTN only 1000 0 Specifies the value of the zero in engineering units Sp
227. n double quotes If the file name is excluded OPC90 will automatically name the file based on the current address specified in the ADDR RING ADDR NODE and ADDR MODULE tags For example assume these tags are currently set to the corresponding values of 1 2 and 3 The file name will be 00100203 C90 or 10203 CFG This convention makes it easy to identify what Bailey module the file corresponds with OPC90 can save the configuration in one of two file formats The FILE TYPE tag selects the file format to utilize When FILE TYPE is reset 0 OPC90 will save the Bailey function block configuration data in files that have a C90 extension This is the OPC90 file format When the file name is included in the command OPC90 will automatically append the C90 extension if it is missing Including the C90 extension in the file name will override the current FILE TYPE tag setting The C90 files are stored in the ABB subdirectory unless an alternative directory path is included as part of the file name When FILE TYPE is set 1 OPC90 will save the Bailey function block configuration data into files that have a CFG extension These files must already exist and are of the format generated by the ABB Bailey CADEWS software and its derivatives When the file name is included in the command OPC90 will automatically append the CFG extension if it is missing Including the CFG extension in the file name will override the curr
228. nction blocks One block is the actual PID algorithm and the other is called a station block STN that handles interaction of the PID control values to Bailey consoles Typical loop variables such as set point process variable control output and mode are involved with this interaction Bailey also makes available a number of auxiliary values associated with the typical values that are also included in the OSTN implementation The RED TAG tag allows the OPC client to indicate the device is currently under a red tag condition The OPC client reports the mode of the control loop via the MODE tag Valid modes are manual 0 auto 1 and cascade 2 OPC90 will receive mode write request from the Bailey system and transfer it to the OPC client by writing the new requested mode value to the MODE tag Bailey logic can lock a control loop into any given mode The OPC client uses the MODE LOCK tag to indicate this condition The PV tag is used by the OPC client to report the process variable of the control loop This value is in engineering units and will be clamped between the zero and span defined for the process variable The OUT tag is used by the OPC client to report the current value of the control output By definition for Bailey systems OUT has a range of 5 0 to 105 0 that expresses a percentage OPC90 will receive control output write request from the Bailey system and when the current mode is manual transfer the control output to the OPC client by
229. ndicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor COLUMNS ee l2 il Number of columns characters per line to use when generating problem report text lll from 50 to 130 are allowed READ VT uM Read Write Set this attribute to request module problem reports to be read for the Bailey module status defined for this block The problem reports are written to the LINEO1 to LINE5O attributes The driver will reset this attribute when the read request is completed NEXT VT BOOL Read Write Set this attribute to request a read of the next group of problem reports The problem reports are written to the LINEO1 to LINE5O attributes The driver will reset this attribute when the next problem report read request is completed LINES un I2 a Number of lines to utilize when generating IE bien report text Values from 2 to 50 are allowed OPC STATUS OPC status value see OPC status section QUALITY VT pue mes Current quality of Bailey values 0 good 1 SEEN f OUT VT ious Read Indicates whether or not the Bailey module is currently experiencing any errors A value of zero indicates no errors A value of one indicates one or more errors They can be determined by examining the STATUS_TEXT attribute and requesting problem reports LINEO 1 to VT ud esc Requested problem report text strings are LINE50 EE to these attributes STATUS TEXT Overview status of the addressed Bailey
230. nication between the OPC90 Server and the Bailey interface if possible it is a good idea to verify the setup by trying to communicate using the Bailey TXTEWS software Generally if this software functions OK you should not experience problems with OPC90 Server All Bailey interfaces have a series of four or eight red LEDs on the hardware module that processes serial communication and manages its database Don t confuse this card with the module that handles the interface with the Bailey communication loop which also has a series of LEDs An indication that communication with the BAILEY interface is occurring can be determined by looking at the serial processing card LEDs Hereafter these LEDs will be referenced as Bailey interface LEDs The Bailey interface LEDs count commands and replies occurring between the OPC90 Server Application Station computer and Bailey interface RoviSys Company Copyright 1999 2015 Page 172 OPC90 Server User Manual V8 2 1 12 1 SENTINEL SYS Causes PC bluescreen on bootup When OPC90 is started it immediately attempts to validate its license by communicating with the sentinel sys driver When OPC90 is setup to run automatically in an auto logon startup environment it can sometimes try to communicate with the sentinel sys driver that has not yet been started by the operating system as a system service This can result in the infamous PC bluescreen of death The solution is to use a program called startme exe
231. nications module per second Total number of bytes transferred on the expander bus to the NIS from the communications module per second RoviSys Company Copyright 1999 2015 Page 128 OPC90 Server User Manual V8 2 1 NIS TX MSG VT l4 Read Total number of messages transferred on the expander bus to the NIS from the communications module per second MB RX BYTE Total number of bytes received from the module bus per second includes bytes of messages received and replies received MB RX MSG Total number of messages received from module bus per second MB TX BYTE Total number of bytes sent to module bus per second includes bytes of messages sent and replies sent MB TX MSG VT l4 Read Total number of messages sent to module bus per second Notes 5 By writing to these tags the OPC client can set the PCU node address to be monitored Use the INTERVAL tag to set how often the communication statistics are read OPC90 will enforce valid ranges for these tags but it is the client s responsibility to write valid addresses of PCU nodes that actually exist The INTERVAL tag specifies how often the node communication statistics are attempted to be read The minimum value it can be set to is 100 milliseconds The recommended interval setting is no less than the total number of PCUMON blocks times 10000 Setting the INTERVAL to zero disables reading of the PCU node communication statistics Up to 19 different statist
232. not live information it s being simulated and is of a test nature The indicate server running when simulation enabled option can be set to request OPC STATUS RUNNING to be returned when simulation is enabled Logged messages include the time of the log millisecond resolution along with the OPC client number or name if the OPC client sets its name for which the error occurred In addition to OPC errors successful read and write OPC operations enabled in the first category of logs previously mentioned can be included in the log This is useful for constructing sequence of events between normal operation and when errors occur Finally the ability to include OPC function tracing can be enabled for all or specific functions supported by OPC90 OPC function tracing can be used to log the time when a function is called and the time when it returns to the OPC client This is a useful feature when trying to track down problems related to DCOM and network communication OPC90 includes logic that can attempt to detect dead OPC clients If an OPC client faults during operation it obviously can t perform a graceful disconnect from OPC90 wasting memory resources The dead OPC client monitoring section can be used to enable two types of dead OPC client detection logic The first is faults that occur when OPC90 tries to send OnDataChange messages to the dead OPC client Error responses to these updates are an indicator that the OPC client has faulted
233. nts Description OPERATION RESET or 1 or CONFIGURE or 2 or Changes a Bailey controller mode EXECUTE or 3 or INITIALIZE or 4 of operation lt RING gt NODE MODULE SAVE FILE NAME RING NODE Saves a Bailey controller MODULE configuration to a file LOAD FILE NAME RING NODE Restores a Bailey controller lt MODULE gt configuration from a file CANCEL none Cancels the currently active command READ lt BLOCK gt lt RING gt lt NODE gt Reads a function block configured lt MODULE gt in a Bailey controller GET lt FUNCTION_CODE gt lt BLOCK gt Gets the default specifications for a lt RING gt lt NODE gt lt MODULE gt Bailey controller function code WRITE lt START_BLOCK gt Writes a function block to a Bailey RoviSys Company Copyright 1999 2015 Page 54 OPC90 Server User Manual V8 2 1 NUMBER BLOCKS controller BLOCK INCREMENT RING NODE MODULE SX INCREMENT MODIFY START BLOCK Modifies an existing function block NUMBER BLOCKS within a Bailey controller BLOCK INCREMENT RING NODE MODULE SX INCREMENT DELETE START BLOCK END BLOCK Deletes one or more blocks within RING NODE MODULE a Bailey controller The command syntax is simple The commands and arguments are case insensitive Each argument must be separated by one or more spaces not commas Note that the characters are not par
234. ny function code supported by a given Bailey module Note that for some older Bailey modules the get request must include a block number value that is consistent with the function code number For example with a Bailey COM module specifying function code 21 for block O will return an error because configuring function code 21 at block 0 is illegal More current modules will return the default data even if the function code could not be configured at the indicated block number Following are some example get commands Command Action GET Get default specifications for currently addressed function code block and address GET 80 Get default specifications for function code 80 for current address GET 30 1 32 30 Get default specifications for function code 30 for ring 1 node 32 module 30 Write Command Use this command to write a new function block to a Bailey module Remember the module must first be in configure mode before a new block can be written The steps involved when writing a new function block is to first define it and then write it First define it by using the READ command to read an existing function block of the same type or using the GET command to read the default settings for the desired function block type Next change the specification settings by writing to the S01 VALUE through S63 VALUE tags After the specifications have been changed to the desired values enter this command Following are some exampl
235. o there is a Device block parameter called Max GMI per second per PCU node that can be configured to automatically limit GMI message generation for all PCU nodes being communicated with The OPC90 throttle only affects GMI activity All other OPC90 functionality such as reading and writing exception reports sending supervisory control commands and exchanging data with OPC clients is not affected See application section following the block notes for details on using this block s faceplate and setting up the throttle level settings Cautions Only use this block after thoroughly understanding its functionality Pay attention to its effect on the PCU node and OPC90 when enabling the throttling capability Be careful with the INTERVAL setting especially when multiple PCUMON blocks are configured After completing an analysis of a nodes performance set INTERVAL to a higher value or zero to disable data collection if it is currently not needed This block uses polling to get the data which means it does use a portion of the available polling bandwidth between OPC90 and the ABB Bailey CIU device Restrictions This OPC90 block is valid for INFI 90 Harmony and Symphony systems The PCU node to be monitored must have INNPMO 1 firmware revision C 1 or later Note that the OPC90 MODSTAT block can be used to determine the firmware revision level of the INNPMO if it is not known All INNPM22 firmware revisions are supported for PCU nodes so equipped
236. ocess started by a OPC client or the user The run time state run stopped is also displayed 5 4 3 View Start In Runtime Select Start In Runtime to enable or disable the mode of operation in which OPC90 automatically starts its communication logic when the program is first executed This occurs regardless of whether or not any OPC clients are attached to it Start in runtime is useful when OPC90 is executed automatically as part of a login startup group It causes the database to be established with the Bailey interface and be made ready for access prior to any OPC client attaching to OPC90 It is most useful for large databases that could take minutes to complete the Bailey interface startup logic Note that if startup in runtime is enabled and monitor mode enabled and than disabled when there are no outstanding OPC clients attached to OPC90 the runtime mode of operation is stopped The program status bar indicates the state of runtime It indicates Run when currently enabled and Stop when not currently active 5 4 4 View Run As Service Select Run As Service to enable or disable OPC90 as a Windows service A dialog will be displayed confirming whether or not the service should be installed or deleted Running as a service is recommended for Windows 2000 XP 2003 Server VISTA 7 2008 2012 Server systems When run as a service is enabled it is initially setup to run from the system account This setting is valid when OPC90
237. ode to use when establishing this point see note 2 ZERO VT R4 Config Read Zero of SP value in engineering units SPAN VT R4 Config Read Span of SP value in engineering units SIG CHANGE VT R4 Config Read Amount that SP must change cycle to cycle before it will be reported to Bailey Expressed as a percentage of the SPAN MAX TIME VT I4 Config Read If SP never changes significantly it will be reported at the maximum time interval seconds defined by this attribute MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor OPC STATUS OPC status value see OPC status section QUALITY Current quality see note 3 of Bailey values 0 good 1 bad SP Set point SP TRACKING VT BOOL Read Write Indicates set point tracking when set 1 Make sure the block number attribute is unique with respect to the other AOL DOL ODD OROM ORMC ORMSC and OSTN OPC90 blocks associated with the same OPC90 DEVICE block The block number attribute must also be defined within the range of 1 to maximum number of allowed outputs set up within the associated OPC90 DEVICE block The Bailey system will receive data from this block at the ring and node address of the Bailey CIU interface module two and block number defined by the block attribute 2 The engineering units code is a
238. omplished via poll messages directed at the node These messages are not as time consuming as poll messages directed to controllers within the PCU node but do consume CIU communication bandwidth and a minimal amount of node bandwidth Therefore it is recommended that the INTERVAL tag and ENABLE tags settings be used judiciously to minimize the impact of this block s data collection on CIU and PCU node communication performance This is especially important when configuring multiple blocks of this type and using database shadowed OPC90 installations When specifically diagnosing a particular node turn on the ENABLE flags of importance to the diagnosis and reduce the INTERVAL setting to see timely updates of the statistical data for diagnosing performance After completion of the diagnoses turn the unneeded ENABLE _ flags off or increase the INTERVAL tag setting back to its original setting All nodes in the system share a node map with each other that defines the topology of the communication loop Therefore when the NISMON block is only being used to read the topology and the other data it returns is not required configuration of only one block per loop is necessary The reason for this is the topology is shared between all nodes on the loop so regardless of what node it is requested from it will be the same The TOPOLOGY tag returns a string defining the topology of the currently addressed loop ring The ENABLE MAP tag must be set to receive the
239. ondition A problem exists with ABB Bailey backup controllers or nodes going offline when many writes to RMSC blocks occur The solution is to limit the number of writes to RMSC blocks to one per second A common mistake is to use RMSC blocks to exchange values generated by OPC clients and ABB Bailey controllers This solution is wrong and bypasses the exception report mechanisms that are built into the ABB DCS The correction implementation is to use OPC90 AOL and DOL blocks linked to ABB Bailey Al I FC 121 and DI I FC 122 blocks 12 16 Last Saved Database Not Automatically Restored On Program Start 1 Verify the last database was saved before exiting OPC90 Run OPC90 select the database and select File gt Save Exit the program and run it again to verify the database is automatically restored 2 Make sure the user account OPC90 is running in includes the power user group This is especially critical when running under Microsoft Windows Server 12 17 Data Updates Stop After 2 Hours The demo version of OPC90 will only provide data updates for 2 hours each time it is started If the demo version is being utilized contact RoviSys to purchase a licensed copy of OPC90 If a licensed copy of OPC90 is installed and the data updates stop after 2 hours the problem is the hardware protection key dongle is not being recognized Make sure a device block has been configured OPC90 does not look for its key if no device blocks are configured in
240. ood state two logic state descriptor GSLSD3 Good state three logic state descriptor MY_BLOCK_TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor FACE_TYPE Faceplate type MSDD S18 OPC STATUS OPC status value see OPC status section QUALITY VT BOOL Read Current quality of Bailey values 0 good 1 bad DISC ACT Alarm active indicator OUT VT pee EE Discrete output value of Bailey MSDD first EON output signal MODE ia 12 Read Write The mode of the Bailey block MODE can be 0 Manual 1 Auto RED CMD VT BSTR Red tag command see red tag users section RED TAG Red tag indicator 0 no 1 yes RED USERS Red tag users current user names or codes F1 State of feedback number 1 Fi TEXT State of feedback number 1 as a string F2 State of feedback number 2 F2 TEXT State of feedback number 2 as a string F3 State of feedback number 3 F3 TEXT State of feedback number 3 as a string F4 State of feedback number 4 FA TEXT VT BSTHR Read State of feedback number 4 as a string RoviSys Company Copyright 1999 2015 Page 97 OPC90 Server User Manual V8 2 1 GOOD STATE VT l4 Read Good state see note 1 GS TEXT VT BSTR Good state as a string REQ STATE VT I4 Read Write Requested state see note 1 RS TEXT VT BSTR Read W
241. opyright 1999 2015 Page 75 OPC90 Server User Manual V8 2 1 GROUP WRITES DEBUG LOG LOG DAYS MY BLOCK TYPE MESSAGE POINT TOTAL ALL STATUS PRI STATUS SEC STATUS ONLINE DATA READY Boolean Config Array 14 Md database The OPC tag database gets updated when the Bailey exception report is received confirming the write was received and accepted This option may be useful when implementing OPC client supervisory control ramping functions Also some Bailey block logic could have supervisory control locks in place These locks prevent the block from completing the request but no exception report is generated indicating the request was rejected When set output exception reports generated from AOL DOL ODD OMSDD ORCM ORMC ORMSC and OSTN blocks will be written using the output group commands Up to fifty values per command can be written OPC90 automatically determines the group size based on current loads and output block updates This setting optimizes output exception reporting and should be used when large numbers of output bocks are configured When this option is not set each value is sent with individual commands The rate at which outputting occurs is also configurable See the OUT XRP UPDATE setting Selected by right clicking on the DEVICE block Enables various logging features that may be useful for diagnosing driver operational performance When any of the logging features are enabl
242. ount values are used to compute the number of values per message Those values are then used to compute what percentage of total possible values per message that represents A percentage packing rate of 100 would indicate the communication system is running at the busiest it can possibly be Lower percentages indicate it has plenty of message capacity available The design of the communication loop is as it gets busy and a message containing exception reports is waiting to get sent the number of values per packet increases This results in more values per message to be exchanged When the communication loop is not very busy fewer values per packet are sent since there is communication loop idle space available when it is time for them to get sent This means smaller packing percentages indicate the loop is not very busy whereas higher factors mean it is Application This block s faceplate is very useful for observing the node diagnostic information and determining faults The faceplate can be viewed by right clicking on the block while in monitor mode and selecting faceplate It appears as follows NIS 1 1 1 Monitoring NIS at Ring 1 Node 1 Wed May 21 15 40 55 2014 Data Collection ms Firmware E6 Resettable NIS Event and Error Counters 1000 Counters amp Statistics sw1 f 0x01 M 13 Days 21 11 21 291 since last reset or rollover 10000 Topology Sw2 0x01 Events Errors i lods T 0067267587 Total messages transmitted total loop traffic 0
243. owed CIU ring address of the Bailey interface v 14 NE Shadowed CIU node address of the Bailey NE eres VT E Read Text message indicating the shadowed ABB Bailey interface type i e INICIOS CICO1 etc and firmware revision Shadow CIU online state 0 No 1 Yes VT BOOL Read Write Set this tag to request the DCS to be time synced to the current PC clock time see note 2 VT I4 Ring address of current time sync master see note 2 VT l4 Read Node address of current time sync master see note 2 CSV file to import see note 3 CSV file import control flag see note 3 Result of CSV import request see note 3 Total active blocks in the turbo poll database Total blocks in the turbo poll database VT l4 Read Total active turbo polled blocks that are stale Notes 1 The DEVICE Definition block is designed to support communication on one or two RS232 ports to a RoviSys Company Copyright 1999 2015 single Bailey interface or two RS232 or SCSI ports to redundant Bailey interfaces The first redundant scheme is single interface redundant channel This scheme provides two RS232 communication paths to a single Bailey interface All Bailey interfaces except SPM CPM CIC CIUO1 INPCIO1 and INICIO3 have two RS232 ports available for communication The second port is switch selectable between a utility port and computer communication port Setting it to a computer communication port allows it to be used for the sing
244. ows the OPC client to indicate the device is currently under a red tag condition This block supports mode When in auto mode logic controls the state of the OUT tag therefore operator commands are ignored In manual mode the operator writes the requested state of OUT OPC90 will receive the write request from the Bailey system and transfer this request to the OPC client by writing the new requested state to the OUT tag When a state change occurs the OPC client must update the feedback tags F1 and F2 to reflect successful arrival of the device at the requested state If feedback cannot be confirmed the OPC client must set the ALARM tag Likewise the OPC client must reset the ALARM flag when a new device state transition is requested and only set it again if feedback cannot be confirmed The Bailey implementation of the DD block defines the required states of the feedback signals for the device off and on condition and has a feedback wait time This is the amount of time to wait for feedback confirmation for the commanded state Therefore a delay in the setting of the ALARM tag by the OPC client when feedback is not confirmed is acceptable The OPC client must also set the ALARM tag if good feedback for the current state is lost sometime after it had been confirmed The FB STATUS tag gives an immediate indication as to whether the current state of the feedback signals matches the device state indicated by OUT The FB STATUS tag is similar to the ALA
245. pace or bandwidth within the Bailey interface TAGNAME TYPE ACCESS DESCRIPTION BOOL Boolean VT BOOL 0 false not zero true BSTR String VT BSTR E Signed I1 VT I1 128 to 127 12 Signed 12 VT_12 32 768 to 32 767 l4 Signed I4 VT 4 2 147 483 648 to 2 147 483 647 UH Unsigned 11 VT_UI 0 to 255 Ul2 Unsigned I2 VT UI2 0 to 65 535 Ul4 Unsigned 14 VT UI4 0 to 4 294 967 295 R4 Real 4 VT R4 R8 Real 8 VT R8 MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor TIMER Running timer in units setup by TIMER CTRL TIMER CTRL VT UM Read Write Timer control 0 secs 1 mins 2 hours 3 ELA aaa days 4 auto reset 8 down timer TIMER ALARM Timer alarm indicator true timed out TIMER LIMIT Timer limit SWAP Swaps state between true false SWAP TIME VT R8 Read Write Time between each state swap seconds RoviSys Company Copyright 1999 2015 Page 67 OPC90 Server User Manual V8 2 1 7 7 Device Driver DD The DD OPC90 block is used to retrieve and control the exception reported output from Bailey Device Driver blocks function code 123 Restrictions This OPC90 block can be utilized with all Bailey interface types except serial port module SPM amp CPMO2 TAGNAME TYPE ACCESS DESCRIPTIO
246. pect to the other AOL DOL ODD OROM ORMC ORMSC and OSTN OPC90 blocks associated with the same OPC90 DEVICE block The block number attribute must also be defined within the range of 1 to maximum number of allowed outputs set up within the associated OPC90 DEVICE block The Bailey system will receive data from this block at the ring and node address of the Bailey CIU interface module two and block number defined by the block attribute 2 The RCM type code is a number used by the Bailey consoles to identify characteristics of its RCM faceplate display Valid codes can be the sum of 1 Output value not displayed 2 Feedback signal to be displayed RoviSys Company Copyright 1999 2015 Page 117 OPC90 Server User Manual V8 2 1 3 When the Device block Set bad quality of max exception timeout property is enabled the QUALITY tag of this block will be set bad if writes to the block input s do not occur within the Exception Report Output Max Time setting of the block When this occurs bad quality will also be written to the CIU and therefore propagated to the users of the block data within the ABB Bailey system The quality can also be set bad by writing a one 1 to this tag 4 SET PERM will default to a value of set The OPC client can disable the ability of Bailey consoles to set the OUT tag by resetting the value of SET PERM Application The OUT tag reports the state of the device as off 0 or on 1 The RED TAG tag allows
247. porting off or on Write TRUE 1 to it to turn exception reporting off Write FALSE 0 to it to enable exception reporting When exception reporting is off and TRUE 1 is written to this attribute an exception report force command will be sent This message causes the block to exception report once but still leave exception reporting off RoviSys Company Copyright 1999 2015 Page 66 OPC90 Server User Manual V8 2 1 7 6 s Data Block DATA The purpose of the OPC90 DATA block is to enable OPC clients to communicate information with each other through values they read write to the various tags supported by this block The DATA block supports VT BOOL VT 11 VT I2 VT I4 VT Ult VT UI2 VT Ul4 VT R4 VT R8 and VT BSTR tag values It also includes a general purpose high resolution timer function and Boolean swap state timer function The high resolution timer units can be setup for seconds minutes hours or days It can also be setup as an up or down timer that automatically restarts or must be manually restarted The Boolean swap state timer flops its value between true and false at the specified period seconds All of these timer functions are controllable from OPC client accessible OPC tags Whenever the database is saved the current OPC client timer settings are included in the saved data and will be restored when OPCO90 is restarted Restrictions This OPC90 block counts against the total block license but does not consume any s
248. previously created The OPC90 convention is to open databases stored in the subdirectory called CFG configuration files A different database cannot be opened while OPC clients are attached and OPC90 is in runtime mode Stop the OPC clients and take OPC90 out of runtime mode by enabling and then disabling monitor mode If OPC clients can t be stopped use the View Lockout OPC Access menu item to temporarily prevent their attachments 5 1 3 Save Select Save to save the currently opened database The OPC90 convention is to save the database in the subdirectory called CFG configuration files The last saved database becomes the OPC90 working database that is automatically restored when the program is opened by the user or another OPC client Therefore it is important to save a newly created database to set it as the working database OPC90 configurations can be saved using any file name and extension The general accepted naming convention adopted by RoviSys is to use a file extension of CFG to denote its a configuration file As just mentioned a subdirectory is generated by the OPC90 install set named CFG as the intended place to save OPC90 configurations 5 1 4 Save As Select Save As to save the database under a new name This newly named database will become the working database the next time the user or OPC client starts OPC90 RoviSys Company Copyright 1999 2015 Page 14 OPC90 Server User Manual V8 2 1 5 1 5 Auto Sav
249. ption reports generated by this block can be received by a Bailey console analog tag Bailey Analog Input Loop blocks function code 26 and Analog Input Infinet blocks function code 121 The OPC90 AOL block will automatically generate the appropriate quality and alarming status based on the value presented at the block input Restrictions This OPC block can be utilized with all Bailey interface types except serial port module SPM CPMO2 amp CPMO3 and computer interface command series CIC TAGNAME TYPE ACCESS DESCRIPTION ADDR RING VT l2 Config Read Bailey CIU ring address ADDR NODE VT l2 Config Read Bailey CIU node address ADDR MODULE VT I2 Config Read Bailey CIU module address ADDR BLOCK VT I2 Config Read Block number to establish this point at within the Bailey interface see note 1 MY BLOCK TYPE VT BSTR Indicates the OPC90 block type INIT VALUE VT R4 Config Read Initial startup value ZERO VT R4 Config Read Zero of IN OUT value in engineering units code SPAN VT R4 Config Read Span of IN OUT value in engineering units code SIG CHANGE VT R4 Config Read Amount that IN must change cycle to cycle before it will be reported to Bailey Expressed as a percentage of the SPAN EU VT l2 Config Read Bailey engineering units code to use when establishing this point MAX TIME VT l4 Config Read If IN never changes significantly it will be reported at the maximum time interval seconds defined
250. r configuration and thus cannot be changed by OPC Clients Each time the Bailey block data is polled the specification values returned are copied to the S01 VALUE through S63 VALUE tags Specification text description data is returned in the corresponding S01 to S63 tags Restrictions None this OPC90 block can be utilized with all Bailey interface types TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address Read Write ADDR NODE Bailey node address Read Write ADDR MODULE Bailey module address Read Write ADDR BLOCK Bailey block address Read Write MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor OPC STATUS OPC status value see OPC status section QUALITY Current quality of Bailey values 0 good 1 bad ACKNAK Result of the last block read A non zero code indicates an error has occurred FC Function code returned for the block FCNAME Function code name returned for the block SX COUNT Number of valid specifications for block SPEC FORMAT VT I2 Determines how specification data is to be formatted see note 1 S01 to S63 VT BSTR Read Text description data for specifications 1 through 63 S01 STRING to Value for specifications 1 through 63 S63 STRING represented as a string S01 TYPE to Type for specifications 1 through 63 see note
251. r the requested new state Therefore a delay in the setting the ALARM tag by the OPC client when feedback is not confirmed is acceptable The OPC client must also set the ALARM tag if good feedback for the current state is lost sometime after it had been confirmed The Bailey MSDD block includes a feature that allows a block input to cause a control override condition This condition overrides operator control transferring control to logic even when the mode is manual Options are available in the MSDD to also transfer the mode to auto when the override control input sets The OPC client must indicate the override condition by setting the OVR CONTROL tag The Bailey MSDD block logic includes another condition in which feedback status is essentially ignored and always considered good regardless of its actual state in comparison to the OUT tag The OPC client indicates this condition by setting the OVR STATUS tag RoviSys Company Copyright 1999 2015 Page 116 OPC90 Server User Manual V8 2 1 7 21 Output Remote Control Memory ORCM The ORCM OPC90 block interfaces with Bailey consoles as a Remote Control Memory block function code 62 Note that this block does not received data from a RCM block running in a Bailey controller Use the OPC90 RCM block for that purpose The OROM is used to indicate on off control of a simple discrete device with a single feedback signal Restrictions This OPC block can be utilized with all Bailey interfac
252. ram Files x86 OPC90 Server CFG Run OPC90 and open the database file File Open Set OPC90 to Startup in Runtime View Startup In Runtime Set OPC90 to run as a service View Run as Service Use the Windows service manager OPC90 automatically will start this up for you and set the Log On tab of the OPC90 Server services to run from a privileged account o This step may not be required if the OPC client and OPC90 are all running on this same o Find OPC90 Server service in Windows service manager window right click on it and select Log On tab Using Windows Explorer find and double click on C Program Files x86 OPC90 Server OPC90_INI_ADD_MAPPING REG and answer yes to allow registry update Run Control Panel Administrative Tools Local Security Policy Security Settings Local Policies Security Options o Network access Let Everyone permissions apply to anonymous user must be Enabled o Network access Sharing and security model for local accounts must be set to Classic local users authenticate as themselves Run Control Panel Administrative Tools Component Services Computers My Computer right click on My Computer and select properties o Select COM Security Tab Under Access Permissions click on Edit Default button o Add these users Everyone ANONYMOUS LOGON INTERACTIVE o Select COM Security Tab Under Access Permissions click on Edit Limits button not all operating systems
253. ration principles and are aware of the current plant operating conditions before using some features of this faceplate The faceplate contains three major sections The boxes with white background indicate possible user input areas based on a particular configuration activity The first section is Addressing This section is used to specify the address of an ABB Bailey module to be configured The example shows configuration data for a Station Function Code 80 read from Ring 1 Node 1 Module 3 and Block 800 The second section is Specification Data This section displays the current specification values and associated descriptions Tunable specifications are indicated with a T following the specification number Also notice the description includes the current specification value This is useful when tuning or modifying an existing function block As a new specification value is typed the current value is still visible as part of the description Pressing the Enter key will abandon entry of a specification value and reset it back to its original value Otherwise it will be updated to the new value after the tune or block write is requested This section can display up to 16 specifications at a time For function blocks with more than sixteen specifications click on the forward and backward not shown in example arrow buttons to scroll to the next set of sixteen block specifications RoviSys Company Copyright 1999 2015 Page
254. ress ADDR MODULE Bailey module address ADDR BLOCK Bailey block address MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor OPC STATUS OPC status value see OPC status section QUALITY Current quality of Bailey values 0 good 1 bad OUT Current output value from Bailey SPAN Span in Engineering Units ZERO Zero in Engineering Units EU Engineering Units Code EU_TEXT VI BSTR Engineering Units String HI LIM The setting for the alarm limit used to detect the high alarm condition Writing a new value to this attribute automatically tunes the alarm limit of the associated Bailey block LO LIM VT R4 Read Write The setting for the alarm limit used to detect the low alarm condition Writing a new value to this attribute automatically tunes the alarm limit of the associated Bailey block HI ACT High alarm active indicator LO ACT VT BOOL Read Low alarm active indicator RoviSys Company Copyright 1999 2015 Page 46 OPC90 Server User Manual V8 2 1 7 2 amp Analog Output Loop AOL The AOL OPC90 block is used to send an exception reported output generated by updates to the block input tag IN Note that this block does not received data from an AOL block FC 30 running in a Bailey controller Use the OPC90 AIL block for that purpose The exce
255. ring and security model for local mR Local Security Setting Network access Sharing and security model for local accounts Classic local users authenticate as themselves OK Cancel Double click on Network access Let Everyone permissions apply to anonymous users and set it to Enabled as shown by following dialog RoviSys Company Copyright 1999 2015 Page 167 OPC90 Server User Manual V8 2 1 Network access Let Everyone permi AE Local Security Setting Explain This Setting Network access Let Everyone permissions apply to anonymous users Enabled Disabled Setup of DCOM on the remote PC is complete If the OPC client cannot access OPC90 after completing this setup try rebooting the OPC client PC Depending on the types of changes made to My Computer DCOM settings a reboot of the PC may be required 10 3 Validating OPC Client Access of OPC90 When one or more OPC clients are started and they have requested a connection with OPC90 a single instance of the program can be observed using the Processes tab of Windows Task Manager shown by the following dialog RoviSys Company Copyright 1999 2015 Page 168 OPC90 Server User Manual V8 2 1 Windows Task Manager File Options View Help Applications Processes Performance Networking Image Name PID User Name CPU Time MemUsage Peak Mem U sapisvr exe 3604 0 00 00 312K OPC90Server exe el msdtc exe METWORK SER
256. rite Requested state as a string see note 2 TRAVEL VT BOOL Travel indicator see note 3 OVR CONTROL VT BOOL Override control indicator OVR STATUS VT BOOL Override status indicator DEFAULT MASK _ VT I2 Default state output mask MSDD 7 OUT MASK1 VT I2 State 1 output mask MSDD S8 OUT MASK 2 VT I2 State 2 output mask MSDD S9 OUT MASK3 VT I2 State 3 output mask MSDD S10 FB MASK1 VT I2 Read Write Feedback mask for state 1 MSDD S11 FB_MASK2 VT I2 Read Write Feedback mask for state 2 MSDD S12 FB MASK3 VT I2 Read Write Feedback mask for state 3 MSDD S13 NEXT1 VT I2 Read Write Next allowable state s from state 1 MSDD 19 NEXT2 VT I2 Read Write Next allowable state s from state 2 MSDD S20 NEXT3 VT I2 Read Write Next allowable state s from state 3 MSDD 21 FB_WAIT VT_R4 Read Write Feedback waiting time in seconds MSDD S16 FAULT WAIT VT_R4 Read Write Fault waiting time in seconds MSDD S17 PULSE_WAIT VT_R4 Read Write Length of pulsed outputs in seconds MSDD S22 MAN_PERMIT VT IH Read Write Manual mode permit flag 1 yes MSDD 15 OVERRIDES VT_l2 Read Write Current status and control override definitions MSDD S14 Notes 1 RoviSys Company Copyright 1999 2015 The GOOD STATE and REQ STATE requested state attributes are used to view current operating state of the block and command its requested state Valid values are zero default one
257. rk 90 systems that have 1400 tag OIUs present on the ABB Bailey Plant Loop The SYNC DCS SYNC RING and SYNC NODE tags are only updated when one of the following time sync options are enabled When they are setting the SYNC DCS tag can be used to force the DCS to be time synced to the PC clock time This also automatically occurs when the PC clock is changed by more than 2 minutes a To enable time syncing the ABB Bailey system type must first be specified Choices are Infi 90 and Network 90 When the system type is Network 90 the system node map must also be configured This node map defines the addresses and type of nodes present on the ABB Bailey Plant Loop Failure to completing and accurately configure the node map could result in malfunction of the time syncing feature Note that it is not necessary to configure the node map when the system type is Infi 90 Also note that the Infi 90 system type should be specified when the interface is a NCICO1 iz Two time syncing options are available The first is PC Get amp Set Bailey System Time This option enables OPC90 to both set the ABB Bailey DCS time to match the PC time and also set the PC time to match the current DCS time When OPC90 starts up with this option set it determines if another ABB Bailey node is currently considered the time sync master If another master exists OPC90 sets the PC time equal to the current DCS time When it is determined that no node is currently the time sync
258. rograms or C programs with any associated data files are not included in the load Contact RoviSys if your needs include loading of programs Any file name can be specified If the file name includes spaces it must be enclosed in double quotes If the file name is excluded OPC90 will automatically load a file name based on the current address specified in the ADDR RING ADDR NODE and ADDR MODULE tags For example assume these tags are currently set to the corresponding values of 1 4 and 5 The file name that will be loaded is 00100405 C90 or 10405 CFG OPC90 can load the configuration from one of two file formats The FILE TYPE tag selects the file format to utilize When FILE TYPE is reset 0 OPC90 will load Bailey function block configuration data from files that have a C90 extension This is the OPC90 file format When the file name is included in the command OPC90 will automatically append the C90 extension if it is missing Including the C90 extension in the file name will override the current FILE TYPE tag setting The C90 files are loaded from the ABB subdirectory unless an alternative directory path is included as part of the file name When FILE TYPE is set 1 OPC90 will load the Bailey function block configuration data from files that have the CFG extension These files are of the format generated by the ABB Bailey CADEWS software and its derivatives When the file name is included in the command OPC90 will automatic
259. rt TCP 8P IP addresshere Port TCP 85 TP address here Port TN As can be seen by this dialog OPC90 supports definition of up to 16 predefined TCP names Definition of each name needs the TCP address of the Ethernet to Serial device and port number to attach with on that device The intention of the TCP_xP and TCP xS names indicate primary and secondary ports These are useful when using the DEVICE block redundant interface and dual interface communication scheme Any TCP name can be used with any DEVICE block port The important thing is to pick one that corresponds with the correct TCP address The naming convention of using the P and S is only for organization purpose It is important to realize that OPC90 will setup a socket connection to the Ethernet to Serial device using the addressing information associated with the chosen TCP name The software provided with the Ethernet to Serial device must be utilized to define what baud rate should be used for the serial connection with the CIU In the case of Lantronix Ethernet to Serial devices this software is called the Devicelnstaller Its web interface tab can be used to set the default baud rate and other settings i e stop bits parity etc to match the CIU settings 5 3 4 Engineering Units Select Edit gt Engineering Units to defined Bailey engineering unit code to engineering string mapping The various analog values received from the Bailey system are already
260. rted as Not defined in registry entry F1 130 or Not defined in registry F131 255 This can usually be corrected by logging into an administrator account and then from Explorer double click on the file called DPC90 INI ADD MAPPING REG RoviSys Company Copyright 1999 2015 Page 183 OPC90 Server User Manual V8 2 1 found in the C Program Files x86 OPC90 Server directory Answer yes to the inquiry to allow addition to the registry After the registry update is completed restart the computer 12 23 CIU Red Lights with LEDs 1 4 5 and 6 On When the CIU red lights with LEDs 1 4 5 and 6 on this means it was commanded to go online but discovered another node at the same address as itself so it cannot continue to operate This condition does not indicate a faulty CIU Recheck the CIU switch settings to make sure they are setup for a unique address within the ABB Bailey system Note when using redundant OPC90 installations that will be sourcing values to the ABB Bailey system using OPC90 AOL DOL ODD OMSDD ORCM ORMC ORMSC and OSTN blocks same address CIUs may be desirable and intentionally setup this way Same address CIUs are supported by OPC90 and utilizes the configuration shadowing feature to share critical CIU information and operational states between the redundant OPC90 servers Therefore configuration shadowing must be enabled on both OPC90 servers and reported as Good in each OPC90 program status bottom of program
261. s Edit Default Click on Edit Default for both the Access Permissions and Launch and Activation Permissions and add the following list of users Make sure allow access for both local and remote is enabled for all of these users For Windows XP SP2 and Windows RoviSys Company Copyright 1999 2015 Page 163 OPC90 Server User Manual V8 2 1 2003 also check Edit Limits options for both the Access Permissions and Launch and Activation Permissions and make sure that these accounts are also added ANONYMOUS LOGON Everyone INTERACTIVE NETWORK NETWORK SERVICES Self SYSTEM Distributed com users These users are not supported on earlier Windows operating systems There are two local security options policies that need to be setup Run Control Panel Administrative Tools Local Security Policy and select Security Options as displayed by the following Local Security Settings File Action View Help x gle E BA Security Settings 49 Account Policies 2 Local Policies GQ Audit Policy 39 User Rights Assignment Security Options 4 Public Key Policies E Software Restriction Policies E 3 IP Security Policies on Local Computer Policy Security Setting RE Network access Do not allow storage of credentials or NET Pa RE Network access Let Everyone permissions apply to anonymous RE Network access Named Pipes that can be accessed anonymously 8 Network access Remot
262. s viewable by notepad and are found in the C Program Files OPC90 Server og directory The log file name begins with OPC90 Error Detection followed by the time and date the log was generated The file name OPC90 Error Detection Log Sun Jan 09 17 27 03 2011 log is an example of this log type Select Edit Error Detection to configuration the error detection log options These settings are retained in the Windows registry so saving the database is not necessary When this menu item is selected the following dialog is displayed RoviSys Company Copyright 1999 2015 Page 31 OPC90 Server User Manual V8 2 1 Error Detection Log Setup GetStatus Return Options V Log errors 10 Maximum log size megabytes Indicate fault when CIU bad Cancel Iv Include successful OPC read write data in error log Indicate server running when simulation enabled Default Dead Client Monitoring Iv OnDataChange Update Faults 10000 ms M Watch GetStatus Abandon Dead Client OPC Functions To Trace OPCServer AddGroup OPCGroup SetState OPCS erver GetErrorString OPCGroup GetState OPCServer GetGroupByName OPCGroup SetName OPCServer GetStatus OPCGroup CloneGroup OPCServer RemoveGroup OPCGroup MoveT oPublic OPCServer CreateGroupE numerator OPCGroup Read OPCServer UpdateClients OPCGroup Write OPCS erver QueryOrganization OPCGroup Refresh OPCServer ChangeBrowsePosition OPCGroup Cancel OPCServer BrowseOPCitemlDs OPCGroup Addltems
263. se Until the license activation code is received setup a couple day demo period 7 You have completed installation of OP C90 Server After installation on Windows 7 right click on the C Program Files OPC90 Server OPC90Server exe file select properties and set compatibility mode to Windows XP This will allow OPC90 to run as a service under Windows 7 and communicate with SCSI CIUs When upgrading first uninstall using Windows add remove programs and then run the above procedure If running OPC90 as a service make sure it is stopped before uninstalling Note that the demo version of OPC90 downloaded from the RoviSys website does not support software licensing It must be uninstalled and the official version installed from the CD to accomplish licensing of the OPC90 software RoviSys Company Copyright 1999 2015 Page 7 OPC90 Server User Manual V8 2 1 4 Bailey Communication Overview Bailey utilizes a communication technique for data exchange called exception reporting Exception reporting means the data is sent when it has changed significantly or a maximum time has expired since the last time it was sent All exception reported data is made available to the rest of the system via a set of exception report related function blocks which are matched by an equivalent OPC90 Server block Bailey has a series of RS232 serial based devices generically called Computer Interface Units that are utilized to receive this exception report data
264. se this option for heavily loaded Network 90 systems It only needs to be enabled when RoviSys Company Copyright 1999 2015 Page 72 OPC90 Server User Manual V8 2 1 a ENHANCED ANALOG Boolean Config PRECISION MSDD PULSE OUT Boolean HANDLING ACCURACY RATING BYTE STN FAST Update 32 Bit UINT Set KFAST on K tag Boolean Config writes Represent STN Boolean Mode As 0 5 Config Config Config PCUs are observed to toggle between the online and offline state when OPC90 Server is starting Utilize the interface exception report screening option This option helps increase throughput by instructing the interface to not report unchanged exception reports received from the sender as a result of its maximum exception report time limit expiring Enables analog data exchange with exception reported blocks using REAL4 representation instead of REAL3 REAL4 representation increases the accuracy of analog values to 7 digits REALS values have an accuracy of 5 digits Enabling this option is only valid for INFI90 Systems It is ignored when the detected system type is NETWORK 90 or Command Series This option adds an extra byte to each analog value exchanged with the CIU The result is a very slight reduction in the maximum number of exception reports that can be exchanged per second Most users should enable this option It has been made optional to maintain compatibility with existing OPC90 installations
265. selects the current file name for the captured SOE data NEXTFILE Flag used to sequence through the most recent to oldest SOE capture files NEXTREC Flag used to sequence through the records of the currently selected SOE capture file RECORD VT I4 Indicates selects a record 1 COUNT for the currently selected capture file POINT TYPE VT BSTR Read Point type Undefined Standard Summary ae Pre fault Post fault and Snap shot for current record of selected SOE file POINT NUM Point number 0 511 for current record of selected SOE file POINT NAME Point name for current record of selected SOE file POINT SCAN Point scan state 0 on scan 1 off scan for current record of selected SOE file POINT DATE Point capture date month day year for current record of selected SOE file POINT TIME Point capture time hour minute second millisecond for current record of selected SOE file POINT Q Point quality 0 good 1 bad for current record of selected SOE file POINT ALARM Point alarm state 0 no 1 yes for current record of selected SOE file POINT VALUE VT BOOL Read Point value 0 or 1 for current record of selected SOE file Application This block is used to monitor and retrieve sequence of events data from Bailey function code 99 and 243 blocks Bailey function code 99 blocks can be any block number within the controller block range On startup OPC90 reads the Bailey SOE block data to
266. set this attribute when the delete block request is completed OPC status value see OPC status section Current quality of Bailey values 0 good 1 bad Result of the last block configuration activity A non zero code indicates an error has occurred Function code number returned for the last block read Also can be written by OPC client when in the process of reading default function code specifications Function code name returned for the last block read or default specification read Number of valid specifications for last block Read Write Determines how specification description data is to be formatted see note 1 S01 to S63 Descriptions for specifications 1 through 63 S01 STRING to Value for specifications 1 through 63 S63 STRING represented as a string S01 TYPE to Type for specifications 1 through 63 see note S63 TYPE 2 S01 VALUE to VT R4 Read Write Value for specifications 1 through 63 S63 VALUE Notes 1 The format of how the specification data is returned can be selected utilizing the SPEC FORMAT attribute The following choices are available e 0 SxName Value e 1 Name Value RoviSys Company Copyright 1999 2015 Format includes spec number its name and current value Format includes spec name and its current value Page 50 OPC90 Server User Manual V8 2 1 e 2 SxName Format includes spec number and its name e 3 Name Format includes just the name of the spec 2 The specification
267. specification values in the SO1 VALUE through S63 VALUE tags and the specification descriptors in the S01 through S63 tags Completion of the read default request is signaled when the DEFAULT tag is reset to FALSE The MESSAGE tag will also return a text message indicating completion of the read default operation or the reason for failure if it cannot be completed When the ACKNAK tag is zero the request was successful non zero indicates an error occurred The fourth step is to change the appropriate specifications from their default values to values that are pertinent to the new block about to be written This is accomplished by writing to the S01 VALUE through S63 VALUE tags Note that these tags are always written as floating point values OPC90 will automatically take care of translating the values to the appropriate types required by the Bailey function block The fifth and last step is to request OPC90 to actually write the block to the Bailey controller This is accomplished when the WRITE tag is set TRUE The value of the S01 VALUE through S63 VALUE tags appropriate for the block function code are translated to the correct data types required for the Bailey function code and the block write occurs Completion of the write operation is flagged when the WRITE tag is reset to FALSE The MESSAGE tag will also return a text message indicating completion of the write operation or the reason for failure if the write cannot be completed When the ACKNAK tag
268. sume large amounts of disk file space After installing the OPC90 Server for the first time and thereafter when it is then started up in Monitor mode or when an OPC client connects to it the OPC90 Server DEVICE block will automatically begin talking with the Bailey interface The startup pattern will vary based on the type of Bailey interface being utilized The first thing you should notice is the Bailey interface serial processing card LEDs begin to sequence Shortly thereafter you may hear the loop interface termination unit relays click on and off several times as the driver is identifying the Bailey interface type Just prior to downloading the OPC90 Server block database to the Bailey interface it will be restarted and the loop interface termination unit relays will click off isolating it from the communication loop Next you should observe the Bailey interface serial processing card LEDs sequence at a steady rate as the OPC90 Server block database is being downloaded Upon completing the database download the Bailey interface will be commanded on line at which time the loop interface termination unit relays will click on and the loop interface card LEDs begin to count loop messages Thereafter the Bailey interface serial processing card LEDs will sequence steadily based on the exception report poll interval setup by in the DEVICE block and individual OPC90 Server POLL blocks when utilized If you experience problems with establishing commu
269. t 1999 2015 Page 134 OPC90 Server User Manual V8 2 1 7 27 Remote Control Memory RCM The RCM OPC90 block is used to retrieve and control the exception reported output from Bailey Remote Control Memory blocks function code 62 Restrictions This OPC90 block can be utilized with all Bailey interface types except serial port module SPM amp CPMO2 TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address ADDR NODE Bailey node address ADDR MODULE Bailey module address ADDR BLOCK Bailey block address F1LSDO Feedback 1 state zero logic state descriptor F1LSD1 Feedback 1 state one logic state descriptor OUTLSDO Output state zero logic state descriptor OUTLSD1 Output state one logic state descriptor MY_BLOCK_TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor FACE_TYPE Faceplate type value of RCM block S8 OPC STATUS OPC status value see OPC status section QUALITY VT BOOL Read Current quality of Bailey values 0 good 1 bad DISC ACT Alarm active indicator OUT Bailey RCM discrete output value see note 1 OUT TEXT VT me Mud mun RCM discrete output value as a string see note 2 SUSTAIN Erud I hif Sustained commands should be used 0 No 1 Yes command OUT with 0 and 1 2 Yes command OUT with 1 and 2 RESET INPUT VT_BOOL State of r
270. t Properties to edit the current definitions setup for the selected device group or block The appropriate properties dialog will be displayed based on whether the device group or block is the last selected database entity 5 3 9 Priority Select Edit gt Priority to edit the default process priority that OPC90 will run When this menu item is selected the following dialog is displayed Default OPC90 Process Priority C Realtime High C Normal As can be seen by this dialog available priority selections are Normal High and Realtime OPC90 switches itself to the new priority as soon as the selection is made It is not necessary to exit OPC90 and run it again for a new priority to be established Note that when running OPC90 as a service and a second instance is attached to that service only the priority of the service is changed The second program instance always remains at the Normal priority Installations having larger databases or OPC clients running at a higher priority than Normal might realize an increase in performance by raising the priority of OPC90 5 3 10 Configuration Shadowing Between Redundant Servers The configuration shadowing feature can be used to automatically keep the database and other program features synced between two different PCs running OPC90 as redundant servers It also manages CIU online states especially important when same addressed CIUs are setup for redundant OPC90 servers see
271. t of the above arguments They indicate the argument is optional If an optional argument is omitted the arguments following it cannot be included in the command The only exceptions to this rule are the WRITE and MODIFY commands The SX INCREMENT argument where X specification number and INCREMENT is the amount to add to the specification value for each new block addition can be added at the end of the command regardless of how many of the other optional arguments are omitted Multiple SX INCREMENT gt arguments per command are supported Note that the italicized commands are under password control WARNING execution of these commands can cause a plant trip or major outage to occur They require the correct password to be sent to the PASSWORD tag before the command can be executed When the OPC90 BLK is configured a case sensitive password is assigned to it Before OPC90 will accept protected command writes to the COMMAND tag the OPC client must first write the correct password to the PASSWORD tag The received or the received password is incorrect The PASSWORD tag returns the text when the correct password has been received For security it is highly recommended that once an OPC client has completed its use of the COMMAND tag it should lock it by sending an invalid password to the PASSWORD tag Note that OPC90 will automatically invalidate the PASSWORD tag after 60 minutes transpires with no OPC client write activity to the OPC90 BL
272. tarts over after 49 days It can also be reset by writing a zero to it which also resets the event and error counters associated with this section The purpose of some of the data in this section is obvious but others are hardware specific and have meaning to an ABB field service person The NISMON observing logic does monitor the error counters and will post information to its log if errors of concern are encountered The Node Performance Statistics section presents various types of message and byte rates the node is exchanging with the communication loop It also includes moving averages NISMON is calculating for the messages per second values being collected These moving averages are useful for trending systems and filter out normal momentary jumps in data rates The NISMON block uses the LOOP TX NODE TX and NODE RX message rates to calculate this nodes contribution of messages occurring on the communication loop The data is presented in terms of percent for messages it is receiving and transmitting The horizontal progress indicators provide a visual indication of these percentages The faceplate can display the real time percentages or the averaged data This is very useful in determining relative levels of node contribution to total communication loop traffic The Resettable Module Exception Report Statistics section presents information associated with receive and transmit of exception report messages This data is used to calculate the relati
273. te ADDR BLOCK 3k ADDR MODULE 3k ADDR_NODE ADDR_RING EU X EU TEXT 3 HL ACT 3 HL LIM LO_ACT LO_LIM 3 MESSAGE 3k MY BLOCK TYPE OPC STATUS OUT 3k QUALITY 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 1 1 3 30 SHORT SHORT SHORT SHORT SHORT STRING BOOLEAN FLOAT BOOLEAN FLOAT STRING STRING SHORT FLOAT BOOLEAN 0 3 3 1 1 U Off 86400 000000 0 000000 ONLINE AIL 192 120 000000 Good Block address Module address Node pcu address Ring loop address Engineering Units Code Engineering Units Text High Alarm Active Indicator High Alarm Limit Low Alarm Active Indicator Low Alarm Limit Block Status My block type OPC status value Current Output Value from Bailey Quality 0 Good 1 Bad 04 17 2012 08 55 07 514 04 17 2012 08 55 07 514 04 17 2012 08 55 07 514 04 17 2012 08 55 07 514 04 17 2012 08 56 53 373 04 17 2012 08 56 53 373 04 17 2012 08 58 59 187 04 17 2012 08 56 53 373 04 17 2012 08 58 59 187 04 17 2012 08 56 53 373 04 17 2012 08 55 07 514 04 17 2012 08 55 07 514 04 17 2012 08 58 59 187 04 17 2012 08 58 59 187 04 17 2012 08 58 59 187 E DIL point E HAI point E HAO point E HDI point E HDO point 4 MODSTAT point 8 MSDD point E RCM point RE RMC point E RMSC point STN point E TEXT point E TEXTSTR point E Misc E
274. tect the low alarm condition Writing to this value tunes the alarm limit of the associated Bailey block HI ACT VT BOOL High alarm active indicator LO ACT VT BOOL Low alarm active indicator OVHR ENABLE VT BOOL Read Write Override allowed 0 No 1 Yes OVR VALUE VT R4 Read Write Override value OVR_STATUS Value overridden 0 No 1 Yes STAT_INHIBT Status inhibit 0 No 1 Yes SUSPECT Value suspect 0 No 1 Yes DRIVEN LO Low overdriven value 0 No 1 Yes DRIVEN HI High overdriven value 0 No 1 Yes CONFIG ERR Configuration error exists 0 No 1 Yes READBACK Readback status 0 Good 1 Bad REFERENCE Reference status 0 Good 1 Bad CALIBRATION Calibration status 0 Good 1 Bad SIM ENABLE VT BOOL Read Write Simulation enable 0 No 1 Yes RoviSys Company Copyright 1999 2015 Page 91 OPC90 Server User Manual V8 2 1 SIM BLOCK VT 2 Read Simulation value block number 7 12 E Harmony Analog Output HAO The HAO OPC90 block is used to retrieve the exception reported output from Bailey Harmony Analog Output function code 223 blocks Restrictions This OPC block is only valid for Bailey interface types INICIO3 INICI12 and INICI13 TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address ADDR NODE Bailey node address ADDR MODULE Bailey module address ADDR BLOCK Bailey block address MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message
275. ted me forwarded and originated by this node per Second Average total number of messages transmitted forwarded and originated by this node per Second Total number of bytes received by destined for this node per second Total number of messages received by this node per second VT Ul4 Read Average total number of messages received by this node per second Total number of bytes sent originated by this node per second Total number of messages sent by this node per second Average total number of messages sent by this node per second VT Ul4 Read Total number of bytes transferred on the expander bus from NIS to the communications module per second VT Ul4 Read Total number of messages transferred on the expander bus from NIS to the communications module per second RoviSys Company Copyright 1999 2015 Page 107 OPC90 Server User Manual V8 2 1 AVG NIS RX MSG VT Ul4 Read Average total number of messages transferred on the expander bus from NIS to the communications module per second NIS TX BYTE VT Ul4 Read Total number of bytes transferred on the expander bus to the NIS from the communications module per second NIS TX MSG VT Ul4 Read Total number of messages transferred on the expander bus to the NIS from the communications module per second AVG NIS TX MSG VT Ul4 Read Average total number of messages transferred on the expander bus to the NIS from the communications module per second
276. terlock inputs are implied to the block operation but are not reported to the Bailey consoles The start permissive inputs are reported The OPC client indicates their state using the PERM1 and PERM2 tags When the device is commanded on without the interlocks or permissive inputs being set this is considered a bad start The OPC client indicates a bad start condition using the BAD START tag A bad start can also occur when the feedback signals do not set after the device has been commanded on and a feedback waiting time has expired The OPC client must also indicate this condition as a bad start using the BAD START tag The OPC client indicates the two feedback signals writing to the F1 and F2 tags If any interlock or feedback signals are lost after a successful start the device is considered to be in fault and de energized The OPC client indicates this condition by writing a zero to the OUT tag and setting the FAULT tag When either a bad start or fault condition occurs the OPC client must use the ERR CODE tag to indicate the reason for the condition Bailey predefines the error codes as indicated in the above note concerning the ERR CODE tag The Bailey implementation of the RMC block defines a hold condition that optionally applies when a bad start arises The choices are no hold hold bad start and error indicators until successful start or hold but reset bad start and error indicators on next stop or start request The OPC client indicates the ho
277. ters and connected devices are listed below El IDE CD ROM ATAPI 1 2 Dual channel PCI IDE Controller Rm IDE CD ROM ATAPI 1 2 Dual channel PCI IDE Controller E DOMEX DMX3194 PCI SCSI Host Adapter xa BAILEY IIMCPO2 BAILEY IIMCPO02 Properties 2 x ey Settings BAILEY IIMCPO02 Properties 2 1x Properties BAILEY IIMCPO2 Ni Device Type SCSI Scanner BAILEY IIMCPO2 Manufacturer BAILEY Target ID 1 Firmware revision G Device Map Not Available Logical unit number 0 Device Status SCSI Adapter Information The device is working properly Name DMX3194 SCSI Port 2 Bus number Notice that the INICIO3 or INICI13A identifies itself to the SCSI adapter card as BAILEY IIMCPO2 SCSI Scanner This is normal The location of the device is given in the settings property dialog For this example OPC90 will assigned S2001 as the device identity 7 8 2 TCP Communication The DEVICE definition block supports direct TCP IP communication with Lantronix Serial to Ethernet devices such as the UDS2100 and EDS4100 Typically the Lantronix serial port redirector software is used to setup COM ports that appear as normal COM ports but behind the scene are mapped to the Lantronix device s IP address and port number at that address Communication using these COM ports is channeled through the Lantronix redirector driver The DEVICE block TCP ports can be used instead of the Lantronix redirected C
278. that allows plant personnel to take direct control of the loop output The OPC client uses the AO BYPASS tag to indicate this condition has occurred Likewise the OPC client uses the DS BAD tag to also indicate that the controller has lost communication with the Digital Control Station hand held station RoviSys Company Copyright 1999 2015 Page 125 OPC90 Server User Manual V8 2 1 7 25 PCU Communication Statistics Monitor PCUMON The PCUMON OPC90 block is used to monitor detailed communication statistics from a PCU node These statistics are useful for diagnosing health of a PCU node and to look for overload conditions A symptom of an overloaded PCU node is a prolonged slowdown in the exception reports being exchanged with that node This is usually caused by too many GMI polled type messages being sent to the PCU node Five different overload conditions can be monitored which are e communication module processing power utilization becoming to high excessive received GMI messages excessive transmitted GMI messages slowdown of received exception reports slowdown of transmitted exception reports When any of these conditions are detected a throttle condition can be flagged Optionally this block can be setup to cause OPC90 to throttle slowdown its GMI polling activities with the PCU node being monitored Doing so could clear the overload condition if OPC90 is generating the excessive amount of GMI messages Note als
279. the CSV file supports the definition of the engineering units map and text message map These maps are normally defined using the OPC90 Edit gt Engineering Units and Edit gt Text Messages dialogs Definitions within the CSV file allow bulk definition of these two maps The format for defining the maps and block definitions are presented by the following tables Map Definition Fields O Block Name Block Type Location Description Read Only Flag Block Name Block Type Location only block Description Max Time Initial Value EU code Zero Span Significant Change High Alarm Limit Low Alarm Limit n Block Name Block Type Location Description FTLSDO F1LSD1 F2LSDO F2LSD1 OUTLSDO OUTLSD1 Read Only Flag DEVICE Device Name Block Type Port Description Max Outputs Watchdog Timer Import Exception Report Update Rate Max Block Specification Reads per Second STN Fast Update Period STN Fast Update period Exception Report Screen Flag Establish Points Online Flag System Type Flag 0 Infi90 1 Network 90 Get Set Time Flag Get Time Flag Time Warp Flag Use DCS Time Stamp Flag Lock Flag Enable Simulation Flag Simulate Device Input Blocks Flag Simulation AOL and DOL Block Inputs Simulate Factor Tag Startup Status 1 Good 2 Uncertain 4 Bad Continuous OPC client Update Flag Exception Report Write Confirmation flag Group Output Writes flag Output Exception Report Update Rate Log
280. the OPC90 configuration file Save the configuration and put OPC90 into Monitor mode View Monitor to verify it can communicate with the Lantronix Ethernet to Serial device A quick check of the OPC90 DEVICE block faceplate will indicate whether or not successful communication is occurring and will show the actual IP and port number for the selected TCP port It is important to note that DEVICE block support of direct TCP communication has been validated with Lantronix UDS2100 and EDS4100 devices It is anticipated that it should also work with other manufacturer Ethernet to Serial devices that support IP and port number addresses but the official devices RoviSys claims support for are Lantronix 7 8 8 Device Communication Faceplate The DEVICE block includes a faceplate that summarizes important communication information associated with the device block To display the faceplate right click on the DEVICE block and select Faceplate The following faceplate will be displayed RoviSys Company Copyright 1999 2015 Page 85 OPC90 Server User Manual V8 2 1 Device Communication CIU Tue Feb 03 03 47 08 2015 STATUS Local Shadow Good Primary COM12 Unused Primary Good Secondary COM13 Unused Secondary ONLINE Unlimited V8 1 1 ADDRESSES Type Ring Mode Module Local INICION E O 1 200 2 Shadow Unused Unused Unused Time Sync Master Time Sync DCS 1 100 Time Sync Master Accuracy Rating 3 STATISTICS Totals Rate per second
281. these DCOM settings This program can be started using the OPC90 Utilities menu item Note that depending on the operating environment Windows Workstation or Server local user account or domain user account the exact DCOM settings may vary The following example sets up the OPC90 settings to default which means use those setup for My Computer It also assigns the most open settings for My Computer If this example does not work for your system or tighter security is required try different combinations until one is found that works correctly and satisfies the security requirements For example instead of setting OPC90 to use the My Computer default settings assign it custom settings with a smaller set of authorized users Running OPC90 as a service will sometimes require additional adjustments depending on the operating system in use its workgroup domain residency and whether or not the service is running as a system service or preferably and required when using the OPC90 Database Shadowing feature in a privileged user account Note that when running as a service make sure it is stopped and started after any changes to the DCOM settings are made The local OPC90 PC and remote PCs that will be running OPC client software must both be setup The settings presented in this section provide the most open remote OPC client access to OPC90 Server Once remote access has been setup and validated the settings can be adjusted for any site sp
282. tilities M89 Dm i zle Block Finder 4f ciu Help Contents Location Data Type Access Value Description Last Update STATUS COMIO R Good All Comm Status 0 Good 1 Bad 04 17 2012 07 59 57 105 About OPC90 Server Ec CYCLE COMIO R 533 Block specification read cycles completed 04 17 2012 07 59 57 105 D off Clients 31 Groups 61 Tags 27795 Rate 4860 Service Run CIU ONLINE Unlimited RoviSys Company Copyright 1999 2015 Page 39 OPC90 Server User Manual V8 2 1 Select About OPC90 Server to determine the current program version and licensing information Select Help Contents to invoke the OPC90 help file Select Block Finder to easily search the database for specific blocks 5 7 1 Block Finder When Block Finder is selected the following dialog is displayed This dialog is used to easily search the database for specific blocks Find Block Search By Search Data Block Type All blocks Find Dore Cancel Block Name E Description Address Ring Node E Module Block Result Click find to start search next to continue search after initial find Block name amp description can use wildcards abc yz amp addresses can be a wildcard A search can be built using the and of up to four conditions block type block name description and address Click on the conditions to be included in the search Next fill in the sear
283. ting up the various features of operation The faceplate can be viewed by right clicking on the block while in monitor mode and selecting faceplate It appears as follows PCU 1 1 1 Monitoring PCU at Ring 1 Node 1 Collection Interval ms 1000 6 Throttle Factors ms BLK 250 MUXCIU 50 PCUMON 3000 POLL 2000 sPEC 100 MODSTAT v Samples Watch and Throttle Level po GMI TX Mon Jul 25 15 46 21 2011 Watch Current Bytes Sec Messages Sec iv LOOPTX 2200 NISTX 3058 Y usRx 856 NODE TX 1826 M NODE RX 347 yz MB TX 3n MBRX 7es CS Log On Current 0 3 60 0 20 Average 0 23 59 D 4 23 63 BEE 10 3 3 18 Default Settings Messages Sec Messages Sec Values Sec Values Sec em Note that all numeric entries for this dialog are completed using the tab key Pressing the enter key will dismiss the dialog The Collection section is used to configure how often the PCU performance statistics are read Keep in mind that these statistics are individually polled values so it does add to the GMI activity the PCU must handle To reduce this effect individual data that is not required can be shutoff and not polled as needed RoviSys Company Copyright 1999 2015 Page 131 OPC90 Server User Manual V8 2 1 Setting the interval to zero completely shuts off all polling ac
284. tion can be selected Selecting Device and input blocks simulates communication with the interface and reception of values The type of value simulation is configurable for each block attribute by right clicking on the attribute and selecting properties and than the simulation signal type The selections are sine ramp random and constant Selecting the AOL and DOL block input simulation option causes communication with the interface to occur normally with the input values to the AOL and DOL blocks to be automatically updated with simulated values that would normally be provided by an OPC client This simulation option also allows configuration of the percent of the total values to change per second Picks the initial OPC status that will be reported to OPC clients for all of the tag values until the Bailey interface has been initialized with the configured database and has begun to report the actual values On startup the tag values associated with AIL AOL DIL and DOL blocks will be initialized to the last saved value before OPC90 was last stopped For this option to be effective the Auto Save database feature must also be enabled With this option set all block values that are not connected to an OPC client or currently being viewed in the program window or faceplate will be automatically disconnected If the exception report for the block value goes into or out of alarm RoviSys Company Copyright 1999 2015 Page 74
285. tivity for the block The samples setting configures how many samples are used for calculating the averages found in the Watch and Throttle section The range for this setting can be from 1 255 samples The Watch section shows various categories of PCU performance statistics This data includes current transmit TX and receive RX data for the various communication paths within the PCU The data is presented in terms of both bytes per second and messages per second The communication paths includes total Infinet transmissions LOOP network interface slave NIS data exchanges specific to the PCU NODE and module bus MB or Control Way Collection of data for each of these communication paths can be individually turned off using the checkboxes within this section if that data is not needed or to lessen the GMI impact on the PCU The Throttle Factors section is used to setup throttle delays for the various block types that generate GMI polling activity So for the above example if a BLK block configuration save is in process and a THROTTLE condition has been detected the BLK block would stop reading module configuration data as fast possible but instead separate each read with a 500 millisecond delay Throttle factors can be applied to BLK MUXCIU PCUMON POLL and SPEC blocks These throttle factors are only applied for those blocks that are directing their GMI polling activity to the PCU being monitored by this block and it has be
286. to dual channel single interface 5 Verify the RS232 cable is connected to the correct PC COM port RoviSys Company Copyright 1999 2015 Page 175 OPC90 Server User Manual V8 2 1 12 5 Appears To Be Communicating But No Data is Being Received If the Bailey interface LEDs sequence at a very steady and periodic rate this means the server is connected to the Bailey interface but the OPC90 Server DEVICE block communication parameters might not be set correctly These settings are determined by the DEVICE block s Primary and Secondary port properties Note that these attributes can be changed while the driver is on line 1 Verify the baud rate settings match between the Bailey interface and COM port the OPC90 Server DEVICE block driver is using 2 Verify the parity usually none and stop bits usually 1 match between the Bailey interface and COM port the server is using 3 Verify the Bailey interface has checksuming enabled If the Bailey interface LEDs are not sequencing but the server indicates good communication status DEVICE PRI STATUS or SEC STATUS is zero 1 Verify the COM port associated with the DEVICE is not a modem port 2 Verify the pin outs on the serial cable or Bailey interface termination dipshunt settings do not have the TX and RX lines pinned together 12 6 Not All Blocks Are Receiving Data 1 Verify the Bailey block addressed by the OPC90 Server block exists and their types match 2 Verify B
287. to the Bailey DADIG block Specifically it allows selection of the CUSTOM input state what input should currently be used control of alarm suppression resetting the alarm latch and control of exception reporting Note that writing to the attributes that report the current state of that block feature can also control these features notes 2 5 When the IN SELECT attribute is TRUE 1 the DADIG block can be commanded to use its various inputs The IN ALTERNATE IN CUSTOM and IN PRIMARY attributes indicate the current input being used by the block They can also be used to command the block to use a different input For example assume the current input is primary then IN PRIMARY will be one IN ALTERNATE and IN CUSTOM will be zero When a one is written to IN ALTERNATE the DADIG block will begin using the alternate input Note that writes will be rejected if the IN SELECT attribute is not TRUE 1 The DADIG block alarm latch is indicated by this attribute By writing FALSE 0 to this attribute the latch will be cleared This attribute indicates alarm suppression is in effect It can also be used to set or reset alarm suppression only if enabled by the DADIG block configuration by writing a respective TRUE 1 or FALSE 0 to this attribute This attribute indicates whether or not exception reporting for this block has been disabled If XRP OFF is TRUE 1 exception reporting is disabled This attribute can be used to turn exception re
288. topology data Topology data is read every TOPOLOGY TIME milliseconds and not tied to the INTERVAL setting RoviSys Company Copyright 1999 2015 Page 108 OPC90 Server User Manual V8 2 1 Topology data is read immediately whenever the GET NOW tag is set The topology data is represented by comma separated values that identify the current loop number nearest fault node number set to zero when no faults a count of total nodes followed by sets of node address and node type code This list always starts with the node address of the CIU OPC90 is communicating with It is then followed by the next node downstream from the CIU node and so on The last node listed is the one just upstream from the OPC90 CIU node completing the loop ring Consider an example string of 1 0 5 30 2 101 0 100 0 2 0 1 0 This string indicates it is for loop 1 no nearest fault node is detected so it is 0 there are 5 nodes in this loop the first node is 30 and is type 2 the second node is 101 and type 0 the third node is 100 type 0 the four node is 2 type 0 and the last node is 1 type 0 Possible node types are Process control unit 0 Console or computer 2 Bridge and Unknown At the time of this writing the node type codes for Bridge and Unknown are not known They can be determined in real time when those node types exist in a given system 4 The XRP RX PACK PCT and XHP TX PACK PCT tags are calculated points The exception report count and pack c
289. tor see note 3 HI DEV ACT High deviation alarm active indicator see note 4 LO DEV ACT VT BOOL Read Low deviation alarm active indicator see note 4 Notes 1 By writing to these tags the OPC client can set the address to be polled and how often the value is polled The server will enforce valid ranges for these tags but it is the client s responsibility to write valid addresses to which block outputs actually exist Polling is disabled when the OPC client writes zero to the interval tag Otherwise the minimum value that can be written is 100 ms 2 Polling discrete Bailey block outputs will be converted to an equivalent floating point value If the block output being polled is a string the OUT will be the count of characters in the string and OUT TEXT will be the actual string 3 Some polled Bailey floating point block outputs also contain high and low alarm active bits The alarm level of any such polled block will be reflected in the HI ACT and LO ACT tags Some polled Bailey discrete block outputs also contain an alarm active bit The alarm level of any such polled block will be reflected in the HI ACT tag RoviSys Company Copyright 1999 2015 Page 133 OPC90 Server User Manual V8 2 1 4 Some polled Bailey floating point block outputs also contain high and low deviation alarm active bits The alarm level of any such polled block will be reflected in the HI DEV ACT and LO DEV ACT attributes RoviSys Company Copyrigh
290. ty 0 Good 1 Bad OUT Current output value from Bailey OUT TEXT Discrete Output Value as Text DISC LIM Discrete alarm state DISC ACT Alarm active indicator OVR ENABLE Override allowed 0 No 1 Yes OVR VALUE Override value OVR STATUS Value overridden 0 No 1 Yes STAT INHIBT Status inhibit 0 No 1 Yes SUSPECT Value suspect 0 No 1 Yes CONFIG ERR Configuration error exists 0 No 1 Yes READBACK Readback status 0 Good 1 Bad SIM ENABLE Simulation enable 0 No 1 Yes SIM BLOCK VT I2 Read Simulation value block number RoviSys Company Copyright 1999 2015 Page 93 OPC90 Server User Manual V8 2 1 7 14 Harmony Digital Output HDO The HDO OPC90 block is used to retrieve the exception reported output from Bailey Harmony Digital Output function code 225 blocks Restrictions This OPC block is only valid for Bailey interface types INICIO3 INICI12 and INICI13 TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address ADDR NODE Bailey node address ADDR MODULE Bailey module address ADDR BLOCK Bailey block address OUTLSDO Output state zero logic state descriptor OUTLSD1 Output state one logic state descriptor MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor CHAN NAME VT BSTR Channel name assigned to this point CHAN STATE
291. type is defined according to the following values Tunable specifications will be indicated by 100 added to these values 1 REAL 2 2 REAL 3 3 BOOLEAN 4 INTEGER 1 5 INTEGER_2 7 INTEGER_4 6 REAL_4 8 STRING 7 3 1 Reading a Bailey Block To retrieve existing block specification information the block address must first be written to the ADDR_RING ADDR_NODE ADDR_MODULE and ADDR_BLOCK tags of this block Once the address is written the READ tag can be set TRUE which instructs OPC90 to retrieve the block specifications The specification values are copied to the SO1_ VALUE through S63 VALUE tags The S01 through S63 tags are also updated with a description of each returned specification The FC tag will return the block function code number and the FCNAME tag will return the name of the function code Completion of the read request is signaled when the READ tag is reset to FALSE The MESSAGE tag will also return a text message indicating completion of the read operation or the reason for failure if the read cannot be completed When the ACKNAK tag is zero the request was successful non zero indicates an error occurred Since Bailey function blocks can have up to 63 specifications tags exist for the maximum number of specifications The actual number of valid specifications for any given block read can be determined by examining SX_COUNT tag or the descriptions assigned to each specification S01 through S63 tags Null descr
292. type or destination count errors Messages dumped with source state errors VT Ul4 Read Messages dumped with source sequence mismatch VT Ul4 Read Multicast messages received excluding original VT UM Multicast destinations received VT Ul4 Read Time sync messages received excluding original VT Ul4 Read Broadcast messages received excluding RoviSys Company Copyright 1999 2015 Page 105 OPC90 Server User Manual V8 2 1 NIS POLL RX NIS POLL ACK NIS POLL BUSY MSG TOTAL TX MSG TOTAL RX TX MSG ORIGINATED BYTES TOTAL RX TX XBUS TO NIS MSG XBUS SIGNALS XBUS STAT REQ XBUS NIS STAT REQ XBUS NIS IRQ BAD ALIGN TX ALIGN RX ALIGN STAT ALIGN RX REQ ALIGN STAT REQ STAT OFLOW NODE READ TSYNC REQ SPUR IRQ7 SPUR IRQ6 SPUR IRQ5 LOOP FAILS When ENABLE SYNC SYNC RING SYNC NODE SYNC ACCURACY When ENABLE MEM MEMORY TOTAL MEMORY UNUSED MEMORY TEMP MEMORY FREE When ENABLE XRP XRP RESET TIME XRP RX PEAK XRP TX PEAK XRP RX COUNT XRP TX COUNT XRP RX PACK COUNT original VT Ul4 Read NIS poll messages received excluding original VT UM NIS poll messages acknowledged by this node VT Ul4 Read NIS poll messages busy not acknowledged by this node VT Ul4 Total messages transmitted total loop traffic VT Ul4 Read Total messages received and forwarded by this node VT Ul4 Read Total messages originated by this node including retries VT Ul Total bytes received and forwarded b
293. uch an error 8 Memory capacity of the Bailey PCU node has been exceeded check its status using a OPC90 Server MODSTAT block Note that this error is extremely rare 12 7 Random Blocks Are Receiving Bad Quality Indication 1 Verify the total number of blocks have not exceeded the capacity of the Bailey interface or OPC90 license limit 2 When this occurs with data values received via DCOM run DCOMCNFG and delete all of the default protocols out of the Default Protocols list except the Connection Oriented TCP IP protocol 12 8 Sporadic Data Transfer of Export Blocks to Bailey The OPC90 AOL DOL ODD OMSDD ORCM ORMC ORMSC and OSTN blocks are used to export data of the named type to Bailey consoles or controllers Unfortunately the ABB Bailey CIU interfaces are primarily designed as data importing devices and handle these export blocks at a much lower priority then the import point types If the OPC90 database contains a large number of import blocks the CIU can become so busy processing the incoming exception reports that it never gets around to sending the export block data that OPC90 successfully commanded it to send For example when the OPC client writes to the OPC90 AOL block IN tag OPC90 transfers that value to the OUT tag after it has been successfully written to the Bailey CIU If that value is never received within the Bailey system or received at significant delays this signifies the ABB Bailey CIU is overwhelmed wit
294. uded as part of a user inputted file name Click on the STOP button to stop the file save operation If the save command is stopped or it fails the file will not be generated and any original file of that name remains unchanged Note that if a user inputted file name or directory path is entered that contains spaces it must be enclosed within quotes C Program Files OPC90 Server ABB Name With Spaces When a user file name is entered it is not necessary to include its extension The default extension selected by the C90 CFG radio button will automatically be appended to the file Including the C90 or CFG file extension overrides the default type Saving a configuration also generates a second file that documents all of the blocks just saved This list includes the block number function code type and specification settings The name of this file is the saved file name with BLOCK LISTING CSV appended to it Microsoft Excel can be used to open the file and look at the blocks contained by the configuration LOAD Click on this button to load the currently addressed module If no file name is RoviSys Company Copyright 1999 2015 Page 61 OPC90 Server User Manual V8 2 1 entered in the File area the file name will automatically be based on the current ring node and module address For the above example it will be 00100103 C90 If the CFG radio button is selected it will be 10103 CFG to match Ba
295. uration file type used by the save and load command is the RoviSys OPC90 C90 file type format When set the ABB Bailey CFG file type format is used COMMAND VT BSTR Read Write Supports a variety of Bailey controller configuration activities using simple text based RoviSys Company Copyright 1999 2015 Page 49 OPC90 Server User Manual V8 2 1 COMMAND ACT VT BOOL OPERATION VT I2 Read Write MODE VT_BSTR WRITE VT_BOOL Read Write DELETE VT_BOOL Read Write OPC_STATUS VT I2 QUALITY VT BOOL ACKNAK VT I2 FC VT I2 Read Write FCNAME VT BSTR SX COUNT VT I2 al VT_l2 pe Read Write SPEC FORMAT commands See user configuration command processing for usage details Set when a text based configuration command is active otherwise reset when command is not active or completed Commands Bailey controllers to different operating modes per the following values 1 request controller software reset 2 request configure mode 3 request execute mode 4 request configuration initialization The driver will reset this attribute to zero when the module operation request has been completed Returns the current operating mode Execute Configure Error of the module addressed by the ADDR_MODULE attribute Set to request a block to be written or modified The driver will reset this attribute when the block write or modification request is completed Set to request a block to be deleted The driver will re
296. us users Enabled Disabled Setup of DCOM on the local OPC90 PC is complete If the OPC client cannot access OPC90 after completing this setup try rebooting the PC Depending on the types of changes made to My Computer DCOM settings a reboot of the PC may be required RoviSys Company Copyright 1999 2015 Page 165 OPC90 Server User Manual V8 2 1 10 2 Configuring DCOM on the Remote OPC Client PC Some OPC clients utilize a mechanism called Data Callbacks to receive data values from an OPC server For these types of clients the remote PC must have its access permissions enabled to receive the callbacks If an OPC client can attach to the server but not receive data values this is a sign it relies on callbacks and therefore the PC access permissions must be adjusted Do the following procedure to make these adjustments Run DCOMOCNFG and select the DCOM properties of My Computer and set the following default properties My Computer Properties Default Protocols MSDTC COM Security General ptions Default Properties v Enable Distributed COM on this computer Enable COM Intemet Services on this computer Default Distributed COM Communication Properties The Authentication Level specifies security at the packet level Default Authentication Level Connect Ed The impersonation level specifies whether applications can determine who is calling them and whether the application can do operations usin
297. ve busyness of the communication loop Collection of the data in this section can be disabled by unchecking its check box This section includes a time since the last NIS hardware reset occurred This time starts over after 49 days It can also be reset by writing a zero to it which also resets the data counters associated with this section The data in this section reports the peak number of exception reports received and sent per second It also presents total points and total packets messages for received and transmit exception reports These values are used to compute the percentage packing rate of the receive and transmit messages The design of the communication loop is as it gets busy and a message containing exception reports is waiting to get sent the number of values per packet increases This results in more values per message to be exchanged When the communication loop is not very busy fewer values per packet are sent since there is communication loop idle space available when it is time for them to get sent This means smaller packing percentages indicate the loop is not very busy whereas higher factors mean it is The transmit and receive percentage packing factors are shown by vertical progress indicators They provide a visual indication of how busy the communication loop is The higher the progress indicator climbs means a busier loop The faceplate can display the real time or averaged percentage packing factors The Time Sync Master
298. with the MAX BLOCK SPECIFICATIONS READ PER PERIOD parameter determine how often read block specification messages are sent for each block So for example setting the period to 15 seconds and MAX BLOCK SPECIFICATIONS READ PER PERIOD to 1 will result in a request for a block specifications to be sent every 15 seconds If there are 100 blocks in the configuration requiring block specifications to be read it will take 1500 seconds to cycle through all of the blocks Defines the maximum block specification read rate per period for STN and SPEC blocks DAANG DADIG DD and MSDD are read once on startup The settable range for this parameter is 1 32 The period is set using the BLOCK SPECIFICATION READ PERIOD parameter Not all CIUs and ABB Bailey systems are capable of reading at 32 per second Most systems should not attempt to read block specifications at such a high rate Setting it too high could cause nodes to become busy Infi 90 Systems or go offline Network 90 systems Also higher settings may cause a slowdown in a PCUs ability to report exception reports Watch the MSG QUEUE tag and if it continues in the double digits for prolong periods lower this setting Unless faster block spec read cycles are absolutely required it is best to leave this setting at the default value or lower it even more So for example setting this parameter to 2 and the BLOCK SPECIFICATION READ PERIOD to 60 seconds will result in two requests for a block spec
299. writing it to the OUT tag Bailey logic can enable control output tracking while in manual mode The OPC client uses the OUT TRACKING tag to indicate this condition The SP tag is used by the OPC client to report the current value of the set point This value is in engineering units and will be clamped between the zero and span defined for the set point OPC90 will receive set point write request from the Bailey system and when the current mode is manual or auto transfer the set point to the OPC client by writing it to the SP tag Bailey logic can enable set point tracking while in manual or auto mode The OPC client uses the SP TRACKING tag to indicate this condition A Bailey STN block can be configured to be a ratio station Ratio stations are similar to a cascaded loop but differs in its method of set point generation when in cascade mode The cascaded set point input wild variable is multiplied by a ratio adjustment factor called the ratio index to determine the actual set point value The RI tag is used by the OPC client to report the current value of the ratio index By definition for Bailey systems the ratio index has a valid range of 0 05 to 10 0 OPC90 will receive ratio index write request from the Bailey system and when the current mode is cascade transfer the ratio index to the OPC client by writing it to the RI tag Some older Bailey systems using the station block have also included a hand held station called a Digital Control Station
300. y Symphony and Command Series Distributed Control Systems System integrity functionality and data throughput is maintained by utilizing standard exception reporting techniques Bandwidth improvements are realized over existing Bailey use of these same hardware interfaces by implementing dual channel capability and redundant interfaces This document is intended for individuals who are familiar with the Bailey configuration principals in terms of the types and how to access exception report blocks An understanding OPC is also required OPC90 Server is an OPC Data Access 1 0 2 0 and 2 05 compliant server This is achieved by using an industrial grade OPC toolkit to implement its OPC interfaces The ongoing maintenance and certification of this toolkit is managed by a company that is a charter member of the OPC Foundation OPC90 Server supports DCOM DCOM allows one PC running OPC90 to provide its data via a local area network to other PCs running OPC client software Refer to the OPC90 Remote Access section of this document for instructions on how to setup DCOM Throughout this document the OPC90 Server will be referenced as OPC90 The Bailey system is referenced as BLY which is defined to include Command Series NETWORK 90 INFI 90 Harmony and Symphony systems RoviSys Company Copyright 1999 2015 Page 5 OPC90 Server User Manual V8 2 1 2 Functional Description OPC90 Server can run on the Windows 2000 XP 2003 Server VIST
301. y node address ADDR MODULE Bailey module address ADDR BLOCK Bailey block address MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor OPC STATUS OPC status value see OPC status section QUALITY Current quality of Bailey values 0 good 1 bad EU Engineering Units Code EU TEXT Engineering Units String OUT Current output value received from Bailey OUT HI LIM VT R4 OUT high limit OUT LO LIM VT R4 OUT low limit SP TRACKING VT BOOL Read Set point is tracking indicator RoviSys Company Copyright 1999 2015 Page 139 OPC90 Server User Manual V8 2 1 7 30 Sequence of Events SOE The SOE OPC90 block is used to monitor and retrieve sequence of events data from Bailey Sequence of Events Log blocks function codes 99 and 243 OPC90 supports up to four ABB Bailey sequence of events recorders by allowing definition of four SOE point sets Each point set consists of 512 points The Edit gt SOE Point Names menu selection is used to define the SOE point sets Configuration of this block includes selection of the SOE point name set it is to be associated with OPC90 Function Block Properties Name SDE 5601 Cancel Description Block Type Point Names SET Qe TENE Ring Mode 1 Module 3 Block 5601 Restrictions This OPC90 block can be uti
302. y of Bailey values 0 good 1 bad MSG_OUT Message number to be displayed MSG_OUT_TEXT VT_BSTR Read Message number to be displayed as a string COLOR Color selection for the message BLINK VT BOOL Read Blink the message flag RoviSys Company Copyright 1999 2015 Page 151 OPC90 Server User Manual V8 2 1 7 34 Text String TEXTSTR The TEXTSTR OPC90 block is used to retrieve the exception reported output from Bailey Text String blocks function code 194 Restrictions This OPC block is only valid for Bailey interface types INICIO3 INICI12 and INICI13 TAGNAME TYPE ACCESS DESCRIPTION ADDR RING Bailey ring address ADDR NODE Bailey node address ADDR MODULE Bailey module address ADDR BLOCK Bailey block address MY BLOCK TYPE Indicates the OPC90 block type MESSAGE Indicates the block operational message TAG Indicates the block name TAGLONG Indicates the block long OPC path name TAGDESC Indicates the block descriptor OPC STATUS OPC status value see OPC status section QUALITY VT BOOL Current quality of Bailey values 0 good 1 bad QUAL_OVR VT_BOOL Quality override 0 Off 1 On EU Engineering Units Code EU_TEXT Engineering Units String MODE VT I2 Read Write The mode of the Bailey block 0 Manual 1 Auto MODE LOCK Mode lock 0 Off 1 On ALARM Alarm active indicator ALARM REQ Alarm request 0 No 1 Yes see note 1 TEXTSTR Text string value see note 2 TEXTSTR LOCK VT BO
303. y this node VT UM Expander bus to NIS handshake messages VT Ul4 Read Expander bus message to transmitt buffer signals VT Ul4 Expander bus PCU status requests VT Ul Expander bus NIS status requests VT Ul4 Expander bus interrupts with invalid status VT Ul4 Read Re alignment of transmit buffer due to invalid contents Re alignment of receive buffer Re alignment of status buffer Re alignment of receive buffer requests Re alignment of status buffer requests Status buffer message overflow node status Read time sync buffer requests Spurious level 7 interrupts Spurious level 6 interrupts Spurious level 5 interrupts Number of loop failures Time Sync Master ID Time sync master ring Time sync master node Time sync master accuracy rating Module Memory Utilization Total memory bytes Unused memory bytes Temporary memory bytes en memory free LE ldem Module Exception Statistics iced Ul4 Read Write Time milliseconds since last module reset or XRP statistics reset command Write O to this tag to reset statistics time iVT UM Exception receive rate peak points second VT Ul4 Read Exception transmit rate peak points second VT Ul4 Exception receive count points VT Ul Exception transmit count points VT Ul4 Read Exception receive packet count RoviSys Company Copyright 1999 2015 Page 106 OPC90 Server User Manual V8 2 1 XRP TX PACK COUNT XRP RX PACK PCT

Download Pdf Manuals

image

Related Search

Related Contents

JANOME JW7630 Instruction Booklet  Kramer Electronics VP-123  Samsung Galaxy Core Brugervejledning  La notion de > chez Daniil Harms  Descargar - Whirlpool    Xerox Scanner M118i User's Manual  Lightolier IS:40714 User's Manual  - Geotool  

Copyright © All rights reserved.
Failed to retrieve file